GENERAL NOTES

ST ANDARD 12" VISOR


I. ALL SIGN PANELS USED ON FLASHING BEACONS ARE CLASS II AND SHALL BE
PIPE POST ENTERS i------ TYPICAL SIGNAL HEAD FABRICATED IN ACCORDANCE WITH:
SLIPFITTER COLLAR 12" YELLOW LENS A. PANELS SHALL BE SINGLE SHEET ALUMINUM 0.100 MINIMUM THICKNESS.
APPROXIMATELY 4" DOOR ---~~~-=-.-1r B. BACKING ZEES ARE 3 IN. X 211#16 IN. 2.33 LBS. PER FT. ALUMINUM.
t FASTENER C. ALL SIGNS SHALL BE FABRICATED USING RETRDREFLECTIVE SHEETING CONFORMING
TD ASTM D4956. THE TYPE SHALL BE DESCRIBED IN THE STANDARD
12"
TYPICAL SIGNAL HEAD SPECIFICATIONS AND/DR AS SHOWN ON THE PLANS.
12" YELLOW DR RED LENS D. BOLTS, U-CLAMPS, NUTS AND METAL WASHERS SHALL BE GALVANIZED
DOOR WITH 150 WATT LAMP DR CADMIUM PLATED.
N
~ HINGE DR !TE AMBER LED
2. INSTALLATION DESIGN CONFORMS WITH AASHTD "STANDARD SPECIFICATIONS FDR
0
N
ATTACH SIGNAL HEAD STRUCTURAL SUPPORTS FDR HIGHWAY SIGNS, LUMINAIRES AND TRAFFIC SIGNALS"
PANEL ATTACHMENT
(SEE DETAILS)
WITH !V2" CLOSE NIPPLE
AND PIPE LOCKNUT
_J l;::!=::::::::~::;r ANO SHALL BE FABRICATED IN ACCORDANCE WITH:
A. STEEL PIPE, PDST ANCHOR PLATES AND BREAK- AWAY PLATES SHALL
PLUG UNUSED OPENINGS CONFORM TD AASHTD M270 (ASTM A709) GRADE 36.
Lt') B. HIGH STRENGTH BDLTS, NUTS AND WASHERS SHALL CONFORM TD ASTM- A325
>-- N
AND SHALL BE GALVANIZED DR CADMIUM PLATED.
SLIPFITTER COLLAR FDR 4" C. HOLES SHALL BE DRILLED AND CUTS SHALL PREFERABLY BE SAW CUTS;
STD. STEEL PIPE (4Y2" O.D.)
HOWEVER,FLAME CUTTING WILL BE PERMITTED PROVIDED ALL EDGES ARE
GROUND. METAL SHALL NOT PROJECT BEYOND THE PLANE OF THE PLATE FACE
%" SET SCREWS
X
~
0
ON BREAK- AWAY PLATES.
N
TYPICAL SIGNAL HEAD - 12 INCH LENS D. ALL WELDING IS TD BE CONTINUOUS AND IN ACCORDANCE WITH CURRENT
AWS SPECIFICATIONS.
E. A "KEEPER PLATE" OF THIN (28 GAGE) GALVANIZED SHEET METAL,
FABRICATED TD MATCH BREAK- AWAY PLATE DIMENSIONS BUT WITH
HOLES RATHER THAN SLDTS, SHALL BE USED TD RESTRAIN BOLT LOOSENING
4" STD. STEEL PIPE DUE TD WIND VIBRATION.
WT. 10.79 LBS./FT. - - - - - BACKING ZEE - - - - -
4" I•
. * • !• *• * •
I• !• * •! 4" • F. PIPE LENGTH VARIES WITH VERTICAL PLACEMENT, MINIMUM GROUND
CLEARANCE (7 FT. ) AND THE SIGN PANEL REQUIRED. IT WILL BE AS
SHOWN ON THE PLANS, DR AS DETERMINED BY CROSS-SECTION, DR AS
DIRECTED BY THE ENGINEER FOR EACH LOCATION (MAXIMUM LENGTH
IS APPROXIMATELY 20 FT.-10 IN. AND MINIMUM LENGTH IS APPROXIMATELY
BREAK-AWAY ASSEMBLY 15 FT.-4 IN. IF LENGTH IS NOT SPECIFIED SUPPLY MAXIMUM - MAY REQUIRE
(SEE NOTE 5 AND DETAIL ON SHEET 2) *= 611 INCREMENTS FIELD CUT TD CONFORM TD TYPICAL SIGN PLACEMENT DETAILS).
(DRILL %" HOLES FOR NUMBER 3. CONCRETE FOOTINGS FDR FLASHING BEACON INSTALLATIONS SHALL CONFORM TD
ATTACH GROUNDING
CABLE BY LUG "DRILLED CAISSONS" AND "STRUCTURAL CONCRETE" (CLASS "BZ").
~ (SEE DETAIL, SHEET 2) BY ZEE LENGTH MINUS 811 ) 4. ALL ELECTRICAL MATERIALS AND WORKMANSHIP SHALL CONFORM TD THE

