THERMAL PERFORMANCES

FOR ONE BOILER


INT BWP
Customer
Portugal -
performances here below are expected performances: Reference 92742-87559 rev. 00 dated 24/08/2022
performance guarantees are given in our proposal Boiler type NBWB 100A page 1

n° 1 2 3 4 5
OPERATION CASE Fuel Gas 100 %MCR 75 %MCR 50 %MCR 25 %MCR 14,2 %MCR
Fuel Gas
STEAM
Steam flow rate at boiler outlet t/h 1,000 0,750 0,500 0,250 0,143
Steam pressure at outlet stop valve bar eff 10 10 10 10 10
Steam temperature at outlet stop valve °C 184 (sat.) 184 (sat.) 184 (sat.) 184 (sat.) 184 (sat.)
COMBUSTION AIR
Mass flow rate t/ h 1,0 0,8 0,6 0,3 0,2
Ambient air temperature °C 25 25 25 25 25
Ambient air humidity % 60% 60% 60% 60% 60%
Burner air inlet temperature °C 25 25 25 25 25
BURNER
Thermal power kW LHV 727 546 365 185 108
Fuel consomption
GN FR LHV : 10,16 kWh/Nm³ Nm³ /h 72 54 36 18 11
- Nm³ /h - - - - -
- Nm³ /h - - - - -
- kg / h - - - - -
- kg / h - - - - -
Flame temperature °C 1826 1799 1762 1714 1689
Excess air % 14,9% 17,3% 20,6% 25,1% 27,6%
Combustion efficiency on LHV basis, ± 2%, at 25°C,
% 97,2% 97,5% 97,7% 97,9% 98,0%
drains 0%
BOILER
Continuous blowdown rate % 0,0% 0,0% 0,0% 0,0% 0,0%
Useful heat kW 700 525 350 175 100
Boiler radiation/convection heat losses EN 12953-11 % 0,8% 1,1% 1,6% 3,2% 5,5%
LHV efficiency, ± 2%, at 25°C, drains 0%, radiation/
% 96,4% 96,4% 96,0% 94,7% 92,5%
convection losses according to EN12953-11
kWh LHV / T 727 728 730 740 756
Ratio burner LHV power / Steam flow at boiler outlet
FLUE GAS
Flow rate t/h 1,10 0,84 0,58 0,30 0,18
Nm³ /h 890 680 470 250 150
Flue gas temperatures
Furnace outlet - tubes inlet °C 969 901 808 662 556
2nd pass outlet °C
Steam generator outlet °C 218 209 199 190 186
Economizer outlet °C 85 79 73 67 64
Flue gas composition
H2O % vol. 18,04 17,74 17,34 16,82 16,55
N2 % vol. 70,37 70,49 70,65 70,84 70,95
CO2 % vol. 8,30 8,15 7,94 7,68 7,54
Ar % vol. 0,84 0,84 0,84 0,84 0,84
O2 % vol. 2,45 2,79 3,23 3,81 4,11
SO2, dry at 3% O2 mg/Nm³ 0 0 0 0 0
Pressure drop accross boiler Pa 589 338 157 43 16
WATER / STEAM
Water directly to evaporator t/h - - - - -
Feed water to economizer inlet t/h 1,00 0,75 0,50 0,25 0,14
Temperature of water to directly evaporator °C - - - - -
Feed water temperature at boiler limits °C 60 60 60 60 60
Water temperature at economizer inlet °C 60 60 60 60 60
Water temperature at economizer outlet °C 99 99 98 99 101
Exchanged heat in economizer kW 46 34 23 12 7
Pressure drop in economizer bar 0,04 0,02 0,01 0,00 0,00