Professional Documents
Culture Documents
Fan Troubleshooting ED100
Fan Troubleshooting ED100
ENGINEERING DATA
Aerovent • TC Ventco • Fiber-Aire • Twin City Fan & Blower • TC Axial • Clarage
Fan Performance
Troubleshooting Guide
Figure 1. Test Points at Constant Speed and
Introduction Standard Air Density
Trying to determine why a fan is not working the way you want
it to can sometimes be a very confusing and frustrating expe- 49 IN. SINGLE WIDTH BACKWARD INCLINED
rience. This document, based on the experience of Twin City 700 RPM
Fan Companies, Ltd., has been put together to help fan users = 0.075 lb/cu.ft
diagnose and troubleshoot fan performance problems.
BRAKE HORSEPOWER
How Fan Systems Work 30
E2
C2
B2
D2
Before getting into troubleshooting it is worth our while to look A2
ted on the lower vertical axis, while the top vertical axis shows 1
the brake horsepower. The point labeled A1 simulates a duct
system where there is no resistance flow since the static pres- 0
A1
O
speeds or other air densities using a set of equations known
as the fan laws. The first fan law states that the change in flow where: P = pressure (in. w.g.)
rate is proportional to the change in speed. This can be writ-
= air density (lb/cu.ft)
ten as:
The change in the power requirement is proportional to the
QN = QO x
( )RPMN
RPMO
cube of the change in speed, as shown in the equation of the
third fan law:
3
where: Q =
RPM =
volumetric flow rate (CFM)
fan speed in revolutions per minute
HpN = HpO x
( )
RPMN
RPMO
x
N
N = new conditions
O = old conditions where: Hp = fan power requirement (hp)
( )
5 700 RPM 30000
P1 = 2 x = 4.5 in. w.g.
650 RPM 20000
4
STATIC PRESSURE
600 RPM
550 RPM
Figure 4 shows these two points along with the system line
3
that is defined by them. If the flow remains turbulent (and it
500 RPM
almost always does) and if the duct configuration does not
2
change (including the position of any dampers), the pressure
required for a given flow rate will follow this line. Some vari-
1 able air volume (VAV) systems require a minimum pressure at
the end of the duct runs in order for the VAV boxes to open.
0
No flow occurs until this pressure is reached. The system line
0 1 2 3 4 5 6
equation for this type of system is:
CFM in 10000's
2
= 0.075 lb/cu.ft
Figure 4. Two Performance Points Along the System Curve
BRAKE HORSEPOWER
30
20
= 0.059 lb/cu.ft
5
10
4
STATIC PRESSURE
3
5
= 0.075 lb/cu.ft
2
4
STATIC PRESSURE
3 1
= 0.059 lb/cu.ft
2 0
0 1 2 3 4 5 6
CFM in 10000's
1
0
0 1 2 3 4 5 6
CFM in 10000's
4 System Effects
STATIC PRESSURE
Most of the time fans are tested with open inlets, and designs
3 that do not have an integral inlet bell will be tested with one
to simulate inlet ductwork. Figure 7 shows the streamlines the
2 air follows as it enters a fan with a well-designed inlet bell and
with a straight run of duct upstream of the fan. The airflow is
1
smooth and the velocity at the entrance is uniform.
30 C2
E2 D2 B2
A2
20
10
F2
E1
5
D1
F1
4
STATIC PRESSURE
SYSTEM
LINES A length of straight duct is required at the outlet to allow
3 C1 the high velocity (kinetic energy) to be converted to static
pressure (potential energy). To get full pressure conversion, a
2 duct at least as long as the 100% effective duct length is
B1 required. AMCA defines the 100% effective duct length to be
a minimum of two and one half equivalent duct diameters for
1
outlet velocities up to 2,500 fpm, with 1 duct diameter added
A1
for each additional 1,000 fpm. Also it is important that the out-
0 let connection be smooth. In the test code, AMCA specifies
0 1 2 3 4 5 6
that the area of the outlet duct be between 95% and 105% of
CFM in 10000's
the fan outlet area and that any transitions used have sides
that are sloped no more than 15° on converging sections and
7° on diverging sections.