• ~~n~~~ LATEST REQUIREMENTS OF THE NEC,NEMA, UL OR EIA WHEREVER

r
APPLICABLE; THE COLORADO PUC AND ANY LOCAL CODES OR
ORDINANCES WHICH MAY APPLY; AND THE FOLLOWING:
REQ'D. UNDER EACH U-CLAMP A. THE CONTRACTOR IS TD PROVIDE ALL NECESSARY WIRING WITHIN THE
J'/4MINIMUM DIA. RIGID
11
BEACON AND FROM THERE TD THE POWER SOURCE PROVIDED BY THE
UNDERGROUND CONDUIT UTILITY COMPANY. THE UTILITY COMPANY WILL MAKE THE
24" MINIMUM BELOW CONNECTION WITH THE CONTRACTOR'S WIRING.
GROUND LEVEL (OPTIONAL)
B. THE ELECTRICAL SERVICE BETWEEN THE POWER SOURCE AND THE
I I
POST ANCHOR SIGN PANEL U-CLAMP FLASHING BEACON SHALL BE UNDERGROUND UNLESS AN AERIAL DROP
I I
(SEE DETAIL, SHEET 2) IS AUTHORIZED BY THE ENGINEER. ALL WIRING EXCLUDING THE AERI AL
DROP WIRE SHALL BE IN CONDUIT.
~-~--~--+-- LJ
TYPICAL CONCRETE
TYPICAL PANEL ATTACHMENT DETAILS C. THE "FLASHER" SHALL BE HOUSED IN A SUIT ABLE ENCLOSURE ON THE
"' FOOTING DETAIL UTILITY POLE AT THE POWER SOURCE UNLESS THE ENGINEER DIRECTS
f l--18" ----I (SEE NOTE 3) THAT THE ENCLOSURE BE MOUNTED ON THE BEACON PIPE OR THAT
THE DEVICE MAY BE CONTAINED WITHIN THE SIGNAL HEAD ITSELF.
D. A SUITABLE ENCLOSURE FOR THE FLASHER SHALL BE IN ACCORDANCE
TABLE OF DIMENSIONS FOR PANELS NOT ILLUSTRATED LATERAL PLACEMENT ( 11 A11 ) WITH "A RAIN TIGHT JUNCTION BOX OR CAN, APPROXIMATELY 8 I N. X 8
N. X 4 IN., SURFACE MOUNT, WITH A FLANGED SCREW ATTACHED

