You are on page 1of 6

2016 International Conference on Electrical Power and Energy Systems (ICEPES)

Maulana Azad National Institute of Technology, Bhopal, India. Dec 14-16, 2016

High Impedance Fault Detection in Microgrid


Using Maximal Overlapping Discrete Wavelet
Transform and Decision Tree
Susmita Kar, Student Member, IEEE S. R. Samantaray, Senior Member, IEEE
School of Electrical Sciences School of Electrical Sciences
IIT Bhubaneswar, India IIT Bhubaneswar, India
Email-Susmita.bit@gmail.com Email-sbh_samant@yahoo.co.in

Abstract— The paper presents a high impedance fault (HIF) An adaptive relaying strategy for microgrid protection with
detection scheme for microgrid using maximal overlapping high penetration of DGs is proposed in [5] which does not
discrete wavelet transform (MODWT) and decision tree (DT). consider islanded mode of operation. A communication based
The small, nonlinear, random and widely varying fault current of protection schemes for grid connected microgrids with an
HIF makes the over-current relay insensitive. Thus, time-
assumption of large amount of fault current contributed from
frequency information is required to distinguish HIF from no-
fault event. The proposed work start with retrieving the fault utility grid is proposed in [6], [7]. The authors in [8] derived
current which is pre-process through (decompose using) sequence components to design the protection relay. However,
MODWT to get the details and approximation coefficient. multiple settings are applied on the derived sequence
Further, some statistical features are estimated using the details components, making the relaying scheme more complex. The
and approximation coefficient. The features extracted are used to voltage based protection scheme is proposed in [9] which uses
train decision tree (DT) for accurate classification of HIF from synchronous reference frame to compare the reference of the
no-fault. The proposed scheme is tested for HIFs detection in phase voltage at the DG source. Data-mining model based
microgrid for different operating conditions. The test results protection scheme for shunt faults is proposed in [10-11],
show that the proposed scheme provides an effective protection
which work efficiently in both grid connected and islanded
measure against HIFs for safe and secured operation of
microgrid. mode. It is observed that the above referenced works are
suitable for solid and low impedance faults and fails to detect
Index Terms — Microgrid, High impedance fault, Maximal high impedance faults (HIFs). However, HIF mostly occurs in
overlapping discrete wavelet transform, Decision Tree. distribution networks when the overhead conductor comes in
electrical contact with the high-impedance surface like
concrete or tree [12].
I. INTRODUCTION A differential energy based microgrid protection scheme is
Integration of distributed generations (DGs) with enabling the proposed in [3] which considered both shunt faults and HIFs
use of renewable energy sources changes the conventional for their study. However, the same scheme does not provide
distribution system into a microgrid. Microgrid provides on- clear idea on HIF detection at different operating modes.
site generation which reduces distribution losses. The use of Further, the scheme suffers from the high computational
renewable energy sources such as wind energy, photo-voltaic burden of the S-transform in computing differential energy,
cells and fuel cells, provides solution to the problems of leading to slower response time of 4 cycles from the fault
greenhouse gas emission and depletion of fossil fuel based inception. The aforementioned protection issues provide a
energy[1-2]. Microgrid can operate in grid connected mode strong motivation for developing a HIF detection scheme in
(connected with the main utility) or in islanded mode microgrid.
(independently) while meeting the service reliability and The HIF does not cause an excessive change in fault current
power quality [3]. However, to experience the benefits, an due to the high impedance path and thus, the overcurrent relay
effective microgrid protection scheme is highly essential [1-4]. fails to provide protection against HIFs. Further, the fault
The protection issue becomes critical in microgrid as the current in HIF is non-linear, random and widely varying in
magnitude and direction of fault current varies with the nature [12-14]. Thus, the proposed scheme utilize both time
operating modes [4]. Thus, the protection scheme must be and frequency information for HIF detection in microgrid. The
sensitive to changes happens in microgrid and ensure safe proposed scheme develops a HIF detection scheme for
operation of microgrid against all types of faults in grid microgrid using MODWT and decision tree. The scheme
connected and islanded mode. Several microgrid protection considered HIF at various locations of the distribution lines
techniques have been proposed [5-10]. with grid connected and islanded mode of microgrid. Further,

