You are on page 1of 14

Ammonia Storage Tank Study

The pressure and venting dynamics model was developed by adding superheated
liquid to the cryogenic ammonia storage tank. It is useful in that it farces to consider
all the processes during feed to a tank and gives a feel for the behavior to expect
when variables are varied.

James N. Tilton
Du Pont Engineering, Newark, DE 19714

Richard H. Squire, Connie S. Saffie, and C. Riek Atkins


Du Pont Agricultural Products, Belle, WV

BACKGROUND B. The vapor returned to the tank at the maximum


rate due to a malfunction of the vapor
The Belle Plant of the Du Pont Company handles replacement heater.
ammonia in a 20,000 ton cryogenic storage tank as a
terminal operation receiving ammonia by barge since C. The rate that the ammonia is pumped out of
the Kellogg ammonia plant was shut down in 1976. the tank. This consideration is for vacuüm
The double-walled and insulated tank operates between relief.
0.3-0.5 psig. Ammonia is used on the site for
refrigeration and in the Amines processes. The D. The amount of vapor normally going to the
ammonia distribution system consists of the 20,000 compressor. This is also for vacuüm relief.
ton storage tank, compressor, natura! gas assisted flare 2. External Factors
stack, and two distribution pumps with heat
exchangers. A. An external fïre of 817 °C completely
engulfing the tank.
The ammonia storage tank is rated at l psig and
has normal and emergency venting capacity. The B. The rate of drop of outside barometric
normal vent allows the bank to be controlled at a pressure.
given set point and the emergency conservation vents
begin opening at the design rating. The vent line from C. The maximum rate of heat input with the
the storage tank goes to the suction of the compressor insulation.
and to the flare stack. Several internal and external
factors were analyzed in the design of the normal and A more than 2x margin of safety was added to the
calculations resulting in the specification of two 10 inch
emergency vents.
emergency conservation vents. Thermal overload
l. Internal Factors resulting from addition of warm ammonia was not
considered in the design basis for the vents. Thermal
A. The heat duty associated with vapor overload is defined as the accumulation of sufficient
displacement while loading into the tank. enthalpy in the tank, either through heat leakage from

63
insulation loss, to cause vaporization rates which boundary layer to a temperature less than the warm
exceed the capacity of the normal vent, or worse, that feed temperature, but higher than the completely
of the emergency vents. Ammonia is unloaded from mixed temperature. This results in greater rates of
barges into the bottom of our storage tank where the vaporization.
addition of warm ammonia is critica!. To determine
the venting requirements for thermal overload events, 3. An extreme version of the preceding case would
a model was developed to predict the dynamics of yield the greatest rate of vaporization. This would
tank pressurization and venting behavior when warm be an assumed condition where no mixing of the
ammonia is added to the tank. warm feed into the cold ammonia occurred, and
the warm ammonia then rose to completely cover
INTRODUCTTON the surface. With the bulk temperature just below
the surface boundary layer suddenly raised to the
Large quantities of ammonia are typically stored
warm feed temperature, potentially very large
cryogenically. Du Pont has three large ammonia
vaporization rates would occur.
tanks, located at its Beaumont, TX, Victoria, TX and
Belle, WV plants. The Belle tank has a 20,000 ton The latter two events are related to a phenomenon
capacity and is rated for l psig. It typically operates described as "rollover". In principle, a rollover can
at 0.3-6.5 psig. The tank is double-walled and occur whenever thermal stratification results in a
insulated to minimize heat leakage to the ammonia, density inversion. Rollovers are often observed
which boils at -33.4°C. seasonally in lakes, and have been reported in oil
Out of a process hazards review of ammonia storage tanks. In principle they can also occur in
handling and storage at the Belle plant came a concern cryogenic storage tanks. For liquids stored under their
over the possibility of venting ammonia to the own vapor pressure, rollovers may be dangerous not
environment through the tank emergency vents, or, only beause of the stresses exerted on the tank by the
worse yet, overpressuring the tank, as a result of moving liquid, but also because of the sudden increase
thermal overload. For the present purposes, thermal in vaporization when superheated liquid is brought to
overload is defined as the accumulation of sufficient the surface. For saturated liquid storage, the
enthalpy in the tank, either through feeding warm possibility of vaporization, and its resultant drastic
ammonia or through heat leakage from insulation loss, increase in destabilizing buoyancy, must be considered
to cause vaporization rates which exceed the capacity when the superheat of a submerged layer is large.
of the normal vent, or, worse, that of the emergency
In 1989, a 10,000 ton capacity ammonia tank
vents.
failed in Lithuania, releasing 7000 tons of ammonia,
An obvious situation where thermal overload could resulting in 7 deaths, 57 injuries and the evacuation of
occur is when warm ammonia is fed into an initially 32,000 people over a 400 km2 area [2]. Thermal
empty tank. More subtle possibilities involve feeding overload has been suspected as one possible cause of
warm ammonia into a tank partially filled with cold the accident.
ammonia. Were the warm ammonia to mix slowly
with the initial liquid so that the liquid surface For a given mass of a warm submerged layer, the
temperature and vapor space pressure rise only very consequences of a rollover become more severe as its
slowly during the feeding, then excessive temperature is increased above the surface
accumulation of warm ammonia could go undetected. temperature. At the same time, the buoyancy force
During or after this accumulation, three events of driving the rollover increases. However, the
increasing severity are conceivable. increasing destabilizing force probably also reduces
the mass of warm material which can accumulate
1. The submerged warm ammonia eventually mixes before the rollover occurs, and also increases the rate
completely with the cold ammonia, bringing the of mixing of the warm feed with the cold initial fluid.
entire tank to a uniform bulk temperature that is While it is possible to imagine enormous rates of
higher than it was prior to the warm feed. This vaporization when a large mass of very warm
will increase the heat flux through the boundary ammonia erupts to the surface of an ammonia tank,
layer at the surface and increase the vaporization the likelihood of such an accumulation developing in
rate. the first place may be quite small. This poses a rather
difficult problem in fluid mechanics and heat transfer.
2. Due to the buoyancy of the warm ammonia, it It involves both natural convection and forced
rises toward the liquid surface as it mixes with the convection because the feed velocity contributes to
cold initial liquid. This brings the bulk liquid mixing.
temperature near part or all of the surface