DESCRIPTION
X
DIMENSIONS (IN.)
y z
LENS
TYPE
BACKING
ZEES w
Al NORMAL LATERAL PLACEMENT "A" FOR WARNING SIGNS
I S 12' PLUS CURB DR SHOULDER WIDTH.
COVER, AND FABRICATED FROM NOT LESS THAN 16 GAGE GALVANIZED
STEEL".
E. A BUilT-IN RADIO INTERFERENCE SUPPRESSION DEVICE AND A
~
_J
NORMAL LATERAL PLACEMENT "A" FOR REGULATORY PHOTOCELL SENSOR TYPE SIGNAL LAMP DIMMER SHALL BE PROVIDED
LL
36" DIAMETER CIRCLE PANEL ( • ) 8 20 8 12" YELLOW 20" D
Cl SIGNS IS 6' PLUS CURB DR SHOULDER WIDTH, FOR EACH FLASHING BEACON.
w w DR IF NONE 12' FROM EDGE OF PAVEMENT.
(!)
_J F. BEACONS SHALL FLASH AT A RATE OF NOT LESS THAN 50 AND NOT MORE
48" DIAMETER CIRCLE PANEL ( • ) 27 toY2 12" YELLOW 20" w
toY2 Cl THAN 60 TIMES PER MINUTE.
w ~ 2' SHALL BE CONSIDERED MINIMUM EXCEPT
"" 5. BREAKAWAY BASE INSTALLATIDN SHALL BE USED FDR UNI-DIRECTIONAL
36" PENTAGON PANEL ( • ) 9 20 9 12" YELLOW 20" I-
THAT IN URBAN AREAS 1' FROM THE CURB FACE CONFIGURATION ONLY. PEDESTAL FOUNDATION (AS SHOWN ON SHEET 3).
IS PERMISSIBLE WHERE SIDEWALK WIDTH IS LIMITED MAY BE USED FOR BOTH UNI-DIRECTIONAL AND BI-DIRECTIONAL CONFIGURATIONS.
48" PENTAGDN PANEL ( • ) 12 25% 9 12" YELLOW 20" DR WHERE EXISTING POLES ARE CLOSE TD THE CURB. 6. WHEN SPECIFIED IN THE PLANS, SOLAR POWERED SYSTEM MAY BE USED IN
48" OCTAGON PANEL ( • ) 12 24 12 12" RED 20" PLACE OF AC POWER SYSTEM SHOWN ON THIS SHEET.
7. FOR ADVANCE PLACEMENT OF WARNING SIGNS SEE MUTCD SECTION 2C.05 AND
24" X 48" RECTANGLE PANEL ( • ) 12" YELLOW REFER TD COLORADO STANDARD PLAN S-614-1 FOR
12 24 12 20" TABLE 2C- 4.
VERTI CAL PLACEMENT REQUIREMENTS.

TYPICAL ELEVATION FACING TRAFFIC TYPICAL SIGN PLACEMENT


Com uter File Information Sheet Revisions Colorado Department of Transportation STANDARD PLAN NO.
Creatio n Date: 0 7 /0 4 / 12 Date: Corrvnenta 2829 W. Howard Pl. FLASHING BEACON AN D
_ cr_e_a_te_d_ By_:_B_u_tt_a_ K_E_N_ _ _ _ _ _ _ _ _ _.... ~
1--La_s_t _M_o_d_ifi_

------------------
c _at_io_n_Da
Last Modifie d By : EBUTT A
_ t_e_:_
07 / 1_9_ _ _ _ _ _ _-I ~
....a/_3_1'-

CAD Ver.: MicroStation V8 Scale: Not to Scale Units: English


(=:)
,..-.,
\-1
8'1
Traffic
Denver, CO 8 0204
Phone: 303- 757 - 9 4 36
FAX: 303 - 757- 9219

8c Safety Engineering MKB


SIGN INSTALLATIONS
Issued By: Traffic & Safety Engineering Branch July 31, 2019.
S-6 14-14
Standard Sheet No. 1 of 4
Pr o j ect Sheet Number :
SECTION A-A SEC TION B-B (PL ATE DETAIL)
2Y2" DIA. HOLE IN POLE CL AMP
CENTER OF PLATES
PIPE CLAMP
ASSEMBLY
BEACON
PIPE