978-1-5090-2476-6/16/$31.00 ©2016 IEEE 258


some no-fault cases such as sudden load change, capacitors R1 =0.413 ohms/km, L0 =1.05 e-3 H/km, L1 =3.32 e-3
switching etc. are considered at different operating conditions. H/km, C0 =11.33 e-9 F/km, X1 =5.01 e-9 F/km,
The proposed scheme retrieves the fault (HIF) currents and x Total loading (sum of L1 to L5) considered : 20MW,
pre-processes (decomposes) it through MODWT-preprocessor 10MVAR.
[15], [16] to obtain the details and approximation coefficient.
Some statistical features such as mean, standard deviation, PCC
B-1 TR -2 DG -1
B-2
energy and entropy are estimated using the details and
approximation coefficients for each phase. The features TR -1 CB-1 DL -1 CB-2
estimated are used to build the decision tree (DT) for HIF and CB_MAIN
B-3
CB-3 DL -2 CB-4
no-fault classification. Fig. 1 shows the schematic diagram of L-2 B-4
TR -3 DG -2
UTILITY
the proposed HIF detection scheme for microgrid.
HIF
CB-5 DL -3 CB-6
IFault L-1 B-5

CB-7 DL -4 CB-8 L-4


L-3

Pre-process using
TR -4 L-5
MODWT

DG -3

Features Final relaying


Extraction DT Decision Fig.2. Studied microgrid
(HIF Detection)

Fig.1. Proposed intelligent HIF protection scheme. III. DESIGN OF PROPOSED RELAYING SCHEME FOR HIF
DETECTION

II. SYSTEM STUDIED A. MODWT and Features Extraction


The test microgrid system for the proposed HIF detection
The wavelet transform is a powerful tool for the analysis
scheme is shown in Fig. 2. The base power has been chosen as
of non-stationary signals like fault current, where frequency
10 MVA. The details of the test system are given as follows:
content varies with time [15]. Wavelet transform is a better
x Utility: rated short-circuit MVA=1000, f=60 Hz, rated kV
tool as compared to Fourier transform and STFT, providing
=120, Vbase = 120 kV.
both time and frequency information which is required to
x Distributed Generations (DGs): extract transient information from the non-stationary signals
¾ DG1, DG3: synchronous generator with rated MW=9, [3].
f=60Hz, rated kV=2.4, Inertia constant H=1.07sec., The wavelet transform represents the signal in time–
Rs=0.0036pu, Xd=1.56 pu, Xd'=0.296 pu, Xd"= frequency domain and provides the time localization of the
0.177pu, Xq=1.06pu, Xq"=0.177pu, Xl=0.052pu, signal [14-17], whereas Fourier transform does not give any
Td'=3.7sec, Td"=0.05sec, Tqo"=0.05 sec. information related to time–frequency domain. Further, the
¾ DG2: Wind farm consisting of three 2 MW wind Short time Fourier transform (STFT) has limitation in
turbines (6 MW), f=60Hz, rated kV=575V, Inertia resolution due to its fixed window size. The wavelet transform
constant H=0.62sec.,Rs=0.006pu, Xd=1.305 pu, Xd'= (discrete) provides uniform time resolution for all frequencies,
0.296 pu, Xd''= 0.252pu, Xq=0.474pu, Xq"=0.243pu, high time resolution and low frequency resolution for high
Xl=0.18pu, Tdo'=4.49sec,Tdo"= 0.0681sec, frequencies and high frequency resolution and low time
Tq"=0.0513sec. 575V, 60Hz. The synchronous resolution for low frequencies. [15] The practical application
generator with inverter interface to main grid has been of wavelet transform is performed using the discrete wavelet
considered for the proposed study (Type- 4 detailed transform (DWT) [15].
model in MATLAB/SIMULINK). However, DWT is limited to the signal length of N which
x Transformer (TRs): is multiple of 2 j where j = 1, 2, 3, . . , J (J is the scale number)
¾ TR1: rated MVA = 15, f = 60 Hz, rated kV = 120/25, [15]. Further, the orthogonal transform of DWT suffers the
Vbase = 25 kV, R1 = 0.00375 pu, X1= 0.1 pu, Rm= 500 lack of the invariance translation in time series analysis.
pu, Xm= 500 pu. Whereas, the maximum overlap discrete wavelet transform
¾ TR2, TR4: rated MVA = 12, f = 60 Hz, rated kV = (MODWT) is the enhanced version of the DWT with ability of
2.4kV/ 25 kV, Vbase = 25 kV. the free selection of a starting point of a time series signal
¾ TR3: rated MVA = 2.5, f = 60 Hz, rated kV = 575 V/ [15]. The MODWT is a non-orthogonal variant of the classical
25 kV, Vbase = 25 kV.
x Distribution lines (DL) : DL1, DL2, DL3, and DL4 : PI- DWT. The MODWT scaling filter hil and the wavelet filter gil
Section, 20km each, Vbase = 25 kV, R0 =0.1153 ohms/km, are related to the DWT filter through (1) and (2).