64
A future paper will report on a computational fluid after the vent opens as the pressure continues to rise
dynamical study of mixing and heat transfer in from the set pressure to the maximum allowed
ammonia tanks. If successful, it will establish bounds overpressure. Take no credit for the cooling this
on the rollover mechanism. In the meantime, a model produces.
has been developed of thermal overload in which flow
and mixing behavior may be assumed, and the For superheats of the order of a few degrees or
dynamic pressure and venting behavior of the tank less, vaporization should be limited to the liquid
calculated. With this model, it is possible to assume surface, and there should be no boiling in the bulk of
various behaviors, such as the rate of mixing between the üquid. This means that the rate of vaporization
warm and cold ammonia, whether, when and how should be proportional to the cross-sectional area of
rapidly the warm layer flows to the surface, and what the tank. It will be determined by the rate of heat
fraction of the surface becomes covered by the warm transfer from the bulk liquid to the interface divided
fluid. For the assumed behavior, consequences for the by the latent heat of vaporization, if convective heat
vapor space pressure and venting rates are then transfer on the vapor side is neglected. At the peak
determined. overpressure, this rate is equal to the venting rate, if
the difference between the interface temperature and
PROBLEM DESCRIPTION the vapor temperature, and the rate of increase of the
vapor space volume are neglected.
Figure l schematically depicts the key features of
Wv
the tank included in the model. There is a normal (D
process vent from the vapor space to refrigeration to A
maintain normal operating pressure, and a pair of
emergency vents to protect against overpressuring the where T,-T;, the difference between the warm
tank. The feed nozzle is near the bottom of the tank. ammonia temperature and the temperature at the
interface, is the degrees of superheat above the
Before filling starts, there is an initial charge of saturation temperature corresponding to the maximum
liquid ammonia with uniform temperature exerting its allowed overpressure. The heat of vaporization is
equilibrium vapor pressure. For a perfectiy insulated taken at the saturation temperature. It is about 320
tank at steady state there would be no vaporization, PCU/lb for small overpressures. The venting rate Wv
and the normal and emergency vents would be closed. is a mass flow rate; A is the cross-sectional area of
If heat gain is taken into account, there would be the tank, and h, is the liquid heat transfer coëfficiënt
some venting through the normal vent. Then, warm at the interface. This last variable is the most
ammonia is fed from a barge or other source for a uncertain. Because natural convection is an important
period of time and stopped. The variables of primary contribution to the heat transfer, the coëfficiënt hl is
interest to calculate are the pressure in the vapor not independent of the degrees of superheat.
space and the venting rates through the normal and Uncertainty in h, is the only aspect which could
emergency vents as functions of time, both during the render Eq. (1) non-conservative.
barge unloading and after the unloading.
Equation (1) is based on the premise that
SIMPLIFIED VENTING EQUATION vaporization occurs at the surface, and therefore the
rate is proportional to the surface area, and not the
Before presenting the dynamic model, a short-cut mass of the warm ammonia. This in contrast to some
venting calculation is described. This short-cut, by previous calculations of venting rate requirements
ignoring numerous mitigating effects, provides a which hold that the required venting rate is
conservative upper bound to which the more careful proportional to the mass of warm ammonia. Such a
dynamic calculations may be compared. Assume that behavior would be reasonable for very high
the warm ammonia is either fed to an initially empty superheats, where boiling would occur throughout the
tank, or rises instantaneously to the surface, volume of warm ammonia. A useful figure to keep in
completely covering the vapor-liquid interface without mind is that near the liquid surface the saturation
mixing or exchanging heat with the cold ammonia. temperature increases at about 0.4 °C per ft of depth
Neglect the reduction of the warm ammonia below the surface. Considering the increased
temperature as vaporization occurs while the pressure saturation temperature at depth, and the need for
is increasing from the initial pressure to the maximum several degrees of superheat of saturation for
allowed pressure. In reality, some ammonia has to homogeneous boiling, it is evident that quite large
vaporize to bring the pressure up to the vent set superheats are needed for boiling at any significant
pressure. Then, an additional amount must vaporize depth below the surface.

