You are on page 1of 16

VALVE SIZING CALCULATION SHEET

ANSI / ISA-75.01.01 (IEC 60534-2-1 Mod) Date : 26/09/2022


Version : v4.4.0 Date : 19/08/2022 Sheet 1 of 16

Customer Tag # PRE-HEATING


Project OVS 5682 Item # #1-[0]
Customer Ref. No. Application ZONE 1 (Right)
Quotation # Function Control
Item Description Series 40, 2-1/2", CL 150, Wafer
SERVICE AND SIZING Cond1 Cond2 Cond3 Cond4
Process Fluid Name Natural gas
Inlet Pressure (bar[g]) 0.1
Outlet Pressure (bar[g]) 0.09
Gas Flow (Nm³/hr) 300
Specific Heat Ratio Factor, cp/cv 1.27
Temperature (°C) 25
Pressure Drop Ratio Factor, Xt 0.25
Adj. Pressure Drop Ratio Factor, Xtp 0.251
Expansion Factor, Y 0.987
Compressibility Factor, Z 0.998
Piping Correction Factor, Fp 1

Valve Diameter, d (in) 2-1/2"


Inlet Pipe Diameter , D1 (in) 2.875
Outlet Pipe Diameter, D2 (in) 2.875
Dynamic Torque
Sizing Coefficient, Cv 98.6
Pressure Drop (bar) 0.01
dP Choked (bar) 0.2539

Noise Calculation
Valve Type Butterfly
Downstream Pipe Size (in) 2.5
Downstream Pipe Schedule STD
Valve SPL (dBA) < 70
Warning Acceptable

Pipe Mach 0.084


Valve Mach 0.084

Valve Series : Series 40 % Opening,


Calculated Cv
Valve Size: 2-1/2"

Rated Cv: 160


B - (76.2,98.6)
Flow Char: Equal Percentage

Travel (%) 10 20 30 40 50 60 70 80 90 100


Cv 2.7 7 13.6 24.4 40 61.2 84.6 107.2 138.4 160
VALVE SIZING CALCULATION SHEET
ANSI / ISA-75.01.01 (IEC 60534-2-1 Mod) Date : 26/09/2022
Version : v4.4.0 Date : 19/08/2022 Sheet 2 of 16

Customer Tag # PRE-HEATING


Project OVS 5682 Item # #2-[0]
Customer Ref. No. Application ZONE 1 (Central + Left)
Quotation # Function Control
Item Description Series 40, 6", CL 150, Wafer
SERVICE AND SIZING Cond1 Cond2 Cond3 Cond4
Process Fluid Name Natural gas
Inlet Pressure (bar[g]) 0.1
Outlet Pressure (bar[g]) 0.09
Gas Flow (Nm³/hr) 900
Specific Heat Ratio Factor, cp/cv 1.27
Temperature (°C) 25
Pressure Drop Ratio Factor, Xt 0.35
Adj. Pressure Drop Ratio Factor, Xtp 0.351
Expansion Factor, Y 0.991
Compressibility Factor, Z 0.998
Piping Correction Factor, Fp 0.988

Valve Diameter, d (in) 6"


Inlet Pipe Diameter , D1 (in) 8.625
Outlet Pipe Diameter, D2 (in) 8.625
Dynamic Torque
Sizing Coefficient, Cv 298
Pressure Drop (bar) 0.01
dP Choked (bar) 0.354

Noise Calculation
Valve Type Butterfly
Downstream Pipe Size (in) 8
Downstream Pipe Schedule STD
Valve SPL (dBA) < 70
Warning Acceptable

Pipe Mach 0.025


Valve Mach 0.044

Valve Series : Series 40 % Opening,


Calculated Cv
Valve Size: 6"

