NATIONAL TRANSMISSION & DBSPATCH COMPANY

(NTDC)

SP ECI FI CATION P -206:2021

VOLTAGE TRANSFORMERS FOR SPECIAL APPLICATIONS


(ENERGY METERING)
66kV, l32kv, 220kV & 500 kV

SUBSTATION DESIGN DEI'ARTMENT NTDC


NATIONAL TRANSMISSION & DESPATCH COMPANY
www.ntdc.com.pk l'-206:2021

FOREWORD
This specification has been prepared by Substation Design Department ofNTDC and supersedes
all previous versions of this specification & Amendments.
This specification is intended for the procurement of material only and does not include necessary
provisions of a contract.

This specification is subject to revision as and when required by Substation Design Department of
NTDC. No other department is authorized to issue any change/amendmcnt in it.

REVISIONS & AME,NDM!]N1'S


Sr. Description Dalc
\o.
I P-206 Voltage Transformer for Special Applications (Energy Issucd in 2005
Metering)

E-mail: ce.s .i ntdc.conr.pk Substation Dcsign Dcpartment I'agc I o! 32


NATIONAL TRANSMISSION & DESPATCH COMPANY
www.ntdc.com.pk l>-206:2021

2.0 REFERENCT]S1'ANI)ARDS .t-


1.0 DEt'tNIt'toNs 1-
i.l
3.2
3.3
3.4
3.5
3.6
3.7
3.8
1.9
3.r0
J-l I

3.12
J.IJ
3.t4
3.15
3. l6
3.1'7
3.r8
3.r9
4.0 s[_Rvtct: ( ()\l)lTIo\s--- 6-
4.1 Cl.t\4A f 1( CoNI)t I toNs ---------.--- 1-
4 l \\4llll,\I ll:MPI Rn Il R1j-- 7-
4 I I{l,l.A llVl llt \,111)l lY 1-
4.2 Al II. i l)l 7-
4.3 A vo\t, l.t{t( (-r)\t)t't tr )\\ .--
I 7-
4.4 Wl\l) l.( l \I)-------- 7-
4.5 Sl t\\llr Co\t)t I l( )\\ ------------------- 7-
4.6 Sr. t,t,i \ S\ st \l ----- 7-

6.I
6.2 'I't.t( UNICAI ll-
6.3
6.4
6.5
6.6 SECoN DARy TLRMINAT.S -------------- l-
.f
6.7 SECoNDARY ERMINAL Box...-....-. ?-
6.8 EAR r HINc TIiRMINALS ---------------- 1

6.9 CoRr:s ANr) wrNl)tNCs ')-


6.r0 I Nsr. I-A t1)R 2-
[i]-mail: ce.sd'ilrntdc.cont.rrk Substation I)csign Depaft ment Page 2 ol 32
NATIONAL TRANSMISSION & DESPATCH COMPAI\IY
}}"n'l .ntdc.com.pk l'-206:2021

6.lt
6.12
6. t3
6.14
6.l5 RA l LD VoL l n cE FAC toR ----------- 14-
6
6.'t TEMpTTRA'r'uRE RlsE --------------------- t4-
6.17 SHoRT CrRCr.JIr Cr rARA(TERIs ncs l5 -
6.18 STATTc MEClrANtcAl- TERMINAL LoAD ------------------ t5-
6.19 DYNAMIC MECI IANICAL TERMINAL LOAD ---. l5 -

8.0 RATINC PI,ATE l5 -


l6 -
l6-

9.4 AccEpTANCri 'l'r,srs/ fn 'f (FACroRy AccliPr^NCL 'fES f) l8-

SCIIItI)t.l-ll Ot l ll('ll\lCAl. DA'l A


PRIMAII.Y I'F]ITM INAL LAYOUT DRAWING 28-

ll-mail: ce.scf i ntdc.conr.pk Substation I)esign I)cpnrtment I'agc 3 of32


NA'T'IONAL'I'IIANSMISSION & DE,SPATCH COMPANY
www,ntdc.com.pk l'-206:2{l2l

1.0 scoPtl
This specification covers the minimum requirement for voltage transformers of 0.2 accuracy class
intended to be used lor special energy metering applications from 66kV up to 500kV systems.

2.0 RUt [.R].\CU S',t A\..l)Altl)S


7.1 'l'he voltagc transfonners shall be designed, manufactured and tested in accordance with the following
Intcrnational E.lcctro-'l'echnical Commission (lEC) Publications as amended to date and particulars
listed hercin.

IF.C Publication 6l 869- l Instrumcnt'l'ransformers (General Requirements)


IIIC Publication 6l 869-3 Inductive Voltage 1-ransformers
IliC t'ublication 6l 869-5 Capacitive Voltage Translormcrs
IEC Publication 60296 Fluids for Electrotechnical applications - Unused
mineral insulating oils lor transformers and
srvitchgear
lllC I)Lrblication 60422 Mineral insulating oils in electrical equipment
Supervision and Maintenance guidance
IIIC Publication 62155 Hollow pressurized and unpressurized ceramic and
glass insulators for use in electrical equiprncnl with
ratcd voltage greater than 1000\/
IIIC I'Lrblicatiorr 605 29 Degrce ofprotection provided by enclosures
IEC I'ublication 60376 Specification of technical grade Sulphur hcxafluoride
(SFs) for use in electrical equipment.
II'lC Publication 62073, lLLll. Specifications of RTV Coating on Porcelain
I 523-2002. llilll: 957'l'M Insulator.

2.2 ln case, the requirements laid down herein dififer, from those given in the IEC Publication in any
particular casc, thc voltage translormers shallcomply with the requirements listed herein in regard to that
requ iremcnt.

3.0 DET'INI'I'IONS
'l'hc definitions of IEC 61869-1, 61869-l and 61869-5 shall apply on voltage transformers. Some of
them are rccollected here lor ease olreference.

3.1 Voltage 'I'ransformer


An instrument transformer in which the secondary voltage, in normal conditions of use, is
substantially proportional to the primary voltage and differs in phase from it by an angle which is
approximately zero for an appropriate direction ofthe connections.

3.2 Primary Winding


'lhe winding to which the voltage to be transformed is applied.

ll.miril : ce.sdi.i ntdc.conr.rlk Substation I)csign I)epartment I'agc 4 ol J2

* /4-
NATIONAL TRANSMISSION & DESPATCH COMPANY
www.ntdc.com.pk l'-206:2021

3.3 Secondary Winding


The winding which supplies the voltage circuits of measuring instruments, meters, relays or similar
apparatus.

3.4 Rated Primary Voltage


The value ofthe primary voltage which appears in the designation ofthe transformer and on which
its performance is based.

3.5 Rated Sccondary Voltage


The value ofthe secondary voltage which appears in the designation ofthe transformer and on which
its performance is based.

3.6 Actual Trensformation Ratio


The ratio ofthe actual primary voltage to the actual secondary voltage.

3.7 Rated Transformation Ratio


The ratio ofthe rated primary voltage to the rated secondary voltage.

3.8 Measuring Voltage Transformer


A voltage transformer intended to supply indicating instruments, integrating meters and similar
apparatus.

3.9 Protective Voltagc Transformer


A voltage transformer intended to provide a supply to electrical protective relays'

3.t0 Voltage Error (Ratio Error)


The error which a transformer introduces into the measurement ofa voltage and which ariscs when
the actual translormation ratio is not equal to the rated transformation ratio. The voltagc error
expressed in percent is given by the formula:
((xn+us)-Up)*100
Voltage Error o/o
=':--np
Where.

