1.1. REFERENCE:
i) LR.NO: CE/D/CSR/EEC/AE/F.kovilambakkam/D.149/22,dt-19.05.2022
HEAD ROOM BEAM HEAD ROOM
ii) LR.NO: SE/CEDC/S-II/AEE/CIVIL/F.kovilambakkam SS/D.68/22,dt-13.05.2022
(230/300x400/500) SLAB
230 2.0. DESIGN DATA:
2400
(iii) DEPTH OF FOUNDATION = 2.0m from the Natural Ground level
2.2.LIVE LOAD ON FLOOR SLAB = 4KN/m²
ROOF SLAB 150 mm THK
GF ROOF LEVEL ROOF BEAM 2.3.LIVE LOAD ON TOILET SLAB = 2KN/m²
(+)6550mm (230/300x500) 2.4.LIVE LOAD ON ROOF SLAB (ACCESSIBLE) = 1.5KN/m²
COLUMN 2.5.LIVE LOAD ON STAIRCASE = 5KN/m²
3.0.DIRECTIVES:
CONTINUOUS HAND RAIL 3.1.FOUNDATION : R.C.C ISOLATED FOOTING IN M25 GRADE USING 12 TO 20mm
LINTEL BEAM B.G METAL OVER P.C.C (1:2:4) USING 12mm to 20mm B.G METAL
(230x150) 3.2. MIX: ALL R.C.C MEMBERS ARE OF M25 GRADE USING 12T020 mm B.G METAL (I.S.456-2000)
8950
3.3. WALLS: (i) MAIN WALLS: BRICK MASONRY IN C.M 1:6, 230mm THICK USING COUNTRY BRICKS
4350
HAVING CRUSHING STRENGTH NOT LESS THAN 7N/mm²
SUNSHADE 600 (ii)PARTITION WALLS: BRICK WORK IN C.M 1:4, 115mm THICK.
3.4. FLOORING: (i) GROUND FLOOR: P.C.C M15, 100mm THICK USING 20mm HBC METAL
PLINTH BEAM AND FINISHED WITH GLAZED TILE SIZE300X300X6mm FINISHED WITH C.M 1:3,20mm
Plinth Beam FLOOR (230x400) THICK TOILET FLOORING NON-SLIPPERY GLAZED/NON GLAZED/NON GLAZED
FLOOR
PLINTH LEVEL FINISHING CONCRETE (ii) BATTERY ROOM : ACID PROOF FLOORING AND ACID PROOF PAINTING.
(+)2500mm (iii) CONTROL ROOM:VITRIFIED 1:3 20mm THK IN GROUND FLOOR AND OVER R.C.C SLAB
BRICK WORK SIDE DADOOING WITH VITRIFIED TILES TO A HEIGHT OF 2.0m OVER C.M 1:3,
IN SUPER 12mm THK AND JOINTS SHALL BE FINISHED WITH WHITE CEMENT NEATLY
2200
STRUCTURE 3.5. PLASTERING: (i) 230mm WALLS: C.M. 1:5, 12mm THICK , 115mm WALL: CM 1:4 12mm THK
(ii)CEILING : C.M. 1:3, 12 mm THICK
3.6. LINTELS,LOFT AND : R.C.C M25 MIX, USING 12 TO 20mm B.G METAL, LINTEL WITH SUN SHADE 600mm
ROAD LEVEL CUP -BOARD SLAB PROJECTION
(+)0.0mm 3.7. ROOFING: R.C.C, M25 MIX150mm THICK, USING 20mm DOWN GRADED B.G METAL PROVIDED WITH
Grade Beam
750
(-)0.75m NECESSARY WATER LINE SANITARY ARRANGEMENTS AND ELECTRICAL FITTINGS
FRONT ELEVATION EXT. G.L
(-)0.75m
AS PER STANDARD SPECIFICATION.
WEATHERING COARSE CONSISTING OF ONE COURSE OF PRESSED TILES EMBEDDED IN
SCALE1:100 CABLE C.M 1:3
DUCT MIXED WITH CRUDE OIL OVER A BED OF BRICK JELLY CONCRETE IN LIME OF 80mm
SAND FILLING
THICK AND SLOPE 1:60
P.C.C 100 mm THK
FOR FOUNDATION DETAILS 3.8. WHITE AND COLOUR WASHING: INSIDE WHITE WASHED WITH TWO COATS OF DISTEMPER .
SAND FILLING 100 mm THK
REFER SEPARATE DRAWING OUTSIDE COLOR WASHED WITH TWO COATS OF CEMENT PAINT OVER A PRIMARY COAT OF WHITE
GRADE BEAM (230/300x400)
CEMENT.