259
hl j

hil (1) i  i
2
X (n ) ¦ D j A j (13)
l 0

gl The original signal can be reconstructed easily from the


gil (2) decomposed signals like DWT techniques (using the obtained
2
details and approximation). In the present application the post
The MODWT filters are also in the quadrature mirrors like fault (HIF) current signal is retrieved and pre-processed
DWT filter is given as (4) and (3)
(decomposed to get details and approximate coefficients) to
i
g (  1) l  1 h L  1  l (3) find out the statistical features such as mean, standard
deviation, energy and entropy of the detailed and approximate
h (  1) l  1 g L  1  l (4)
coefficients at each decomposition level. The energy of detail
where l = 0, 1, 2, . . . , L − 1 and L is the width of the filter. coefficients at each decomposition level ED,i is obtained as
The nth element of the first-stage wavelet and the scaling follows:
coefficients of MODWT with the input time series signal Y (n) N 2
1
is as follows:
L1  1
E D ,i
N
¦ D ij (14)
j 1
i hil Y n  l m o d N
W 1,n ¦ (5) The standard deviation of detail coefficients at each
l 0
decomposition level STDD,i is obtained as follows:
L1  1
1
Vi 1 , n ¦ gil Y n  l m o d N (6) § 1 N
·2
l 0 S T D D ,i ¨ ¦ ( D ij  P i ) 2 ¸ (15)
Where n= 1, 2, 3,..., N and N is the length of signal in sample. © N j 1 ¹
L1  1
The entropy of detail coefficients at each decomposition level
iA 1 , n gil Vi 1 , n  l m o d N
¦ (7) EntD,i is obtained as follows:
l 0 N
L1  1 E n t D ,i  ¦ D ij2 lo g ( D ij2 ) (16)
i 1,n hil W
i
D ¦ 1,n  l m o d N (8) j 1
l 0
The total energy ETOTAL is obtained as follows:
The first-stage approximations and details can be calculated N 2
2

by (7) and (8). The MODWT scaling coefficients Vij and W


j
j
E TOTAL ¦ A ij  ¦¦ D ij (17)
i j 1 i
wavelet coefficients at the nth element of the jth stage are
Where i =1, 2, 3,..., l (level of decomposition, in this
given by the eqns. (9) and (10)
application 4) and N is the number of samples in each
L j 1
decomposed data.
Vi j ,n ¦ gi j ,1
Yi n  l m o d N (9) In the present application, one cycle post HIF current signal
l 0 samples are retrieved and pre-processed through MODWT to
L j 1
obtained the details and approximate coefficients at different
i h Yi n  l m o d N
W j ,n ¦ j ,1
(10) decomposition level. The different statistical features such as
l 0 mean, standard deviation, energy and entropy are estimated
for the details and approximate coefficients. Further, the
Similarly, the approximations j j of the
A j and the details D j
features estimated are used to build the DT for HIF and no-
nth element of the jth stage MODWT are given by the (11) and fault classification. Fig. 3(a) and (b) shows the fault current
(12). and the detail coefficients at different decomposition level,
L j 1 respectively.
0
i gi Vi 1 , n  l m o d N In the proposed study, 12 features are derived from the
A j ,n ¦ j ,l
(11)
current signal (post HIF) retrieved at each phase. The
l 0