Kn is the rated transFormation ratio:


Up is the actual primary voltage;
U.r is the actual secondary voltage when Up is applied under the conditions of measurement

3.u Phase Displaccmcnt

The differencc in phase betwcen the primary voltage and secondary voltagc vectors, thc dircction oI
the vectors being so chosen that the angle is zero for a perfect transformer. The phase displaccrncnt is
said to be positivc whcn thc secondary voltage vector leads the primary voltage vector. lt is usually
cxprcsscd ill t'rlinutcs or ccntiradians.
Fl-mail: cc,s(l'rintdc.conr.Dk Substation l)esign Dcpanmenl Page 5 ol32

lw. e( ft-
NA'I'IONAL TRAIISMISSION & DESPATCH COMPANY
www.ntdc.com.pk P -206:2021

Notc: l'his definition is strictly correcl for sinusoidal voltages only

3.12 Accuracy Class


A designation assigned to a voltage transformer the errors of which remain within specified limits
under prescribed conditions of use.

,.t-, Rated Insulation Level


The combination of voltage values which characterizes the insulation of a transformer with regard to
its capability to withstand dielectric stresses.

3.t4 Burden
1'he impedance ofthe secondary circuit in ohms and power-factor. The burden is usually expressed
as the apparent power in volt-amperes absorbed at a specified power-factor and at the rated secondary
current.

3.r5 Rated Burden


The value ofthe burden on which the accuracy requirements ofthis specification are based.

3.r6 Rated Output


'l'hc valuc ofthe apparent power (in volt-ampercs at a specified power-factor) which the transformer
is intended to supply to the secondary circuit at the rated secondary voltage and with rated burden
connected to it-

3.t7 Highest Voltage for Equipment


'l'he highest r.m.s. phase-to-phase voltage for which a transformer is designed in respect of its
insulation.

3.18 Rated Insulation Levcl


The cornbination ofvoltage values which characlerizes the insulation ofa transformer with regard to
irs capability to withstand dielectric stresses.

3. l9 Ratcd Voltagc Factor


'l'hc multiplying factor to be applied to the rated primary vollage to determine the maximum voltage
at which a transformer must comply with the relevanl thermal requirernents lbr a specified time and
with the relevant accuracy requirements.

4.0 SI]RVICIi (]oNDI'IIONS


'l'hc voltagc transformers and all accessories shall be suitable for satisfectory operation under the
lollowing scrvice conditions. lf the actual site ssrvice conditions ofany project dil-fer lrom these
service conditions, voltage transfonner shall be designcd to comply with those service conditions
described in schedule of requirements.

ll-mail: cc.sd ri ntdc.com.pk Substation Dcsign Dcpartmcnt l'agc 6 ol'32

LW * t'1^'
NATIONAL TRANSMISSION & DESPATCH COMPANY
*ruw.ntdc.com.pk l'-206:2021

4.1 Climatic Conditions


4.1.1 Ambicnt Tcmpcraturc
Maxim um 50 "c
Maximum mean over any 24 hours 45 .C
Mean in any year 30 "c
Minimum -10"c

4.1 .2 Relative I'Iumidily

The relative humidity may range from 0 to 100 percent. The maximum value of the ambient
temperature and humidity, however, do not occur simultaneously. During the monsoons, high
humidity may persist for many days at a time along with temperatures ranging from 30"C to 40nC.

4.2 Allitudc
The voltagc translormers shall be suitable for installation up to 1000 m above sea level

4.3 Atmospheric Conditions


It may be assumed that the air is not normally heavily polluted by dust, smoke, aggressive gases,
vapors or salt spray. Howevcr, at certain times ofthe yearr severe dust storms may be experienced.

4.4 Wind Load


The maximum wind load shall be taken as 122 kglsq. m. (corresponding to wind speed of 44.2 m/s)

4.5 Seismic Conditions

1'hc voltage transformers along with steel supporting structures (as per NTDC specifications P- I 9' P-
82, P- I 39, P- l 82. erc. ) shall be suitable to withstand the seismic stress/magnitude according to Richer-
scale up to 7 (horizontal acceleration up to 4mls' (0.4g) for safety of equipmcnl under heavy
earthquake conditions unless otherwise specified in the tender.

.1.6 Supply System

The voltage transformers shall be suirable for installation in 500kV, 220kV, I32kV & 66kV three
phase A.C. solidly earthed supply system ofthe following characteristics:

Rated Voltage 550kv 245kV l45kv 72.5kV


Nominal 500kv 220kv ll2kv l66kv I

Voltage
Irrequency 5 0llz 5 0Hz 50Hz 5lHz

5.0 RATINGS & CHARECTERISTICS


5.1 The voltage translormers shall comply with the following ratings, characteristics and meet all test
requirements laid down herein with respect to insulation strenglh, accuracy etc.

Il-mail: cc.sd a ntclc.conr.nlr Substation l)csi gn Departmcnt I'>agc 7 ()1 32

L,ry * \ 7.
NATIoNAL TRANSMISSION & DESPATCH COMPAN\
ww\v. nldc.com.pk P-206:2021

Sr. Designation of Voltage 500 kv 220 kv 132 kv 66 kV


No. Transformers
I I{atcd Voltage. [Jrn. kV rms 550 245 145 72.5
l Nominal Voltagc, kV rms 500 720 132 66

-) Itatcd frcquency, IIz 50 50 50 50 I

4 No. ol secondary windings I I I I

l Ilated burden, VA I 50 50 50 50
6 Accuracy Class 0.2 0.2 0.2 I

7 Rated voltage lactor I

a) Continuous I 2 2 l.z I 7
b) 30 seconds I ) 5 I 5 I 5

8 Maximum temperature rise ,15 rl5 45 45


(top oil) at an ambient of
50'c.'c
9 One minute power frequency 680 460 215 t40
withstand voltage, kV rms
10. Rated lightning inrpulse r 550 1050 650 3?5
u,ithstand voltagc (1.2/50
psec), kV peak
tl One minute power frequency ) -) J
withstand secondary circuit, kV
rms
l2 Rated switching impulse ll75
I
withstand ro ltagc. kV peak
13. Translbnnation ratios s00/i3kv 220t.'bkv 132l!3kV 66l{3kV
/l l0/!3v /l l0/J3v /r l0/^J3v /l lo/./3v
l4 Minimum external creepage 17050 7 595 449 5
distance, mm
,tl Short circuit impedance
(referred to secondary), ohm
0.5 0.5 0.5 0.5

(max.)
16. Radio interference voltage at 2500 2500 2500 2500
I

l.l Ur/./3kV and 1000 kHz,


pV
17. Partial Discharge,
I
a) Um kV, pC l0 l0 t0 t0
b) 1.2 Um/!3 kv, pC 5 5 5 )
18. 'l'an 6. Max 0.005 0.005 0.005 0.005
Rated Mechanical Static
t9. 4000 2500 2000 1250
withstand Load, N

l l-mail : ct'.sd ii.ntdc.conr.pk SLrbstation Design I)cpanmcnl Pagc 8 ofJ2

b9 q|^
l-t-
NATIONAL TRANSMISSION & DESPATCH COMPANY
www.ntdc.com.pk P-206:2112l

I
I(ated Mcchanical Dynamic
20 I
5600 1500 2000 1750
withstand l.oad. N

Note: l'he limits oftemperature rise specificd in the relevant IEC standard have been reduced by lOoC
to account for higher ambient condition required in this specification.

6.0 CONSTITUC'I'IO\
6.1 General

6.1 .l The voltage translormers shall be capacitive or inductive type. The dcsign shall bc such that
installation. replacement and gcneral maintenance may be undcrtaken within a rninimum time and all
parts are easily assembled and protected from rusting or corrosion. The material and workmanship
shall be of best quality and in accordancc with the modern practices to cnsure wcll establishcd
physical. electrical and mcchanical characteristics as per I[lC 61869-1. 61869-3 and 61869-5.
International lactors ofsafctl'shall be uscd in the design. Provision shall be rrade in thc design ofthe
VTs to ensure that propcr operation is not impaired by vermin, insccts. small animals and birds.

