-Product Manual

HD4 Sulphur Hexafluoride


Circuit Breaker 40.5 kV, 1250…3150 A, 25…31.5 kA

• Self-energy + air-assisted blowing breaking

technology • Smooth breaking characteristics, no operating

overvoltage • High compatibility and safety


Machine Translated by Google
Machine Translated by Google

content

1 Overview 04

2. Selection and ordering of circuit breakers 09

3. Product performance 16

4. Dimensions 18

5. Electrical schematic 20
Machine Translated by Google
4 HD4 Sulfur Hexafluoride Circuit Breaker Product Manual

General

As a leading enterprise in the global medium voltage switch industry, Xiamen ABB Switchgear Co.,

Ltd. has been widely recognized and praised by the market since the introduction of HD4 sulfur

hexafluoride circuit breakers in 2001, and has always dominated the market of sulfur hexafluoride

medium voltage switches. developing.

Based on ABB's continuous technology upgrade and product improvement concept, combined with

ABB's global R&D strength, ABB has launched a new HD4 circuit breaker for the market. The new

HD4 circuit breaker has been comprehensively improved in terms of product electrical performance,

series integrity and wider application occasions, so as to meet the diversified and customized demand

trend of today's customers.

The new HD4 circuit breaker has the same external dimensions as the existing HD4 product series,

ensuring compatibility and interchangeability, and will completely replace the existing HD4 circuit

breaker specifications to better serve customers and the Chinese market.

Advanced breaking

technology • Using sulfur hexafluoride (SF6) gas as arc extinguishing and insulating

medium • Based on the principle of arc extinguishing combined with thermal expansion

and compressed air blowing • Especially suitable for switching of capacitive or inductive loads, its

back-to-back capacitor bank Switching current up to 1250 A (Class C2)

Excellent safety performance

• Perfect mechanical and electrical interlocking device to prevent misoperation •

Standard mechanical anti-jump device to avoid conflict with external electrical anti-jump function •

Provide two-level action alarms for low pole air pressure and insufficient air pressure, and can

Optional digital display SF6 gas density monitoring device • The sealing life of the pole meets the

requirements of GB/T 1984 and IEC 62271-100, and the maintenance is low

Scientific selection of materials and

processes • Select composite insulating materials with excellent flame retardant

properties • Use trivalent chromium electroplating with low toxicity and low pollution
Machine Translated by Google
Overview 5

The principle of arc principle, the technology has long been widely used in the field of high-voltage switches. It has a very

extinguishing technology HD4 circuit breaker uses sulfur hexafluoride (SF6) gas as the arc extinguishing smooth breaking characteristic, no current cut-off phenomenon occurs when breaking the current, so no

and insulating medium. The thermal expansion, negative charge and fast compound action of sulfur operating overvoltage will occur.

hexafluoride gas make it an ideal medium for arc extinguishing.

Excellent characteristics ensure that the HD4 circuit breaker has a long electrical life and avoids shocks to

HD4 circuit breaker is an arc extinguishing based on a combination of thermal expansion and compressed air the load equipment in operation.

7 6

10
3

11

1. Upper and lower outlet

ends 2, insulating sleeve 3,

nozzle 4, moving main

contact 5, moving arc

contact 6, static arc contact

2 7, static main contact 8,

insulating pull rod 9,

explosion-proof membrane

10, upper air chamber 11.

Lower air chamber

9
Machine Translated by Google
6 HD4 Sulfur Hexafluoride Circuit Breaker Product Manual

The closing current of • When the breaking current is small, the arc is naturally extinguished at the zero-crossing point. At this time , fresh SF6 gas

the circuit breaker flows from the upper terminal from the static main contact to the moving part of the moving main contact.
is blown along the contact surface, and the dielectric strength is quickly established between the two contacts to

complete the breaking.

When the separation • When the breaking current is large, the gas in the upper chamber is heated by the arc, and its pressure rises rapidly. When

current of the main contact is transferred from the main contact to the arcing contact, no arc will be generated, and the the nozzle is separated from the static arc contact, the high-pressure gas is blown out from the nozzle at a high speed,

moving contact will continue to move downward, compressing the gas in the lower chamber, causing the air pressure in the and the circuit breaker works in a "pure self-blowing" state. The pressure increase in the upper air chamber is

lower chamber to rise, and the gas from the lower chamber will rise. The chamber flows into the upper air chamber until the proportional to the arc current, ensuring that the arc is extinguished when the current crosses zero for the first time

pressure in the upper and lower air chambers is the same.

Separation of arc Once the circuit breaker

contacts When the arc contacts are just separated, the electrodes break down to ignite the arc and form a current channel. is opened and the arc is extinguished, the self-generated pressure in the upper air chamber is reduced, the valve is

In the initial stage, the thermally expanding gas cannot be released from the nozzle due to the fact that the nozzle has not reopened, and a fresh air flow is re-injected into the upper air chamber and "cleans" the arc extinguishing chamber, the

yet been separated from the static arcing contact and the arc plugging effect. dielectric strength is rapidly increased, and The contact temperature is lowered by the rapid cooling characteristics of SF6

gas . The interrupter chamber "cleaned" by fresh gas can be used for the next closing and opening operation.

circuit breaker closed main contact separation Arc contact separation circuit breaker open
Machine Translated by Google
Overview 7

Applications HD4 Operational safety

circuit breakers can be used to control and protect lines and power equipment in power distribution systems, lockout mechanism prevents incorrect operation, and the lockout mechanism provides a high degree of safety

and are especially suitable for applications that are particularly sensitive to dielectric strength requirements, for operators and equipment even after unexpected operating errors occur. The HD4 circuit breaker has

such as capacitor banks, compensating reactors, etc. complete mechanical and electrical locking (optional), and can complete the safe power distribution function

with the appropriate switch cabinet.

Installation

method The HD4 circuit breaker operating mechanism is arranged on the front, and there are two installation The blocking electromagnet is used to automatically establish an interlocking relationship, which can be used to block

methods: fixed type and withdrawable type. the circuit breaker rocking in and out and/or the circuit breaker closing operation.

The Door locking device (optional) ensures that the circuit breaker can only be rocked in and out after the

standard HD4 circuit breaker complies with relevant standards such as GB/T 1984, and has passed the switchgear door is closed.

following various tests, which can ensure safe and reliable service under any normal installation conditions.

A key and padlock device (optional) ensures correct closing and/or rocking in and out operation.

• Type test: insulation test, main circuit resistance measurement, temperature rise test, short-time withstand

current and peak withstand current test, additional test for auxiliary and control circuits, mechanical

operation test at normal temperature, sealing test, short-circuit current closing And breaking test, no-load

cable switching test and capacitive current switching test, etc.

• Factory test: insulation test of main circuit, test of auxiliary and control circuit, resistance measurement of

main circuit, structural and visual inspection, inspection of mechanical characteristics and mechanical

operation, and sealing test


Machine Translated by Google
8 HD4 Sulfur Hexafluoride Circuit Breaker Product Manual

The quality management

system complies with the ISO 9001: 2008 standard and is certified by a third-party independent organization.