11/4" CONDUIT
A NIPPLE
SHIM DETAI L
FURNISH TWO (2) .012 IN.± THICK LOCKNUT
%011 X 27'4" H.S. BOLT
AND TWO (2) .032 IN.± THICK SHIMS.
WITH HEX HEAD AND
THREE FLAT WASHERS
SHIMS SHALL BE FABRICATED FROM BUSHING ENCLOSURE
BRASS SHIMS STOCK DR STRIP
(NOTE: WELD VARIES WITH CONDUIT OR
BREAK-AWAY ASSEMBLY BOLTING PROCEDURE CONFORMING TD ASTM-B 36.
NIPPLE WALL THICKNESS.)
I. ASSEMBLE POST TD FOOTING WITH BOLTS- ONE FLAT WASHER ON EACH BOLT TOP AND BDTTDM,AND ONE FLAT
WASHER AND THE KEEPER PLATE BETWEEN THE BREAK-AWAY PLATES. USE BRASS SHIMS TO PLUMB THE POST.
2. TIGHTEN ALL BOLTS TO MAXIMUM POSSIBLE WITH A 12 TO 15 INCH PIPE WRENCH TO BED WASHERS AND SHIMS TYPICAL PI PE
TO CLEAN BOLT THREADS, THEN LOOSEN EACH BOLT IN TURN AND RETIGHTEN IN A SYSTEMATIC ORDER TO 450 ATTACHMENTS
INCH-POUNDS TORQUE.
3. BURR THREADS AT JUNCTION WITH NUT USING A CENTER PUNCH TO PREVENT NUT LOOSENING.

TYPICAL BREAK-AWAY ASSEMBLY DETAILS


NOTES VI EW AT BEACON UNDERGROUND CONNECTI ON
VIEW AT POWER SOURCE VIEWS AT ENCLO SURES
LOCATION AND CONFIGURATION OF ELECTRICAL
EQUIPMENT IS DIAGRAMATIC ONLY (USE ANY
POWER SUPPLY METHOD COMPLYING WITH THE GENERAL NOTES).
• EXISTING GROUND AT SERVICE POLE;
OTHERWISE PULL THRU CONDUIT DR
AERIAL DROP IIIL±....._~ METER ~ ~---. ATTACH TD CONDUIT AND TAP OFF
SERVICE UNDERGROUND. ALTERNATE SIGN
CIRCUIT
BREAKER • DRILL AND TAP PIPE FOR 1/. 11 ROUND FLASHER PANEL
ROUND HEAD BRASS SCREW,Y/ LONG LOCAT~ONS
FDR GROUND LUG.
• FLASHER
• PROVIDE WEEP HOLE WITH AERIAL DROP SERVICE BEACON
ENCLOSURE Jl/4"MIN. DI A. DRILL AND TAP FDR
SERVICE POLE # BEDDING MATERIAL FDR CONDUIT SHALL BE PLACED PIPE UNDERGROUND LOCKNUT GROUND LUG 1/4" X 1"4 11
UNDERGROUND~----~•
IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE. RIGID CONDUIT DR WELD BRASS SCREW
SERVICE
NIPPLE

UNDERGROUND VIEWS AT POWER SOURCE TRENCHI NG DETAI L


4" X 8" X 1/4 11
METAL PLATE --j 6"f--
FLANGE SECTION A-A

MINIMUM DEPTH
24"UNDERGROUND
30"UNDER ROADWAY

CONDUIT
SERVICE POLE IN FOOTING
7'4" GRAVEL FOOTING
TYPICAL ALTERNATE GROUNDING METHODS
TYPICAL ALTERNATE GROUNDING METHODS
POST ANCHOR DETAILS TYPICAL ELECTRICAL SERVICE DETAIL
Com uter File Information Sheet Revisions Colorado Department of Transportation STAN DARD PLAN NO.
Crea tion Date: 0 7 /0 4 / 12 Date: Conmenta 2829 W. Howard Pl. FLASHING BEACON AND
1--
Cr_e_a_te_d___...:_B_u_tt_a_K.;.;E;.;.N_ _ _ _ _ _ _ _ _ _-1 (=:)
By