6.1.2 Oil filled voltage transfomers shall be independent, single pole, single corc, free standing, and
hermetical ly sealed, sclf-contained, outdoor type.

6.1.3 SFs filled voltage transformers (For GIS) shall be independent, single-core, self-contained,
indoor/outdoor type.

6.1 .4 Oil filled V-fs shall bc supplicd complete with oil lcvcl indicators markcd for 25 oC, stccl supporting
structurcs, solderless clamp typc IIV terminal connectors for conncction to conductor. tcrminal boxcs
with terminals for outgoing secondary wires. grounding terminals and marshalling boxcs as specificd.

6. I.5 SF6 voltage transformers shall conform to NTDC Specification P-223 (amended to datc) and shall
be suppliedwith terminal boxes having terminals for outgoing secondary wires, grounding terminals
and marshaling boxes as specified. Separate compartments for gas insulated metering voltage
transformer shall bc used. Additional core(s) in existing voltagc transformer(s) is not acccptable.

6.1.6 ]'he oil shall be un-inhibited, non-PCB and class I confbrming to IDC-60296.

6.t.7 The voltage translormers shall be constructed to provide adequate insulation lor the insulation class
specified and to withstand mechanical and thermal stresses produced during short circuil conditions.
AII insulation and magnetic materials shall have proven and wcll established physical and electrical
properties such as to give continuous and prolonged service without deterioration.

6. 1.8 The oil filled voltage lranslormers shall be hermetically sealed with arrangements othcr than nitrogen
cushion. Synthetic or stainless steel bellows, or expandable cells shall be provided to accommodatc
oil level variation. A suitable device lor indicating thc position of the bellows visiblc lrom ground
shall be provided.

L-mail: cc.sll {i ntdc.c()nl.pk Substntion Design I)cpanmcnt Pa-qe 9 ol 32

t: t-
NA'I'IONAL'TRANSMISSION & DESPATCH COMPANY
www.ntdc.com.pk l'-206:2021

6.1.9 All the steel and malleable iron parts shall be hot dipped galvanized.

6. t .10 'l'hc CV'ls shall consist of a capacitor divider unit containing a large number of series connected oil
imprcgnatcd capacitor elements and an electromagnetic unit (lntermediate Voltage Transformer)
oonnecled between the intermediate terminal and the earth terminal of the capacitor divider unit lor
providing thc secondary output.

6.1.I I
-fhc entire capacitor divider unit i.e. high voltage capacitor and intermediate capacitors shall be
hcrmctically scaled, preferably, in the same hollow porcelain housing so that the measuring errors due
to changes in temperature and contaminations are minimized.

6.t.t2 'l'hc capacitor units shall be complctcly flllcd with oil. In order to increase the margin to corona
inccption, the capacitor unit shall bc prcssurized. 'l'he oil expansion technique shall incorporate the
provision other than nitrogen gas cushion such as synthctic or stainless steel bellows or expandable
cclls to accommodate oil level variation. Suitable grade ofstainless steel shall be used ifsteel bellows
are provided with the provision of suitable device for indicating the position of bellows. Each
capacitor shall bc equipped with a pressure indicator. Oil level gauge shall be ofa type which can be
rcad with the equipment energized

6. t.l3 'l'hc capacitor electrodes shall be made ofaluminum foil. The dielectric shall consist ofseveral Iayers
-['he
of high quality papcr impregnated rvith special rnineral oil and shall be properly assembled.
capacitor divider unit shall offer negligible capacitance variation with temperaturc, and shall have
optimum stability olratio for different arnbient temperatures. Suitable means shall be providcd in the
design ofCVTs to prevent corona discharges, in order to reduce the high frequcncy noise level

6.1.14 'l'hc capacitors oflthe voltage divider unit shall have low dielectric losses, small insertion losses at
high frcquency, high resonance liequency and low radio interlerence voltage level.

6.1.15 'l'hc electromagnetic unit ofCVTs shall consist ofan intermediate voltage transformer, a device lor
supprcssion of Ferro resonance oscillations, and a compensating reactor to ensure correct phase and
ratio rclationship between primary and secondary voltages. These shall be housed in a hermetically
sealcd steel tank filled with oil. 'l'hc tank shall be capable of withstanding excessive pressure under
lauh conditions without distortion. 'fhe oil in the steel tank shall be separated from the oil in the
porcclain unit. A drain screrv and an oil filing screw shall also be provided. The transformers shall
havc thrcc legged core, made of high grade silicon steel stampings, the winding shall be arranged
concentrically on the middle Ieg of thc core and insulated with oil impregnated paper. The primary
winding shall have uniform voltage distribution. The 1.V.1'. shall have a low design flux density. Ifa
ground switch is provided for intermediate transformcr, it shall be lockable in the open position.

6. I . I 6 A test device shall also be provided to check the working ol the suppression circuit at any time with
the transfbrmer energized.

6.t.17 A signaling dcvice operated by liberation ofgas shall be provided fbr the detection ofslightcst fault
which may affect the accuracy ofthe measurement and also indicate any abnorrnal lall in the oil level.

6. l.l8 Protectivc dcvice shall be provided for limiting ovcr voltage to about twice the full load voltage across
thc auxiliary capacitor in the event ofshort circuit ofburden impedance.

Il-mai I : 9g.5gl!i!1!!ja!LpL Substation Dcsign l)epanment Pagc I0 oi'J2

q^ I -1-

)*+e
NATIONAL TRANSMISSION & DESPATCH COMPANY
www.ntdc.com.pk l'-206:2021

6.2 'I'cch n ical

6.2.1 The tEC specified accuracy requirement shall be met without having to make adjustment for changes
of power factor, burden or voltage.

6.3 Painting
6.3.l All cxposcd mctallic parts shall be painted except where painting will interfere with the normal
opcration of'the equipment. Where surface is left unpainted lor mounting purposes, they shall be
suitably protected to prevent rusting during storage and ocean transport.

6.3.2 After preparation and cleaning ofall surfaces to bc painted, the surfaces not in contact with oil shall
be painted wilh two coats of an epoxy primer containing red lead, zinc or aluminum.
'l'hc surlaces
shall bc finish coated with two coats ofenamel applied to provide a uniform smooth surlace lice from
blemishes.

6.3.3 The inlerior and exterior surfaces ofthe voltage transformers shall be given manufacturers' standard
finish belore shipping but a dull grey color finish shall be preferred. A very light color or aluminum
paint shall not be used.

6.4 Housing and Tank

6.4.1 'fhe tank housing shallbe constructed ofgalvanized steel or corrosion proof, high quality, cavity-free,
cast aluminum alloy and shall be suitably reinlorced to withstand rigors of handling and excessivc
pressure under fault conditions without distortion. All welded joints, pipe work and valves ctc. shall
be leak proof.

6.4.2 'l'hc housing or tank shall be of sufficicnt strength and rigidity to provide a tight- iitting gaskct and
scalcd enclosure. l-he complete assemblics shall lbrrn sealed enclosures capable of sustaining lull
pressure developed within housing or tank, either above or below atmospheric. under normal
operating conditions. The rvindings and bushings shall be hermetically sealed to prevent thc
cnlrance olmoisture or leakage ofthe diclectric during transportation, storage and installation ctc.

6.4.3 All welded joints, pipe work and valves etc. shall be oil/SFo-leak tested.

A clamp on covcr shall preferably be provided to allow access to component parts within thc tank
6.4.4
without undue diffi culty.