The environmental

management system complies with the ISO 14001: 2004 standard and is certified by a third-party independent organization.

Occupational health and safety management system

complies with OHSAS 18001: 2007 standard and is certified by a third-party independent organization.
Machine Translated by Google
Selection and ordering of circuit breakers 9

Technical parameters of withdrawable HD4 circuit breaker

breaker HD4 / Z

standard GB/T 1984 ÿ

IEC 62271-100 ÿ

Rated voltage Ur [kV] 40.5

Rated insulation voltage Us[kV] 40.5

Power frequency withstand voltage Out ÿ1 minÿ [kV] 95ÿ1ÿ 185

Lightning impulse withstand Up[kV] ÿ1ÿ

voltage, rated frequency, rated Fr [Hz] 50

current (2), rated short-circuit Go to] 1250 1600 2000 2500 3150ÿ3ÿ

breaking current Isc [kA] 25 31.5

Rated short-time withstand current (4 s) I[kA] 25 31.5

Rated short-circuit making current Ip [kA] 63 80

Nominal Operation Sequence [O-0.3 s-CO-180 s-CO] ÿ

Opening time [ms] 35~65

arc time [ms] ÿ15

Breaking [ms] 40~80

time Closing time [ms] 60~100

Maximum external size H[mm] 1575

L[mm] 895

I D[mm] 720

weight [kg] 270 270 300 300 320

[kPa] 550
Pole SF6 gas pressure (absolute value) Pole

[kPa] 480
SF6 gas alarm pressure (absolute value) Operating

ambient temperature [ÿ] -5~+40ÿ4ÿ

Note:

(1) The power frequency withstand voltage/lightning impulse voltage of the switch fracture is 118/215 kV.

(2) If you need 1.1 times the rated current carrying margin, please consult the manufacturer.

(3) 3150 A needs forced air cooling. (4) The

lowest operating ambient temperature can reach -25ÿ, and the lowest storage and transportation temperature can reach -40ÿ, please consult the manufacturer.

Standard configuration of withdrawable HD4 circuit

breaker • ESH operating mechanism • Closing/opening • Auxiliary switch for opening and closing (-BB1/-BB2) •

button and operation counter • Mechanical anti-trip Closing spring charged/uncharged signal contact (-BS2) • Air plug connecting

device • Energy storage motor (-MS) • Closing release (- auxiliary circuit • Isolation contact finger • Working/isolated position of circuit

MC) • Opening trip (-MO1) • Closing blocking solenoid (- breaker trolley Signaling contacts (-BT1/-BT2) • SF6 gas control

RL1)
Machine Translated by Google
10 HD4 Sulfur Hexafluoride Circuit Breaker Product Manual

Fixed HD4 circuit breaker technical parameters

Circuit HD4

breaker standard GB/T 1984 ÿ

IEC 62271-100 ÿ

Rated voltage Ur [kV] 40.5

Rated insulation voltage Us[kV] 40.5

Power frequency withstand voltage Out ÿ1 minÿ [kV] 95ÿ1ÿ 185

Lightning impulse withstand Up[kV] ÿ1ÿ

voltage rated frequency Fr [Hz] 50

Rated current Go to] 1250 1600 2000 2500

Rated short-circuit breaking current Isc [kA] 25 31.5

Rated short-time withstand current (4 s) I[kA] 25 31.5

Rated Short-Circuit Making Current Ip [kA] 63 80

Rated Operation Sequence [O-0.3 s-CO-180 s-CO] ÿ

Opening [ms] 35~65

time Arc time [ms] ÿ15

Breaking [ms] 40~80

time Closing time [ms] 60~100

Maximum external size H[mm] 1314

L[mm] 1010

I
D[mm] 653

weight [kg] 270 270 300 300 310

[kPa] 550
Pole SF6 gas pressure (absolute value) Pole

[kPa] 480
SF6 gas alarm pressure (absolute value) Operating

ambient temperature [ÿ] -5~+40ÿ2ÿ

Note:

(1) The power frequency withstand voltage/lightning impulse voltage of the switch fracture is 118/215 kV. (2)

The lowest operating ambient temperature can reach -25ÿ, and the lowest storage and transportation temperature can reach -40ÿ, please consult the manufacturer.

Standard configuration of fixed HD4 circuit

breakers • ESH operating mechanism • • Closing and blocking electromagnet (-

Closing/opening button and operation counter RL1) • Opening and closing auxiliary switch (-BB1/-

• Mechanical anti-trip device • Energy storage BB2) • Closing spring charged/uncharged signal contact (-BS2) • Air

motor (-MS) • Closing release (-MC) • Opening plug connecting auxiliary circuit • SF6 gas control device

release (-MO1)
Machine Translated by Google
Selection and ordering of circuit breakers 11

Description of the model number of HD4 circuit

breakers The model identification code of HD4 circuit breakers is composed of the parts described

in the table below.

In order to correctly understand the meaning of the device model, please refer to the HD4 circuit

breaker technical data sheet.

HD4 X XX.XX.XX

Installation method /WITH

withdrawablefixed

Rated voltage 40.5 kV 40

Rated current 1250 A 12

1600 A 16

2000 A 20

2500 A 25

3150 A 31

Rated short-circuit breaking current 25 kA 25

31.5 kA 31

Model identification code

meaning example code HD4/Z 40. 16. 25

Represents a withdrawable circuit breaker installed in Unigear ZS3.2 switchgear

with a rated voltage of 40.5 kV, a rated working current of 1600 A, and a rated

short-circuit breaking current of 25 kA.


Machine Translated by Google
12 HD4 Sulfur Hexafluoride Circuit Breaker Product Manual

12

13
Machine Translated by Google
Selection and ordering of circuit breakers 13

1. The parallel opening release (-MO1) can realize the


characteristic:

remote control of the circuit breaker opening.


AÿDCÿÿ 24, 30, 48, 60, 110-132, 220-250V

One ÿAC, 50 Hzÿ ÿ 110-127, 220-240V


This trip unit operates universally on AC and DC power and can be triggered by a pulse or continuous
Operating voltage range: ÿ35%Un Prevent circuit breaker from closing
command. When the command is in pulse form, the shortest pulse current duration should not be less
35-65%Un open circuit breaker
than 100 ms.
85-110%Un breaker can operate normally

Inrush power (Ps): 250 W/VA


characteristic:

Inrush duration: about 150 ms


AÿDCÿÿ 24, 30, 48, 60, 110-132, 220-250V
Continuous working power (Pc): 5 W/VA
Un (AC, 50Hz): Operating 110-127, 220-240V
Pressure level: 2000 V 50 Hz ÿ1 minÿ
voltage range: 65%...110%UnÿDCÿ

85% ... 110% One ÿACÿ

Inrush power (Ps): 125 W/VA 5. The auxiliary contacts of the circuit breaker (-BB1, -BB2) are

about 45 ms used to provide the opening and closing position signals of the circuit breaker. The standard configuration
Inrush duration:

Continuous working power (Pc): of the withdrawable circuit breaker is 12 auxiliary contacts (6NO+6NC), and the standard configuration
5 W/VA
of the fixed circuit breaker is 16 auxiliary contacts (8NO+8NC).
Pressure level: 2000 V 50 Hz ÿ1 minÿ

Note: The number of auxiliary contacts of the withdrawable circuit breaker can be up to 16 (8NO+8NC).