65
Maher and Van Gelder of Chicago Bridge & Iron Vaporization can occur from either or both zones.
[2] in this discussion of rollover and thermal overfill During a rollover, each zone occupies a fraction of
in LNG storage tanks reported the following empirical the vapor/liquid interfacial area. At the interface, with
equation for the venting rate as a function of the temperature 7), heat transfer from the bulk liquid to
depression of the pressure at the liquid surface below the interface is described by a liquid side heat transfer
the vapor pressure of the underlying warmer liquid. coëfficiënt, h,, and from the interface to the bulk
vapor by a vapor side heat transfer coëfficiënt hv. The
(2) difference in heat flux between the phases determines
the rate of vaporization through the latent heat. The
fraction ƒ of the interface occupied by the hot zone
where Wv is in Ib/hr, APS is in inches of water, and can be any arbitrarily specified function of time, so
the tank diameter D is in ft. Using methane as an that all the scenarios described in the Introduction can
approximation for LNG and employing the Clausius- be studied.
Clapeyron equation, the following estimate can be
derived for the heat transfer coëfficiënt by comparing The tank is equipped with two types of vent. One
Eq. (1) and Eq. (2). is the normal vent used to keep the tank at its normal
operating pressure. The other is a pair of conservation
/z;=105(r(-7;.)'/3 vents to keep the tank within a maximum allowed
overpressure beyond the design pressure in an
where temperature is measured in degrees Celsius and emergency. The emergency vents begin opening at a
ht is in PCU/hr ft2 °C. For a l °C superheat, the set pressure Ps (l psig for the Belle tank) and are fully
heat transfer coëfficiënt is 105 PCU/hr ft2 C and for open at a higher pressure P0 (taken as 1.4 psig). The
5 °C of superheat it is 180 PCU/hr ft2 C. These fully open capacity is obtained from an orifice
fïgures may help give a feel for the expected values of equation with the effective orifice area computed from
h, for ammonia tanks, hearing in mind of course that the actual manufacturer's capacity curve. Between Ps
physical property differences will influence /z;. and P0, the capacity variation with pressure is assumed
Ammonia has a greater thermal conductivity, but a linear.
smaller coëfficiënt of thermal expansion than liquid
methane. A heat transfer coëfficiënt of A ; = 1000 The normal vent line is branched. One branch goes
PCU/hr ft2 °C is probably a very conservative to the refrigeration compressor, and the other to the
estimate for superheats of a few degrees or less. plant flare stack. For simplicity, the conservative
choice is made to neglect flow to the compressor. All
DYNAMIC MODEL the flow is assumed to go to atmosphere via the flare.
This path is a 6-inch line with an equivalent resistance
The model, illustrated in Fig. 2, uses lumped estimated at about 16.7 velocity heads with the vent
average temperatures in two liquid zones and one valve wide open. Rather than simulate the actual
vapor zone. One liquid zone, the "hot" zone, consists control scheme for the vent, it is assumed that the
of the ammonia which has been fed warm from the valve for normal venting begins opening at a set
barge, and the other is the "cold" ammonia which pressure (Psn) and is fully open at a higher pressure
was initially present in the tank. Mixing between the (Pai) with a linear variation of flow rate in between.
two zones is important because it reduces their In the calculations, the values POT=0.5 and Pon=0.6
temperature difference. This effect is modelled by a psig are taken.
"heat transfer" coëfficiënt h^ and a contact area A^
between the two zones. Heat transfer coefficients are Time-dependent material and energy balances are
usually used to describe the rate of heat transfer written on the vapor and on each of the liquid zones,
across a phase interface. In this case, there is no giving six differential equations. Along with these are
phase interface, and h^ really describes a rate of various algebraic relations among the variables in
mixing within a single phase. It includes the exchange these differential balance equations.
of enthalpy by mixing of fluid across the imaginary
boundary between the rather arbitrarily defined "hot" The warm ammonia feed rate may be any specified
and "cold" zones. The limit h^ ~* O corresponds to function of time. Rollover phenomena are included by
no mixing or heat exchange between the zones, and specifying the surface fraction ƒ as a function of time.
hfc ~* oo corresponds to a single well-mixed liquid For example, a rapid rollover of a large mass of
zone. An order-of-magnitude estimate for the area A^ warm liquid could be specified by ramping ƒ from
is taken as A^V^s^. The product h^^ is the zero to unity over a small period of time, such as one
mixing rate of enthalpy per degree of temperature minute.
difference.