6.5 Primary Terminals


6.5.1 'lhe primary terrninal shall be single-stem, horizontal, flat bar type made of aluminum /Tin plated (12
micron) copper (l00xl00xl5) adequately shielded and corona free.

6.6 Secondary Terminals

6.6.t All the secondary leads shallbe brought out through the voltage transformer tank wall by mcans of
multiple bushings, equipped with connectors for 2.5 mm2 to 4 mm2 conductor and shall terminatc in
a low voltage weather proofbox mounted on the side ofthe tank. Provision shall be made in'l'crminal

Pagc I I ol-32

w*
li-mail: ce'.sd ri nt .conr.nk Substation l)csign I)cparrmcnt

J4"
NATIONAL TRANSMISSION & DE,SPATCH COMPANY
www.ntdc.com.pk l'-206:.2071

Box for cntry of4 core 2.5 mm'zcopper control cable. Brass cable glands shall be provided. Protection
class ofterminal box shall be IP 55.

6.7 Secondary Terminal Box

6.7.1 The terminal box shall be located in such a manner that they will line up when the V-ls are banked
in linc lor three phase operation.

6.7.2 Removable cable gland plate shall be provided on terminal box.

6.7.3 The nameplate shall be fixed outside ofthe terminal box in order to be visible with the box closed.

6.7.4 Connection diagram shall be affixed inside the secondary terminal box so that it can be easily read
while working in the box.

6.7.5 Provision shall bc rnade for sealing thc tenninal box by mcans o1'lashcd wire as well as pad lock.

6.8 Earthing Terminals


6.8.1 Two (02) Earthing terminals at diagonally opposite position shall be provided. Each terminal shall be
capable of carrying lull short circuit current and shall be suitable for accommodating 95 to 185 mm2
copper Earthing leads.

6.9 Cores and Windings


-l'he
6.9.1 core shall be made ofhigh quality non-aging grain oricnted annealed silicon steel, or some other
superior matcrial, carefully selected and tested to provide the best magnetic characteristics to provide
low losses, high accuracy and low saturation levels and shall be suitably reinforced to withstand
rigors ofhandling and excessive pressure under fault conditions without distortion. The winding shall
be supplied with negligible leakage reactance in the whole windings and between tapings.

6.9.2 AII welded joints, pipe work and valves etc. shall be oil/Slro-leak tested.

6.9.3 A clamp on cover shall preferably be provided to allow access to component parts within the tank
without undue diffi culty.

6. l0 Insulator
6.10.1 All porcelain insulators shall be electrical grade, wet process, homogeneous and free from cavities
and other defects. lnsulator shall conform to IEC 62155 and tested in accordance with IEC-60273.
The color of insulators shall be chocolate glazed brown. Fittings shall be made of steel and hot dip
galvanizcd.

6.10.2 Porcelain insulators shall be designed to withstand internal pressure of three times the maximum
operating pressure and shall have the same Insulation Level as the voltage transformer. These shall
be airtight undcr pressure and shall have adequate mechanical strength to withstand the wind loads,
seismic stress, static and dynamic forces from conductor.

I l-mail : cc.s,,l'rr:ntde.cont.pk Substation Dcsign Dcpartmcnt l'agc l2 ol 32

L*,:> * i
NATIONAL TRANSMISSION & DESPATCH COMPANY
rrT,\d.ntdc.com.pk l'-2ll(t:2112 |

6. r0.3 Minimum creepage distance from live to earthed parts for porcelain insulators shall bc as per clause
5.1 ofthis specification under the prevailing atmospheric conditions as mentioned in clause 4 of this
specification.

6. 10.4 Outdoor porcclain housing shall withstand a washing pressure of 3800 kPa without permitting water
ingress into the V'fs or secondary terminal box.

6. 10.5 Duly certilied cornplete type test reports in line with NTDC'l'ype test repots carried oul as per relevant
IEC on offered insulators by the manulacturcr having samc design characteristics, shall be provided.
Name of manufacturer should be embossed on the insulator. Manufacturer's routinc 'l'est reports
carried out as per relcvant IEC shall be submitted at the time of pre-delivery inspcclion/l"ATs.

6. 10.6 R-fV Coated Porcelain insulator shall be provided if mentioned in schedule as per NTDC
specifications revised to date and relevant IEEE & IEC standards.

6.10.7 The primary winding neutral end conneclion shall be brought out through the welded steel plate tank
wall or cover, with a dry polyurethane type bushing, capable of withstanding a 4 kV, 501'lz test for
connection to a neutral conductor.

6.1 I Marshaling Box


6.1 I .l A marshaling box shall be erected on center phase supporting structure containing isolating type
terminals to all sccondary circuits, threc single pole, high speed MCBs of 3 Amp for VT protection
with two auxiliary contacts for annunciation purposes. At least 200 spare terminals shall be provided
in the box.

6.11.2 The box shall be fabricated lrom steel sheet. not less than 3 mm thick, seam-wclded at corners.
Howevcr. in casc of rigid frame design, the thickness of steel sheets may be reduced according to
manufacturcr's standard desi gn.

6.1 1.3 'fhe box shall bc dcsigned for protcction class IP55 in accordance with IEC-60529

6.11.4 Removablc cablc glands shall be providcd for proper termination olcables

6.11.5 Provision shall be made for locking the marshaling box by pad locks and sealing by means of lashed
wire and lead seals.

6.1 1.6 Heaters with thermostat and humidistats shall be provided inside each marshaling box

6.11.7 Lamps wirh door operatcd swirch shall be provided for intcrnal illumination.

6. I 1.8 There shall be a single-phase powcr socket inside each marshaling box.

6.11.9 Two (02) MCBs with auxiliary contact shall be provided. One MCB shall be used for switching
ON/OFF the AC power supply to the heater and the other one shall be used for illumination and power
socket.

6.1 l.l0 Star-point ol'thc V.l' circuit shall be scparately grounded.


Il-mail: ce.sd rr ntdc.conr.pl Substation I)csign l)cparlmcnt l'ri-qo lf, ()1 32

D",? d
(1*
NATIONAL TRANSMISSION & DESPATCH COMPANY
www.ntdc.com.pk l'-2116:2021

6.1 l.ll Provision shall be made in the bottom plate of marshaling box for entry offour (04) No.4x2.5 mm2
control cables through GI pipe of suitable size and three (03) No. 4x2.5 mm2 control cables through
cable glands.

6.12 Accessories

6.t2.t 'fhe voltagc transfbrrners shall bc provided with the lollowing accessones:

a) Lifting lugs.
b) Drain and filling valves with stainless steel plugs.

6. l3 Mechanical Strength

6.13. l The voltage transformers shall be capable of withstanding the mechanical cantilever stresses
€quivalent to those produced by winds and horizontal earthquake acceleration as mentioned in clause
4 ofthis spccification.

6.t4 Effect of Transicnts


6. 14. I
'fhe transicnt response of the capacilor voltage transformer shall be such that on the application of a
short circuit to the primary and earth terminal the secondary output voltage shall fall to a value less
than l0% ofthe peak value before short circuit in less than one cycle ofrated frequency.

6. | 4.2 When a capacitor voltage transformer supplied at 1200A of 'alcd voltage and with substantially zero
burden has its secondary terminal short circuited and the short circuit is suddenly removed, the peak
ofthe secondary voltage shall revcrt to a value which does not differ from its notninal value by more
than 107o after l0 cycles of2 seconds.

6.t4.3 When a CVl'supplied at voltage corrcsponding to its rated voltage factor and with a substantially
zero burden, has its secondary tcrminal short circuited and the short circuit is suddenly removed
ferroresonancc shall not be sustaincd fbr rnore than 2 seconds.