2. The second parallel opening release (-MO2) (optional) The second parallel

opening release can be powered by another set of secondary power supply independent of -MO1, and
characteristic: Suitable for AC-15 or DC-13 load types

is connected with the above parallel opening release -MO1 In the same way, -MO2 can also realize
One: 24 ... 250 V AC / DC
remote control of circuit breaker opening.
Conventional free air heating current: Ith=10 A

Pressure resistance: 2000 V 1 min 50 Hz


The electrical and operating characteristics of the second shunt opening release are identical to -MO1.
resistance: ÿ6.5 mÿ

Examples of ratings and current interrupting capabilities based on electrical

One durability: Power factor Cos Time constant (ÿ) breaking current
3. The parallel switch release (-MC) can realize the
220V~ 0.70 -
20 A
remote control of the circuit breaker closing.
0.45 -
10 A

-
1 ms 12 A
This trip unit operates universally on AC and DC power sources. Can be triggered by pulse or sustained
24V -
15 ms 9A
command. When the command is in pulse form, the shortest pulse current duration should not be less
-
50 ms 6A
than 100 ms.
-
1 ms 10 A

60V -
15 ms 6A
characteristic:
-
50 ms 4.6 A
AÿDCÿÿ 24, 30, 48, 60, 110-132, 220-250V -
1 ms 7A

One ÿAC, 50 Hzÿ ÿ 110-127, 220-240V


110V -
15 ms 4.5 A
Operating voltage range: 85%...110%A
-
50 ms 3.5 A
Inrush power (Ps): 250 W/VA -
1 ms 2A
Inrush duration: about 150 ms
220V -
15 ms 1.7 A
Continuous working power (Pc): 5 W/VA -
50 ms 1.5 A
Pressure level: 2000 V 50 Hz ÿ1 minÿ -
1 ms 2A

250V -
15 ms 1.4 A
4. Under-voltage release (-MU) (optional) When the voltage
-
50 ms 1.2 A
is too low or disappears, the under-voltage release is released to open the circuit breaker.

The circuit breaker can only be closed when the undervoltage release is powered on. The undervoltage

release can operate universally with AC and DC power.

The undervoltage release can be used in conjunction with the electrical time delay device (-KT) to

prevent the circuit breaker from accidentally opening in the event of a short-term temporary drop or

power loss of the secondary power supply.


Machine Translated by Google
14 HD4 Sulfur Hexafluoride Circuit Breaker Product Manual

6. Handcart position contacts (-BT1, -BT2) The handcart position 11. The closing and blocking electromagnet (-RL1) can

contacts are installed on the handcart of the withdrawable circuit breaker. only be closed when the closing and blocking electromagnet is energized.

7. Energy storage motor (-MS) The characteristic:

energy storage motor can automatically perform energy storage operation on the closing spring of the AÿDCÿÿ 24, 30, 48, 60, 110-132, 220-250V

circuit breaker operating mechanism. When the circuit breaker is closed, the energy storage motor Un (AC, 50 Hz): Operating 110-127, 220-240V

immediately recharges the closing spring. voltage range: 80% ... 110% U ÿDCÿ

Inrush power (Ps): 250 W/VA

In the event of power failure or maintenance, the closing spring can be manually charged. Inrush duration: about 150 ms

Continuous working power (Pc): 5 W/VA

characteristic: Pressure level: 2000 V 50 Hz ÿ1 minÿ

A (DC)ÿ 24, 30, 48, 60, 110-132, 220-250V

One (AC, 50 Hz) ÿ 110-127, 220-240V 12. SF6 gas density monitoring device (-PGD) (optional) digital display SF6 gas density

Operating voltage range: 85%...110%A monitoring device, which can display SF6 gas pressure value intuitively and in real time .

Inrush power (Ps): 1500 W/VA

Inrush duration: about 100 ms


A local human-machine interface (LHMI) installed on the panel of the low-pressure chamber is also
Continuous working power (Pc): 200 W/VA

Energy storage time: ÿ8 s optional, which makes it more convenient to observe the state of SF6 gas.

Pressure level: 2000 V 50 Hz (1 min)

characteristic:

Display range 0~999 kPa (absolute pressure)


8. A group of (two) microswitches of the closing spring charged/uncharged signal
measurement accuracy 1.5% at 20°C, 2.5% at -30°C
contacts (-BS2) can send a signal that the closing spring of the circuit breaker operating mechanism is
Protection class: IP5X
charged/uncharged.
Communication interface 1): RS-485 interface (1)

Protocol: Modbus RTU, baud rate 9600 bps


When the spring is not charged, two micro-switch signals: 1NO+1NC.

Low-voltage room local human-machine interface (LHMI):


9. The SF6 gas control device consists

of two stages of pressure switch or density switch (-BP1, -BP2, -BP3) and auxiliary relays (-KA1, -KA2)
Rated voltage: 24 V DC

installed on the pole. Communication Interface: RS-485

Panel cutout: 154x94 mm

When the first stage acts, an alarm signal is provided; when the second pole acts, the SF6 gas control 13. Door locking device (optional) This locking

device locks the circuit breaker in the current state. device is used to prevent the circuit breaker from swinging into the circuit breaker when the cabinet door

is open. This locking device can only be used if the corresponding interlocking device is also installed on

The characteristic parameters of auxiliary relay are as follows: the door of the switch cabinet/compartment .

characteristic:

AÿDCÿÿ 24, 30, 48, 60, 110-132, 220-250V

One ÿAC, 50 Hzÿ ÿ 110-127, 220-240V

10. The handcart blocking electromagnet (-RL2) (optional) The

withdrawable circuit breaker can be rolled in/out only when the handcart blocking electromagnet of the

circuit breaker is energized.

characteristic:

AÿDCÿÿ 24, 30, 48, 60, 110-132, 220-250V

One ÿAC, 50 Hzÿ ÿ 110-127, 220-240V

Operating voltage range: 80%...110%UnÿDCÿ

Inrush power (Ps) 250 W/VA

Inrush duration: about 150 ms

Continuous working power (Pc): 5 W/VA

Pressure level: 2000 V 50 Hz ÿ1 minÿ


Machine Translated by Google
Machine Translated by Google
16 HD4 Sulfur Hexafluoride Circuit Breaker Product Manual