66
The temperature at the vapor/liquid interface is No energy can accumulate at the interface. All the
determined by the requirement that the pressure in the heat reaching the interface from the liquid and vapor
vapor space equal the vapor pressure of the liquid at is absorbed by vaporization.
the interfacial temperature. This is the only place a) Vapor/Cold Liquid Interface
where vapor and liquid coexist in equilibrium.
(l -flAh^- T)WJ(Cpv- Cp)(T- T) + A J+(1 -f)Ahv(T-Tv)
Tank insulation is assumed perfect in these (12)
calculations. The effect of loss of insulation is also
under investigation, but will not be reported here. b) Vapor/Hot Liquid Interface
fAhl(Tlh-T:) = Weh[(CpyCl,!)(T-Tr)+ \r]+fAhv(T-Tv)
The following equations constitute the (13)
mathematica! model.
The interface temperature establishes the vapor
Vapor Mass Balance pressure. Pressure is in psia and temperature in
Keivin.
dM„
(3) lnP=17.694826-3237.4292/r.-0.006267012ir.
UI
(14)
Cold Liquid Mass Balance Ideal Gas Law
dM
lc
—— W
Wec (ft
W (15)
dt
Liquid Volume
Hot Liquid Mass Balance a) Cold M
dM
lH = W-W
l eh x (5)
/ (16)
dt b) Hot '
Vapor Internal Energy l/ ——
' lh
Ih
(17)
Uv=MJCpv(Tv-Tr) + \r]-PVv (6) Venting Rate.
Vapor Energy Balance
(18)
^=(Weh+ WJ[Cpv(T-Tr+ \r] +Ahv(T-Tv) Emergency
dt For — Paan < PS,
W\C (T
H'vlSvUv
T)+ M
*r)+ A rJ rP
^
v (?)
(19a)
For P, ^ P-Pam<P0,
Liquid Internal Energy
a) Cold l2PM„(P-Paan)
ve \ p p ^ ^(/^oe *\ (m
1 RTV
S
b) Hot For P-PoJ > P0,
^lh~"^lh^p^lh •*(•) ""tl W w -r A I2PMJ. """' ( \f\f\
Liquid Energy Balances KI
Normal
a) Cold P-Paan < PS„,
dU,£ r-Tr)- -MT^-TÏ-P^- (20a)
=-
dt Psn < Paan < P„n,
(10)
b) Hot i P-Paan-P \
Wm =\
\ D_D
-IA
/ «a (20è)
on sn NRT
düilh =
J
= WlCp{,Tfl-Tr)-WehCpl(T-Tr)-Ahlf(Tlh-Ti-)
'™ v vJ

P-Paan > P ,
~dt
•"- •"- - Oi lef (l 1)
(20c)
NRTV
where ƒ is the fraction of the vapor-liquid interface The total volume in the tank is fixed.
occupied by the hot liquid. V
Y
ta =V
r +V
lh^ v H-F
lc^ v
v (21)

