You are on page 1of 1

Test device Date/Time 07/06/2022 08:53

Test device CT-Analyzer Device serial no PC033N


Hardware version 01/01/09/05/01/11

Asset
Ipn 800.0 A Object Location
Isn 1.0 A Manufacturer ENPAY Company SOFIDEL
Standard IEC 61869-2 Type Country UK
Application Protection Serial number Station SOFIDEL
Class PX Core 3 Feeder T2
Frequency 50.0 Hz Tap 3S1-3S2 Phase 2V
Optional IEC-ID IEC 61869-2
Comment

Secondary winding resistance


R-meas (13.0 °C) 4.520 Ω I-DC 0.989722 A V-DC 4.4737 V
R-ref (75.0 °C) 5.652 Ω

Ratio
Ratio 800.0 : 1.0001 Polarity OK
ε 0.007 %
∆φ 1.97 min

Excitation
Ls 0.003934 H Lm 96.7979 H
Standard IEC 61869-2
V-kn 435.77 V I-kn 0.0156 A

Excitation
1000.00

100.00
X1_X2_1
Rectified voltage

10.00

1.00

0.10 Knee IEC 61869-2

0.01
0.00 0.001 0.01 0.10 1.00 10.00
RMS current

1/1