Ambient temperature

under normal conditions Example: • 2000 m

of use • The highest value +40ÿ Installation altitude: 40.5 kV 95

• The average value within 24 hours is not greater +35ÿ • Rated voltage: • Power kV

than • The lowest value (indoor) -5ÿ1ÿ frequency withstand voltage: • Lightning impulse

withstand voltage: 185 kV • Ka coefficient, found from the chart: Ka=1.13

Humidity • The average relative humidity measured within 24 hours does not exceed From the above parameters, the components must be able to withstand (test

95% • The average water vapor pressure measured within 24 hours does not exceed 2.2 conditions at an altitude of zero meters above sea level): • Power frequency

kPa • The average relative humidity measured within 1 month does not exceed 90% • 1 withstand voltage: 95x 1.13=107.35 kV • Lightning impulse withstand voltage:

The average value of water vapour pressure measured within a month does not exceed 1.8 kPa 185x1.13= 209.05 kV

Altitudeÿ1000m 2) The above calculation results show that circuit breakers used in high altitude areas must

be able to withstand higher insulation level tests in zero altitude areas. Please contact
Note:
the manufacturer for specific circuit breaker selection.
1) The operating temperature can be as low as -25°C, and the minimum storage and transportation temperature can be as low as -40°C, please consult the

manufacturer. 2) For practical applications beyond this condition, please consult the manufacturer.

Adaptable to humid tropical

climate HD4 circuit breakers are manufactured in strict accordance with relevant standards, and can

be used in hot and humid climates and high salinity conditions. All important parts are specially

treated to resist the erosion of the surrounding environment of class C according to the UNI

9223-2012 standard. The galvanizing process is carried out according to the GB/T 9799 standard,

the classification number is Fe/Zn 12, the thickness is 12 ÿm, and the color-coated chromate

passivation is carried out according to the GB/T 9800 standard.

Due to these measures, HD4 circuit breakers and their accessories meet the

following standards: GB/T 4797.1 (Climate Map No. 8) GB/T 2423.2 (Test B: High

Temperature) GB/T 2423.4 (Test Db: Alternating Damp Heat ( 12h+12h cycle)

The insulation

performance of the air at altitude decreases with the increase of altitude, so the influence

of this phenomenon on the external insulation of the switch must be considered when using

at altitude, and the insulation inside the arc chute will not be affected in any way because

its insulation Capability is guaranteed by SF6 gas.

If the switchgear is installed in an area above 1000 m above sea level, the influence

of altitude should be considered in the design stage of insulating parts.

In this case a correction factor must be considered, which can be found in the table

below, which is based on GB/T 11022 and IEC 62271-1. A calculation example

based on the above correction principle is given below:


Machine Translated by Google
Product performance 17

Environmental Protection Anti-trip device

Program HD4 circuit breakers are produced in strict accordance with the ISO 14000 standard (a series of All sizes of HD4 circuit breakers are equipped with the same ESH operating mechanism with mechanical anti-

environmental management standards). jump device to prevent the circuit breaker from reclosing under continuous mechanical or electrical command.

The manufacturing process follows standards and pays attention to environmental protection in terms of

energy consumption, raw material consumption and waste generation. All of this relies on our environmental The anti-jump device prevents the closing mechanism and the opening mechanism from acting at the same

management system for medium voltage switch manufacturing. time, ensuring that each closing operation can only be performed after the circuit breaker is opened. Any

further closing is only possible after the release of the closing button and/or the release of the closing release.

Factors such as environmental impact, low energy consumption and appropriate raw material consumption

throughout the product's life cycle are solid considerations during the design phase. Careful selection of raw

materials, manufacturing procedures and packaging allows HD4 circuit breakers to be efficiently recycled at The anti-trip device allows the circuit breaker to close under the following

the end of their useful life. conditions: • The operating mechanism spring is fully charged • The opening

pushbutton and/or the opening release (-MO) is not activated • The circuit breaker main

contacts are in the open position condition


Machine Translated by Google
18 HD4 Sulfur Hexafluoride Circuit Breaker Product Manual

Dimensions

Withdrawable HD4 circuit breaker

1.0 times rated current carrying requirements (standard) 1.1 times rated current carrying requirements

Rated current Dimension drawing code: 1VCD000223 Dimension drawing code: 1VCD000224

A B A B

1250 A O35 mm O76 mm O35 mm O76 mm

1600 A O35 mm O76 mm O49 mm O90 mm

2000 A O79 mm O120 mm O79 mm O120 mm

2500 A O79 mm O120 mm O109 mm O158 mm

3150 A O79 mm O120 mm

42±1 386 245

ØB

328
A

1575

25
25
1314

100
15

21
900
50 21
45
Ø20

40
550 45
510
30
18
22 16 510
485

120
20
85

103
100 Ø80

140 150
32.5
188 25 230 200

718.5 505

578
760 45
588

Withdrawable dynamic and static contacts matching dimensions

Note: The handcart travel (running position to isolation position) is 450 mm.
Machine Translated by Google
Dimensions 19

Fixed HD4 circuit breaker

Dimension drawing code Rated current

1YHT310004R0101 1250 A

1600 A

2000 A

2500 A

372.6

299

80

40

40
328

*16
22.7
1312

*27 C

110.7
*12
900

D
71.5

*15
550

22
510.8

18
16

20

120
85 80

103

25 140 150

870.5 230 200


920 45
489 36

Circuit breaker and cabinet interlocking matching instructions:


Rated current Recommended connection busbar (not less than)

Left interlock:
1250 A 10×100
Upper interlock lever (A): When pressed in by 13±1 mm, the lock is
1600 A 10×100
closed Lower interlock lever (B): Extends 33±2 mm at the closing position
2000 A 2×10×100

2500 A 2×10×100
Right chain:
Note:
Upper interlock lever (C): When pulled out 13±1 mm, the lock is closed
1. After the circuit breaker is pushed into the cabinet, it must be firmly fixed with the cabinet.

2. When the length of the circuit breaker lapped busbar is more than 50 cm, it is necessary to increase the support of the busbar.
Lower interlock lever (D): Extend 33±2 mm in closed position
3. The length of the left and right interlocking rods can be customized according to user requirements.