67
MODEL BEHAVIOR emergency vent is closing. After the emergency vent
A commercially available equation-based chemical is fully closed, the pressure begins to drop rapidly.
process simulator was used to solve the set of This is because the diminishing vaporization rate is no
simultaneous differential and algebraic equations. The longer partially offset by a diminishing vent area as it
simulator reads the equations and writes the Fortran was while the emergency vent was still open. Several
coding necessary to solve them. Gear's method is hours after the rollover, the pressure has dropped
used for the integration. To illustrate the behavior of back to nearly the normal vent set pressure.
the model, several test calculations and sensitivity
studies are made. Figure 4 shows the normal, emergency and total
venting rates. The total rate quickly reaches a peak
The uncertain parameters in the model are the after the rollover. In the time scale of the process, the
coefficients hv, h, and h^. In order to investigate the one-minute rollover time is effectively instantaneous.
sensitivity of the model to these uncertain parameters, The peak total venting rate is 24,255 Ib/hr, of which
a "base case" set of values hv = 1.0, ht = 1000 and about 17% goes to the flare and the remainder goes
hhc = 10 PCU/hr ft2 °C is chosen. The base case also directiy to the atmosphere. It is interesting to compare
includes the design parameters for the Belle tank and the peak total venting rate to that which would be
an initial charge of 5000 tons at -33 °C. A 2500 ton computed from Eq. (1). At 15.79 psia, the saturation
barge load of ammonia is fed at a uniform rate for 8 temperature at the interface is —32.0 °C. With a bulk
hrs. The simulation starts one-hour before the feed liquid temperature of -33 °C, a heat transfer
begins, to demonstrate the initial steady-state coëfficiënt h, = 1000 PCU/hr ft2 °C, a tank cross-
behavior. One hour after the barge unloading is sectional area of A = 9677 ft2, and a heat of
complete, at t = 10 hr, a rollover is assumed. Over a vaporization of about 327 PCU/lb, Eq. (1) gives a
1-minute interval, the vapor-liquid surface area venting rate of 29,600 Ib/hr. The peak rate in the
fraction is ramped linearly from all cold liquid to all dynamic calculation is nearly as great as the simplified
hot liquid. calculation result. This happens because for the
parameters chosen, there is very little interchange
Setting the initial condition Mlh = O would cause between the hot and cold liquid before the rollover
divide-by-zero errors in the numerical solution of the event, because the rollover happens quickly, and
balance equations on the hot zone. Rather than because the mass of hot liquid is very large compared
complicate the model with various conditional to the mass required to vaporize in bringing the vapor
instructions to modify the equations during the first space up to the peak pressure.
hour while the hot zone does not exist, the initial
value of Mlh is set to a negligible mass; the value Inspection of Figure 5 shows that the small value
Mlh= l Ib is chosen. Then hot zone equations can be of hhc used in the base case gives very slow mixing
solved from time zero. between the zones, so that the hot liquid is still very
near its feed temperature when it rolls to the surface.
Figures 3-5 plot time-dependent results for the This extreme case of rapid rollover after virtually no
base case. At time t = l hr, unloading commences. mixing is worse than what would happen if the warm
Figure 3 shows the pressure transient. Pressure is liquid had been fed directiy on top of a small heel of
constant for the first hour before barge unloading cold liquid, so that venting could occur continuously
begins. Then during the 8 hour period from t = l to throughout the barge unloaded. Figure 6 shows the
t = 9 hr the pressure rises as warm ammonia is fed. pressure and total vent rate history when the barge is
The pressure rise is largely from compression of the unloaded on top of a shallow heel (165,000 Ib) of
vapor as liquid volume is increased. Vapor cold ammonia. There is no rollover because the warm
compression and condensation raise the vapor and fluid is on the top from the outset. Otherwise, the
interface temperatures. The liquid feed coincidentally conditions are identical to the base case. From a
stops just at the time when the tank pressure reaches starting pressure of 0.31 psig, the pressure rises very
the set pressure of the normal vent. Once the liquid rapidly over the first hour of feeding, and then
feed stops, the pressure drops briefly before a new gradually approaches a peak of 0.75 psig. The peak
steady state is reached. Then, at t = 10 hr, the time venting rate is an order of magnitude lower than in
arbitrarily selected for the rollover, the hot liquid is the base case, but it remains near its peak throughout
brought to the surface over the assumed l minute the 8-hour barge unloading. Of course, once the
interval. Both normal and emergency vents open as pressurization and excessive venting began, the tank
the pressure surges to 15.79 psia (1.03 psia). At the operator would quickly discontinue the unloading. The
peak pressure, the emergency vent is barely open; it conditions of Figure 6 correspond to an actual
would be fully open at 16.1 psia. The pressure experience at Belle, where it was attempted to unload
diminishes steadily for about an hour while the ammonia with 2 °C superheat on top of less than a

68
foot of cold ammonia. After adding only one or two As expected, there is an increase in peak pressure
hundred tons, the pressure had risen from 0.3 to 0.7 and venting rate with an increase in the liquid-side
psig and unloading had to be stopped. heat transfer coëfficiënt h,. The peak venting rate is
not directly proportional to ht because of dynamic
Sensitivity studies with respect to the model effects, and, more importanüy, because the peak
parameters reveals their importance and shows that a pressure also changes with h„ which in turn influences
better understanding of the fluid mechanics is needed the superheat. Over the reasonable range of hv, the
for accurate calculations. Table n shows the results are rather insensitive. The transfer coëfficiënt
sensitivity of peak pressure and venting rates to model hhc reflecting interchange between the hot and cold
parameters and operating conditions. In each section, liquids has a substantial effect on peak pressure and
the parameter value corresponding to the base case venting rates. For small values, the asymptotic limit
condition of Table I is highlighted. When the of no mixing/heat transfer is approached. This gives
parameter in question is changed from the base-case the greatest peak values of P and Wv. For large
value, all the remaining ones retain their base-case values, the asymptotic limit of a single well-mixed
values. liquid phase is approached. This limit gives the least
Table H. Sensitivity Studies values of P and Wv. Note that when hhc is increased
beyond some value between 100 and 1000 PCU/hr ft2
P(max) ÏFv„(max) Wve (max) Wv(max) C, the emergency vent no longer opens.
Base Case* The effect of the initial cold liquid mass is minor
(psig) Ib/hr as long as the feed liquid is submerged beneath it and
mixing is slow before a rollover. As the initial cold
1,091 4,240 20,020 24,260 liquid mass increases, there is a small increase in peak
pressure and venting rate because of the diminishing
Effect of fy (PCU/hr ft2 °C) volume of the vapor space.
100 0.771 3,540 O 3,540
Liquid feed temperature is extremely important. If
500 1.043 4,140 9,140 13,280
the feed temperature is reduced from the base case
1000* 1.091 4,240 20,020 24,260
-31°C to -32°C (1°C superheat above the cold
Effect of /iv (PCU/hr ft2 °C) liquid at — 33 °C), the peak pressure is only 0.9 psig,
the emergency vent does not open, and the peak
0.1 1.091 4,240 20,050 24,280 venting rate is 3,830 Ib/hr. If the superheat is
l* 1.091 4,240 20,020 24,260 increased to 5°C (Tfl= -28°C) the peak pressure is
10 1.089 4,240 19,630 23,870 1.38 psig and the peak total venting rate is 98,400
Ib/hr. The peak pressure is more than 10% above the
Effect of hhc (PCU/hr ft2 °C) tank design pressure and tank damage would be
l 1.095 4,250 21,040 25,290 expected. At Tfl= -23 °C, the calculated peak
10* 1.091 4,240 20,020 24,260 pressure is 3.05 psig and the peak total vehting rate is
100 1.054 4,160 11,720 15,890 161,800 Ib/hr. At this pressure, tank failure would be
1000 0.699 3,360 O 3,360 likely.
10,000 0.620 3,160 O 3,160
Reduction of the mass of ammonia unloaded from
Effect of Initial Cold Liquid Mass (tons) the barge over the 8-hour period by a factor of five
(from the base case 2500 to 500 tons) reduces the
2500 1.091 4,240 20,020 24,260 peak pressure from l .09 to l .04 psig, and the peak
5000* 1.091 4,240 20,020 24,260 total venting rate by about half (from 24,260 to
10,000 1.097 4,250 21,310 25,560 12,840 Ib/hr). Increasing the barge mass to 5000 tons
15,000 1.098 4,250 21,720 25,980 increases the peak pressure to 1.1 psig and the peak
venting rate to 26,190 Ib/hr. While the increase 'm
Effect of Tfl(°C) venting rate is modest, the large venting rate lasts for
-32 0.899 3,830 O 3,830 a much longer time than in the base case. For large
-31* 1.091 4,240 20,020 24,260 feed mass, the hot liquid temperature changes very
-28 1.376 4,800 93,640 98,440 little either before or during the rollover. However,
-23 3.047 7,430 154,400 161,800 for small feed mass, the heat lost to the cold üquid or
to vaporization is enough to drop the hot liquid
Effect of Barge Mass (tons) temperature and cause a substantial reduction in the
2500* 1.091 4,240 20,020 24,260 peak venting rate. This effect would not be picked up
500 1.041 4,130 8,700 12,840 by the simple analysis of Eqn. (1).