6.t4.4 The exciting irnpedance of intcrrncdiate translormer and capacitance of voltage divider lorrn a
resonant circuit. 'fhe basic ficqucncy of this circuit shall be greater than 0.3 times the system
frequency so that thc dccaying oscillation shall not be sustaincd or periodic.

6.15 Rated Voltage Factor

6.15. r The standard value of rated voltage factor shall be 1.2 for continuous duty and 1.5 for 30 seconds
duration.

6.16 Temperature Rise


6. l6. t The temperalure rise ofthe voltage transformer under IEC specified conditions shall not be more than
the values mentioned in IEC with a reduction of l0"C due to higher ambient temperature.

l-mail: cc.stl r nLtle.conr.pL Substation I)csi gn Dcpi.lrlr'rcnl I'agc 14 ol 32

I
4 \_l
l-t-
NATIONAL TRANSMISSION & DESPATCH COMPANY
w*"rv.ntdc.com.pk l'-206:2021

6.17 Short Circuit Cha racteristics


6.17.1 The voltage transforrners shall be capable of withstanding for one second the mechanical and thermal
stresses resulting from short circuit on secondary terminals with maximum rated voltage maintained
on primary terminals.

-fhe
6.17.2 tempcraturc ofthe winding under the short circuit condition given above shall not cxcced 250'C
assuming an initial copper temperature of 95'C. The secondary short circuil current shall be at least
200 arnps.

6. l8 Static Mechanical Terminal Load

6. l8.l Voltage transformer shall be capable of withstanding thc static loads to be applied in any direction to
the primary term inals.

6.t9 Dynamic Mcchanical'l'crminal Load

6. l9.l Voltage translorrrer shall be capable of withstanding the dynamic loads (e.g. short circuits) of 1.4
times the static rvilhstand load.

7.0 Terminal Markings


7.1 The terminals shall be marked clearly and indelibly in accordance with IEC publication 61869-3 and
61869-5 and shall clcarly identify the secondary terminals.

8.0 Rating platc


A stainless steel nameplate shall be securely attached to the voltage transformer and shall include at
least the following information marked in an indelible manner in accordance with 61869-3 and 61869-
5, which shall be visible under normal service condition. In addition to the data mentioned in IEC
Standard, secondary winding resistance at specified temperature shall be engraved on the nameplate.
Engraving shall be white on a black background.

a) Manufacturer's name.
b) Designation and type.
c) Serial number.
d) Contract No. /Purchase Order No. and date.
e) Rated primary and secondary voltage expressed as a ratio.
f) Rated frequency, Hz.
g) Class of insulation.
h) Accuracy class
i) Thermal burden rating at 5OoC temperature rise, VA
j) Highest system voltage, kV
k) Rated insulation level:
o
Power frequency withstand voltage, kV rms
.
Lightning Impulse withstand voltage, kV peak
.
Switching Impulse withstand voltage, kV peak
l) Rated voltage factor and corresponding rated time
m) Connection diagram and polarity markings
li-rnail: ce.scl a ntdc.eonr.nk Substation l)csign I)epa|tmcnt I'agc l5 ol 32

I,b9 a( \ t4'
NATIONAL TRANSMISSION & DF],SPATCH COMPANY
www.ntdc.com.pk P-206:2021

n) Capacitance value (for CVTS):


.
High voltage capacitor Cr (pf)
.
Intermediate voltage capacitor Cz (pf)
o) Rated capacitance between high voltage and low voltage terminal (for CVTs):
C, *C"
'"- TllE
p) Identification numbers ofthe capacitor units belonging to the capacitor voltage transformer
q) Rated open circuit intermediate voltage ratio
0 Measured voltage ratio
s) Rated mechanical static and dynamic terminal loads.
0 Quantity and weight of oil.
u) 'fotal weight, kg
v) Name of Purchaser

9.0 'fests

9.1 Gencr:rl

Tests shall be perlormed in accordancc with the relevant IEC standards amended to date in line with
N'I-DC't'ype test policy to ascertain that the voltage transformers comply with the specified rating,
characteristics and operational requircments regarding dcsign, size, material and manufacture. The
voltage transformers shall be subjected to type and routine tests specified herein.

9.2 Typc Tests


9.2.1 Duly cenified and complete reports for type tests carried out as per NTDC's Type tesl policy on the
voltage transformers having same design, voltage ratings & transformation ratios shall be acceptable
in lieu ofactual tesl.s. The validity ofthe type tests reports shall be as pcr NTDC's 1'ype test policy.
ln casc of non-production ofthe requisite type test reports or if the type test reports are not acceptable
to the Substation Design N1-DC, the lbllowing tests in accordance with relevant IEC standards and
this specification shall bc performed on the voltage transformer having same design, voltage ratings
& transtbrmation ratios as ordered in presence of two representatives one from Substation Design,
N'I'DC and other lrom purchaser at a l-ab approved by Design NTDC in line with N'IDC'S Type test
policy at the cost and arrangemcnt of the manufacturer including travel expcnses, boarding, lodging
and daily allowancc ctc. lor the represcntal.ives.

l'or I nductir,c voltagc transformcr:


a) Measuremcnt ofthe resistance of primary and secondary windings.
b) Impulse voltage withstand test (Lightning, Switching, Choppcd)
c) Power frequency voltage withstand test at Primary & secondary windings, between sections
and for ea(hed terminal (dry).
d) Wct test for outdoor type transformers
c) Partial discharge measurement during induced voltage test.
D Electromagnctic compatibil ity (EMC) tests.
'lemperature-rise test.
c)
h) Measurement of capacitance and dielectric dissipation Factor.
i) Tests for accuracy.
i) Verification of degree of protection by enclosures.
[---mail : cr.sd antdc.con.pk Substation Design Dcpanmenl Paqe 16 ol 32

q
1,, l--f\
NATIONAL TRANSMISSION & DESPATCH COMPANY
www,ntdc.com.pk l'-2|.16:2021

k) Verification of terminal marking


l) Enclosure tightness test at ambient temperature
m) Pressure test for the enclosure.
n) Short-circuit withstand capability test.
o) Radio lnterference Voltage (RIV) Test.
p) Mechanical test.
q) Transmitted Overvoltage Measurement
r) Determ ination of percentage voltage (ratio) errors and phase d isplacement at 80%, 100% and
I 20oZ of rated voltage, at rated freq uency and al25o/o and I 00oZ of rated burden for measuring
winding and at a power factor of 0.8 lagging for measuring accuracy class.

For Capacitive voltage transformer:


a) Measurement ofthe resistance ofprimary and secondary windings.
b) Impulse voltage withstand test on primary. (Lightning, Chopped, Switching)
c) Power frequency voltage withstand test at Primary & secondary windings, between sections
and for earthed terminal (dry).
d) Wet test for outdoor type transformers
e) Electromagnetic compatibility (EMC) tests.
0 Temperature-risetest.
g) Measurement ofcapacitance and dielectric dissipation Factor.
h) Capacitance and tan 6 at power frequency
i) Tests for accuracy.
j) Verification ofdegree ofprotection by enclosures.
k) Enclosure tightness test at ambient temperature
l) Pressure test for the enclosure.
m) Shon-circuit withstand capability test.
n) ["erro-rcsonancetest
o) Type test for carrier lrequency accessorics
p) Partial discharge measurement during induced voltage test
q) Radio Interference Voltage (RIV)'fest.
r) Mechanical test.
s) Transmitted Overvoltage Measurement.
t) Deterrnination of percentage voltage (ratio) errors and phase displacement at
80yo. l\Oy" and l20o/o of rated voltage, at rated frequency and at 25o/o and
100% of rated burden for measuring winding and at a power factor of 0.8
lagging for measuring accuracy class.