Duct fittings or fan installations that do not provide
smooth, uniform flow at the fan inlet or complete pressure
recovery at the fan outlet cause the fan to perform at a level
below its catalog rating. Elbows cause non-uniform airflow at
BRAKE HORSEPOWER
STATIC PRESSURE
Case Study 1
System Resistance Higher Than Anticipated
This case study demonstrates one of the most common fan
RPMnew = 1196 x ( ) 15000
13600
= 1319
1319 3
performance problems. A 36" tubeaxial fan was selected
and installed to deliver 15,000 CFM at a static pressure of
HPnew = 6.8 x ( ) 1196
= 9.12
1.70 in. w.g. After the fan was installed, an air performance 1319 2
test indicated a flow rate of 13,600 CFM with a static pres-
sure of 1.68 in. w.g. and 6.8 horsepower.
SPnew = 1.68 x ( ) 1196
= 2.04
4.0 MEASURED 8
CFM & HP
S T A T I C P R E S S U R E ( I N. W. G.)
3.5 7
SP
BRAKE HORSEPOWER
3.0 BHP 6
2.5 5
EXPECTED
CFM & SP SP REQ'D. FOR
2.0 DESIGN FLOW
4
DESIGN CFM & SP
1.5 3
MEASURED
CFM & SP
AS DESIGNED 2
1.0 SYSTEM CURVE
AS INSTALLED
SYSTEM CURVE
0.5 1
0 0
0 4 8 12 16 20 24 28
C F M ( i n 1, 0 0 0 's)
CURVE #1
3.0 24
BRAKE HORSEPOWER
2.5 20
BHP
2.0 16
WITH STRAIGHTENERS
WITH PROBES IN INLET
1.5 12
WITHOUT STRAIGHTENERS
1.0 8
WITH PROBES IN INLET WITH STRAIGHTENERS
WITH PROBES REMOVED
0.5 4
SYSTEM CURVE
0 0
0 10 20 30 40 50 60
C F M ( i n 1, 0 0 0 's)
CURVE #2
Figure 21. Air Handling Unit Measured and Expected Performance Curves
Customer: Fan Tag: CFM: 20,000
Job Name: Model: DWDI Fan
SP: 4
RPM: 1,038
PERFORMANCE CURVE BHP: 16.35
Outlet Vel.: 1,775
6 24
Density: 0.075
3%
5 20
S T A T I C P R E S S U R E ( I N. W. G.)
DESIGN
MEASURED PERFORMANCE
PERFORMANCE BHP
BRAKE HORSEPOWER
4 SP 16
DESIGN
3 SYSTEM 12
CURVE
2 8
AS TESTED
SYSTEM CURVE
1 4
0 0
0 5 10 15 20 25 30 35 40
C F M ( i n 1, 0 0 0 's)
CURVE #3
FLOW PATTERNS
AIR
FLOW
A A
SECT. A-A
BEFORE
FLOW
STRAIGHTENER
SECT. A-A
AFTER
50
S T A T I C P R E S S U R E ( I N. W. G.)
20
MEASURED CFM & HP MEASURED CFM & SP
WITHOUT STRAIGHTENER WITH STRAIGHTENER
BRAKE HORSEPOWER
16 40
12 30
MEASURED
CFM & SP
WITHOUT
8 STRAIGHTENER 20
4 10
SYSTEM CURVE
0 0
0 4 8 12 16 20 24 28 32
C F M ( i n 1, 0 0 0 's)
CURVE #4
CATALOG SP DESIGN
S T A T I C P R E S S U R E ( I N. W. G.)
25 POINT
20
MEASURED CFM & SP
MEASURED CFM & SP WITH INLET BELL
WITH INLET BELL WITHOUT SCREEN
WITH SCREEN
25
MEASURED
10 CFM & SP
WITHOUT
BELL WITH
SCREEN
5
SYSTEM CURVE
AMCA TOLERANCE
0
0 1 2 3 4 5 6 7 8 9
C F M ( i n 1, 0 0 0 's)
CURVE #5