Steel Column Design

DESIGNED BY: Group 10 Steel- Group 2 RCD - CE 3203


Proposed 3- storey Twin Building at Poblacion IV, Sto. Tomas City, Batangas
DATE: June 4 2021
Column Size:W14x53

1.0 REFERENCES:

1.1 National Structural Code of the Philippines 2015 Edition


1.2 American Concrete Institute (ACI 318-14, Building Code Requirements for Strucutural Concrete)
1.3 American Iron and Steel Institute (AISI)
1.4 American Institute of Steel Construction (AISC)
1.5 Steel Deck Institute (SDI)

Column W14x53 Steel Grade: ASTM A992


A 15.6 in² Fy: 50 ksi
rx 5.89 in
ry 1.92 in
L 3m= 118.11 in
Calculation:

A. Brace Frame
K= 1
Effective Length
Lc = KL
Lc = 1x 118.11
Lc = 118.1

𝐿𝑐 118.11
=
𝑟𝑥 3.61
𝐿𝑐
= 20.05263158 < 200 okay
𝑟𝑥

𝐿𝑐 118.11
=
𝑟𝑦 2.08

𝐿𝑐
𝑟𝑦
= 61.515625 < 200 okay

Consider larger slenderness ratio

thus, slenderness ratio= 61.52


61.515625 <

61.515625 < 113.4 okay

therefore,

Euler Elastic Critical Buckling Stress

Fe= 75.64 ksi

Flexural Buckling Stress

Fcr= 37.91 ksi

Nominal Axial Compression Strength

ϕPn= 532.3 kips


2368 kN
Steel Column Design
DESIGNED BY: Group 10 Steel- Group 2 RCD - CE 3203
Proposed 3- storey Twin Building at Poblacion IV, Sto. Tomas City, Batangas
DATE: June 4 2021
Column Size:W12x96

1.0 REFERENCES:

1.1 National Structural Code of the Philippines 2015 Edition


1.2 American Concrete Institute (ACI 318-14, Building Code Requirements for Strucutural Concrete)
1.3 American Iron and Steel Institute (AISI)
1.4 American Institute of Steel Construction (AISC)
1.5 Steel Deck Institute (SDI)

Column W12x96 Steel Grade: ASTM A992


A 28.2 in² Fy: 50 ksi
rx 5.44 in
ry 3.09 in
L 3m= 118.11 in
Calculation:

A. Brace Frame
K= 1
Effective Length
Lc = KL
Lc = 1x 118.11
Lc = 118.1

𝐿𝑐 118.11
=
𝑟𝑥 3.61
𝐿𝑐
= 21.71139706 < 200 okay
𝑟𝑥

𝐿𝑐 118.11
=
𝑟𝑦 2.08

𝐿𝑐
𝑟𝑦
= 38.22330097 < 200 okay

Consider larger slenderness ratio

thus, slenderness ratio= 38.22


38.22330097 <

38.22330097 < 113.4 okay

therefore,

Euler Elastic Critical Buckling Stress

Fe= 195.9 ksi

Flexural Buckling Stress

Fcr= 44.93 ksi

Nominal Axial Compression Strength

ϕPn= 1140 kips


5073 kN
Steel Column Design
DESIGNED BY: Group 10 Steel- Group 2 RCD - CE 3203
Proposed 3- storey Twin Building at Poblacion IV, Sto. Tomas City, Batangas
DATE: June 4 2021
Column Size: W14x132

1.0 REFERENCES:

1.1 National Structural Code of the Philippines 2015 Edition


1.2 American Concrete Institute (ACI 318-14, Building Code Requirements for Strucutural Concrete)
1.3 American Iron and Steel Institute (AISI)
1.4 American Institute of Steel Construction (AISC)
1.5 Steel Deck Institute (SDI)

Column W14x132 Steel Grade: ASTM A992


A 38.8 in² Fy: 50 ksi
rx 6.28 in
ry 3.76 in
L 3m= 118.11 in
Calculation:

A. Brace Frame
K= 1
Effective Length
Lc = KL
Lc = 1x 118.11
Lc = 118.1

𝐿𝑐 118.11
=
𝑟𝑥 3.61
𝐿𝑐
= 18.80732484 < 200 okay
𝑟𝑥

𝐿𝑐 118.11
=
𝑟𝑦 2.08

𝐿𝑐
𝑟𝑦
= 31.41223404 < 200 okay

Consider larger slenderness ratio

thus, slenderness ratio= 31.41


31.41223404 <

31.41223404 < 113.4 okay

therefore,

Euler Elastic Critical Buckling Stress

Fe= 290.1 ksi

Flexural Buckling Stress

Fcr= 46.52 ksi

Nominal Axial Compression Strength

ϕPn= 1624 kips


7226 kN
Steel Column Design
DESIGNED BY: Group 10 Steel- Group 2 RCD - CE 3203
Proposed 3- storey Twin Building at Poblacion IV, Sto. Tomas City, Batangas
DATE: June 4 2021
Column Size: W18x97

1.0 REFERENCES:

1.1 National Structural Code of the Philippines 2015 Edition


1.2 American Concrete Institute (ACI 318-14, Building Code Requirements for Strucutural Concrete)
1.3 American Iron and Steel Institute (AISI)
1.4 American Institute of Steel Construction (AISC)
1.5 Steel Deck Institute (SDI)

Column W18x97 Steel Grade: ASTM A992


A 28.5 in² Fy: 50 ksi
rx 7.82 in
ry 2.65 in
L 3m= 118.11 in
Calculation:

A. Brace Frame
K= 1
Effective Length
Lc = KL
Lc = 1x 118.11
Lc = 118.1

𝐿𝑐 118.11
=
𝑟𝑥 3.61
𝐿𝑐
= 15.10358056 < 200 okay
𝑟𝑥

𝐿𝑐 118.11
=
𝑟𝑦 2.08

𝐿𝑐
𝑟𝑦
= 44.56981132 < 200 okay

Consider larger slenderness ratio

thus, slenderness ratio= 44.57


44.56981132 <

44.56981132 < 113.4 okay

therefore,

Euler Elastic Critical Buckling Stress

Fe= 144.1 ksi

Flexural Buckling Stress

Fcr= 43.24 ksi

Nominal Axial Compression Strength

ϕPn= 1109 kips


4934 kN