9.2.2 Following visual inspection/checks on the assembly subject to type tests shall be carried out and made
part ofthe type test report.

a) Verification of nameplate data and terminal marking.


b) Check of constructional and performance requirements.
c) Visual & dimensional verification of VT assembly, steel supporting structures, terminal
connectors and earth terminals.
d) Measurement ofcreepage & dry arcing distance.
e) Verify all components/devices are correctly labeled.

Ll-mail: cc.srl rr ntdc.conr.trk Substation Dcsign Department I'agc 17 ol 32

w & > (.r


NA'I'IONAI, TRANSMISSION & DESPATCH COMPANY
www.ntdc.com.pk P-206:2021

9.2.3 'Iypc 'I'cst Rcports

The type test report must contain the given below details in addition to above type tests duly stamped
by the testing lab (as per NTDC Type tests policy) shall be submitted with the bid. Such information
shall include, but is not restricted to the followings:
(a) Complete outline drawings.
(b) Data, photographs, details ofsupporting structure.
(c) Operating mechanism.
(d) Record oftest quantities oftested voltage xransformer.
(e) Drawing of VT general assembly.
(f) 'fhe details ofmountings, lixings and insulator.
(g) Creepage length, dry arcing distance and shed profile.
(h) Outline drawing, height and rated cantilever strength of insulator.
(i) 1'he resistance mcasured before and after the type tests of both primary and secondary
windings.
0) Manufacturer's name along with Country of origin of all components (like insulator,
connector, terminal head, core, winding, bellows, etc.) used during type testing.

9.i Routine Tests (For Quality Assurance)


'l'he manufacturer shall perform routine tests on all voltage transformers according to respective
clauses of IEC 61869-1, 61869-3 and 61869-5 and test repofts shall be submitted at the time of pre-
dclivery inspcction.

9.4 Acceptance Tests/ FAT (Factory Acceptance Test)


9 4.1 The following tests shatl be made on 100%o ofthe ordered quantity ofVTs & CVTs to be offered for
pre-delivery inspection/testing in presence of NTDC representative(s). The arrangement, test
conditions, and criteria to pass the tests shall be in accordance with relevant clauses of IEC 6 I 869- l,
6 I 869-3 and 6l 869-5 amended to date for each vohage transformer. The determination of errors test
shall be perfonncd after all other tests.

a) Measurement ofthe resistance of primary and secondary windings. The resistance should not
cxceed the resistance measured during type tests on voltage transformer.
b) Power frequency voltage withstand test at primary & secondary windings and between
sections.
c) l'artial discharge measurement.
d) Measurement ofcapacitance and dielectric dissipation Factor test.
e) Tests for accuracy.
l) Verification of marking
9 .4.2 Following tests shall be perforrred on one Voltage 'lransformer prior to the tests mentioned in 9.4.1
as per IEC standards randomly selected from the offered quantity of voltage transformers. If one
specimen lails to meet the requirements of any individual test specified below, then two additional
samples shall be selected at random from the offered lot. Failure ofany specimen from the second
sarnpling shall cause rejection ofthe entire lot.

a) Mechanical Test
b) Enclosure tightness test at ambient temperature
Ii-mail: cc.sr,l rr ntdc.conr.pk Substation I)csign Dcpartment Pagc l8 of32

7 t-t-
NATIONAL TRANSMISSION & DESPATCH COMPANY
www.ntdc.com.pk P -206:2021

c) Pressure test for enclosure

9.4.3 One complete VT & CVT shall be fixed on the steel supporting structures for following examination:
a) Verification ofname plate data and terminal marking.
b) Check ol constructional and performance requirements.
c) Visual & dimensional verification of Vl' & CVT assembly, steel supporting structures,
terminal connectors and earth terminals.
d) Measurement of creepage distance.
e) Verify all components/devices are correctly labeled.
9.4.4 The acceptance/inspection certificate should clearly indicate the performance of above tcsts during
pre-delivery inspection/testing and test results shall be submitted to the Purchaser. A copy ol bill of
quantity indicating thc total quantity of each component, parts, structure, their accessories, etc, duly
signed by the inspectors(s) required lor consignee for verification on receipt of material in
warehouse/store shall also be attached with the inspection certificate.

10.0 I)RAWINGS AND DESCRIPTIVE DA'TA


10. I Data to be submitted with the bid

l0.l.l Supply record ofoffered type, voltage rating and ratios ofvTs & CVTs for last five years on the
following format:
Sr. Contract/Pu rchasc Quantity Volttlgc Dclivery Clicnt
No. Order r.-o. & datc ralio pcriod Addrcss/
Phonc/ !-ax
No./ E-mail,
etc.
10. l .2 The schedule oftechnical data duly filled-in anached hereto along with supponing documents. The
word indicating "as per specification/standard" or "refer to ---" will not be acceptable.

10.1.3 Dimensional & outline drawing of VTs showing dimensions of each individual part including,
terminal head for high voltage connections, size of terminals lor earthing and terminal connector.

10. I .4 Non submission ol' completely filled-in schedule of technical data, supponing documcnts as
mentioned therc-in and supply record on the above format or submission of incomplcte
information/data as mentioned above with the bid, may render the bid non-responsive.

10.2 Approval of Drawings and Data to be submitted after Award of Contract/Purchasc Ordcr
The following drawings/descriptive data shall be submitted for approval of Design Departrnent N'f DC
before manufacturing the equipment:

a) Schedule oftechnical data duly filled-in along with supporting documents.


b) Instruction Manual for installation indicating site test procedure before energizing/operat ion,
maintenance/replacement ofcomponents procedure and storing requirements ofthe V'fs.
c) Dimensional & outline drawing ofVTs showing dimensions ofeach individual part including.
terrninal head for high voltage conncctions, sizc of terminals for earlhing and tcrminal
conneclor.

l:-mail: ce.sd.r ntdc.conr.l)k Substation l)csign I)cpanmcnt I'asc 19 ol 32

b/; et F*
C
NA'I'IONAL TITANSMISSION & DI.]SPATCH COMPANY
www.ntdc.com.pk l'-206:2021

d) Sectional drawing ofthe voltage transformer indicating the inner details.


c) Primary connections arrangement and secondary terminal box drawing.
l) Drawing showing fixing arrangement of the bellows, if applicable.
g) Drawing showing the method of sealing and attachmcnt in case of bellows also indicating
material and endurance life.
h) Typical curves showing the voltage ratio error and phase displacernent as a function of the
voltage from 5ok to l50Yo ofthe rated voltage for 25% and 100%o ofrated burden specified.
i) 'l'ypical curvcs showing thc voltage ratio error and phase displacement as a function ofthe
burden specified from zero to 100%, for 80o% and l20o% ofrated voltage and at 80% and 100%
power factor.
j) 1'he rnaximum allowable mechanical loads for:
. Any one primary terminal in any direction.
. Total resulting load applicablc to top assembly in any direction on primary terminals.
. Torque/ resulting torquc in horizontal direction on primary terminals.
k) 'l-cchnical catalogue in respect ofthe bushings.
l) Installation, erection, maintenance and opcration instruction manuals.
m) Drawings of steel supporting structure, foundation/grouting bolt drawing showing static and
dynamic loading ofVTs & CVTs. Photographs in fully arranged and erected condition.
n) 'lype test reports ofVTs & CVTs, insulator, terminal connectors.
o) Itating plate drawing and earthquake simulation and response calculations.
I t.0 PACKING
'l'hc Voltagc l'ransfonners / Capacitor Voltage Transforrners and all allied material including steel
supporting structure, connector, etc. shall be supplied in individual packing suitable for transport by
rail/road and sea as per international practice.'l'hc VTs/ CVTs and all allied material including steel
supporting structures shall be supplicd in packing suitable for transport by rail/road and sea as per
intcrnational practice. Special precaution may be essential for protection ofinsulation during transport
to prcvcnt moisture absorption due, for instance, to rain, snow or condensation. In every package of
cquipmcnl lor shiprnent onc number installation, crcction, maintenance and operation instruction book
enclosed in water proof material shall be provided. Bill of quantity shall indicate the quantity, size,
length, weight and assembly mark ofeach member ofstructure including nuts & bolts. washers, plates,
foundation bolts and all finings complete lor structurc, connector etc.

