You are on page 1of 1

NOTES:

1.1. REFERENCE:
i) LR.NO: CE/D/CSR/EEC/AE/F.kovilambakkam/D.149/22,dt-19.05.2022
HEAD ROOM BEAM HEAD ROOM
ii) LR.NO: SE/CEDC/S-II/AEE/CIVIL/F.kovilambakkam SS/D.68/22,dt-13.05.2022
(230/300x400/500) SLAB
230 2.0. DESIGN DATA:

2.1.TYPE OF FOUNDATION: (i) INDIVIDUAL COLUMN FOOTING (ISOLATED FOUNDATION)


PARAPET WALL (ii) SAFE BEARING CAPACITY OF SOIL 20t/m²
LOFT
Roof Beam

2400
(iii) DEPTH OF FOUNDATION = 2.0m from the Natural Ground level
2.2.LIVE LOAD ON FLOOR SLAB = 4KN/m²
ROOF SLAB 150 mm THK
GF ROOF LEVEL ROOF BEAM 2.3.LIVE LOAD ON TOILET SLAB = 2KN/m²
(+)6550mm (230/300x500) 2.4.LIVE LOAD ON ROOF SLAB (ACCESSIBLE) = 1.5KN/m²
COLUMN 2.5.LIVE LOAD ON STAIRCASE = 5KN/m²
3.0.DIRECTIVES:
CONTINUOUS HAND RAIL 3.1.FOUNDATION : R.C.C ISOLATED FOOTING IN M25 GRADE USING 12 TO 20mm
LINTEL BEAM B.G METAL OVER P.C.C (1:2:4) USING 12mm to 20mm B.G METAL
(230x150) 3.2. MIX: ALL R.C.C MEMBERS ARE OF M25 GRADE USING 12T020 mm B.G METAL (I.S.456-2000)

8950
3.3. WALLS: (i) MAIN WALLS: BRICK MASONRY IN C.M 1:6, 230mm THICK USING COUNTRY BRICKS

4350
HAVING CRUSHING STRENGTH NOT LESS THAN 7N/mm²
SUNSHADE 600 (ii)PARTITION WALLS: BRICK WORK IN C.M 1:4, 115mm THICK.
3.4. FLOORING: (i) GROUND FLOOR: P.C.C M15, 100mm THICK USING 20mm HBC METAL
PLINTH BEAM AND FINISHED WITH GLAZED TILE SIZE300X300X6mm FINISHED WITH C.M 1:3,20mm
Plinth Beam FLOOR (230x400) THICK TOILET FLOORING NON-SLIPPERY GLAZED/NON GLAZED/NON GLAZED
FLOOR
PLINTH LEVEL FINISHING CONCRETE (ii) BATTERY ROOM : ACID PROOF FLOORING AND ACID PROOF PAINTING.
(+)2500mm (iii) CONTROL ROOM:VITRIFIED 1:3 20mm THK IN GROUND FLOOR AND OVER R.C.C SLAB
BRICK WORK SIDE DADOOING WITH VITRIFIED TILES TO A HEIGHT OF 2.0m OVER C.M 1:3,
IN SUPER 12mm THK AND JOINTS SHALL BE FINISHED WITH WHITE CEMENT NEATLY

2200
STRUCTURE 3.5. PLASTERING: (i) 230mm WALLS: C.M. 1:5, 12mm THICK , 115mm WALL: CM 1:4 12mm THK
(ii)CEILING : C.M. 1:3, 12 mm THICK
3.6. LINTELS,LOFT AND : R.C.C M25 MIX, USING 12 TO 20mm B.G METAL, LINTEL WITH SUN SHADE 600mm
ROAD LEVEL CUP -BOARD SLAB PROJECTION
(+)0.0mm 3.7. ROOFING: R.C.C, M25 MIX150mm THICK, USING 20mm DOWN GRADED B.G METAL PROVIDED WITH
Grade Beam