------------------ ,---.,
Last Modification Date:
Last Modified By:
(=:)
\.__./
SQ
Traffic & Safety Engineering
Denver, CO 8 0204
Phone: 303- 75 7 - 9436
FAX : 303-757- 9219
MKB
SIGN INSTALLATIONS
Issued By: Traffic & Safety Engineering Branch July 31, 2019.
S-614-14
Standard Sheet No. 2 of 4
Pr o j ect Sheet Numb er :
CAD Ver.: MicroStation VB Scale: Not to Scale Units: English (=:)
GENERAL NOTES
SOLAR PANEL SOLAR PANEL
(AC POWERED SYSTEM MAY (AC POWERED SYSTEM MAY

~
ALSO BE USED WHEN SPECIFIED) ALSO BE USED WHEN SPECIFIED)

I. THE RRFB SYSTEM SHALL ADHERE


SOLAR PANEL
TD ALL ASPECTS OF THE FEDERAL
(AC POWERED SYSTEM MAY
ALSO BE USED WHEN SPECIFIED) HIGHWAY ADMINISTRATION, INTERIM
APPROVAL 21-RECTANGULAR RAPID-FLASHING
BEACONS AT UNCONTROLLED MARKED
SIGN Wll-2 CONTROL CABINET CROSSWALKS (FHWA IA-21).
(SEE NOTE 10) ENCLOSURE
(SEE NOTE 5) 2. AN RRFB SHALL ONLY BE USED TD
SUPPLEMENT A POST-MOUNTED Wll-2,
SI-I, DR Wll-15 SIGN WITH 16-7P PLAQUE,
LOCATED IMMEDIATELY ADJACENT TD AN
SIGN Wll-2 UNCONTROLLED MARKED CROSSWALK.

SIGN Wll-2 3. PEDESTRIAN PUSHBUTTON AND SIGN


SIGN Wll-2
CONTROL CABINET ASSEMBLY MAY BE SEPARATE PARTS.
ENCLOSURE USE Rl0- 25 (9" X 12") SIGN IN ACCORD-
RECTANGULAR (SEE NOTE 5) ANCE WI TH 2009 MUTCD. SIGN MAY INCLUDE
RAPID-FLASHING INTEGRATED WARNING LIGHTS.
BEACON - APPROX.
24" X 411 X 1-1/2" RECTANGULAR 4. TERMINATE RRFB CONNECTI ONS PER MANU-
(SEE NOTE 7) RAPID-FLASHING FACTURER'S RECOMMENDATION.
BEACON ·
SIDE OF POLE RECTANGULAR RECTANGULAR 5. CONTROL CABINET ENCLOSURE SHALL
SIGN W16-7PR MOUNTING BRACKET
MOUNT SHOWN RAPID-FLASHING RAPID-FLASHING BE SIZED BY THE RRFB MANUFACTURER.
DR W16-7PL AND STEEL STRAP (TYP.)
(30" x 18" OPTIONAL) BEACON - BEACON -
SIDE OF POLE SIDE OF POLE 6. BEACON ASSEMBLY MAY BE MOUNTED ON
' - - - - - WINDBEAM (TYP.) MOUNT SHOWN MOUNT SHOWN THE SIDE OF THE POLE AS SHOWN OR ON
~ - - - - 4" STD. STEEL PIPE SIGN Wl6-7PR THE TOP OF THE POLE IF SPECIFIED.
WT.10.79 LBS./FT. DR W16-7PL
SIGN Wl6-7PL 7. RRFB DISPLAYS SHALL BE LED TYPE MEETING
SIGN W16-7PR OR Wl 6-7PR THE INTENSITY REQUIREMENTS OF SAE J595
DR Wl 6-7PL FDR CLASS 1 YELLOW, BUT SHALL NOT EXCEED
- - - - - S I G N Wll-5Dl • 1000 CANDELAS DURING DAYLIGHT AND 500
12" X 12 11 CANDELAS AFTER DARK.