69
Figures 7-18 illustrate the transient tank behavior less beneath a large mass of cold ammonia,
for several of the sensitivity study cases. In the overpressuri/ation of the Belle tank is not a likely
temperature plots, the hot liquid temperature variation event in the absence of rollover, or if a rollover
during the first hour shows the cooling of the l pound occurs following significant mixing between the warm
of warm ammonia placed in the tank at time zero. feed and cold initial fluid. If mixing is poor and a
Figures 9, 12, 15 and 16 show the approach of the rollover occurs with a large degree of superheat, then
hot and cold liquid toward a uniform temperature as overpressurization could occur. Addition of warm
the mixing rate coëfficiënt h^ is increased. The ammonia on top of a small quantity of cold ammonia
corresponding pressure profiles show the diminishing could cause very large venting rates, and given
danger as hhc increases. sufficient superheat, could overpressure a tank if
operators faüed to discontinue feed despite the onset
Recycle of warm ammonia is another possible of high pressure and venting. However, at reasonably
cause of thermal overload. Unless plant design small superheats, less than a few degrees Celsius,
precludes the possibility, it is conceivable that venting rates will be large but the pressure will be
ammonia with much more than a few.degrees of controlled at safe levels. Recycle of highly
superheat could be recycled to a storage tank. It has superheated ammonia is to be avoided.
been reported [2] that in the Lithuanian tank incident,
14 tons of ammonia at 10 °C was fed into the tank In Du Pont there is no known evidence that a
over a three-hour period prior to the tank faüure rollover bringing significantly superheated ammonia to
which released 7000 tons. (There is some cause to the surface of a tank has ever happened. However,
suspect that much more than 14 tons were recycled.) this does not prove that it cannot happen. Should such
Figures 19 and 20 show model results using the base- an event occur, this study shows that the consequences
case parameters for the Belle tank, with an initial cold are potentially severe, given sufficient superheat.
liquid mass of 7000 tons rather than 5000 tons, and Limiting operating procedures to ensure the safety of
with 14 tons of 10 °C ammonia fed at a uniform rate the tank even under the assumption of poor mixing
over the three hour period from t = l to t = 4 followed by a rapid rollover is prudent. A more
hours, followed by a rollover of the warm ammonia careful fluid mechanical study of mixing of warm feed
to the surface immediately after the recycle was into the cold initial ammonia is needed to establish the
concluded. The pressure spikes to 1.43 psig, which is credibility of the assumed worst-case events.
more than 40% beyond the design pressure of the
tank, and the total venting rate reaches the REFERENCES
extraordinary value of 108,000 Ib/hr. At the peak
pressure, some deformation of the tank might be 1. J. B. Maher and L.R. Van Gelder, "Understanding
expected. The vent capacity of the Lithuanian tank Roll-Over and Thermal Overfül in Flat Bottom
was less than 20,000 Ib/hr. LNG Tanks," Amer. Gas Assoc. Distribution
Conf., Atlanta (1972).
DISCUSSION
2. B. O. Andersson, "The Lithuanian Ammonia
The model development and results are useful from Accident, March 20, 1989," AIChE Ammonia
more than one perspective. First, they force Symposium, Paper 96A, November 1989.
consideration of all the processes which are going on
during feed to a tank. It gives a feel for the ranges of
behavior to expect as a result of variations of both
known (e.g., initial liquid mass, tank volume) and
unknown (e.g., heat transfer coefficients) variables.
The uncertainties in the model parameters, and the
sensitivity of the results to these parameters, motivates
the development of a more careful computational fluid
dynamic analysis. This analysis should give a better
feel for these parameters, and indeed show whether
the rollover phenomenon is a realistic expectation at
all.

