You are on page 1of 6

HDI-040 Module Description

32 CHANNEL DIGITAL INPUT MODULE


DC
-+ Ch 1 +

Ch 1 -
DC
-+ Ch 2 +

Ch 2 -
DC
-+ Ch 3 +

Ch 3 -

32 Similar Channels

DC
-+ Ch 31 +

Ch 31 -
DC
-+ Ch 32 +

Ch 32 -

Introduction
Features
Contact:
The HDI-040 is a 32 channel digital input Status or Contact Monitoring sales@microsol.com
module for contact or voltage monitoring. www.microsol.com
It can also be used as a low frequency Differential Voltage Input
pulse counter (up to 60 Hz).
High Noise Immunity
The HDI-040 Module is suitable for
Approved to Industry Standards
operation at 48 volt nominal field voltage.
48 Volt Nominal Field Voltage

Supports 1 ms time tagging No part of this document


should be reproduced
5 KV isolation without the prior approval
of Microsol
HDI-040 Module Description 1.00

I/O Connections

Figure 1 - HDI-040 Connection Diagram

Page 2 of 6
HDI-040 Module Description 1.00

Module Interface Characteristics

Figure 2 - HDI-040 Interface Diagram

Page 3 of 6
HDI-040 Module Description 1.00

Module Jumpers
The HDI-040 32-channel digital input module has one jumper as shown in the diagram below and the
function of which is given in the associated table.

JP1

Figure 3 - HDI-040 Jumper Positions

Page 4 of 6
HDI-040 Module Description 1.00

Module Jumper Settings

Link Position Function


JP1 Back-plane Slot Select

No Jumper Slots 1 & 2 Selected

Jumper Linked Slots 3 & 4 Selected

Note: It is imperative that this link is in the correct


I/O Slots
Processor
position for the I/O module slot within the cell into Module 1
2
which the HDI-040 is inserted. An incorrect position 3
4
for this link WILL cause the XCell to report incorrect
values for these inputs and may affect reports from
other modules.

Module Troubleshooting
This section provides some basic information about troubleshooting the operation of the HDI-040
module.

Symptoms Possible Cause Possible Action


Error message when downloading The hardware configuration has Verify and save the hardware
a configuration not been saved configuration
No input seems to be detected The card or channel has no Verify the LED display. Verify
incoming DC supply or the presence of external DC.
reference to ground Verify the reference to ground.
Verify the jumper settings on
the card.
No inputs are reported via a Incorrect protocol configuration Using Workbench, visualise the
protocol IO module and verify the correct
operation of the channel. Then
check the protocol
Inputs are detected, but the Possible overlap in the protocol Verify the integrity of the
wrong message is reported via configuration protocol mapping
the protocol

Page 5 of 6
HDI-040 Module Description 1.00

Technical Characteristics
Module Related Data
Number of Inputs 32
Type of Input Differential
Indication processing Single, fleeting, double indications, BCD, TAP, counter
Differential voltage between inputs max. 130 V
Isolation 5 kVpp channel to cell
130 V channel to chassis (ground)
Module Power consumption ( at CPR input) 0.15 W
Field Power consumption – all inputs ON @ 48V 8.2 W
Input Voltage and Currents
Nominal Input Voltage (Field Voltage) 48V DC
Input resistance 9 kΩ
Nominal Value “On” state 22 - 72V
Nominal Value “Off” state 0–4V
Filter Times, Acquisition Times
Input Detection Accuracy 1 ms
Time Stamp Resolution 1 ms
Software Input Filter (fixed) 10 ms
User Configurable Validation Filter 0 ms to 60 s
Indications and Diagnostics
Process Indications 32 green LEDs on associated CPR module reflect the channel status
Electrical Noise Immunity
High Frequency disturbance • IEC 60255-22- 1 Class 3 and C37.90.1
Fast Transient disturbance • IEC 61000-4-4 Class 4 and C37.90.1
Electrostatic Discharge • IEC 61000-4-2
RFI Susceptibility • IEC 61000-4-3 CISPR 22
EMC Compliance • IEC 60255-22-3, EN50082-2
UK National Grid Company NGTS 2.13 • Class Z
Environmental Conditions
Temperature
• Continuous Operation • -10° to +60° C
• Transportation and storage • -40° to +70° C
• IEC 60068-2-1 & IEC 60068-2-2
Relative Humidity • 0 to 95% non-condensing
• IEC 60068-2-3 & IEC 60068-2-30
Vibration • IEC 60068-2-6
Drop & Topple • IEC 60068-2-31
MTBF
MTBF for continuous operation at average 270,080 hours
temperature of 40°C
Dimensions and Weight
Dimensions (W * H * D) 5 hp x 6U (1 x 10.5 x 6.7 inches) / (25.4 x 266.7 x 170mm)
Weight Approx. 0.55 lbs / 250 grams

Email: sales@microsol.com Web: www.microsol.com


© Microsol Ltd. 2005 the information in this document is subject to change without prior
notice. Microsol does not assume responsibility for any errors in fact or design in this
publication. The publication is provided for general information only and shall not form part
of any contract.
HDI-040 Module Description issue Rev 1.00

Page 6 of 6

You might also like