VersaMax 24VDC 0.

5Amp Positive Logic with ESCP, Output Module


October 2008 GFK-2535

Discrete output modules IC200MDL741 and BXIOODP1624 provide


one group of 16 discrete outputs.
Discrete output modules IC200MDL742 and BXIOODP3224, shown Module Characteristics
below, provides two groups of 16 discrete outputs. Points IC200MDL741, BXIOODP1624: 1 group of 16 outputs
Each point has electronic overcurrent protection and short circuit IC200MDL742, BXIOODP3224: 2 groups of 16 outputs
protection, and generates a fault if either condition exists. The outputs Module ID IC200MDL741, BXIOODP1624: FFFF8080
are positive or sourcing type outputs. They switch the loads to the IC200MDL742, BXIOODP3224: 80808080
positive side of the DC supply and thus supply current to the loads. Isolation: User input to logic (optical) and frame ground: 250VAC
continuous; 1500VAC for 1 minute
IC200MDL741, BXIOODP1624: Group to group: not
FLD applicable
Q PWR OK
IC200MDL742, BXIOODP3224: Group to group: 250VAC
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 continuous; 1500VAC for 1 minute

OUTPUT 24VDC
Point to point: none
POS LOG ESCP .5A 32PT
LED indicators One green LED per point shows individual point on/off
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
state
One amber LED per point shows individual point
Q
FLD
PWR
OK overloads
FLD PWR LED indicates field power is present
OK LED indicates backplane power is present
Backplane current IC200MDL741, BXIOODP1624: 5V output: 75mA
An external DC power supply must be provided to switch power to the consumption maximum
loads. IC200MDL742, BXIOODP3224: 5V output: 150mA
maximum
Intelligent processing for this module is performed by the CPU or NIU.
External power supply +18 to +30VDC, +24VDC nominal
Thermal derating See diagrams
LED Indicators
Individual green LEDs indicate the on/off state of the output points. The Output Characteristics
LEDs are dependent on field power, but independent of load conditions. Output voltage +18 to +30VDC, +24VDC nominal
Individual amber LEDs indicate overload conditions on each output. Output voltage drop 0.5V maximum
The green FLD PWR LED is on when field power is applied to the Load current 0.5A at 30VDC maximum (resistive)
module. 2.0A inrush maximum for 100ms
Steady-state 1.6A typ., 0.7A to 2.5A max range
The green OK LED is on when backplane power is present to the overcurrent trip point
module.
Output leakage 0.5mA at 30VDC maximum
current
Diagnostics On and Off response 0.5ms, maximum
time
The module reports the presence of any overloaded points to the
Protection (each Short circuit and overcurrent protection, free-wheeling
system on a per-module basis. Amber LEDs indicate the overload output) diodes
conditions on a per-point basis. Once the overload condition is
removed, normal operation is resumed.
Product Revision History
Preinstallation Check Rev Date Description
Carefully inspect all shipping containers for damage. If any equipment IC200MDL741F October 2008 Updated Power Supply OK signal
is damaged, notify the delivery service immediately. Save the damaged BXIOODP1624F circuitry.
shipping container for inspection by the delivery service. After IC200MDL742E
unpacking the equipment, record all serial numbers. Save the shipping BXIOODP3224E
containers and packing material in case it is necessary to transport or IC200MDL741E April 2005 Improvement to latching mechanism
ship any part of the system. BXIOODP1624E
IC200MDL742D
BXIOODP3224D
External Power Supply Requirements IC200MDL741D April 2004 Changed to V0 plastic for module
The external power supply used to power the loads must provide IC200MDL742C housing.
sufficient field power for the module during short circuit events. When a IC200MDL741C January 2004 ATEX approval for Group 2 Category
load is shorted, an inadequate external power supply may allow field IC200MDL742B 3 applications.
power to drop below the specified operating range, causing BXIOODP1624D January 2004 Changed to V0 plastic for module
misoperation of the module. The external power supply must be BXIOODP3224C housing. ATEX approval for Group 2
capable of providing short circuit energy without degradation of output Category 3 applications.
voltage levels. The amount of energy required depends on the number IC200MDL741A December 1998 Initial product release.
of simultaneously-shorted points that might occur. Refer to power BXIOODP1624A
supply short circuit operation specifications when selecting the power IC200MDL742A
supply to be used with the loads. BXIOODP3224A
Local energy storage (either batteries or capacitors) can be used to
compensate for insufficient power supply characteristics. Additional
best practices including minimizing wiring resistance from the external
power supply to the module must be observed.