Rated Cv: 1350


B - (51.9,298)
Flow Char: Equal Percentage

Travel (%) 10 20 30 40 50 60 70 80 90 100


Cv 31.5 71.8 122.3 186.8 274 402 582 814 1098 1350
VALVE SIZING CALCULATION SHEET
ANSI / ISA-75.01.01 (IEC 60534-2-1 Mod) Date : 26/09/2022
Version : v4.4.0 Date : 19/08/2022 Sheet 3 of 16

Customer Tag # HEATING 1


Project OVS 5682 Item # #3-[0]
Customer Ref. No. Application ZONE 2
Quotation # Function Control
Item Description Series 40, 6", CL 150, Wafer
SERVICE AND SIZING Cond1 Cond2 Cond3 Cond4
Process Fluid Name Natural gas
Inlet Pressure (bar[g]) 0.1
Outlet Pressure (bar[g]) 0.09
Gas Flow (Nm³/hr) 752
Specific Heat Ratio Factor, cp/cv 1.27
Temperature (°C) 25
Pressure Drop Ratio Factor, Xt 0.38
Adj. Pressure Drop Ratio Factor, Xtp 0.376
Expansion Factor, Y 0.991
Compressibility Factor, Z 0.998
Piping Correction Factor, Fp 1

Valve Diameter, d (in) 6"


Inlet Pipe Diameter , D1 (in) 6.625
Outlet Pipe Diameter, D2 (in) 6.625
Dynamic Torque
Sizing Coefficient, Cv 246
Pressure Drop (bar) 0.01
dP Choked (bar) 0.3797

Noise Calculation
Valve Type Butterfly
Downstream Pipe Size (in) 6
Downstream Pipe Schedule STD
Valve SPL (dBA) < 70
Warning Acceptable

Pipe Mach 0.036


Valve Mach 0.036

Valve Series : Series 40 % Opening,


Calculated Cv
Valve Size: 6"

Rated Cv: 1350


B - (46.8,246)
Flow Char: Equal Percentage

Travel (%) 10 20 30 40 50 60 70 80 90 100


Cv 31.5 71.8 122.3 186.8 274 402 582 814 1098 1350
VALVE SIZING CALCULATION SHEET
ANSI / ISA-75.01.01 (IEC 60534-2-1 Mod) Date : 26/09/2022
Version : v4.4.0 Date : 19/08/2022 Sheet 4 of 16

Customer Tag # HEATING 2


Project OVS 5682 Item # #4-[0]
Customer Ref. No. Application ZONE 3 (Right)
Quotation # Function Control
Item Description Series 40, 4", CL 150, Wafer
SERVICE AND SIZING Cond1 Cond2 Cond3 Cond4
Process Fluid Name Natural gas
Inlet Pressure (bar[g]) 0.1
Outlet Pressure (bar[g]) 0.09
Gas Flow (Nm³/hr) 564
Specific Heat Ratio Factor, cp/cv 1.27
Temperature (°C) 25
Pressure Drop Ratio Factor, Xt 0.32
Adj. Pressure Drop Ratio Factor, Xtp 0.323
Expansion Factor, Y 0.99
Compressibility Factor, Z 0.998
Piping Correction Factor, Fp 0.984

Valve Diameter, d (in) 4"


Inlet Pipe Diameter , D1 (in) 5.563
Outlet Pipe Diameter, D2 (in) 5.563
Dynamic Torque
Sizing Coefficient, Cv 188
Pressure Drop (bar) 0.01
dP Choked (bar) 0.3276

Noise Calculation
Valve Type Butterfly
Downstream Pipe Size (in) 5
Downstream Pipe Schedule STD
Valve SPL (dBA) < 70
Warning Acceptable

Pipe Mach 0.039


Valve Mach 0.062

Valve Series : Series 40 % Opening,


Calculated Cv
Valve Size: 4"

Rated Cv: 375


B - (57.1,188)
Flow Char: Equal Percentage

Travel (%) 10 20 30 40 50 60 70 80 90 100


Cv 9 26.8 53.4 94.2 145 205 269.5 325 366 375
VALVE SIZING CALCULATION SHEET
ANSI / ISA-75.01.01 (IEC 60534-2-1 Mod) Date : 26/09/2022
Version : v4.4.0 Date : 19/08/2022 Sheet 5 of 16