4. According to the actual needs, the left chain or the right chain can be selected, or the left and right chain are not matched.
-XB1 -XB -XB -XB1 -XB1 -XB -XB -XB1
-QB -QB
9 ~ - ~
47 509 +
VF
-KA1
-XB5 22
47 47 -XB5
-MS
48 *C)
10 510 508 12 -BS1
35 25
-XB5 24 21 73
48 48 8 12 12
-KA2
M
35 35 2 2 1 25 25
-XB5 1
19 12 1
512 511 9
-XB5 31 34
19 19 11 9 9
-BP1
-XB4
1
14
78 401 86
27
-XB4
4 12 11
27 27
~
404 +
~ -
-SC
-KA1 -MC
-BP2
-XB5
1
406
14
*I) 14 4
78 405
A2 A1
501 5 12 11 14 14 3 1 4 4
-BP3
407
14
2
~ +
12 11 -RL1
~ -
-BP1 -XB2 -XB2
37 37 -KA2 -XB5 -BT1
-XB4
6 -XB5
20 74 513
514 70 201 10
37
21
3 1 11 12 44 43
22 20 20 14 13 10 10
2 -XB2
1
-KA2
-BT2
-XB4
3 202
-XB5
2 -BP2 -XB4
2
-XB5
77 203 49
505 79
502 403 402
44 43 49 49
A2 A1 21 22 3
5
-BP3
3
-XB5
21 22
~ +
3
-XB5
3
~ +
-XB15 -XB15
~
-
4 3 3 -TR5
-XB17
~ - -XB17
-
2 46 45
~
2 2 1 46 46 45 45
2 ~
2 -RL2 1
14 +
-XB17
2 1
-XB17 4
1702 1701
BNBU 1
~
2 +
-MU -SO
~ -
-ALSO
44 2 802 801 1 43
1704 RDBK 1703 *B)
44 44
3 1 43 43
-XB8 -XB8
5
¦ÿ
F1
2
-XB18 -XB18
1
1802 1801
¦ÿ
F2 F1
~ +
¦ÿ -BB1 -SO
F2 F1 -XB61 -XB61
-XB5 -KA2 -XB5
16
75 506
515 31
6103
6104
4 3 6 21 22 15 31 31
4 3
~ - ~ +
*AND)
-DR
N -BM
~
-
-TR1
RS-485
Serial
Communication
Line-
XB1
-XB19

I
+12V
*J)
30
-
41A 41
515 - -LHMI
+V ~
30 30
~ 41 41
-MO1
1901 +
B A+ B
F1 F1 F1
A -PGD3 A -PGD2 A 1 5 5 A
-PGD1
-XB19
¦ÿ ¦ÿ ¦ÿ
F2 B F2 B B 7
1902
2 15 15
~ -
~ +
-BB1 -SO
-TR2 -XB61 -XB61
-
15 44 43
13A 6108 6107
~ 7
44 44 8 43 43
~ 8 7
-MO2
+
-BS2
34 24
*E,F)
34 34
3 -BS2
4 24 24 -BM
36 26 13
36 36
1 2 26 26
13 13
19 9
Electrical control diagram of withdrawable HD4 circuit breaker (standard version 6NO6NC)
Electrical schematic

HD4 Sulfur Hexafluoride Circuit Breaker Product Manual 20
Machine Translated by Google
-XB1 -XB -QB -XB -XB1
18 6102 6101 8
-XB61 -XB61
2 2 -BB1 1
18 18 1 8 8
(1-6C)
4 3
46 6106 6105 45
-XB61
*
-XB61
46 46 6 6 5 5 45 45
(1-8A)
8 7
33 6110 6109 23
-XB61 -XB61
33 33 10 10 9 23
9 23
15 6112 6111 5
-XB61 *
-XB61
15
12 12 11
15 -XB63
11 5 5
16 6302 6301 6
-XB63
16 16 2 16 15 6 6
1
*H)
38 6304 6303 28
-XB63
-XB63
38 38 4 18 17 28
3 28
13 6305
-XB63
*
13 13 5 20 19
39 6202 -BB2
6201 29
-XB62
-XB62
39 39 2 2 1 29
1 29
17 6204 6203 7
-XB62
-XB62
17 17 4 4 3 3 7 7
42 6208 6207 32
-XB62
-XB62
42 42 8 8 7 7 32 32
22 6210 6209 11
-XB62
22 22 10 10 9 11 11
9
21 6212
-XB62
21 21 12 12 11
50 702 701
-BT2
-XB7 -XB7
50 50 2 14 13
1
51 703
-BT1
-XB7
51 51 3 14 13
32
53 5 705 704 52
-XB7 -XB7
24 -BT2 23
53 53 4 52 52
54 6 706
-XB7 -BT1
24 23
54 54
56 708 707 55
8
*G)
-XB7
-XB7 54 -BT1 53
56 56 55 55
7
58 10 710 709 57
-XB7 54 -XB7
58 58 53 9 57 57
-BT2
51
1 1
40 40
Electrical control diagram of withdrawable HD4 circuit breaker (standard version 6NO6NC)
21 Electrical schematic
Machine Translated by Google
-XB1 -XB -XB -XB1 -XB1 -XB -XB -XB1
-QB -QB
~ -
47 9 ~ +
509 VF
-KA1
47 47 -XB5 22
-XB5
-MS
48 *C)
10 510 508 12 -BS1
35 25
-XB5 -KA2
24 21 73
48 48 8 12 12
M
35 35 2 2 1 25 25
-XB5 1
19 12 1
512 511 9
-XB5 31 34
19 19 11 9 9
-BP1
-XB4
1
14
78 401 86
27
-XB4
4 12 11
27 27
~
404 +
~ -
-SC
-KA1 -MC
-BP2
-XB5
1
406
14
*I) 14 4
78 405
A2 A1
501 5 12 11 14 14 3 1 4 4
-BP3
407
14
2
~ +
-BP1
12 11 -RL1
~ -
-XB2 -XB2
37 37 -KA2 -XB5 -BT1
-XB4
6 -XB5
20 74 513
514 70 201 10
37
21 22
3 1 11 12 44 -BT2
43
20 20 14 13 10 10
2 -XB2
1
-KA2
-XB4
3 202
-XB5
2 -BP2
-XB5 -XB4
2
77 203 49
505 79
502 403 402
44 43 49 49
A2 A1 21 22 3
5
-BP3
3
-XB5
21 22
~ +
3
-XB5
3
~ +
-XB15 -XB15
~
-
4 3 3 -TR5
-XB17
~ - -XB17
-
2 46 45
~
2 2 1 46 46 45 45
2 ~
2 -RL2 1
14 +
-XB17
2 1
-XB17 4
1702 1701
BNBU 1
2 ~ +
-MU -SO
~ -
-ALSO
44 2 802 801 1 43
1704 RDBK 1703 *B)
44 44
3 1 43 43
-XB8 -XB8
5
¦ÿ
F1
2
-XB18 -XB18
1
1802 1801
¦ÿ
F2 F1
~ +
¦ÿ -BB1 -SO
F2 F1 -XB61 -XB61
-XB5 -KA2 -XB5
16
75 515
506 31
6103
6104
4 3 6 21 22 15 31 31
4 3
-~ ~ +
*AND)
N -DR
-BM
~
-
-TR1
RS-485
Serial
Communication
Line-
XB1
-XB19