750
(-)0.75m NECESSARY WATER LINE SANITARY ARRANGEMENTS AND ELECTRICAL FITTINGS
FRONT ELEVATION EXT. G.L
(-)0.75m
AS PER STANDARD SPECIFICATION.
WEATHERING COARSE CONSISTING OF ONE COURSE OF PRESSED TILES EMBEDDED IN
SCALE1:100 CABLE C.M 1:3
DUCT MIXED WITH CRUDE OIL OVER A BED OF BRICK JELLY CONCRETE IN LIME OF 80mm
SAND FILLING
THICK AND SLOPE 1:60
P.C.C 100 mm THK
FOR FOUNDATION DETAILS 3.8. WHITE AND COLOUR WASHING: INSIDE WHITE WASHED WITH TWO COATS OF DISTEMPER .
SAND FILLING 100 mm THK
REFER SEPARATE DRAWING OUTSIDE COLOR WASHED WITH TWO COATS OF CEMENT PAINT OVER A PRIMARY COAT OF WHITE
GRADE BEAM (230/300x400)
CEMENT.
18060 3.9. PAINTING: ALL EXPOSED FACES OF WOOD/STEEL PAINTED WITH TWO COATS OF APPROVED
PAINT OVER A PRIMARY COAT. WOOD WORK IN CONTACT WITH MASONRY WORK PAINTED WITH TWO
SECTION X-X COATS OF SOLING BEFORE USE
SCALE1:100 3.10.DOORS & WINDOWS:

D1 - DOOR = 900 X 2100


D2 - P.V.C FRAMED WITH P.V.C SHUTTERS = 750 X 2100
W - WINDOW ANODIZED ALU. GLAZED WINDOW WITH GRILL = 1180 X 1480
V - ANODIZED ALU. GLAZED VENTILATOR = 1180 X 580
COLUMN
3.11. RAIN WATER PIPE: 100mm DIA P.V.C. DOWN FALL PIPE TO BE PROVIDED SUITABLY TO DRAIN RAIN
300x400
1 2 X 3 4 5 6 7 8 RAIN WATER PIPE 100mm Ø WATER FROM ROOF AS PER REQUIREMENT TO THE NBC 2016
3.12. STAIRCASE : STEPS RISE - 160mm, TREAD - 250mm, USING BRICK WORK IN C.M. 1:4 ,PLASTERED
20000 20000 WITH CM 1:3. WAIST SLAB OF 200mm THK USING MIX M25 AND HAND RAIL SIMPLE GRILL WORK
3500 3500 3300 3300 3300 3100 3.13. WATER TANK: P.V.C WATER TANK OF 2000 LTS CAPACITY MAY BE PROVIDED ABOVE THE HEAD ROOM
230 3500 3500 3300 3300 3300 3100
W/V W/V W/V W/V W/V W/V 230 3.14. GENERAL:
F (i) FOUNDATION IS DESIGNED FOR (G+1) FLOOR ONLY
(ii) ANTI TERMITE TREATMENT TO BE GIVEN FOR BUILDING FOUNDATION AS PER I.S 6313 PART(II)
(ii) SALIENT FEATURES OF BUILDING LIKE YEAR OF CONSTRUCTION, NO OF FLOORS
1500

DESIGNED AND LOAD ASSUMED Etc TO BE DISPLAYED IN A PROMINENT PLACE INSIDE


CABLE DUCT
THE BUILDING FOR FUTURE REFERENCE.
3500

3500
W/V
(iv) USE SUITABLE FLY ASH BRICKS IN PLACE OF CONVENTION BRICKS.
W/V

BATTERY

3500

3500
ROOM
BEAM SPECIAL NOTE:
COLUMN 1.0. REINFORCEMENT: ALL REINFORCEMENT SHALL BE OF HYSD BARS HAVING CHARACTERISTIC STRENGTH
D2 300x300 OF 415N/mm2 CONFORMING TO I.S. 1786 - 1985