Customer Tag # HEATING 2


Project OVS 5682 Item # #5-[0]
Customer Ref. No. Application ZONE 4 (Left)
Quotation # Function Control
Item Description Series 40, 4", CL 150, Wafer
SERVICE AND SIZING Cond1 Cond2 Cond3 Cond4
Process Fluid Name Natural gas
Inlet Pressure (bar[g]) 0.1
Outlet Pressure (bar[g]) 0.09
Gas Flow (Nm³/hr) 564
Specific Heat Ratio Factor, cp/cv 1.27
Temperature (°C) 25
Pressure Drop Ratio Factor, Xt 0.32
Adj. Pressure Drop Ratio Factor, Xtp 0.323
Expansion Factor, Y 0.99
Compressibility Factor, Z 0.998
Piping Correction Factor, Fp 0.984

Valve Diameter, d (in) 4"


Inlet Pipe Diameter , D1 (in) 5.563
Outlet Pipe Diameter, D2 (in) 5.563
Dynamic Torque
Sizing Coefficient, Cv 188
Pressure Drop (bar) 0.01
dP Choked (bar) 0.3276

Noise Calculation
Valve Type Butterfly
Downstream Pipe Size (in) 5
Downstream Pipe Schedule STD
Valve SPL (dBA) < 70
Warning Acceptable

Pipe Mach 0.039


Valve Mach 0.062

Valve Series : Series 40 % Opening,


Calculated Cv
Valve Size: 4"

Rated Cv: 375


B - (57.1,188)
Flow Char: Equal Percentage

Travel (%) 10 20 30 40 50 60 70 80 90 100


Cv 9 26.8 53.4 94.2 145 205 269.5 325 366 375
VALVE SIZING CALCULATION SHEET
ANSI / ISA-75.01.01 (IEC 60534-2-1 Mod) Date : 26/09/2022
Version : v4.4.0 Date : 19/08/2022 Sheet 6 of 16

Customer Tag # SOAKING


Project OVS 5682 Item # #6-[0]
Customer Ref. No. Application ZONE 5 (Right)
Quotation # Function Control
Item Description Series 40, 2-1/2", CL 150, Wafer
SERVICE AND SIZING Cond1 Cond2 Cond3 Cond4
Process Fluid Name Natural gas
Inlet Pressure (bar[g]) 0.1
Outlet Pressure (bar[g]) 0.09
Gas Flow (Nm³/hr) 171
Specific Heat Ratio Factor, cp/cv 1.27
Temperature (°C) 25
Pressure Drop Ratio Factor, Xt 0.32
Adj. Pressure Drop Ratio Factor, Xtp 0.321
Expansion Factor, Y 0.99
Compressibility Factor, Z 0.998
Piping Correction Factor, Fp 0.993

Valve Diameter, d (in) 2-1/2"


Inlet Pipe Diameter , D1 (in) 3.5
Outlet Pipe Diameter, D2 (in) 3.5
Dynamic Torque
Sizing Coefficient, Cv 56.1
Pressure Drop (bar) 0.01
dP Choked (bar) 0.3253

Noise Calculation
Valve Type Butterfly
Downstream Pipe Size (in) 3
Downstream Pipe Schedule STD
Valve SPL (dBA) < 70
Warning Acceptable

Pipe Mach 0.033


Valve Mach 0.048

Valve Series : Series 40 % Opening,


Calculated Cv
Valve Size: 2-1/2"

Rated Cv: 160


B - (57.6,56.1)
Flow Char: Equal Percentage

Travel (%) 10 20 30 40 50 60 70 80 90 100


Cv 2.7 7 13.6 24.4 40 61.2 84.6 107.2 138.4 160
VALVE SIZING CALCULATION SHEET
ANSI / ISA-75.01.01 (IEC 60534-2-1 Mod) Date : 26/09/2022
Version : v4.4.0 Date : 19/08/2022 Sheet 7 of 16

