:STC-QA&QC/FRM-007
Stecon Electromechanical Contracting L.L.C
Rev :00
CLIENT
STRUCTURE RECEIPT REPORT Date: Jan 01, 2014
Page: I of 1
Reference Drawings:
1 Structural Steel received, verified the tags correct and there is no physical
damage on it
(Checked
see remarks if anysteel
structural damage found
surface )
coating / painting when received ( see remarks
2
if any damage found)
3 Initial bolt tightness (bolt code system)
10 Tightness of holding down bolts, after 72 hours of grout cured (if applicable)
Tolerances
a) Beams:-
The maximum tolerance for level and alignment is + 5 mm on any particular floor / tier of the
structure.
The maximum differential between connecting beams and adjacent beams is < 2mm.
b) Stanchions:-
The distance between the centers of adjacent stanchions at any one floor / tier level is < 5
mm.
The cumulative tolerance over 3 or more bays is as following.
Over 30 m = + 10 mm
Remarks:-