I
+12V
*J)
30
-
41A 41
515 - -LHMI
+V ~
30 30
~ 41 41
-MO1
1901 +
B A+ B
F1 F1 F1
AWAY-PGD3 AWAY-PGD2 AWAY-PGD1 -XB19
1 5 5 A
¦ÿ ¦ÿ ¦ÿ
F2 F2 7
1902
2 15 15
~
- ~ +
-BB1 -SO
-TR2 -XB61 -XB61
-
15 44 43
13A 6108 6107
~ 7
44 44 8 43 43
~ 8 7
-MO2
+
-BS2
34 24
*E,F)
34 34
3 -BS2
4 24 24 -BM
36 26 13
36 36
1 2 26 26
13 13
19 9
Electrical control diagram of withdrawable HD4 circuit breaker (8NO8NC)
HD4 Sulfur Hexafluoride Circuit Breaker Product Manual 22
Machine Translated by Google
-XB1 -XB -XB -XB1 -XB1 -XB -XB -XB1
-QB -QB
5
24 23 4
53 53 52 52
6
18 18 2 2 1 1 8 8
24 23
54 54
8
*G) 4
54
3
56 56 53 55 55
7
*
10
46 46 6 6 5 5 45 45
54 53
58 58 9 57 57
8 7
51
33 33 10 10 9 23
9 23
1 1
*
12 12 11
15 15 -XB63
11 5 5
40 40
2 16 15
16 16 1 6 6
*H)
38 38 4 18 17 28
3 28
*
13 13 5 20 19
39 39 2 2 1 29
1 29
17 17
4 4 3 7 7
3
42 42 8 8 7 7 32 32
2 14 13 59
60 60 1 59
3 16 15
61 61
5 18 17 62
63 63 4 62
6 20 19
64 64
22 22 10 10 9 9 11 11
12 12 11
21 21
2 14 13
50 50 1
3 14 13
51 51
32
Electrical control diagram of withdrawable HD4 circuit breaker (8NO8NC)
23 Electrical schematic
Machine Translated by Google
Machine Translated by Google
24 HD4 Sulfur Hexafluoride Circuit Breaker Product Manual

Actuator status At 450 kPa, contacts 21-22-24 are original from the illustration

• The circuit breaker is open and in the working position location switch. If the gas pressure recovers from the absolute value

• Control circuit not powered of 450 kPa to the absolute value of 480 kPa, touch

• The closing spring is not charged Click to return to original state

• The gas pressure is at the rated use value (at 20°C, the absolute value is 550 -KA1 = When the air pressure is low, the auxiliary switch activated by the pressure switch contact

kPaÿ auxiliary relay

-KA2 = When the air pressure is insufficient, the auxiliary activated by the pressure switch contact

The standard configuration auxiliary relay

Fig. -MS Energy storage motor -MS = closed spring charging motor (see "Note" C)

1 Fig. -MC Parallel brake release -QB = main circuit breaker

2 Fig. -RL1 Closing and blocking electromagnet -BB1-BB2 = auxiliary contacts of circuit breaker

3 Fig. -MO1 1st parallel opening release -BS1 = limit switch for spring-loaded motor

7 Fig. -BP1...-BP3 pressure switch -BS2 = closing spring charged/uncharged signaling contact

Figure 19 -BS2charged/uncharged signal contact


14 Closing spring -BT1 = circuit breaker trolley operating position signal contact (see "Note

Fig. 32 -BB1, -BB2 circuit breaker auxiliary switch meaning "G)

Fig. 51 -BT1, -BT2 circuit breaker trolley in working and isolating position -BT2 = circuit breaker trolley isolated position signaling contact (see "Note

time signal meaning "G)

SC = button or contact for closing the circuit breaker

incompatibility SO = circuit breaker opening button or contact

On the same circuit breaker, the control circuits shown in the following figures are not compatible -TR1, TR2 = Rectifiers for parallel opening releases -MO1 and -MO2

A decent 5-9. -TR5 = Blocking Solenoid - Rectifier for RL2

XB = Plug for the control circuit of the circuit breaker trolley

Electrical Control Diagram Description -XB1 = terminal block on switchgear (outside of circuit breaker trolley)

Figure = Closing spring charged motor circuit (see Note C) -XB2...XB64 = Auxiliary connector in the secondary circuit

1 Figure = Parallel gate circuit -MC = in combination with the brake release

2 Figure 3 = latching electromagnet, mechanical latching of circuit breaker in the event of a loss of power -RL1 = closing blocking solenoid

Can't close -RL2 = Circuit breaker trolley lockout solenoid

Figure 4 = latching electromagnet, mechanical latching of circuit breaker in the event of a loss of power -MO1 = 1st shunt opening release (see "Note" E)

trolley roll in/roll in (see "NOTE" H) -MO2 = second parallel opening release (see "Notes" E, F)

Figure = undervoltage release (see Note B) -MU = undervoltage release (see Note B)

5 Figure = 1st shunt opening release (see "Note" E) -VF = filter

7 Figure = 2nd shunt opening release (see "Notes" E, F) -PGD1...-PGD3= Gas pressure digital indicator

9 Figure 14 = Gas pressure control circuit consisting of the following devices (see -ALSO = Gas pressure digital indicator power adapter

“Caution” I): -DR = Gas Pressure HMI Display Power Adapter

• When the gas pressure is lower than the minimum functional pressure, KA2 -LHMI = Gas pressure HMI display, installed in switchgear

Relay blocking circuit breaker closing and opening function Low pressure room panel

• Provides signal contacts for normal, low, and insufficient air pressure

• See related entry for pressure switch action value Optional

Figure 15 = Gas density digital display RS-485 communication (see "Notes" Figure -RL2 Circuit breaker handcart locking electromagnet

meaning" J) 4 Figure -MU Undervoltage release

Figure 16 = gas density digital display 5 Figure -MO2 The second parallel opening release

Figure 19 = closing spring charged/uncharged signaling contact 9 Figure -PGD1...-PGD3 Gas density digital display RS-485 communication

Figure 32 = circuit breaker closed/open status signaling contact 15 Figure 16 -PGD1...-PGD3 Gas Density Digital Display

Figure 51 = Signal contact when the circuit breaker trolley is in the working and isolating positions

point (see "NOTE" G) Notice

A) The secondary components of the circuit breaker can only be ordered by the manufacturer

Alpha/Numeric Symbol Description Equipped, please refer to the product manual when compiling an order.

ÿ = wiring diagram number


*
= see the "NOTE" item to which the letter refers B) The undervoltage release is powered by an independent power supply, or powered by the power supply side,

BM = shunt opening release circuit breakage monitoring device (see The release is instantaneous action, the closing of the circuit breaker can only be

"Caution" E) It is realized when the button is excited and energized (mechanical locking).