Customer Tag # SOAKING


Project OVS 5682 Item # #7-[0]
Customer Ref. No. Application ZONE 6 (Central)
Quotation # Function Control
Item Description Series 40, 2-1/2", CL 150, Wafer
SERVICE AND SIZING Cond1 Cond2 Cond3 Cond4
Process Fluid Name Natural gas
Inlet Pressure (bar[g]) 0.1
Outlet Pressure (bar[g]) 0.09
Gas Flow (Nm³/hr) 171
Specific Heat Ratio Factor, cp/cv 1.27
Temperature (°C) 25
Pressure Drop Ratio Factor, Xt 0.32
Adj. Pressure Drop Ratio Factor, Xtp 0.321
Expansion Factor, Y 0.99
Compressibility Factor, Z 0.998
Piping Correction Factor, Fp 0.993

Valve Diameter, d (in) 2-1/2"


Inlet Pipe Diameter , D1 (in) 3.5
Outlet Pipe Diameter, D2 (in) 3.5
Dynamic Torque
Sizing Coefficient, Cv 56.1
Pressure Drop (bar) 0.01
dP Choked (bar) 0.3253

Noise Calculation
Valve Type Butterfly
Downstream Pipe Size (in) 3
Downstream Pipe Schedule STD
Valve SPL (dBA) < 70
Warning Acceptable

Pipe Mach 0.033


Valve Mach 0.048

Valve Series : Series 40 % Opening,


Calculated Cv
Valve Size: 2-1/2"

Rated Cv: 160


B - (57.6,56.1)
Flow Char: Equal Percentage

Travel (%) 10 20 30 40 50 60 70 80 90 100


Cv 2.7 7 13.6 24.4 40 61.2 84.6 107.2 138.4 160
VALVE SIZING CALCULATION SHEET
ANSI / ISA-75.01.01 (IEC 60534-2-1 Mod) Date : 26/09/2022
Version : v4.4.0 Date : 19/08/2022 Sheet 8 of 16

Customer Tag # SOAKING


Project OVS 5682 Item # #8-[0]
Customer Ref. No. Application ZONE 7 (Left)
Quotation # Function Control
Item Description Series 40, 2-1/2", CL 150, Wafer
SERVICE AND SIZING Cond1 Cond2 Cond3 Cond4
Process Fluid Name Natural gas
Inlet Pressure (bar[g]) 0.1
Outlet Pressure (bar[g]) 0.09
Gas Flow (Nm³/hr) 171
Specific Heat Ratio Factor, cp/cv 1.27
Temperature (°C) 25
Pressure Drop Ratio Factor, Xt 0.32
Adj. Pressure Drop Ratio Factor, Xtp 0.321
Expansion Factor, Y 0.99
Compressibility Factor, Z 0.998
Piping Correction Factor, Fp 0.993

Valve Diameter, d (in) 2-1/2"


Inlet Pipe Diameter , D1 (in) 3.5
Outlet Pipe Diameter, D2 (in) 3.5
Dynamic Torque
Sizing Coefficient, Cv 56.1
Pressure Drop (bar) 0.01
dP Choked (bar) 0.3253

Noise Calculation
Valve Type Butterfly
Downstream Pipe Size (in) 3
Downstream Pipe Schedule STD
Valve SPL (dBA) < 70
Warning Acceptable

Pipe Mach 0.033


Valve Mach 0.048

Valve Series : Series 40 % Opening,


Calculated Cv
Valve Size: 2-1/2"

