Mode Table for Central Clean / Dirty Exhaust (AC-11)

Normal Normal Normal Normal


Activate of 2nd
(FAN (FAN (FAN (FAN Activate of 1st per
FS Zone alarm of FS Zone alarm of FS Zone alarm of FS Zone alarm of FS Zone alarm of FS Zone alarm of per 3 floor probe
FS Module Equipment OFF) ON) OFF) ON) 3 floor probe type VAC Override
1st Floor 2nd Floor 3rd Floor 4th Floor 5th Floor 6th Floor type smoke
(CCMS (CCMS (Local (Local smoke detector
detector
Mode) Mode) Mode) Mode)
YES Central EXF OFF ON OFF ON ON ON ON ON ON ON OFF OFF OFF
By LMCP 2nd per 3 storey interval probe NORMA NORMA NORMA NORMA
NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL ACTIVATE NORMAL NORMAL
Control type smoke detector L L L L
YES 6th Floor Branch CFSD OPEN OPEN OPEN OPEN CLOSE OPEN OPEN OPEN OPEN OPEN OPEN OPEN CLOSE
YES 5th Floor Branch CFSD OPEN OPEN OPEN OPEN OPEN CLOSE OPEN OPEN OPEN OPEN OPEN OPEN CLOSE
YES 4th Floor Branch CFSD OPEN OPEN OPEN OPEN OPEN OPEN CLOSE OPEN OPEN OPEN OPEN OPEN CLOSE
By LMCP 1st per 3 storey interval probe NORMA NORMA NORMA NORMA
NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL ACTIVATE NORMAL
Control type smoke detector L L L L
YES 3rd Floor Branch CFSD OPEN OPEN OPEN OPEN OPEN OPEN OPEN CLOSE OPEN OPEN OPEN OPEN CLOSE
YES 2nd Floor Branch CFSD OPEN OPEN OPEN OPEN OPEN OPEN OPEN OPEN CLOSE OPEN OPEN OPEN CLOSE
YES 1st Floor Branch CFSD OPEN OPEN OPEN OPEN OPEN OPEN OPEN OPEN OPEN CLOSE OPEN OPEN CLOSE