NOTES:

1.1. REFERENCE:
i) LR.NO: SE/CDC/TANGEDCO/AEE/T/HD/F.KURINJI NAGAR SS/D.1145/22,dt-20.07.2022

2.0. DESIGN DATA:

2.1.TYPE OF FOUNDATION: (i) INDIVIDUAL COLUMN FOOTING (ISOLATED FOUNDATION)


(ii) SAFE BEARING CAPACITY OF SOIL 20t/m²
(iii) DEPTH OF FOUNDATION = 2.0m from the Natural Ground level
2.2.LIVE LOAD ON FLOOR SLAB = 4KN/m²
2.3.LIVE LOAD ON TOILET SLAB = 2KN/m²
2.4.LIVE LOAD ON ROOF SLAB (ACCESSIBLE) = 1.5KN/m²
2.5.LIVE LOAD ON STAIRCASE = 5KN/m²
3.0.DIRECTIVES:
3.1.FOUNDATION : R.C.C ISOLATED FOOTING IN M25 GRADE USING 12 TO 20mm
B.G METAL OVER P.C.C (1:2:4) USING 12mm to 20mm B.G METAL
3.2. MIX: ALL R.C.C MEMBERS ARE OF M25 GRADE USING 12T020 mm B.G METAL (I.S.456-2000)
3.3. WALLS: (i) MAIN WALLS: BRICK MASONRY IN C.M 1:6, 230mm THICK USING COUNTRY BRICKS
HAVING CRUSHING STRENGTH NOT LESS THAN 7N/mm²
(ii)PARTITION WALLS: BRICK WORK IN C.M 1:4, 115mm THICK.
3.4. FLOORING: (i) GROUND FLOOR: P.C.C M15, 100mm THICK USING 20mm HBC METAL
AND FINISHED WITH GLAZED TILE SIZE300X300X6mm FINISHED WITH C.M 1:3,20mm
THICK TOILET FLOORING NON-SLIPPERY GLAZED/NON GLAZED/NON GLAZED
(ii) BATTERY ROOM : ACID PROOF FLOORING AND ACID PROOF PAINTING.
(iii) CONTROL ROOM:VITRIFIED 1:3 20mm THK IN GROUND FLOOR AND OVER R.C.C SLAB
SIDE DADOOING WITH VITRIFIED TILES TO A HEIGHT OF 2.0m OVER C.M 1:3,
12mm THK AND JOINTS SHALL BE FINISHED WITH WHITE CEMENT NEATLY
3.5. PLASTERING: (i) 230mm WALLS: C.M. 1:5, 12mm THICK , 115mm WALL: CM 1:4 12mm THK
(ii)CEILING : C.M. 1:3, 12 mm THICK
3.6. LINTELS,LOFT AND : R.C.C M25 MIX, USING 12 TO 20mm B.G METAL, LINTEL WITH SUN SHADE 600mm
PARAPET WALL CUP -BOARD SLAB PROJECTION
LOFT ROOF SLAB 3.7. ROOFING: R.C.C, M25 MIX150mm THICK, USING 20mm DOWN GRADED B.G METAL PROVIDED WITH
ROOF BEAM 150 mm THK NECESSARY WATER LINE SANITARY ARRANGEMENTS AND ELECTRICAL FITTINGS
(230x500) AS PER STANDARD SPECIFICATION.
GF ROOF LEVEL WEATHERING COARSE CONSISTING OF ONE COURSE OF PRESSED TILES EMBEDDED IN
(+)6550mm C.M 1:3
COLUMN MIXED WITH CRUDE OIL OVER A BED OF BRICK JELLY CONCRETE IN LIME OF 80mm
BRICK WORK THICK AND SLOPE 1:60
CONTINUOUS IN SUPER 230 ROOF BEAM 3.8. WHITE AND COLOUR WASHING: INSIDE WHITE WASHED WITH TWO COATS OF DISTEMPER .
LINTEL BEAM STRUCTURE (300x750) OUTSIDE COLOR WASHED WITH TWO COATS OF CEMENT PAINT OVER A PRIMARY COAT OF WHITE
(230x150) CEMENT.

4350
3.9. PAINTING: ALL EXPOSED FACES OF WOOD/STEEL PAINTED WITH TWO COATS OF APPROVED
PAINT OVER A PRIMARY COAT. WOOD WORK IN CONTACT WITH MASONRY WORK PAINTED WITH TWO
600 COATS OF SOLING BEFORE USE
SUNSHADE
3.10.DOORS & WINDOWS:
Plinth Beam
PLINTH BEAM FLOOR FLOOR D1 - DOOR = 900 X 2100
PLINTH LEVEL CONCRETE FINISHING D2 - P.V.C FRAMED WITH P.V.C SHUTTERS = 750 X 2100
(230x400/450)
(+)2400mm W - WINDOW ANODIZED ALU. GLAZED WINDOW WITH GRILL = 1180 X 1480
V - ANODIZED ALU. GLAZED VENTILATOR = 1180 X 580
3.11. RAIN WATER PIPE: 100mm DIA P.V.C. DOWN FALL PIPE TO BE PROVIDED SUITABLY TO DRAIN RAIN