Rated Cv: 160


B - (57.6,56.1)
Flow Char: Equal Percentage

Travel (%) 10 20 30 40 50 60 70 80 90 100


Cv 2.7 7 13.6 24.4 40 61.2 84.6 107.2 138.4 160
VALVE SIZING CALCULATION SHEET
ANSI / ISA-75.01.01 (IEC 60534-2-1 Mod) Date : 26/09/2022
Version : v4.4.0 Date : 19/08/2022 Sheet 9 of 16

Customer Tag # PRE-HEATING


Project OVS 5682 Item # #9-[0]
Customer Ref. No. Application ZONE 1 (Right)
Quotation # Function Control
Item Description TriLok, 12", CL 150, Wafer
SERVICE AND SIZING Cond1 Cond2 Cond3 Cond4
Process Fluid Name Air
Inlet Pressure (bar[g]) 0.12
Outlet Pressure (bar[g]) 0.108
Gas Flow (Nm³/hr) 3168
Specific Heat Ratio Factor, cp/cv 1.4
Temperature (°C) 400
Pressure Drop Ratio Factor, Xt 0.34
Adj. Pressure Drop Ratio Factor, Xtp 0.341
Expansion Factor, Y 0.99
Compressibility Factor, Z 1
Piping Correction Factor, Fp 0.973

Valve Diameter, d (in) 12"


Inlet Pipe Diameter , D1 (in) 16
Outlet Pipe Diameter, D2 (in) 16
Dynamic Torque
Sizing Coefficient, Cv 1855
Pressure Drop (bar) 0.012
dP Choked (bar) 0.3845

Noise Calculation
Valve Type Butterfly
Downstream Pipe Size (in) 16
Downstream Pipe Schedule STD
Valve SPL (dBA) < 70
Warning Acceptable

Pipe Mach 0.039


Valve Mach 0.069

Valve Series : TriLok % Opening,


Calculated Cv
Valve Size: 12"

Rated Cv: 3515


B - (54.1,1855)
Flow Char: Equal Percentage

Travel (%) 10 20 30 40 50 60 70 80 90 100


Cv 104.6 388.5 758 1177.2 1642.3 2155.9 2701.1 3215.5 3565.9 3515
VALVE SIZING CALCULATION SHEET
ANSI / ISA-75.01.01 (IEC 60534-2-1 Mod) Date : 26/09/2022
Version : v4.4.0 Date : 19/08/2022 Sheet 10 of 16

Customer Tag # PRE-HEATING


Project OVS 5682 Item # #10-[0]
Customer Ref. No. Application ZONE 2 (Central + Left)
Quotation # Function Control
Item Description TriLok, 20", CL 150, Wafer
SERVICE AND SIZING Cond1 Cond2 Cond3 Cond4
Process Fluid Name Air
Inlet Pressure (bar[g]) 0.12
Outlet Pressure (bar[g]) 0.108
Gas Flow (Nm³/hr) 9504
Specific Heat Ratio Factor, cp/cv 1.4
Temperature (°C) 400
Pressure Drop Ratio Factor, Xt 0.34
Adj. Pressure Drop Ratio Factor, Xtp 0.347
Expansion Factor, Y 0.99
Compressibility Factor, Z 1
Piping Correction Factor, Fp 0.96

Valve Diameter, d (in) 20"


Inlet Pipe Diameter , D1 (in) 28
Outlet Pipe Diameter, D2 (in) 28
Dynamic Torque
Sizing Coefficient, Cv 5631
Pressure Drop (bar) 0.012
dP Choked (bar) 0.3871

Noise Calculation
Valve Type Butterfly
Downstream Pipe Size (in) 28
Downstream Pipe Schedule STD
Valve SPL (dBA) < 70
Warning Acceptable

Pipe Mach 0.038


Valve Mach 0.075

Valve Series : TriLok % Opening,


Calculated Cv
Valve Size: 20"