-BP1...BP3= Pressure switch fixed on L1-L2-L3 poles, it has

There are two levels of action air pressure setting: C) To verify whether the power supply capacity of the auxiliary circuit allows to start more than one at the same time

• 1st: Action in case of low air pressure: When the air pressure Possibility of working with the energy storage motor of the closing spring. in order to avoid

Decrease from 550 kPa absolute to 480 kPa absolute, contacts Excessive power consumption, before supplying power to the auxiliary circuit, it is recommended to

11-12-14 from the original position shown in the figure Charge the spring manually.

set switch. If the air pressure opens from an absolute value of 480 kPa

When it returns to the absolute value of 510 kPa, the contact returns E) The disconnection monitoring of the winding circuit of the parallel opening release must be carried out in this way

original state mode, when the auxiliary power supply voltage is lower than 220 V, connect it in parallel

• Second: Action in case of insufficient air pressure: When the gas The monitoring circuit current of the gate release must not exceed 20 mA. when assisting

Pressure reduction from 550 kPa absolute to absolute value The power supply voltage is higher than or equal to 220 V, connected to the parallel opening release
Machine Translated by Google
Electrical schematic 25

The monitoring loop current cannot exceed 10 mA. I) Pins 27 and 37 in Figure 14 are only used for functional testing of relays KA1 and KA2, and should not

be powered during normal operation. During the test, apply corresponding voltage between pins

F) The second opening release in parallel is optional. It is necessary to expand the auxiliary contact of 2-27 and 2-37 respectively, and the relay operates normally, and vice versa.

the air pressure insufficient relay KA2 outside the circuit breaker to block the circuit and ensure

that the circuit breaker cannot be opened when the air pressure is insufficient.

J) When the RS-485 serial communication bus is connected in parallel, pay attention to the positive and negative polarity to prevent reverse

G) The position where the circuit breaker trolley is rocked/rolled in along the guide rail The signal contacts connection and short-circuit connection, and prevent the external auxiliary power supply from being connected by mistake. It is

(BT1 and BT2 in Figure 51) are installed on the circuit breaker trolley. recommended to use shielded twisted pair for connection.

H) When Figure 4 is used, the contacts (pins 45-46) of BB1 in Figure 32 are occupied. When Figure 9 is

selected, the contacts (13 pins) of BB1 in Figure 32 are occupied. When Figure 15 is selected,

the contacts (pins 5-15) of BB1 in Figure 32 are occupied.


-XB1 -XB -XB -XB1 -XB1 -XB -XB -XB1
-QB -QB
~ -
47 9 509 ~ +
VF
-KA1
-XB5 22
47 47 -XB5
-MS
48 *C)
10 510 508 12 -BS1
35 25
-XB5 24 21 73
48 48 8 12 12
-KA2
M
35 35 2 2 1 25 25
-XB5 1
19 12 1
512 511 9
-XB5 31 34
19 19 11 9 9
-BP1
-XB4
1
14
78 401 86
27
-XB4
4 12 11
27 27
~
404 +
~ -
-SC
-KA1 -MC
-BP2
-XB5
1
406
14
*I) 14 4
78 405
A2 A1
501 5 12 11 14 14 3 1 4 4
-BP3
407
14
2
12 11
-BP1
37 37 -XB4
6
37
~ +
-RL1
21 ~ -
22
-KA2 -XB5
-XB5
-KA2
-XB4
3
-XB5 -XB5
2 -BP2
-XB4
2
20 74 514 513 10
505 79
502 403 402 77 3 1
20 20 14 11 12 13 10 10
A2 A1 21 22
5
-BP3
-XB5
21 22 3
~ +
3
-XB5
3 ~ +
-MU -SO
~ -
4 3 3
-XB17 2
- -XB17 44 802 801 1 43
*B)
2
44 44
3 1 43 43
-XB8 -XB8
2 2 1
2
14 5
2
-XB17 -XB17
1
1702 1701
BNBU
-ALSO
1704 RDBK 1703
¦ÿ
F1
2
-XB18 -XB18
1
1802 1801
¦ÿ ~ +
F2 F1 -BB1 -SO
-XB61
4 -XB61
-XB5 -KA2 -XB5
75 506
515 31
6103
6104
¦ÿ 4 3 6 21 22 15 31 31
F2 F1 3
16
~ - ~ +
*AND)
-BM
~
-
-TR1
-
30 41
41A
-DR ~
N 30 30
~ 41 41
-MO1
RS-485
Serial
Communication
Line-
XB1
-XB19

I
+12V
*J)

+
515 - -LHMI
+V
1901 7
A+ A B
B F1 F1 F1
A -PGD3 A -PGD2 A 1 5 5
-PGD1
-XB19
¦ÿ ¦ÿ ¦ÿ
F2 B F2 B B
1902
~ -
~ +
2 15 15 -BB1 -SO
-TR2 -XB61 -XB61
-
44 6107 43
13A 6108
15 ~
44 44 8 7 43 43
~ 8 7
-MO2
+
-BS2
34 24
*E,F)
34 34
3 -BS2
4 24 24
-BM
36 26 13
36 36
1 2 26 26
13 13
19 9
Fixed HD4 circuit breaker electrical control diagram
HD4 Sulfur Hexafluoride Circuit Breaker Product Manual 26
Machine Translated by Google
-XB1 -XB -XB -XB1
-QB
18 18
4 2 1 8 8
3
4 3
46 46
6 6 5 45 45
5
8 7
10 10 9
33 33 23 23
*
12 12 11
15 15 5 5
2 14 13
50 50 49 49
4 16 15
16 16 3 6 6
6 18 17
38 38 5 28 28
*
8 20 19
13 13
*H)
39 39
2 2 1 29 29
17 17
4 4 3 7 7
52 52
6 6 5 51 51
5
42 42
8 8 7 32 32
7
12 12 11
54 54 53 53
2 16 15
56 56 55 55
4 18 17
22 22 3 11 11
5 20 19
21 21
32
1 1
40 40
Fixed HD4 circuit breaker electrical control diagram
27 Electrical schematic
Machine Translated by Google
Machine Translated by Google
28 HD4 Sulfur Hexafluoride Circuit Breaker Product Manual

Actuator status -KA1 = When the air pressure is low, the auxiliary switch activated by the pressure switch contact

• The circuit breaker is open and in the working position auxiliary relay

• Control circuit not powered -KA2 = When the air pressure is insufficient, the auxiliary activated by the pressure switch contact

• The closing spring is not charged auxiliary relay

• The gas pressure is at the rated use value (at 20°C, the absolute value is 550 -MS = closed spring charging motor (see "Note" C)

kPaÿ -QB = main circuit breaker

-BB1-BB2 = auxiliary contacts of circuit breaker

The standard configuration -BS1 = limit switch for spring-loaded motor

Figure -MS Energy storage motor -BS2 = closing spring charged/uncharged signaling contact

1 Figure -MC Parallel brake release SC = button or contact for closing the circuit breaker

2 Figure -RL1 Closing and blocking electromagnet SO = circuit breaker opening button or contact

3 Figure -MO1 1st parallel opening release -TR1, TR2 = Rectifiers for parallel opening releases -MO1 and -MO2

7 Figure -BP1...-BP3 pressure switch XB = Plug for the control circuit of the circuit breaker trolley

14 Figure -BS2 Closing spring charged/uncharged signal contact -XB1 = terminal block on switchgear (outside of circuit breaker trolley)