L j 1 complete features set consider in this work are as follows:


i h
0
i F1=Sum of Energy obtained for detailed coefficients at
D j ,n ¦ j ,l
W 1, n  l m o d N (12)
each decomposition level for phase a
l 0
0 0
F2= Sum of standard deviation obtained for detailed
Where gi l is periodized gi to length N and also the h l is coefficients at each decomposition level for phase a
F3= Sum of Entropy obtained for detailed coefficients at
periodized h to length N. So the original time series signal each decomposition level for phase a
can be stated in terms of the approximations and the details as F4= Total Energy obtained for detailed coefficients at
follows: each decomposition level and final approximation for
phase a

260
F5=Sum of Energy obtained for detailed coefficients at the decision tree for HIF classification. The proposed work
each decomposition level for phase b simulates the HIF and no-fault cases at different location of
F6= Sum of standard deviation obtained for detailed the distribution feeder at various operating conditions (grid
coefficients at each decomposition level for phase b connected and islanded).
F7= Sum of Entropy obtained for detailed coefficients at DT [18] being rule-based, is more transparent and human
each decomposition level for phase b friendly. Thus, it is a popular classification and decision
F8= Total Energy obtained for detailed coefficients at making tool for high dimensional data spaces [18]. The
each decomposition level and final approximation for proposed work uses the powerful open-source data mining
phase b. software package ‘R’ for generating the DT [18-21]. Training
F9=Sum of Energy obtained for detailed coefficients at of the DT starts with estimation of the statistical features for
each decomposition level for phase c the particular kth instance. Initially, all the 12 statistical
F10= Sum of standard deviation obtained for detailed features are set as input against one target output of 1 (for
coefficients at each decomposition level for phase c HIF) and 0 (for no-fault situation) for a particular kth instant.
F11= Sum of Entropy obtained for detailed coefficients at The feature set at kth instant is passed through the DT and the
each decomposition level for phase c process continues till convergence. The proposed work
F12= Total Energy obtained for detailed coefficients at considered 1493 (973 HIF and 520 no-fault) cases. Out of
each decomposition level and final approximation for 1493 cases, 70% data of the feature space is used for training
phase c of the DT, whereas the rest 30% data is used for testing.
Further, performance assessment is carried out.
The training feature set includes 1045 generated cases (685
Current amplitute (in pu)

0.2
numbers of HIF cases and 360 numbers of no fault cases). The
0.1
DT generated for HIF and no-fault classification is shown in
0
Fig. 4. It is observed that, though 12 features are used to train
-0.1
the DT only 5 features such as F1, F5, F8, F9 and F12 are
-0.2
participating in the classification process. While testing the
0 50 100 150 200 250
Samples
trained DT using the rest 30% data (448 cases), it is found
Fig. 3(a) classification accuracy of 99.77%. Out of 448 data count
(testing data set), 01 case is misclassified (1 no-fault case
0.2 classified as HIF).
0
-0.2
0 50 100 150 200 250
F1 >= 6.28
Current amplitute (in pu)