If any provisional conclusions are to be drawn


from the current study, they are the following. When
feeding warm ammonia of a few degrees superheat or

70
NOTATION

A tank cross-sectional area


Afc contact area between hot and cold liquid
Aoe emergency vent area
Am normal vent area
C0 orifice coëfficiënt
Cpl liquid heat capacity
Cpv vapor heat capacity
f fraction ofsurface occupied by hot zone
hhc exchange coëfficiënt between hot and cold zones
hL liquid-side heat transfer coëfficiënt
hv vapor-side heat transfer coëfficiënt
Mlc mass of cold liquid
Mlh mass of hot liquid
Mv mass of vapor
Mv molecular weight
N vent line resistance
R gas constant
P pressure
Patm atmospheric pressure
Pa emergency vent juli open pressure
Pon normal vent Juli open pressure
Ps emergency vent set pressure
Psn normal vent set pressure
A Ps depression below bulk liquid vapor pressure
t time
7j interface temperature
Tf bulk liquid temperature
Tlc cold liquid bulk temperature
Tlh hot liquid bulk temperature
Tr reference temperature
Ufc cold liquid intemal energy
Uth hot liquid internal energy
Uv vapor internal energy
Vlc cold liquid volume
Vft hot liquid volume
Vtot total tank volume
Vv vapor volume
Wec vaporization rate from cold liquid
Weh vaporization rate from hot liquid
Wf hot liquid feed rate
Wv total venting rate
Wve venting rate through emergency vent
Wm venting rate through normal vent
A heat of vaporization
\r heat of vaporization at Tr
Pt liquid density

71
OPERATING PARAMETERS FOR 6. Inform the barge companies of the expectations
BELLE STORAGE TANK that the ammonia should be -33.4°C and at O
psi.
Du Pont at Belle believe for our application, a
bulk cryogenic storage tank is the safest, most 7. Maintain detailed data sheets in order to
economical and environmentally sound method of monitor each transfer.
storing anhydrous ammonia. However, operating 8. Operating personnel have been educated to the
guidelines and parameters must be understood and importance of keeping within the operating
closely monitored to maintain this desired state. A parameters and changed old mentalities of
clear understanding of the tank desigo basis is critical hurrying to unload barges to reduce demurrage
to our operation. The 20,000 ton storage tank at Belle costs. There is also the understanding that the
was originally part of a 1000 ton/day Kellogg plant storage tank is not a flash vessel.
which is no longer in operation. The main feed
streams into our tank are the barge unloading pipe These operating parameters are all adrninistrative
line, recycle from our distribution pumps, and the procedures. Therefore it is imperative that each person
return stream from the compressor. unloading barges fully understands the results of
operating outside of these guidelines. Barge unloading
The barge unloading line is the greatest concern personnel are currently being certified with the U.S.
for introducing large amounts of heat into the bottom Coast Guard as tankermen to allow them to be more
of the tank therefore, operating instructions include
involved in the unloading. This practice has proven
guidelines to follow during barge unloading transfers.
most effective.
There are several ammonia storage tanks that have
flash nozzles at the top of the tank that take 10% of Du Pont at the Belle Plant are extremely proud of
the unloading flow into the top layer of the tank. This our recent upgrades to the 20,000 ton storage tank
will indicate the barge is warm due to the pressure and distribution system and desire to maintain its
increase. It is critical to keep these on line during current status and integrity. Many people have
transfers and not valve them out so the unloading provided guidance, support, and input to our efforts to
rates may be increased. Since the Belle tank is not maintain safety and environmental performance.
equipped with this configuration, other guidelines are Dr. Richard Squire and Dr. Richard Knowles, plant
in place to insure safe operation. manager, for supporting continuous improvement.
1. Assure the barge pressure is at most O psi and
the liquid mass is at most at -33.4°C upon
arrivsl at the doek.
2. Closely monitor the unloading line
temperature and not allow it to be above
-32 °C.

3. Unload at a maximum rate of 300 tons/hr.

4. Assure the normal vent to the flare stack does


not exceed 30% valve opening during the
barge transfer.

5. Cool down the empty barge unloading lines


prior unloading, especially in the case of long
piping systems that could introducé large
amounts of heat into the tank bottom during
the initial transfer.