18060 3.9. PAINTING: ALL EXPOSED FACES OF WOOD/STEEL PAINTED WITH TWO COATS OF APPROVED
PAINT OVER A PRIMARY COAT. WOOD WORK IN CONTACT WITH MASONRY WORK PAINTED WITH TWO
SECTION X-X COATS OF SOLING BEFORE USE
SCALE1:100 3.10.DOORS & WINDOWS:
3500
W/V
(iv) USE SUITABLE FLY ASH BRICKS IN PLACE OF CONVENTION BRICKS.
W/V
BATTERY
3500
3500
ROOM
BEAM SPECIAL NOTE:
COLUMN 1.0. REINFORCEMENT: ALL REINFORCEMENT SHALL BE OF HYSD BARS HAVING CHARACTERISTIC STRENGTH
D2 300x300 OF 415N/mm2 CONFORMING TO I.S. 1786 - 1985
7000
7000
2.0. CEMENT: HIGH STRENGTH ORDINARY PORTLAND CEMENT CONFORMING TO I.S 8112 OF 43
E GRADE.
CONTROL ROOM BUILDING FOR 3311 KV SS AT KOVILAMBAKKAM (i). MINIMUM CEMENT CONTENT AND MAXIMUM WATER CEMENT RATIO SHOULD BE ADOPTED
AS PER TABLE 5 & 6 OF I.S. 456 -2000
SL
(ii)THE MINIMUM FREQUENCY OF SAMPLING OF CONCRETE OF EACH GRADE
O
PE
SHOULD BE IN ACCORDANCE WITH CLAUSE 15-2-2 OF I.S. 456-2000.
3500
3500
3500
3500
W/V
W/V
1
3.0 AS THE PROPOSED BUILDING IS CONSTRUCTED UPTO F.F, IT MAY BE ENSURED THAT WATER IS NOT
IN
STORE ROOM
80
STAGNATED IN THE SUNKEN PORTION OF SLAB.
4.0 DOWEL RODS FOR COLUMN OVER GROUND FLOOR (GF) SHOULD BE PROVIDED
D2 5.0. EXHAUST FAN SHOULD BE PROVIDED IN TOILETS AT SUITABLE LOCATIONS.
6.0. ALL MATERIALS USED FOR CONSTRUCTION SHOULD BE FREE FROM SALINE NATURE
D 7.0. POTABLE WATER ONLY SHOULD BE USED FOR CONSTRUCTION INCLUDING CURING
CABLE DUCT
COLUMN
W/V W/V W/V W/V 500x500 8.0. FOR PLINTH BEAM AND GRADE BEAM DETAILS REFER RESPECTIVE DRAWING DETAILS ONLY
UP 9.0. FOR SUPER STRUCTURE AND STAIRCASE REFER APPROVED R.C.C DETAILS
3300 3300 3300 3100 3300 3300 3300 3100 10.0.R.C.C ROOF MAY BE PROVIDED FOR HEAD ROOM.
11.0. EXCAVATED EARTH WITH EXPANSIVE NATURE SHALL NOT BE USED FOR REFILLING PURPOSE.
3500
3500
3500
3500
W/V
W/V
12.0.BRICK MASONRY WORK SHALL BE CONSTRUCTED WITH FLY ASH BRICKS (OR) FLY ASH CONTENT BRICKS (OR)
18060
18060
FAL-G BRICKS
13.0 CABLE TRENCHES MAY BE PROVIDED TO 5M TO THE SITE CONDITIONS.
14.0.ALL THE ELECTRICAL FIXTURES AND FITTINGS SHOULD BE OF ENERGY SAVING EQUIPMENTS. INSTRUCTION
ISSUED IN THE CIRCULAR MEMO.NO.CE/CD/SE/DEI/E1/A1/DM-II/D.523/D3.DT..
15.0. PLEASE DO NOT MEASURE THE DRAWINGS, ADOPT THE DIMENSIONS AS INDICATED .
C 16.0.ALL DIMENSIONS ARE IN MILLIMETER UNLESS OTHERWISE SPECIFIED.
3500
3500
3500
3500
RS
W/V
COLUMN
B D1
APPROVED
230
DN
STAIRCASE STAIRCASE
4060
4060
4060
4060
TOILET
V
EE/C/DN-1 A2
GROUND FLOOR PLAN TERRACE FLOOR PLAN CONSTRUCTION OF CONTROL ROOM DATE
SCALE1:100 PASSED BUILDING FOR 33/11 KV SS AT
SCALE1:100 KOVILAMBAKKAM (TNSCB)
Scale
GENERAL ARRANGEMENT DRAWING
1:100
E1