0.02
0 s No
-0.02 Ye
0 50 100 150 200 250 F5 >= 5.5 HIF
0.05

0 Yes No

-0.05
0 50 100 150 200 250
F9 < 5.3 F8 >= 6.31
0.1
s No No
Ye s
0 Ye
-0.1 No Fault F12 >= 6.29 HIF
0 50 100 150 200 250
No Fault
0.1 s No
Ye
0
-0.1 No Fault HIF
0 50 100 150 200 250
Samples
Fig. 3(b) Fig. 4. DT generated for HIF and no-fault classification.
Fig.3(a). Fault current and Fig. 3(b) the detail coefficients at different
decomposition level.
IV. RESULT ANALYSIS AND DISCUSSION
B. Building DT for HIF and no-fault classification Performance assessment of the proposed HIF detection
scheme is carried out using the following reliability measures
The instantaneous one cycle post HIF current signals are [18].
retrieved using CT and then pre-processed through MODWT x Dependability: It is defined as the ratio between
(decompose the main signal into details and approximation total number of HIF cases predicted and total number
coefficient). Some statistical features like energy, mean, of actual HIF cases.
standard deviation and entropy are estimated using the details
and approximation coefficient. These features are used to train

261
x Security: It is defined as the ratio between total The high value reliability measures make the scheme suitable
number of no-fault cases predicted and total number candidate for HIF detection in microgrid.
of actual no-fault cases.
x Accuracy: It is defined as the ratio between total REFERENCES
number of correctly predicted (HIF + no-fault) cases [1] Stadler, M., Siddiqui, A, Marnay, C, Aki, H. and Lai,J : ‘Control of
greenhouse gas emissions by optimal DER technology investment and
and total numbers of actual (HIF + no-fault) cases. energy management in zero-net-energy buildings’, European
Transactions on Electrical Power, 2009, 2, (2), pp.1291-1309.
Dependability shows the selectivity of the relaying scheme [2] Venkataramanan, G. ; Marnay, C.: ‘A larger role for microgrids’, IEEE
whereas security shows the false-alarm which indicates the Power and Energy Magazine, 2008, 6, (3), pp. 78–82.
number no-fault cases predicted as fault (HIF) [18]. However, [3] Kar, S. and Samantaray, S. R.: ‘Time-frequency transform–based
mis-detection is most critical compared to the false-alarm for differential scheme for microgrid protection’, IET Genr Transm &
Distrib., 2013, 8, (2), pp.310-320.
fault protection relay. The fault current magnitude varies
[4] Girgis, A and Brahma, S.M. : ‘Effect of distributed generation on
significantly with the operating conditions of microgrid [18]. protective device coordination in distribution system, system’, in Proc.
Thus, to show the efficacy of the proposed HIF detection Large Eng.Syst. Conf. Power Eng., Jul. 2001, pp. 115–119.
scheme performance assessment is carried out separately for [5] Wan, H, Li, K.K. and Wong,K.P:‘An Adaptive
grid-connected mode and islanded mode. This uses another Multiagent Approach to Protection RelayCoordination With Distributed
data set of 891 cases (449 cases in grid connected mode (326 Generators in Industrial Power Distribution System’, IEEE Trans. Ind.
Appl., 2010, 46, (5), pp. 2118–2124.
HIF and 123 no-fault) and 441 cases in islanded mode (328
[6] Casagrande, E. and Woon. L. N : ‘A differential sequence component
HIF and 113 no-fault)). protection scheme for microgrids with inverter based distributed
The performance test results at grid connected mode are generators’, IEEE Trans. Smart Grid., 2014, 5, (1), pp. 29–37.
shown in Fig. 5. This test includes 326 HIF cases and 123 no- [7] Al-Nasseri, H. , Redfern, M. and Li, F. : ‘A voltage based protection for
fault cases. It is observed that the proposed HIF detection microgrids containing power electronic converters’, in Proc. IEEE
scheme has classification accuracy of 100% (with Power Eng. Soc. Gen. Meeting, Jun. 2006, pp. 1–7.
dependability 100% and security 100 % in grid-connected [8] Mahat, P., Chen, Z,Bak-Jensen, B and Bak, C.L.: ‘A simple adaptive
over current protection of Distributed Systems with Distributed
mode. Thus, the proposed scheme is able to classify all cases Generations’, IEEE trans. Smart grid, 2011, 2, (3), pp.428-437.
correctly in grid connected mode. While, performance [9] Hadzi-Kostova, B. and Styczynski, Z: ‘Network protection in
assessment is carried out in islanded mode, it is observed that, distribution systems with dispersed Generation’, in Proc. Transm.
the proposed HIF detection scheme has classification accuracy Distrib.Conf. Exhibit., May 2006, pp. 1–6.
of 99.32% with dependability 100% and security 98.23 % is [10] Redfern, M. A. and Al-Nasseri, H. : ‘Protection of microgrids
shown in Fig. 6. This shows the potential ability of the dominated by distributed generation using solid state converters’, IET 9th
international conference on Develop. Power Syst. Protection, 2008, pp.
proposed scheme for HIF classification in different operating 670–674.
mode. [11] Taha Selim Ustun, Cagil Ozansoy, and Aladin Zayegh, “ Modeling of a
Centralized Microgrid Protection System and Distributed Energy
Resources According to IEC 61850-7-420”, IEEE Trans. Power Sys,
100.5 27(3), pp.1560-1567, 2012.
Grid connected mode
Islanded mode
[12] Samantaray, S. R, Panigrahi, B.K and Dash, P.K, “High impedance fault
100 99.8%
99.6%
detection in power distribution networks using time-frequency transform
99.5 99.35%
99.475% and probabilistic neural network”, IET Gen. Trans. Distribution, 2008,
99.02%
2, pp. 261-270.
Percentage