1
VersaMax 24VDC 0.5Amp Positive Logic with ESCP, Output Module
October 2008 GFK-2535

Installation in Hazardous Locations Wiring Connections for Carriers with Two Rows of Terminals
• EQUIPMENT LABELED WITH REFERENCE TO CLASS I, Row B connections are for 32-point modules only.
A
GROUPS A, B, C & D, DIV. 2 HAZARDOUS LOCATIONS IS
SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8 Q9 Q10 Q11 Q12 Q13 Q14 Q15 Q16
C, D OR NON-HAZARDOUS LOCATIONS ONLY
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
• WARNING - EXPLOSION HAZARD - SUBSTITUTION OF 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I,
Q1 Q1 Q1 Q2 Q2 Q2 Q2 Q2 Q2 Q2 Q2 Q28 Q29 Q30 Q3 Q32
DIVISION 2;
• WARNING - EXPLOSION HAZARD - WHEN IN HAZARDOUS B
LOCATIONS, TURN OFF POWER BEFORE REPLACING OR Wiring Connections for Carriers with Three Rows of Terminals
WIRING MODULES; AND
• WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT Side B connections are for 32-point modules only.
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF
OR THE AREA IS KNOWN TO BE NONHAZARDOUS. - +
Q13 Q14 Q15 Q16
Q29 Q30 Q3 Q32

Field Wiring Terminals 13 14 15 16 17 18 13 14 15 16 17 18

Terminal Connection Terminal Connection Q7 Q8 Q9 Q10 Q11 Q12


Q2 Q2 Q2 Q2 Q2 Q28
A1 Output 1 B1 Output 17 *
A2 Output 2 B2 Output 18 * 7 8 9 10 11 12 7 8 9 10 11 12

A3 Output 3 B3 Output 19 *
A4 Output 4 B4 Output 20 *
Q1 Q2 Q3 Q4 Q5 Q6
A5 Output 5 B5 Output 21 * Q1 Q1 Q1 Q2 Q2 Q2

A6 Output 6 B6 Output 22 * A 1 2 3 4 5 6 B 1 2 3 4 5 6
A7 Output 7 B7 Output 23 *
A8 Output 8 B8 Output 24 *
A9 Output 9 B9 Output 25 *
A10 Output 10 B10 Output 26 * Operating Note
A11 Output 11 B11 Output 27 * If hot insertion of a module is done improperly, the operation of other
A12 Output 12 B12 Output 28 * modules on the same backplane may be disrupted. See Installing a
A13 Output 13 B13 Output 29 * Module on a Carrier in the VersaMax Modules Manual, GFK-1504.
A14 Output 14 B14 Output 30 *
A15 Output 15 B15 Output 31 *
A16 Output 16 B16 Output 32 *
A17 DC - B17 DC - *
A18 DC + B18 DC + *
* Inputs for 32-point modules only.
Each group of 16 outputs has a DC+ and a DC- terminal.
When wiring outputs to inductive loads, use of external suppression
circuits is recommended. See chapter 2, “Installing Wiring for I/O
Devices-Wiring to Inductive Loads” in the VersaMax I/O System
Manual, GFK-1504, for more information.

For modules IC200MDL741 and BXIOODP1624, if additional bussed


terminals are needed, the B terminals can be made available by using
a shorting bar. The shorting bar has a maximum current-carrying
capacity of 2A per point. See chapter 2 of the VersaMax I/O System
Manual, for additional information about the shorting bar.

2
VersaMax 24VDC 0.5Amp Positive Logic with ESCP, Output Module
October 2008 GFK-2535

Thermal Derating Thermal Derating Charts for Modules IC200MDL742, BXIOODP3224


The number of points that can be on at the same time depends on the Ambient Temperature
ambient temperature, the external voltage, and the orientation of the 5ºC 10ºC 15ºC 20ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC 55ºC 60ºC
32
module and DIN rail. The charts below show example thermal deratings

Number of Points On At the Same Time


for the module at 24VDC and 30VDC with the maximum output current 28 B A
per point.
24 24VDC 24VDC

20 A
A A 16
30VDC
B
C 5 pts/ group
12 30VDC
4 pts/ group
8
3 pts/ group
4
2 pts/ group

D
B
Ambient Temperature
5ºC 10ºC 15ºC 20ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC 55ºC 60ºC
D 32

Number of Points On At the Same Time


28 D C
24 24VDC 24VDC

Thermal Derating Charts for Modules IC200MDL741, BXIOODP1624 20 C


Ambient Temperature 30VDC 7 pts/ group
16 D
5ºC 10ºC 15ºC 20ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC 55ºC 60ºC
6 pts/ group
16 30VDC
Number of Points On At the Same Time

12

14
8
4 pts/ group
12 4 1 pts/ group
A
10
24VDC

8
B
6
A
4
30VDC
2
B

Ambient Temperature
5ºC 10ºC 15ºC 20ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC 55ºC 60ºC
16
Number of Points On At the Same Time

14 C
24VDC
12

10
D

8
C
6
30VDC

4 D
2