Rated Cv: 10805


B - (53.7,5631)
Flow Char: Equal Percentage

Travel (%) 10 20 30 40 50 60 70 80 90 100


Cv 321.6 1194.3 2330.1 3618.7 5048.5 6627.3 8302.9 9884.2 10961.5 10805
VALVE SIZING CALCULATION SHEET
ANSI / ISA-75.01.01 (IEC 60534-2-1 Mod) Date : 26/09/2022
Version : v4.4.0 Date : 19/08/2022 Sheet 11 of 16

Customer Tag # HEATING 1


Project OVS 5682 Item # #11-[0]
Customer Ref. No. Application ZONE 2
Quotation # Function Control
Item Description TriLok, 20", CL 150, Wafer
SERVICE AND SIZING Cond1 Cond2 Cond3 Cond4
Process Fluid Name Air
Inlet Pressure (bar[g]) 0.12
Outlet Pressure (bar[g]) 0.108
Gas Flow (Nm³/hr) 8272
Specific Heat Ratio Factor, cp/cv 1.4
Temperature (°C) 400
Pressure Drop Ratio Factor, Xt 0.37
Adj. Pressure Drop Ratio Factor, Xtp 0.366
Expansion Factor, Y 0.99
Compressibility Factor, Z 1
Piping Correction Factor, Fp 0.988

Valve Diameter, d (in) 20"


Inlet Pipe Diameter , D1 (in) 24
Outlet Pipe Diameter, D2 (in) 24
Dynamic Torque
Sizing Coefficient, Cv 4769
Pressure Drop (bar) 0.012
dP Choked (bar) 0.4191

Noise Calculation
Valve Type Butterfly
Downstream Pipe Size (in) 24
Downstream Pipe Schedule STD
Valve SPL (dBA) < 70
Warning Acceptable

Pipe Mach 0.045


Valve Mach 0.065

Valve Series : TriLok % Opening,


Calculated Cv
Valve Size: 20"

Rated Cv: 10805


B - (48,4769)
Flow Char: Equal Percentage

Travel (%) 10 20 30 40 50 60 70 80 90 100


Cv 321.6 1194.3 2330.1 3618.7 5048.5 6627.3 8302.9 9884.2 10961.5 10805
VALVE SIZING CALCULATION SHEET
ANSI / ISA-75.01.01 (IEC 60534-2-1 Mod) Date : 26/09/2022
Version : v4.4.0 Date : 19/08/2022 Sheet 12 of 16

Customer Tag # HEATING 2


Project OVS 5682 Item # #12-[0]
Customer Ref. No. Application ZONE 3 (Right)
Quotation # Function Control
Item Description TriLok, 16", CL 150, Wafer
SERVICE AND SIZING Cond1 Cond2 Cond3 Cond4
Process Fluid Name Air
Inlet Pressure (bar[g]) 0.12
Outlet Pressure (bar[g]) 0.108
Gas Flow (Nm³/hr) 6204
Specific Heat Ratio Factor, cp/cv 1.4
Temperature (°C) 400
Pressure Drop Ratio Factor, Xt 0.33
Adj. Pressure Drop Ratio Factor, Xtp 0.329
Expansion Factor, Y 0.989
Compressibility Factor, Z 1
Piping Correction Factor, Fp 0.978

Valve Diameter, d (in) 16"


Inlet Pipe Diameter , D1 (in) 20
Outlet Pipe Diameter, D2 (in) 20
Dynamic Torque
Sizing Coefficient, Cv 3617
Pressure Drop (bar) 0.012
dP Choked (bar) 0.3749

Noise Calculation
Valve Type Butterfly
Downstream Pipe Size (in) 20
Downstream Pipe Schedule STD
Valve SPL (dBA) < 70
Warning Acceptable

Pipe Mach 0.049


Valve Mach 0.076

Valve Series : TriLok % Opening,


Calculated Cv
Valve Size: 16"

Rated Cv: 6548


B - (55.8,3617)
Flow Char: Equal Percentage

Travel (%) 10 20 30 40 50 60 70 80 90 100


Cv 194.9 723.8 1412.1 2193 3059.4 4016.2 5031.7 5990 6642.8 6548
VALVE SIZING CALCULATION SHEET
ANSI / ISA-75.01.01 (IEC 60534-2-1 Mod) Date : 26/09/2022
Version : v4.4.0 Date : 19/08/2022 Sheet 13 of 16