19 Figure 32 -BB1, -BB2 circuit breaker auxiliary switch -XB2...XB64 = Auxiliary connector in the secondary circuit

-MC = in combination with the brake release

incompatibility -RL1 = closing blocking solenoid

On the same circuit breaker, the control circuits shown in the following figures are not compatible -RL2 = Circuit breaker trolley lockout solenoid

A decent 5-9. -MO1 = 1st shunt opening release (see "Note" E)

-MO2 = second parallel opening release (see "Notes" E, F)

Electrical Control Diagram Description -MU = undervoltage release (see Note B)

Figure = Closing spring charged motor circuit (see Note C) -VF = filter

1 Figure = Parallel gate circuit -PGD1...-PGD3= Gas pressure digital indicator

2 Figure 3 = latching electromagnet, mechanical latching of circuit breaker in the event of a loss of power -ALSO = Gas pressure digital indicator power adapter

Can't close -DR = Gas Pressure HMI Display Power Adapter

Figure = undervoltage release (see Note B) -LHMI = Gas Pressure Human Machine Interface Display, installed in switchgear

5 Figure = 1st shunt opening release (see "Note" E) Low pressure room panel

7 Figure = 2nd shunt opening release (see "Notes" E, F)

9 Figure 14 = Gas pressure control circuit consisting of the following devices (see Optional

“Caution” I): Figure -MU Undervoltage release

• When the gas pressure is lower than the minimum functional pressure, KA2 5 Figure -MO2 The second parallel opening release

Relay blocking circuit breaker closing and opening function 9 Figure -PGD1...-PGD3 Gas density digital display RS-485 communication

• Provides signal contacts for normal, low, and insufficient air pressure 15 Figure 16 -PGD1...-PGD3 Gas Density Digital Display

• See related entry for pressure switch action value

Figure 15 = Gas density digital display RS-485 communication (see "Notes" Notice

meaning" J) A) The secondary components of the circuit breaker can only be ordered by the manufacturer

Figure 16 = gas density digital display Equipped, please refer to the product manual when compiling an order.

Figure 19 = closing spring charged/uncharged signaling contact

Figure 32 = circuit breaker closed/open status signaling contact B) The undervoltage release is powered by an independent power supply, or powered by the power supply side,

The release is instantaneous action, the closing of the circuit breaker can only be

Alpha/Numeric Symbol Description It is realized when the button is excited and energized (mechanical locking).

ÿ = wiring diagram number


*
= see the "NOTE" item to which the letter refers C) To verify whether the power supply capacity of the auxiliary circuit allows to start more than one at the same time

BM = shunt opening release circuit breakage monitoring device (see " Possibility of working with the energy storage motor of the closing spring. in order to avoid

Attention "E) Excessive power consumption, before supplying power to the auxiliary circuit, it is recommended to

-BP1...BP3= Pressure switch fixed on L1-L2-L3 poles, it has Charge the spring manually.

There are two levels of action air pressure setting:

• 1st: Action in case of low air pressure: When the air pressure E) The disconnection monitoring of the winding circuit of the parallel opening release must be carried out in this way

Reduced from 550 kPa absolute to 480 kPa absolute, contacts mode, when the auxiliary power supply voltage is lower than 220 V, connect it in parallel

11-12-14 are The monitoring circuit current of the gate release must not exceed 20 mA. Dangsuke

location switch. If the air pressure starts to recover from the absolute Auxiliary power supply voltage higher than or equal to 220 V, connected in parallel to trip

value of 480 kPa to the absolute value of 510 kPa, the touch The monitor loop current of the device must not exceed 10 mA.

Click to return to original state

• Second: Action in case of insufficient air pressure: When the gas F) Optional parallel second opening release, which needs to be expanded outside the circuit breaker

Pressure reduction from 550 kPa absolute to absolute value The auxiliary contact of the undervoltage relay KA2 is used to block the circuit,

At 450 kPa, contacts 21-22-24 are original from the illustration Make sure that the circuit breaker cannot be opened when the air pressure is insufficient.

location switch. If the gas pressure recovers from the absolute value

of 450 kPa to the absolute value of 480 kPa, touch H) When Figure 4 is used, the contacts of BB1 in Figure 32 (45-46

needle) is occupied. When Figure 9 is selected, the contacts of BB1 in Figure 32


Click to return to original state
(pin 13) is occupied. When selecting Figure 15, BB1 in Figure 32

of contacts (pins 5-15) are occupied.


Machine Translated by Google
Electrical schematic 29

I) Pins 27 and 37 in Figure 14 are only used for functional testing of relays KA1 and KA2,

and should not be powered during normal operation. During the test, apply

corresponding voltage between pins 2-27 and 2-37 respectively, and the relay

operates normally, and vice versa.

J) When the RS-485 serial communication bus is connected in parallel, pay attention to the positive and negative polarity to prevent reverse

connection and short-circuit connection, and prevent the external auxiliary power supply from being connected by mistake. It is

recommended to use shielded twisted pair for connection.


Machine Translated by Google
30 HD4 Sulfur Hexafluoride Circuit Breaker Product Manual

Electrical graphic symbols

Connect the chassis

Thermal effect
to the bottom plate

Electromagnetic effect Conductors in shielded wire (two shown)

delay connect

push action Terminal

key operation Receptacles and Plugs (Female and Male)

ground (general symbol) Resistor (generic symbol)

Capacitor (general symbol)


Temporarily closed transitional contact when

the operator is released

Motor (general symbol) position switch, moving contact

Bridge Full Wave Rectifier position switch, break contact

Circuit breakers with automatic release


Moving (normally open) contacts triggered by built-in measuring relays or
trip units

Break (normally closed) contact Operating device (general symbol)

Break-before-make changeover contacts Lamp (general symbol)


Machine Translated by Google

ABB
— Connect
your one-stop digital assistant

Quickly and easily access and use ABB electrical information in the office, field or on the go.

• Convenient search function

• Find complete ABB electrical content: product catalogs, industry applications, installation instructions, selection guides,

Services and common tool connections, etc.

• Save frequently used data on the device and automatically update •

Customize the types of messages you expect to receive • Online customer

service support

ABB Connect is available on iOS, Android and Windows 10 devices

Scan the QR
code to enter ABB Connect

Technical data and certificates

Products, Industries and Services

sample

tool

save document

personal workspace

contact us

News & Events


Machine Translated by Google

Xiamen ABB Switchgear Co.,

Ltd. No. 885, Fangshan West 2nd Road, Xiang'an

District, Xiamen City, Fujian Province Postcode: 361101

Tel: 0592 602 6033 Fax: 0592 603 0505

ABB (China) Customer


Service Hotline : 800-820-9696
400-820-9696 Email: cn-ep-hotline@abb.com

www.abb.com.cn

ABB Electric official WeChat ABB through train ABB China Customer Service Center

The product information contained in the catalog is subject to the actual product. If there is any change

without prior notice, ABB (China) Co., Ltd. has the final right of interpretation.