Figure 9-3.

crane lift
Figure 9-4. bolts

10. Installation Notes

the severest conditions. Emerson recommends


1. Condensers should be installed in a location that condensers to be installed in an area with
offering maximum security and access for clean air, away from loose dirt and foreign
maintenance. matter that might clog the coil.
2. The service area must be respected 5. For roof installation, mount the condenser on
3. Avoid areas prone to heavy snow or ice suitable curbs or other supports in accordance
accumulations. with local rules
4. The installation site must guarantee a sufficient 6. Follow the installation arrows on the condenser
/dispersion of the air to allow operation in even for the installation direction

7. Horizontal installation (vertical air flow) With vertical airflow installation a free area of
In order to allow sufficient air through the unit at least 4 m above the condenser has to be
and space for any eventual maintenance, The guarantee for a correct air circulation with the
Service Area should be left free of aim to avoid air shot-cut from discharge to
obstructions. suction air side of condenser.
8. Vertical installation ( horizontal air flow)

19.03.2014 11 English
Always position the condenser so that the
copper pipes are on the bottom.
In order to allow sufficient air through the unit
and space for any eventual maintenance, The
Service Area should be left free of
obstructions.
During vertical installation, the top condenser
must be installed on a rack and the cushion
pads should be used between the condenser
and the rack for damping. It is prohibited to
stack two condensers directly through bolt
connection.
If the condenser is installed on stilts vertically,
you must ensure that the support has sufficient
strength. For the single-fan condenser, at least
two supports are required; for the double-fan
condenser, at least three supports are
required. And each support area cannot be
less than 345mm × 80mm, see Figure 10-1 for Figure 10-1: vertical installation
an example.

19.03.2014 12 English
11. Space Requirements
The condenser needs sufficient installation and service space around the installation place. The detailed space requirements
are shown in Figure 11-1 and Figure 11-2.

Figure 11-1: Horizontal installation space requirements

Horizontal installation Vertical installation


Model
A B C D E F
MCS028 496 620 745 993 660 1210
MCM035 523 653 784 1045 705 1293
MCM040 523 653 784 1045 705 1293
MCL055 627 784 940 1254 852 1562
MCM070 709 886 1064 1418 705 1293
MCM080 709 886 1064 1418 705 1293
MCL110 847 1059 1271 1695 852 1562
MCM160 983 1229 1475 1966 705 1293
MCL165 1020 1275 1530 2040 852 1562

Table. 11-1 space requirements

- Vertical installations

a) b) c)
F
E
A A

A = Air flow passage equivalent or larger than the frontal surface of the condenser.

Figure. 11-2 . Vertical installation space requirements

19.03.2014 13 English