Customer Tag # HEATING 2


Project OVS 5682 Item # #13-[0]
Customer Ref. No. Application ZONE 4 (Left)
Quotation # Function Control
Item Description TriLok, 16", CL 150, Wafer
SERVICE AND SIZING Cond1 Cond2 Cond3 Cond4
Process Fluid Name Air
Inlet Pressure (bar[g]) 0.12
Outlet Pressure (bar[g]) 0.108
Gas Flow (Nm³/hr) 6204
Specific Heat Ratio Factor, cp/cv 1.4
Temperature (°C) 400
Pressure Drop Ratio Factor, Xt 0.33
Adj. Pressure Drop Ratio Factor, Xtp 0.329
Expansion Factor, Y 0.989
Compressibility Factor, Z 1
Piping Correction Factor, Fp 0.978

Valve Diameter, d (in) 16"


Inlet Pipe Diameter , D1 (in) 20
Outlet Pipe Diameter, D2 (in) 20
Dynamic Torque
Sizing Coefficient, Cv 3617
Pressure Drop (bar) 0.012
dP Choked (bar) 0.3749

Noise Calculation
Valve Type Butterfly
Downstream Pipe Size (in) 20
Downstream Pipe Schedule STD
Valve SPL (dBA) < 70
Warning Acceptable

Pipe Mach 0.049


Valve Mach 0.076

Valve Series : TriLok % Opening,


Calculated Cv
Valve Size: 16"

Rated Cv: 6548


B - (55.8,3617)
Flow Char: Equal Percentage

Travel (%) 10 20 30 40 50 60 70 80 90 100


Cv 194.9 723.8 1412.1 2193 3059.4 4016.2 5031.7 5990 6642.8 6548
VALVE SIZING CALCULATION SHEET
ANSI / ISA-75.01.01 (IEC 60534-2-1 Mod) Date : 26/09/2022
Version : v4.4.0 Date : 19/08/2022 Sheet 14 of 16

Customer Tag # SOAKING


Project OVS 5682 Item # #14-[0]
Customer Ref. No. Application ZONE 5 (Right)
Quotation # Function Control
Item Description TriLok, 10", CL 150, Wafer
SERVICE AND SIZING Cond1 Cond2 Cond3 Cond4
Process Fluid Name Air
Inlet Pressure (bar[g]) 0.12
Outlet Pressure (bar[g]) 0.108
Gas Flow (Nm³/hr) 1881
Specific Heat Ratio Factor, cp/cv 1.4
Temperature (°C) 400
Pressure Drop Ratio Factor, Xt 0.38
Adj. Pressure Drop Ratio Factor, Xtp 0.377
Expansion Factor, Y 0.991
Compressibility Factor, Z 1
Piping Correction Factor, Fp 0.991

Valve Diameter, d (in) 10"


Inlet Pipe Diameter , D1 (in) 12.75
Outlet Pipe Diameter, D2 (in) 12.75
Dynamic Torque
Sizing Coefficient, Cv 1072
Pressure Drop (bar) 0.012
dP Choked (bar) 0.4319

Noise Calculation
Valve Type Butterfly
Downstream Pipe Size (in) 12
Downstream Pipe Schedule STD
Valve SPL (dBA) < 70
Warning Acceptable

Pipe Mach 0.041


Valve Mach 0.059

Valve Series : TriLok % Opening,


Calculated Cv
Valve Size: 10"

Rated Cv: 2605


B - (45.8,1072)
Flow Char: Equal Percentage

Travel (%) 10 20 30 40 50 60 70 80 90 100


Cv 77.5 287.9 561.8 872.4 1217.1 1597.8 2001.8 2383 2642.7 2605
VALVE SIZING CALCULATION SHEET
ANSI / ISA-75.01.01 (IEC 60534-2-1 Mod) Date : 26/09/2022
Version : v4.4.0 Date : 19/08/2022 Sheet 15 of 16