12.0 ENCLOSURES
l. 'l'ransformer
Schedule ofTechnical Data for Voltage Transformer and Capacitor Voltage
2. Primary Terminal layout drawing

Ir-mail : cc.sd.r ntdc.conl.l)k Substation Dcsign Dcpanmcnt Pagc 20 ol 32

o1
Lv t-*
NATIONAL TRANSMISSION & DESPATCH COMPANY
www.ntdc.com.pk P -206:2021

All Rights Reserved. Unless otherwisc specified. no part of his document may be reproduced or utilized in any
lbrm or by any means without pcrmission in writing fiom NTDC.

Spccifi cation llcview Committec

1 ca"-* ]-
{a----.-tt /Lr-r;A
Engr. Malik .Iaved Mahmood Engr. Atif Mujeeb Usmani [ingr. Farooq Rashid
()eneral Manager Chief Engineer Chief llngineer
(A.M) North NTDC (P&C) NTDC (PSP) N'I'r)C
(Mcmbcr) (Mcmber) (Mcmbcr)

l"t* \<o^^ryt-'
\.S'
E,ngr. Lubna Kausar rffiffi-r4x'at-.--
Chief Engincer ,/ chicl E{einccr
(c&M)) N'I'DC Substation Dcsign NTDC
I
(Mcmbcr) (Sccrctary)

Iingr. Malik Javed Mahmood


Gcncral Manager (D&E) NTDC
(Convener)

ll-mail: cc.sela c.cont.pk Suhstation Design Depanmcnt Pagc 2l ol-32


NATIONAL TRANSMISSION & DESPATCH COMPANY
wrrrv.ntdc.com.pk P -206:2021

SCIIT],DULI' oI' I'IlCI INICAL DA'I'A


!-oI{ MI.],1'!],ItIN(; VOLTA(;F], 1'IIANSI.'OIIMEIi. OI- kv

A'_ NTDC SPECIFIED DATA/PARAMETER. BLANK DATA'tO BE FILLED AT THE


.IIME OF BIDDING
I

.B' _ PROPOSEI) I)A'I'A/PAITAMETERS I}Y 'I'IIE


CON'I'RACI'OIVBII)DIiIUSUPPLIEIUVI'NI)OR
.C' . III]MAIIKS SI.JPPoR'I-INC T}IE PIIoPoSEI) DI]VIA'I-ION IN CoI,UMN 'I}'
(*) - DATA/PAnAM rt'I.tR't'O BE PROV I txt I)/PROPOSED BY't't I ll
CONTI{AC'I'OII/IIII)I)EIUSUPPLIE,R/VENIX)IT IN COLUMN'I]'
REFERENCE DESCITI PI'0\ .B' 'c'
SECTION I

NO.
I1pc/l)csignation o l'oll'crcd V I

5.0 IIA'I'IN(IS
Norninal voltage, rms (kV)
Ilatcd voltage(Um), rms (kV)
Rated Frequency (Hz) 50
No. of Secondary Windings I

Rated Burden (VA) 50


Accuracv Class 0.2
Rated Voltage Faclor
a)Continuous 2
b)30 scconds 5
Maximuml'emperature Rise above on 55
Ambient of 50'C
One Minute Porver Frequency Withstand
Voltage (kV)
I
Rated Lightning Impulsc withstand voltage
I

1.2/50ps, (kV peak)


Power I"requency Withstand Secondary
Circuit, kV rms
Ratcd switching Impulsc Withslarrd
Voltage, kV Peak
Norninal Transformation ralios
Rated Primary Voltage(Phase to Neutral)
KV
Rated Secondary Voltage (V) ll0/\i3
Minimum External Creepage Distance (mm)
Short Circuit Impcdancc(O), relerred to 0.5 I

Secondary (max)
lladio lntcrlercnce Voltagc at l.l. UR/!3kV 25 00
[]-mail : ce.scl'iJ.ntdc.conr.pk Suhstirtion I)csigrl I)cpa meDt Pasc 22 of32
NATIONAL TRANSMISSION & DESPATCH COMPANY
www.ntdc.com.pk l'-2116:2021

and 1000 kHz. (Miffo Volts)


Ambient Conditions: I

i) 'l'cmperature Range ("C)


I
ii) Wind Velocity (Km/h)
i ii) Earthquake (g)

Capacitance:
i) High Voltage Capacitor: C I
ii) lntermediate Voltage Capacitor :C2
6.0 C()NS'I'III.ICTION
Complete height of the VT (mm)
Clearance to ground (mm)
Material of bellows Synthetic
or stainless
steel
Material of primary winding
Material of secondary winding
Material of rating plate
'fhickness of rating plate (rnm)
Dimensions of rating plate (LxW), (mm)
Weight per pole (kg)
Wcight of oil per polc (kg)
6.0 ST'I]EL SUPPOITTIN(; STITUC'TURI,],
[)imensions fbr steel support structure:
Height (mm)
Breadth (mm)
I Width (mrn)
Structure fixing foundation details
'fensile Strength of Angles/plates (Kgimm2)
'['cnsile Strength olNuts & Bolts (Kg/mm2)
l: longation (%)
Wcight of Zinc Coating of angles/nuts &
bolts.
I
'lhickness ofzinc coating angles/nuts &
bo lts.
Ilardness olnuts & bolts (FlB)
Designed soil-bearing capacity
Scism ic withstand stress/magnitude. (Attach
design calculations).
'l'otal weight of supporting steel structure
rvith foundation bolts (kg)
6. t CIIARACTEIIIS'I'I (]S OT' OIL
Viscosity at 40"C, max. (mm2ls)
V iscosity at -30'C, max. (mm2/s)
Density at 20"C. max. (g/ml)
Irlash point ('C)
l)iclectric dissipation fhctor, tan 6 at 90'C.
Fl-mail: ce.sd ii.ntdc.ctrn.nk Suhstation Dcsian Deoartmcnt I)agc 23 ol J2
NAI'IONAI,'I'IIANSMISSION & DESPATCII COMPANY
www.ntdc.com.pk l'-2O6:'2O21

Max.
Pour point, max. ('C)
Diclectric strength. rnin. (kV) I

I'C[] Content. I

Acidity, max. ( mg KOH/g)


6.2 I'!]ItMI NAI-
Material of primary term inals. aluminum
/l'in plared
copper
Sizc ol prirnary terminals.(mm) l00xl00xl
5
Current carrying capacity of primary
terminals (A)
Static withstand load of primary terminals I I

(ke) I
I

Dynamic withsund load of primary


terminals (kg)
Whether brass cablc glands arc provided in
the secorrdary tcrminal box (Yes,No)
Matcrial ol- sccondarv tcrm inals-
Whcthcr two llarthing tenninals are
providcd (YcsA.Jo) I

Matcrial of Earthing terminal I

6.1 0 I \ST ]I,A'I'OIt


-l'ype
of lnsulator Porcelain
Copy of 'l'ype tests Reports Attached
(Yes,No)
Details of Type Tests if performed.
I Mechanical test.
Irnpulse withstand voltagc.
Powcr lrequcncy withstand voltage
Radio interlerence Voltage
Diameter of insulator (mm)
I Icight of Insulator (rnm)
I Crccpagc distance (Phase to Earth) (mm)
Phase to phase clearance (mm)
Max RIV (pV) I