8. SEE SHEET 1, 2 AND 4 FOR STANDARD


- - - - -PEDESTRIAN PUSHBUTTON BASE AND FOUNDATIONS DETAILS.
AND SIGN ASSEMBLY
(SEE NOTE 3) 9. WHEN SPECIFIED IN THE PLANS, AC POWER
PEDESTRIAN PUSHBUTTON SYSTEM (AS SHOWN ON SHEET 1) MAY BE USED
AND SI GN ASSEMBLY IN PLACE OF SOLAR POWERED SYSTEM SHOWN
(SEE NOTE 3) ON THIS SHEET.
PEDESTRIAN PUSHBUTTON
AND SIGN ASSEMBLY JO.FOR POSTED SPEEDS OF 35 MPH DR LOWER,
(SEE NOTE 3) THE Wll- 2 SIGNS SHALL BE 36" x 36". FOR
POSTED SPEEDS OF 40 MPH OR HIGHER, THE
Wll-2 SIGNS SHALL BE 48" x 48".
MATCHLINE
------ - - - - - - -- -
_ MAT CHLINE__ 1 __ ____ _
SIDE ELEV ATION VIEW
11. PEDESTAL FOUNDATION MAY BE USED
FDR BOTH UNI-DIRECTIONAL AND Bl-DIRECTIONAL
____ MATCHLINE __ _
UNI- DIRECTI ONAL CONFIGURATI ON CONFIGURATIONS. BREAKAWAY BASE INSTALLATION
DE TAI LS SIDE ELEVATION VIEW (AS SHOWN ON SHEET 1) SHALL BE USED FOR
UNI-DIRECTIONAL CONFIGURATION ONLY.
BI - DIRECTIONAL CONFI GURATION
PEDESTAL FOUNDATION (SEE NOTE 11 AND DETAI LS
DETAIL ON SHEET 4

FRONT ELEVATIO N VIEW

RECT AGULAR RAPID-FLASHING BEACON (RRFB)

Com uter File Information Sheet Revisions Colorado Department of Transportation STANDARD PLAN NO.
Creation Date: 07 /31/19 Date: Corrvnenta 2829 W. Howard Pl. FLASHING BEACON AN D
Creat ed By: EBu tta
Last Modi f ic ation Date:
Last Modified By :
CAD Ver.: MicroStation VB Scale: Not to Scale Units: English
c::) 1 - - - - - + - - - - - - - - - - - - 1
c::) 1-----+----------~
c::)
c::)
8'1
Traffic 8c
Denver, CO 80 204
Phone: 303- 757 - 94 36
FAX: 303 - 757- 9219
Safety Engineering MKB
SIGN INSTALLATIONS
Issued By: Traffic & Safety Engineering Branch July 31, 2019.
S-6 14-14
Standard Sheet No. 3 of 4
Pr oject Sheet Number :
GENERAL NOTES
1. POLE AND PEDESTAL MUST BE DESIGNED TD MEET THE REQUIREMENTS OUTLINED IN THE "STANDARD SPECIFICATIONS FDR STRUCTURAL
SUPPORTS FDR HIGHWAY SIGNS LUMINAIRES AND TRAFFIC SIGNALS", PUBLISHED BY M SHTD, FDR A WIND VELOCITY OF 100 MPH.
THE CONTRACTOR SHALL SUBMIT TWO SETS OF WORKING DRAWINGS, SIGNED AND SEALED BY A PROFESSIONAL ENGINEER REGISTERED
IN THE STATE OF COLORADO, IN ACCORDANCE WITH SECTION 105.02 OF THE STAND ARD SPECIFICATIONS FDR ROAD AND BRIDGE CONSTRUCTION.

