You are on page 1of 2

4 ×30 TR=120 TR(−25° C)

12000 BTU / H 1,055 KJ / H H KJ


120 TR × × × =422 =422 KW
TR BTU / H 3600 s S
1 ×4 0 TR=4 0 TR(−18 ° C)
12000 BTU / H 1,055 KJ / H H KJ
40 TR × × × =140,66 =140,66 KW
TR BTU /H 3600 s S
Qeva(−25 ° C)=mbaja(−25 ° C) ×(hn−hm )
422 KJ / S Kg
Mbaja(−25 ° C )= =0,9527
KJ S
(489,778−46,84 )
Kg
Qeva(−18 ° C )=mbaja(−18° C) ×( hl−h k )
140,66 KJ /S Kg
Mbaja(−18 ° C )= =0,3006
KJ S
(514,624−46,84 )
Kg
Kg Kg Kg
Mtotal=0,9527 + 0,3006 =1,2533 (desplazamiento de las bomba)
S S S
Vr de eb
M b= × Nv
V esp asp
Mb ×V esp asp
Vr de eb=
Nv

1,07538 Kg/S ×1,15868 m3 /Kg m3


Vr de eb= =1,2714
0,98 S

m3 m3
1,2714 ÷3 compresores (tornillo)=0,4238
S S
1,2533 Kg/S Kg
Fvapor al comp= =0,3133
4 S
Vr de eb
Mb= × Nv
V esp asp
Mb ×V esp asp
Vr de eb=
Nv

0,3133 Kg/ S ×1,15868 m3 /Kg m3


Vr de eb= =0,37
0,98 S
3 3
100 % 0,4238 m / s 100 % ×0,37 m / s
→ 3
= 3
=87,3 % ¿
x 0,37 m / s 0,4238 m /s

You might also like