7000

7000
2.0. CEMENT: HIGH STRENGTH ORDINARY PORTLAND CEMENT CONFORMING TO I.S 8112 OF 43
E GRADE.
CONTROL ROOM BUILDING FOR 3311 KV SS AT KOVILAMBAKKAM (i). MINIMUM CEMENT CONTENT AND MAXIMUM WATER CEMENT RATIO SHOULD BE ADOPTED
AS PER TABLE 5 & 6 OF I.S. 456 -2000

SL
(ii)THE MINIMUM FREQUENCY OF SAMPLING OF CONCRETE OF EACH GRADE

O
PE
SHOULD BE IN ACCORDANCE WITH CLAUSE 15-2-2 OF I.S. 456-2000.
3500

3500

3500

3500
W/V
W/V

1
3.0 AS THE PROPOSED BUILDING IS CONSTRUCTED UPTO F.F, IT MAY BE ENSURED THAT WATER IS NOT

IN
STORE ROOM

80
STAGNATED IN THE SUNKEN PORTION OF SLAB.
4.0 DOWEL RODS FOR COLUMN OVER GROUND FLOOR (GF) SHOULD BE PROVIDED
D2 5.0. EXHAUST FAN SHOULD BE PROVIDED IN TOILETS AT SUITABLE LOCATIONS.
6.0. ALL MATERIALS USED FOR CONSTRUCTION SHOULD BE FREE FROM SALINE NATURE
D 7.0. POTABLE WATER ONLY SHOULD BE USED FOR CONSTRUCTION INCLUDING CURING
CABLE DUCT

COLUMN
W/V W/V W/V W/V 500x500 8.0. FOR PLINTH BEAM AND GRADE BEAM DETAILS REFER RESPECTIVE DRAWING DETAILS ONLY
UP 9.0. FOR SUPER STRUCTURE AND STAIRCASE REFER APPROVED R.C.C DETAILS
3300 3300 3300 3100 3300 3300 3300 3100 10.0.R.C.C ROOF MAY BE PROVIDED FOR HEAD ROOM.
11.0. EXCAVATED EARTH WITH EXPANSIVE NATURE SHALL NOT BE USED FOR REFILLING PURPOSE.
3500

3500

3500

3500
W/V

W/V

12.0.BRICK MASONRY WORK SHALL BE CONSTRUCTED WITH FLY ASH BRICKS (OR) FLY ASH CONTENT BRICKS (OR)
18060

18060

FAL-G BRICKS
13.0 CABLE TRENCHES MAY BE PROVIDED TO 5M TO THE SITE CONDITIONS.
14.0.ALL THE ELECTRICAL FIXTURES AND FITTINGS SHOULD BE OF ENERGY SAVING EQUIPMENTS. INSTRUCTION
ISSUED IN THE CIRCULAR MEMO.NO.CE/CD/SE/DEI/E1/A1/DM-II/D.523/D3.DT..
15.0. PLEASE DO NOT MEASURE THE DRAWINGS, ADOPT THE DIMENSIONS AS INDICATED .
C 16.0.ALL DIMENSIONS ARE IN MILLIMETER UNLESS OTHERWISE SPECIFIED.
3500

3500

3500

3500
RS
W/V

COLUMN

B D1
APPROVED
230

DN

STAIRCASE STAIRCASE
4060

4060

4060

4060

TOILET
V

SE/CD CE/MTS & GTS


UP

A VERIFIED CHECKED DRG.NO.


V
1750 5250 900 TAMIL NADU GENERATION AND CE/MTS
1750 5250 1200 7000 & GTS/-
DISTRIBUTION CORPORATION LTD
7000
X

EE/C/DN-1 A2
GROUND FLOOR PLAN TERRACE FLOOR PLAN CONSTRUCTION OF CONTROL ROOM DATE
SCALE1:100 PASSED BUILDING FOR 33/11 KV SS AT
SCALE1:100 KOVILAMBAKKAM (TNSCB)

Scale
GENERAL ARRANGEMENT DRAWING
1:100
E1