Impulse withstand voltage (kV)


I)owcr liequcncy withstand test voltage
Dry I rn inute (kV) I

Wctl0sec.(kV)
Ultimatc strcngth of column (kg)
Withstand [)ressure:
Cantilcvcr Strenglh (N)
'l'cnsile strength
Q.,l)

E-mail : ce.scltilnLdc.con.pk Substation I)esi gn Department t'agc 24 o1 32


NATIONAL 'IItAn-SMISSION & DESPATCH COMPANY
www.ntdc.com.pk l'-206:2021

'l-orsional strcngth (N)


I

Compression strcngth (N)


llcnding (N)
Matcrial and color of insulator. Chocolate
glazed
brown
Refercnce Manufacturing IEC Standard of IEC 62 t55 I

insu lator. and IEC- |


60273 I

R-l'V Coated Porcelain (YesAlo)


9.2 'l'Y I'E 1 [S-l'S
I{cports Attached (YcsAIo) I

Status ol"l csts Perlormcd


Nanrc of l,ab
Ilcport No
Rcport Date
For I nduclivc voltage transformer
Mcasurement of the resistance of primary
and sccondary windings (YesA',lo)
lmpulsc voltage withstand test (Yes,4',lo)
Ibwcr liequency voltage
rvithstand tcst at I'rimary &
sccondary u,indings. betwecn
scctions and lbr earthcd
tcrminal (dry). (Yes,No)
Wet test lor outdoor type
transfonrers(Y es,t,lo)
Partial discharge measurement during
induccd voltage test. (Yes/No)
Electromagnetic compatibility (EMC) tests
(Yes/No)
I'cnrpcraturc-risc tcst. (Yes^io)
Measurcmcnt of capacitance and dielectric
dissipation Facror. (YeVNo)
Tests for accuracy. (Yes/No)
Verifi cation of degree of
protection by enclosures.
(Yes.4.,lo)
Verifi cation of terminal
I []nclosure tightness test at
ambient tcmperature(Yes/No)
Prcssure test lor the
enclosure. (YesNo)
Short-c ircu it withstand
capability tcst. (Yesn!o)

Il-mail : ce.sclri ntdc.crrnr.Dk Substation Design Dcpartment l'agc 25 ol 32


NA'I'IONAL'I'IIANSMISSION & DESPA'I'CH COMPANY
www.ntdc.com.pk l'-2116:2ll2l

Radio Interference Voltage


(RIV)'fest. (Yes,4.,lo)
Mechanical test. (Yes,No)
I Transmitted Ovcrvoltage
Measuremcnt (YesNo)
Determination of percentage
I
voltage (ratio) errors and
phase displacernent at 809/0,
100% and l20Yo of rated
voltage, at rated frequency
and at 25Yo and l00oZ ofrated
burden lor measuring winding
and at a power factor of 0.8
lagging lor measuring
accurac class. Ycs,No
l'or Ca acilivc Voltage'l'ranslbrmcr
Measurement of resistance of I

primary and secondary


I windings (Yes/No)
lmpulsc voltagc withstand
tcsts on primary tcrminals
(YesA',lo)
Choppcd impulsc withstand
test (Yes/No
Powcr lrequency voltage
withstand test a1 primary and
second windin (YesA'{o
Wet tcst (YesfNo)
Electromagnetic Compatibi I itY
'l'est Yes,4.Jo
Temperature rise test
(Yes/No)
Measurcment ol'Capacitancc
and Diclectric Dissipation
l:ac1()r Yes/No)
'fest lbr accuracy (YesA',lo)
Capacitance and tan 6 at
I power frequency (YesAIo)
Verification of dcgree of
protection by enclosures
(YesA,Jo
Enclosure tightncss test at
ambient Tcmpcrature
es/No
Pressure 'fest for cnclosure
(YesNo)

lr-miril: cc.sd nldc Substation Dcsign Dcpartment Pagc 26 of32


NATIONAL TRANSMISSION & DESPATCH COMPANY
www.ntdc.com.pk l'-206:2021

Short circuit withstand


capabil ity tcst (Yes/No)
l"crro-resonance tcst
['artial discharge
rreasLlrcn'lcnt during induccd
I

vollagc lcst (YesNo)


Iladio inlcr[crencc lest (RIV)
(YesNo)
Mechanical test (Ycs,Aio)
Transmittcd over voltage
measurerncnl (Yes/No)
Determination of percentage voltage (ratio)
crrors and phase displacement at 80o%,
100% and l20oZ of rated voltage, at raled
liequcncy and at 25o/o and 100% of ratcd
burden lbr mcasuring winding and at a
pou er lactor of 0.8 lagging lor measuring
accuracy class. (YesA.{o)

Ir-mail: cc.\d a nt.ic.cijnr.pk Substation I)csi-qn Depanrncnt I']aec 2? ol 32


NATIONAL TRANSMISSION & DESPATCH COMPANY
lyrvw.ntdc.com.pk l'-206:2021

PRIMARY TI.],II,M TNAL LAYOUl' I)ItAWING

,,,
,

20

160
100

20

AII Dimcnsions arc in Millimcters.


NATIONAL TRANSMISSION & DESPATCH COMPANY
}}Tr.w.ntdc.com.pk P -206:2021

OTHER PAIITICULARS TO BE FILLED UP BY


BIDDER/VENDOR/SUPPLIER/CONTRACTOR

Actual Manulacturer of Vendor/Supplier/Contractor


Equ ipment/Material

GE'f,RAI-

Manufacturer's name &


address. (Attach
Manufacturer's catalogue)

Name of the Company


Location and address

Name and Signature of


authorized representalive
and date

Official Seal/Stamp of the


Company & Date

CONSTRUC'TI0N

(Attach photograph of C'l'


shorving all parts and a
detail legend)

Name of the Cornpany


Location and address

[-mail: cc.scl ri ntdc.crrnr.nk Suhstation Design Depanrrcnt Pagc 29 ol'32


NA'I'IONAL TRAIISMISSION & DESPATCII COMPANY
www.nldc.com,pk l'-206:2021

Name and Signature of


aul.horized representative
and date

Official Scal/Stamp of the


Cornpany & Date

I\SI.JI,A'I'OR

Manufacturer's name &


address. (Altach
Manufacturer's catalogue
and oulline/dimensional
drawing)

Namc o1-thc Cornpany


Location and address

Namc and Signature of


authorizcd representative
and date

Ollicial Seal/Starnp of the


Company & Date

li-nrail: cc.sd a ntdc.conr.pk Substation I)csign Depanmcnt Pagc 30 of32


NA'I'IONAL TRANSMISSION & DESPATCH COMPAIIY
wrv$'.ntdc.com.pk l'-206:2021

S-I'II,I, SUPP0R'I'I\(;
S'f Il tr (11'U Iil-
Manu f-acturer's namc &
addrcss. (Attach
drawing/photograph ol' thc
support structure).

Namc of the Cornpanl'


l,ocation and address

Name and Signature of


authorized representative
and date

Official Seal/Stamp of the


Cornpany & Date

'l [. tt] \,.\ t_

Manuf'acturer's name &


address. (Attach
drawing/photograph of thc
terrninal).

Narne of the Company


l,ocation and address

Name and Signature of


authorized rcprcsentative
and date

Olficial Seal/Stamp of the


Company & Date

l,-mail : ce.scl ri ntdc.conr.rrk Substation Design Dcpanment I'agc 3l d-32