LARSEN & TOUBRO LIMITED

ECC Division - EDRC Rev A

PROJECT: DOCUMENT NO DATE


Proposed Construction Of Plant-2 at Manesar for Maruti
Suzuki India Limited O10042-C-FB-08-DC-0001 30/10/2010
DESIGNED CHECKED SHEET
1 of 5
TITLE:
CANTEEN BUILDING - LOAD CALCULATION CJM AKA

STRUCTURAL SYSTEM

Canteen Building is of size 30m width, 60m length and 3.2m clear height.
Structural system consists of RC Column supported on isolated footings and RCC beam slab system

1 DEAD LOAD

Self Weight of Slab

Considering 150 mm thick slab

Total load = 0.15*25 = 3.75 kN/m2

Brick Load

Self weight of the wall of height 3.65m per meter run = 0.23x3.65x20 = 16.79 kN/m
(0.15+0.5+3)
Assuming 15% openings in wall

Self weight of wall per m = 14.27 kN/m

Self weight of the wall of height 4.4m per meter run = 0.23x4.4x20 = 20.24 kN/m
(0.15+0.5+4.5-0.75)
Assuming 15% openings in wall

Self weight of wall per m = 17.2 kN/m

Self weight of the wall of height 1.15m per meter run = 0.23x1x20 = 4.6 kN/m
(0.15+0.5+5.5-0.75-0.75-3.65)

Self weight of wall per m = 4.6 kN/m

Services

Load from Services = 0.50 kN/m2

Weathering Course
LARSEN & TOUBRO LIMITED
ECC Division - EDRC Rev A

PROJECT: DOCUMENT NO DATE


Proposed Construction Of Plant-2 at Manesar for Maruti
Suzuki India Limited O10042-C-FB-08-DC-0001 30/10/2010
DESIGNED CHECKED SHEET
2 of 5
TITLE:
CANTEEN BUILDING - LOAD CALCULATION CJM AKA

Average Thickness of screed = 200 mm


Imposed load from weathering course 0.2 * 24 = 4.8 kN/m2

Parapet Wall

Self Weight of wall of height 1m = 0.115*1*20 = 2.3 kN/m

Load from Chiller and Air Washer

Imposed load from Chiller and Air Washer = 3.5 kN/m2

Load from Pipe rack

Imposed load from pipe rack = 5 kN/m2

2 LIVE LOAD

Load On Roof

Live load as per ( IS875 - Part 2 (1987)) Roof with access = 1.50 kN/m2

FFL
LARSEN & TOUBRO LIMITED
ECC Division - EDRC Rev A

PROJECT: DOCUMENT NO DATE


Proposed Construction Of Plant-2 at Manesar for Maruti
Suzuki India Limited O10042-C-FB-08-DC-0001 30/10/2010
DESIGNED CHECKED SHEET
3 of 5
TITLE:
CANTEEN BUILDING - LOAD CALCULATION CJM AKA

0.5 m

FGL FGL

0.15

0.375

2.5m below FGL or


2m below NGL
1.975 m
LARSEN & TOUBRO LIMITED
ECC Division - EDRC Rev A

PROJECT: Proposed Construction Of Plant-2 at Manesar for Maruti DOCUMENT NO DATE


Suzuki India Limited O10042-C-FB-08-DC-0001 30/10/2010
DESIGNED CHECKED SHEET
TITLE:
CANTEEN BUILDING - LOAD CALCULATION CJM AKA

Seismic load :

Zone factor Z = 0.24

Response reduction factor R = 5

Importance factor I = 1

Damping percentage = 5

Soil type = Medium

Width of the building (Along staad -X) = 30 m

Length of the building (Along staad -Z) = 60 m

Height of the building = 5.8 m

Seismic weight of structure , W = 28476.01 kN

Seismic base shear coefficient, Ah = (Zx I x Sa (/(2x Rx g)

Ah x = 0.04909
Ah z = 0.05949

Base Shear X = Ah X W = 1397.887 kN

Base Shear Z = Ah X W = 1694.038 kN

Staad Base Shear (Response spectrum With time period as per Fig 2 of IS 1893)

Staad base shear X = 1890 kN

Staad base shear Z 1583 kN

Scale Factor in X = 1
Scale Factor in Z = 1.07