Professional Documents
Culture Documents
Ch 1 -
DC
-+ Ch 2 +
Ch 2 -
DC
-+ Ch 3 +
Ch 3 -
32 Similar Channels
DC
-+ Ch 31 +
Ch 31 -
DC
-+ Ch 32 +
Ch 32 -
Introduction
Features
Contact:
The HDI-040 is a 32 channel digital input Status or Contact Monitoring sales@microsol.com
module for contact or voltage monitoring. www.microsol.com
It can also be used as a low frequency Differential Voltage Input
pulse counter (up to 60 Hz).
High Noise Immunity
The HDI-040 Module is suitable for
Approved to Industry Standards
operation at 48 volt nominal field voltage.
48 Volt Nominal Field Voltage
I/O Connections
Page 2 of 6
HDI-040 Module Description 1.00
Page 3 of 6
HDI-040 Module Description 1.00
Module Jumpers
The HDI-040 32-channel digital input module has one jumper as shown in the diagram below and the
function of which is given in the associated table.
JP1
Page 4 of 6
HDI-040 Module Description 1.00
Module Troubleshooting
This section provides some basic information about troubleshooting the operation of the HDI-040
module.
Page 5 of 6
HDI-040 Module Description 1.00
Technical Characteristics
Module Related Data
Number of Inputs 32
Type of Input Differential
Indication processing Single, fleeting, double indications, BCD, TAP, counter
Differential voltage between inputs max. 130 V
Isolation 5 kVpp channel to cell
130 V channel to chassis (ground)
Module Power consumption ( at CPR input) 0.15 W
Field Power consumption – all inputs ON @ 48V 8.2 W
Input Voltage and Currents
Nominal Input Voltage (Field Voltage) 48V DC
Input resistance 9 kΩ
Nominal Value “On” state 22 - 72V
Nominal Value “Off” state 0–4V
Filter Times, Acquisition Times
Input Detection Accuracy 1 ms
Time Stamp Resolution 1 ms
Software Input Filter (fixed) 10 ms
User Configurable Validation Filter 0 ms to 60 s
Indications and Diagnostics
Process Indications 32 green LEDs on associated CPR module reflect the channel status
Electrical Noise Immunity
High Frequency disturbance • IEC 60255-22- 1 Class 3 and C37.90.1
Fast Transient disturbance • IEC 61000-4-4 Class 4 and C37.90.1
Electrostatic Discharge • IEC 61000-4-2
RFI Susceptibility • IEC 61000-4-3 CISPR 22
EMC Compliance • IEC 60255-22-3, EN50082-2
UK National Grid Company NGTS 2.13 • Class Z
Environmental Conditions
Temperature
• Continuous Operation • -10° to +60° C
• Transportation and storage • -40° to +70° C
• IEC 60068-2-1 & IEC 60068-2-2
Relative Humidity • 0 to 95% non-condensing
• IEC 60068-2-3 & IEC 60068-2-30
Vibration • IEC 60068-2-6
Drop & Topple • IEC 60068-2-31
MTBF
MTBF for continuous operation at average 270,080 hours
temperature of 40°C
Dimensions and Weight
Dimensions (W * H * D) 5 hp x 6U (1 x 10.5 x 6.7 inches) / (25.4 x 266.7 x 170mm)
Weight Approx. 0.55 lbs / 250 grams
Page 6 of 6