You are on page 1of 1

LOAD COMPUTATION

NEMA - 1 ENCLOSURE (INDOOR TYPE) 240 VOLTS, 2 WIRE+ GROUND, 1-Ø


MAIN : 200AT/250AF

LOAD SIZE OF WIRE & CONDUIT (mm2


CKT NO. LOAD DESCRIPTION VA VOLTS AMPERE THHN) OVER CURRENT PROTECTION DEVICE
1 LIGHTING FIXTURES @ GROUND FLOOR & STAIRS 1,980.0 230 8.61 2 - #3.5, 1 - #2.0, 1 - 20mmф - C 20AT/50AF, 240V, 60Hz
2 LIGHTING FIXTURES OF @ GROUND FLOOR 2,400.0 230 10.43 2 - #3.5, 1 - #2.0, 1 - 20mmф - C 20AT/50AF, 240V, 60Hz
3 LIGHTING FIXTURES @ SECOND FLOOR 2,880.0 230 12.52 2 - #3.5, 1 - #2.0, 1 - 20mmф - C 20AT/50AF, 240V, 60Hz
4 CONVENIENCE OUTLET @ GROUND FLOOR 1,600.0 230 6.96 2 - #3.5, 1 - #2.0, 1 - 20mmф - C 20AT/50AF, 240V, 60Hz
5 CONVENIENCE OUTLET @ GROUND FLOOR 2,000.0 230 8.70 2 - #3.5, 1 - #2.0, 1 - 20mmф - C 20AT/50AF, 240V, 60Hz
6 CONVENIENCE OUTLET @ SECOND FLOOR 2,000.0 230 8.70 2 - #3.5, 1 - #2.0, 1 - 20mmф - C 20AT/50AF, 240V, 60Hz
7 CONVENIENCE OUTLET @ SECOND FLOOR 2,000.0 230 8.70 2 - #3.5, 1 - #2.0, 1 - 20mmф - C 20AT/50AF, 240V, 60Hz
8 REF OUTLET 1,500.0 230 6.52 2 - #3.5, 1 - #2.0, 1 - 20mmф - C 20AT/50AF, 240V, 60Hz
9 WASHING MACHINE / DRYER OUTLET 1,000.0 230 4.35 2 - #3.5, 1 - #2.0, 1 - 20mmф - C 20AT/50AF, 240V, 60Hz
10 RANGE/RANGE HOOD OUTLET 3,000.0 230 13.04 2 - #5.5, 1 - #3.5, 1 - 25mmф - C 30AT/50AF, 240V, 60Hz
11 WATER HEATER OF KITCHEN SINK 2,500.0 230 10.87 2 - #5.5, 1 - #3.5, 1 - 25mmф - C 30AT/50AF, 240V, 60Hz
12 WATER HEATER OF T&B @ GROUND FLOOR 2,500.0 230 10.87 2 - #5.5, 1 - #3.5, 1 - 25mmф - C 30AT/50AF, 240V, 60Hz
13 WATER HEATER OF T&B @ SECOND FLOOR 2,500.0 230 10.87 2 - #5.5, 1 - #3.5, 1 - 25mmф - C 30AT/50AF, 240V, 60Hz
14 WATER HEATER OF MASTER T&B @ SECOND FLOOR 2,500.0 230 10.87 2 - #5.5, 1 - #3.5, 1 - 25mmф - C 30AT/50AF, 240V, 60Hz
15 ACU OF BEDROOM 1 @ GROUND FLOOR 1,000.0 230 4.35 2 - #3.5, 1 - #2.0, 1 - 20mmф - C 20AT/50AF, 240V, 60Hz
16 ACU OF BEDROOM 1 @ SECOND FLOOR 1,000.0 230 4.35 2 - #3.5, 1 - #2.0, 1 - 20mmф - C 20AT/50AF, 240V, 60Hz
17 ACU OF BEDROOM 2 @ SECOND FLOOR 1,000.0 230 4.35 2 - #3.5, 1 - #2.0, 1 - 20mmф - C 20AT/50AF, 240V, 60Hz
18 ACU OF BEDROOM 3 @ SECOND FLOOR 1,000.0 230 4.35 2 - #3.5, 1 - #2.0, 1 - 20mmф - C 20AT/50AF, 240V, 60Hz
19 ACCU OF LIVING/DINING AREA @ GROUND FLOOR 1,900.0 230 8.26 2 - #5.5, 1 - #3.5, 1 - 25mmф - C 30AT/50AF, 240V, 60Hz
20 ACCU OF FAMILY AREA @ SECOND FLOOR 1,000.0 230 4.35 2 - #5.5, 1 - #3.5, 1 - 25mmф - C 30AT/50AF, 240V, 60Hz
21 ACCU OF MASTER BEDROOM @ SECOND FLOOR 1,100.0 230 4.78 2 - #5.5, 1 - #3.5, 1 - 25mmф - C 30AT/50AF, 240V, 60Hz
22 PERIMETER LIGHTING & WEATHERPROOF OUTLETS @ ROOFDECK 1,600.0 230 6.96 2 - #3.5, 1 - #2.0, 1 - 20mmф - C 20AT/50AF, 240V, 60Hz

TOTAL LOAD 39,960.0 165.15

using demand factor = 134.73

IL = 165.15 + ( 25% x 13.04 ) = 168.41 USE: 2 - #60 mm² THHN / 1 - # 8.0 mm²THW in 32mm Ø IMC Conduit