2400
Grade Beam WATER FROM ROOF AS PER REQUIREMENT TO THE NBC 2016
(+)0.45m 3.12. STAIRCASE : STEPS RISE - 160mm, TREAD - 250mm, USING BRICK WORK IN C.M. 1:4 ,PLASTERED
WITH CM 1:3. WAIST SLAB OF 200mm THK USING MIX M25 AND HAND RAIL SIMPLE GRILL WORK
ROAD LEVEL 3.13. WATER TANK: P.V.C WATER TANK OF 2000 LTS CAPACITY MAY BE PROVIDED ABOVE THE HEAD ROOM
(+)0.0m 3.14. GENERAL:
EXT. G.L GRADE BEAM (i) FOUNDATION IS DESIGNED FOR (G+1) FLOOR ONLY
(+)0.0m (ii) ANTI TERMITE TREATMENT TO BE GIVEN FOR BUILDING FOUNDATION AS PER I.S 6313 PART(II)
22000 22000
(300x600)
SAND FILLING (ii) SALIENT FEATURES OF BUILDING LIKE YEAR OF CONSTRUCTION, NO OF FLOORS
P.C.C 100 mm THK DESIGNED AND LOAD ASSUMED Etc TO BE DISPLAYED IN A PROMINENT PLACE INSIDE
FOR FOUNDATION DETAILS
ELEVATION SAND FILLING 100 mm THK
REFER SEPARATE DRAWING
THE BUILDING FOR FUTURE REFERENCE.
(iv) USE SUITABLE FLY ASH BRICKS IN PLACE OF CONVENTION BRICKS.
SCALE1:100 GRADE BEAM (230x350)
SECTION X-X SPECIAL NOTE:
SCALE1:100 1.0. REINFORCEMENT: ALL REINFORCEMENT SHALL BE OF HYSD BARS HAVING CHARACTERISTIC STRENGTH
OF 415N/mm2 CONFORMING TO I.S. 1786 - 1985
2.0. CEMENT: HIGH STRENGTH ORDINARY PORTLAND CEMENT CONFORMING TO I.S 8112 OF 43
GRADE.
(i). MINIMUM CEMENT CONTENT AND MAXIMUM WATER CEMENT RATIO SHOULD BE ADOPTED
AS PER TABLE 5 & 6 OF I.S. 456 -2000
(ii)THE MINIMUM FREQUENCY OF SAMPLING OF CONCRETE OF EACH GRADE
SHOULD BE IN ACCORDANCE WITH CLAUSE 15-2-2 OF I.S. 456-2000.
3.0 AS THE PROPOSED BUILDING IS CONSTRUCTED UPTO F.F, IT MAY BE ENSURED THAT WATER IS NOT
STAGNATED IN THE SUNKEN PORTION OF SLAB.
4.0 DOWEL RODS FOR COLUMN OVER GROUND FLOOR (GF) SHOULD BE PROVIDED
5.0. EXHAUST FAN SHOULD BE PROVIDED IN TOILETS AT SUITABLE LOCATIONS.
6.0. ALL MATERIALS USED FOR CONSTRUCTION SHOULD BE FREE FROM SALINE NATURE
7.0. POTABLE WATER ONLY SHOULD BE USED FOR CONSTRUCTION INCLUDING CURING
8.0. FOR PLINTH BEAM AND GRADE BEAM DETAILS REFER RESPECTIVE DRAWING DETAILS ONLY
9.0. FOR SUPER STRUCTURE AND STAIRCASE REFER APPROVED R.C.C DETAILS
10.0.R.C.C ROOF MAY BE PROVIDED FOR HEAD ROOM.
Y COLUMN RAIN WATER PIPE 100mm Ø 11.0. EXCAVATED EARTH WITH EXPANSIVE NATURE SHALL NOT BE USED FOR REFILLING PURPOSE.
1 2 3 4 5 6 7 400x500 12.0.BRICK MASONRY WORK SHALL BE CONSTRUCTED WITH FLY ASH BRICKS (OR) FLY ASH CONTENT BRICKS (OR)
FAL-G BRICKS
13.0 CABLE TRENCHES MAY BE PROVIDED TO 5M TO THE SITE CONDITIONS.
230 14.0.ALL THE ELECTRICAL FIXTURES AND FITTINGS SHOULD BE OF ENERGY SAVING EQUIPMENTS. INSTRUCTION
W/V W/V W/V W/V W/V
C ISSUED IN THE CIRCULAR MEMO.NO.CE/CD/SE/DEI/E1/A1/DM-II/D.523/D3.DT..
15.0. PLEASE DO NOT MEASURE THE DRAWINGS, ADOPT THE DIMENSIONS AS INDICATED .
D2 16.0.ALL DIMENSIONS ARE IN MILLIMETER UNLESS OTHERWISE SPECIFIED.
COLUMN
2750

GENTS V 300x450
BEAM TOILET
5500

5500

5500
SL
W/V

OP
STAIRCASE

STAIRCASE

E1
D2

IN
80
2750

LADIES V
CONTROL ROOM BUILDING FOR 33 TOILET
11 KV SS
11000

11000

COLUMN
B AT KURINJI NAGAR AT PERUNGALATHUR 300x450
2750

BATTERY
W/V

ROOM

SL
X X

OP
D1

E1
5500

5500

5500
IN
STAIRCASE

STAIRCASE

80
2750

FOC
W/V

COLUMN CG
RS
A D1
W/V W/V W/V W/V
STAIRCASE
STAIRCASE
3600 3600 3600 3600 3600 4000
22000
3600 3600 3600 3600 3600 4000 APPROVED
22000 TERRACE FLOOR PLAN
Y GROUND FLOOR PLAN SCALE1:100
SCALE1:100
SE/CD CE/MTS & GTS

VERIFIED CHECKED DRG.NO.


CE/MTS
TAMIL NADU GENERATION AND
& GTS/-
DISTRIBUTION CORPORATION LTD

EE/C/DN-1 A2
CONSTRUCTION OF CONTROL ROOM DATE
PASSED BUILDING FOR 33/11 KV INDOOR SS AT
KURINJI NAGAR AT PERUNGALATUR

Scale
GENERAL ARRANGEMENT DRAWING
1:100