Customer Tag # SOAKING


Project OVS 5682 Item # #15-[0]
Customer Ref. No. Application ZONE 6 (Central)
Quotation # Function Control
Item Description TriLok, 10", CL 150, Wafer
SERVICE AND SIZING Cond1 Cond2 Cond3 Cond4
Process Fluid Name Air
Inlet Pressure (bar[g]) 0.12
Outlet Pressure (bar[g]) 0.108
Gas Flow (Nm³/hr) 1881
Specific Heat Ratio Factor, cp/cv 1.4
Temperature (°C) 400
Pressure Drop Ratio Factor, Xt 0.38
Adj. Pressure Drop Ratio Factor, Xtp 0.377
Expansion Factor, Y 0.991
Compressibility Factor, Z 1
Piping Correction Factor, Fp 0.991

Valve Diameter, d (in) 10"


Inlet Pipe Diameter , D1 (in) 12.75
Outlet Pipe Diameter, D2 (in) 12.75
Dynamic Torque
Sizing Coefficient, Cv 1072
Pressure Drop (bar) 0.012
dP Choked (bar) 0.4319

Noise Calculation
Valve Type Butterfly
Downstream Pipe Size (in) 12
Downstream Pipe Schedule STD
Valve SPL (dBA) < 70
Warning Acceptable

Pipe Mach 0.041


Valve Mach 0.059

Valve Series : TriLok % Opening,


Calculated Cv
Valve Size: 10"

Rated Cv: 2605


B - (45.8,1072)
Flow Char: Equal Percentage

Travel (%) 10 20 30 40 50 60 70 80 90 100


Cv 77.5 287.9 561.8 872.4 1217.1 1597.8 2001.8 2383 2642.7 2605
VALVE SIZING CALCULATION SHEET
ANSI / ISA-75.01.01 (IEC 60534-2-1 Mod) Date : 26/09/2022
Version : v4.4.0 Date : 19/08/2022 Sheet 16 of 16

Customer Tag # SOAKING


Project OVS 5682 Item # #16-[0]
Customer Ref. No. Application ZONE 7 (Left)
Quotation # Function Control
Item Description TriLok, 10", CL 150, Wafer
SERVICE AND SIZING Cond1 Cond2 Cond3 Cond4
Process Fluid Name Air
Inlet Pressure (bar[g]) 0.12
Outlet Pressure (bar[g]) 0.108
Gas Flow (Nm³/hr) 1881
Specific Heat Ratio Factor, cp/cv 1.4
Temperature (°C) 400
Pressure Drop Ratio Factor, Xt 0.38
Adj. Pressure Drop Ratio Factor, Xtp 0.377
Expansion Factor, Y 0.991
Compressibility Factor, Z 1
Piping Correction Factor, Fp 0.991

Valve Diameter, d (in) 10"


Inlet Pipe Diameter , D1 (in) 12.75
Outlet Pipe Diameter, D2 (in) 12.75
Dynamic Torque
Sizing Coefficient, Cv 1072
Pressure Drop (bar) 0.012
dP Choked (bar) 0.4319

Noise Calculation
Valve Type Butterfly
Downstream Pipe Size (in) 12
Downstream Pipe Schedule STD
Valve SPL (dBA) < 70
Warning Acceptable

Pipe Mach 0.041


Valve Mach 0.059

Valve Series : TriLok % Opening,


Calculated Cv
Valve Size: 10"

Rated Cv: 2605


B - (45.8,1072)
Flow Char: Equal Percentage

Travel (%) 10 20 30 40 50 60 70 80 90 100


Cv 77.5 287.9 561.8 872.4 1217.1 1597.8 2001.8 2383 2642.7 2605