DESIGN DATA
THE DESIGNS HEREIN ASSUME THAT FLASHING BEACONS ARE INSTALLED WITHIN
THE ROADWAY PRISM WITH THE FOLLOWING SOIL PARAMETERS:
SOIL DENSITY v = 110 LB./CU.FT.
7"
SOIL COHESION = 750 LB./SQ.FT. FDR MEDIUM STIFF COHESIVE SOIL
SOIL 0 ANGLE = 30 DEG. FDR MEDIUM DENSE CDHESIDNLESS SOIL
SF= 3.0 FDR FLEXURAL RESISTANCE

CONTACT THE ENGINEER IF THE FLASHING BEACON WILL NOT BE INSTALLED WITHIN
THE ROADWAY PRISM DR IF ANY OF THE FOLLOWING SOIL CONDITIONS ARE ENCOUNTERED DURING DRILLING:
(/)
0... 6'-0" /0 THE SOIL HAS A HIGH ORGANIC CONTENT OR CONSISTS OF
0 +l
0 SATURATED SILT AND CLAY.
2-#4 STIRRUPS ::c:
AT 611 ± AROUND ")

"*
"'
f-
<C
B) THE SITE WON'T SUPPORT THE WEIGHT OF THE DRILLING RIG.
C) THE FOUNDATION SOILS ARE NOT HDMDGENDUS.
ANCHOR BDL TS. ~ D) FIRM BEDROCK IS ENCOUNTERED.
E) A HIGH GROUNDWATER TABLE IS ENCOUNTERED.
F) LARGE BOULDERS ARE ENCOUNTERED.

FOOTING DESIGN IS BASED ON 100 MPH WIND LOAD ON A 48 IN. X 48 IN. DIAMOND SIGN PANEL
MOUNTED 9 FT.ABOVE THE GROUND, WITH A 24 IN. X 24 IN. RECTANGULAR PLAQUE UNDERNEATH
3" AND A FLASHING BEACON 12 IN. ABOVE. IF A SIGN CONFIGURATION IS PROPOSED THAT EXCEEDS
THESE DIMENSIONS, THE FOOTING DESIGN MUST BE ENGINEERED AND SIGNED AND SEALED BY
A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF COLORADO.

1'-6"

FOOTING NOTES
CD HEX NUTS ® INST ALL ANCHOR BDLTS (FURNISHED WITH
POLE) PER MANUFACTURER'S TEMPLATE PRINT
@ SQUARE NUTS (FURNISHED WITH ORDER)
8
~ HAND HOLE SHALL BE PROVIDED. (j) MI NIMUM OVERLAP OF 12 IN.

IA\ 4 IN. MIN. NON-SHRINKABLE


~ GROUT OVER ROUGH FOUNDATION ® l-Y2 IN. CLEARANCE FDR HOOPS

® STAND ARD PULL BOX.... TYPE m


@ SCHEDULE 80 PVC (24 IN. MIN. DEPTH,
CAISSON DESIGNS REQUIRE THAT THE CAISSON
30 IN. MIN. DEPTH UNDER ROADWAY)
CONDUIT STUB FROM PULL BOX TD POLE BE FOUNDED IN COMPACT SAND, CLAY OR
SHALL BE 2" MIN. DIAMETER. SANDY CLAY. IF, BY VISUAL INSPECTION OF
ALTERNATE PEDESTAL BASE INSTALLATION THE HOLE, OTHER MATERIAL I S PRESENT, THE
CAISSON DESIGN SHALL BE MODIFIED AS
DETERMINED BY THE ENGINEER.

Com uter File Information Sheet Revisions Colorado Department of Transportation STANDARD PLAN NO.
Creation Date: 0 7 /0 4 /12 Date: Corrvnenta 2829 W. Howard Pl. FLASHING BEACON AN D
a_te_d_By_:_B_u_tt_a_K_E_N_ _ _ _ _ _ _ _ _ _... ~
_ cr_e_
1--La_s_t _M_o_d_ifi_

------------------
Last Modified By :
e_:- - - - - - - - - - - 1 ~
c _at_io_n_Da_t_

CAD Ver.: MicroStation VB Scale: Not t o Scale Units: English


(=:)
,,.-.,
\-1
8 '1 Denv er, CO 80 2 04
Phone:303- 757 - 9 4 36
FAX: 303 - 757-9 21 9
Traffic 8c Safety Engineering MKB
SIGN INSTALLATIONS
I ssued By: Traffic & Safety Engineering Branch July 31, 2019.
S-614-14
Standard Sheet No. 4 of 4