72
Normal Vent |NH3 Tonk F i U i n g goUover |

1Q"BreatherVents

Figure 4. Venting rates during base-case


simulation.
Liquid Feed

Figure 1. Belle ammonia storage tank.


w v,

|NH3 Tank FlUing Rollover |

215- 215, 215.


Tv, P, Mv

Tfc,

-W,

Figure 5. Zone and interface temperatures


Figure 2. Key features modelled. In the smaller during base-case simulation.
figures, hot liquid zone has risen to first
partially, and then completely, cover the surface.
(NH3 Tank F i LI ing Rol lover |

INH3 Tonk FilUnql

VIT
Wfc(0)=16S,000 B)
£ 1=6. Mfc(G)=74aOO kg

£
g 150.

Figure 3. Pressure transient during base-case Figure 6. Pressure and total venting rate for
simulation. unloading into a nearly empty tank.

73
lNH3 Tank Fullnq Rouovprl |NH3 Tank F J U i n q Rot lover |

Figure 7. Pressure transient with A;reduced to


100 PCU/hr ft2 °C.
Figure 10. Pressure transient with khe increased
to 100 PCU/hr ft 2 °C.

JNH3 Tank F i t t i n g Rol l over | JNH3 Tank F u t ing Rot lover |

39000 30000., 30000

Figure 8. Venting rate with fyreduced to 100


PCU/hr ft 2 °C.
Figure 11. Venting rates with hhc = 100 PCU/hr
ft 2 °C.

|NH3 Tank FiUing Rol lover | |NH3_Tonk Rilling RoUover j

213. 215. 215.


h
*~l*tT-

210J 210J 210.

Figure 9. Temperatures with fc/(creduced to 1 Figure 12. Temperatures with hhc = 100 PCU/hr
PCU/hr ft2 ° C. ft2 °C.

74
|NH3 Tank FiUing RoUover | JNH3 Tank FtUing RoUover |

fc
" hr ft! *C

^56.700-£-

I' 5
s

Figure 13. Pressure transient with hllc Figure 16. Temperatures with hhc = 10,000
increased to 1,000 PCU/hr ft 2 °C. PCU/hr ft 2 °C.

|NH3 Tonk FiUing RoUover | |NH3 Tonk Ft H ing RoUover |

Figure 14. Venting rate with hhc = 1,000 Figure 17. Pressure transient with initial cold
PCU/hr ft 2 °C. mass increased to 15,000 tons.

|NH3 Tonk FiUing RoUover | [NH3 Tank FiU ing Rot Lover |

£
S 211
g

(hours >

Figure 15. Temperature with hhc = 1,000 Figure 18. Venting rate with Mu = 15,000
PCU/hr ft 2 °C. tons.

75
|W3 Tank War» Recycle !•( Lons 10 C | |NH3 Tor*. Worm Recycle 11 Lons 10 C
12.700 kg 12.700 kg
xio5
X1Q-
iB5 vfi XI O5
1.50 l. 50

l .20 1.20 1.20

3 è S
0.90 0.90 0,90

155

V z
O.EO
S
0.60 O.GO

j'»
i°-3°
z
|o.30
ï f030

0.00 0.00
t i 2 3 * S B
0.00
( 1 2 3 4 5 6
Tinp (hours > Tin* (hours

Figure 19. Pressure transient with warm Figure 20. Venting rate with warm recycle
recycle and assumed rollover. and assumed rollover.

D1SCUSSEON
Rudolph Frey, M. W. Kellogg Company. Houston, TX: l Frey: You couldn't put a sparger or a top loading system in?
would like to know first of all whether this is a doublé Saffle: No.
integrity tank or full containment as deflned by the EEMUA in Frey: This is very effective in preventing rollover. The other
Europe? thing done is providing a recirculation system to avoid the
Saffle: Yes, this tank is a doublé walled, doublé integrity accumulation of a rollover cell in the tank. In terms of the
tank. mathematical modeling, there has been some work done in
Frey: The outer wall is able to contain the full fluid, full LNG relative to the convection cells, which build up in the
hydrostatic pressure at the cold temperature. tank and provide the incubation period for the rollover. I was
Saffle: Yes. wondering if that work was addressed in setting up your model.
Frey: That was one of my concerns with regards to practice in Guy Legendre, Monsanto, Luling, LA: You mentioned that
ammonia storage here, vis-a-vis European practice. An LNG you don't allow the temperature to get above -32 °C. If it does,
tank is very common to provide top loading to get the vapor do you have an interlock which shuts down the unloading and
dispersion immediately. I think one of the graphs in this study at what temperature is that interlock set?
showed that. Was there any consideration in providing this? Saffle: There is no interlock on that system. There is a
Or, was this a situation where you didn't want to make any thermocouple on the unloading line. It is monitored
mechanical modifications up there? continuously. It is completely administrative when that
Saffle: Basically, this was just for our tank design and we put temperature is exceeded and it is shut down.
the ammonia into the bottom of the tank. So, this study is
just for our tank.

76

You might also like