99 [13] Sarlak, Mostafa and Shahrtash, S.M., “High impedance faulted branch
identification using magnetic field signature analysis”, IEEE trans Power
98.5 98.24% Del. 28(1),2013, pp.67-74.
98 [14] S.K. Aggarwal, L.M. Saini and A. Kumar, “Price forecasting using
MODWTand LSE based mixed model in Australian electricity market”,
97.5 International Journal of Energy Sector Management, 2 (2008), 521-546.
97
[15] S.J. Yao, Y.H. Song, L.Z. Zhang, X.Y. Cheng, MODWT and Neural
Dependability Security Accuracy Networks for Short-term Electrical Load Forecasting, Energy
Conversion and Management, 41(18) (2000), 1975-1988.
Fig.5. Performance of DT for fault detection in grid connected and islanded
mode. [16] A. R. Sedighi, M. R. Haghifam, O. P. Malik and M. H. Ghassemian,
"High impedance fault detection based on wavelet transform and
statistical pattern recognition," IEEE Trans. Power Del, 20(4), 2005, pp.
V. CONCLUSIONS 2414-2421.
The proposed scheme develops a HIF detection scheme is [17] C. H. Kim, H. Kim, Y. H. Ko, S. H. Byun, R. K. Aggrawal and A. T.
Johns, "A Novel Fault Detection Technique of High Impedance Arcing
for microgrid using MODWT and decision tree. The statistical Faults in Transmission Lines Using the Wavelet Transform", IEEE
features derived from the details and approximation Power Engineering Review, 2002, 22(7), pp. 61-61.
coefficients (obtained on decomposition through MODWT) [18] Kar, S. and Samantaray, S. R.: ‘Data-mining-based intelligent anti-
are used to build the DT for HIF and no-fault classification. islanding protection relay for distributed generations’, IET Gener.,
The proposed scheme provides high classification accuracy of Transm., Distrib., 2014, 8,(4), pp.629-639.
more than 99% with dependability 100% at different modes. [19] Khalil El-Arroudi, Géza Joós, Innocent Kamwa, , and Donald T.
McGillis, "Intelligent-Based Approach to Islanding Detection in

262
Distributed Generation”; IEEE Trans on Power Del., 2007, 22,(2),
pp.828 – 835.
[20] Rattle (the R Analytical Tool to Learn Easily), by D. Williams, ver. 2.6,
Dec 2010 [on line]: http://rattle.togaware.com/.
[21] T. Hastie, R. Tibshirani, J. Friedman, “The Elements of Statistical
Learning: Data Mining, Inference, and Prediction”, 2nd Edition,
Springer-Verlag: New York, 2009, pp745.

263

You might also like