Professional Documents
Culture Documents
217
Copyright 2015 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part. Due to electronic rights, some third party content may be suppressed from the eBook and/or eChapter(s).
Editorial review has deemed that any suppressed content does not materially affect the overall learning experience. Cengage Learning reserves the right to remove additional content at any time if subsequent rights restrictions require it.
218 Chapter 6 GFCI, AFCI, SPD, IDCI, and ALCI Protection
Copyright 2015 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part. Due to electronic rights, some third party content may be suppressed from the eBook and/or eChapter(s).
Editorial review has deemed that any suppressed content does not materially affect the overall learning experience. Cengage Learning reserves the right to remove additional content at any time if subsequent rights restrictions require it.
Chapter 6 GFCI, AFCI, SPD, IDCI, and ALCI Protection 219
Copyright 2015 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part. Due to electronic rights, some third party content may be suppressed from the eBook and/or eChapter(s).
Editorial review has deemed that any suppressed content does not materially affect the overall learning experience. Cengage Learning reserves the right to remove additional content at any time if subsequent rights restrictions require it.
220 Chapter 6 GFCI, AFCI, SPD, IDCI, and ALCI Protection
Grounded
conductor
Equipment
Replacing a receptacle
grounding “Hot”
where grounding conductor
means exists conductor
A B C
GRND GRND
RESET
Grounded
Old two-wire Grounding-type GFCI box
receptacle receptacle receptacle
Figure 6-20 If a wall box (E) is properly grounded by any of the methods specified in 250.118 or if
the branch-circuit wiring contains an equipment grounding conductor (D), an existing receptacle of the
type shown in (A) must be replaced with a grounding-type receptacle (B) or with a GFCI receptacle (C).
See 406.4(D)(1).
1. Any accessible point on the grounding elec- box is not grounded [Figure 6-21(E)] or where an
trode system equipment grounding conductor has not been run
2. Any accessible point on the grounding elec- with the circuit conductors [Figure 6-21(D)], four
trode conductor choices are possible for selecting the replacement
receptacle:
3. The equipment grounding terminal bar within
the enclosure where the branch circuit for the 1. The replacement receptacle may be a non-
receptacle originates grounding type [Figure 6-21(A)].
4. The grounded service conductor within the ser- 2. The replacement receptacle may be a GFCI
vice-equipment enclosure type [Figure 6-21(C)].
Note, however, that this permission is only for • The GFCI replacement receptacle must
existing installations. See Figure 6-21. be marked “No Equipment Ground,” as in
Be sure that the equipment grounding conductor Figure 6-22.
of the circuit is connected to the receptacle’s green
hexagon-shaped grounding terminal. • The green hexagonal grounding terminal
of the GFCI replacement receptacle does
Do not connect the white grounded circuit
not have to be connected to any grounding
conductor to the green hexagon-shaped grounding
means. It can be left “unconnected.” The
terminal of the receptacle.
GFCI’s trip mechanism will operate prop-
Do not connect the white grounded circuit con-
erly when ground faults occur anywhere
ductor to a metal box.
on the load side of the GFCI replacement
receptacle. Ground-fault protection is still
Replacing Existing Two-Wire there. Refer to Figure 6-6.
Receptacles Where Grounding
Means Does Not Exist • Do not connect an equipment grounding con-
ductor from the green hexagonal grounding
When replacing an existing 2-wire nonground- terminal of a replacement GFCI receptacle
ing-type receptacle [Figure 6-21(A)] where the (see Figure 6-22) to any other downstream
Copyright 2015 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part. Due to electronic rights, some third party content may be suppressed from the eBook and/or eChapter(s).
Editorial review has deemed that any suppressed content does not materially affect the overall learning experience. Cengage Learning reserves the right to remove additional content at any time if subsequent rights restrictions require it.
Chapter 6 GFCI, AFCI, SPD, IDCI, and ALCI Protection 221
Grounded
conductor
Replacing a receptacle No equipment
where grounding “Hot”
grounding conductor
means does not exist conductor run
with circuit D
conductors
A B C
GRND GRND
RESET
Nongrounded
Old 2-wire Grounding-type GFCI box
receptacle receptacle receptacle
Figure 6-21 If a box (E) is not grounded or if in an equipment grounding conductor has not been run
with the circuit conductors (D), an existing nongrounding-type receptacle (A) may be replaced with a
nongrounding-type receptacle (A), a GFCI-type receptacle (C), a grounding-type receptacle (B) if supplied
through a GFCI receptacle (C), or a grounding-type receptacle (B) if a separate equipment grounding
conductor is run from the receptacle to any of the locations permitted by 250.130(C). See Figure 6-23.
receptacles that are fed through the replace- • The green hexagonal equipment grounding
ment GFCI receptacle. terminal of the replacement grounding-type
The reason this is not permitted is that receptacle (Figure 6-21[B]) need not be con-
if at a later date someone saw the conductor nected to any grounding means. It may be left
connected to the green hexagonal grounding “unconnected.” The upstream feed-through
terminal of the downstream receptacle, there GFCI receptacle (Figure 6-21[C]) trip mech-
would be an immediate assumption that the anism will work properly when ground faults
other end of that conductor had been properly occur anywhere on its load side. Ground-fault
connected to an acceptable grounding point protection is still there. Refer to Figure 6-6.
of the electrical system. The fact is that the
• Do not connect an equipment grounding
so-called equipment grounding conductor had conductor from the green hexagonal ground-
been connected to the replacement GFCI re- ing terminal of a replacement GFCI recep-
ceptacle’s green hexagonal grounding termi- tacle (Figure 6-22) to any other downstream
nal that was not grounded in the first place. receptacles that are fed through the replace-
We now have a false sense of security, a real ment GFCI receptacle.
shock hazard. The far better choice from a
safety standpoint is to go to the time and ex- 4. The replacement receptacle may be a ground-
pense of installing the equipment grounding ing type (Figure 6-21[B]) if
conductor as permitted in 250.130(C). • an equipment grounding conductor, sized
per Table 250.122, is run from the replace-
3. The replacement receptacle may be a grounding
ment receptacle’s green hexagonal grounding
type (Figure 6-21[B]) if it is supplied through a
screw and properly connected to one of the
GFCI-type receptacle (Figure 6-21[C]).
four locations described earlier in this chapter.
• The replacement receptacle must be marked You are not permitted to make the equipment
“GFCI Protected” and “No Equipment ground connection to the interior metal water
Ground,” as in Figure 6-22. piping anywhere beyond the first 5 ft (1.5 m).
Copyright 2015 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part. Due to electronic rights, some third party content may be suppressed from the eBook and/or eChapter(s).
Editorial review has deemed that any suppressed content does not materially affect the overall learning experience. Cengage Learning reserves the right to remove additional content at any time if subsequent rights restrictions require it.
222 Chapter 6 GFCI, AFCI, SPD, IDCI, and ALCI Protection
No Equipment Ground
No Equipment Ground
GFCI Protected
TEST
RESET
Figure 6-22 Where a grounding means does not exist, there are certain marking requirements, as
presented in this diagram. Do not connect an equipment grounding conductor between these
receptacles; see 406.3(D)(2).
receptacle
Copyright 2015 Cengage Learning. All Rights Reserved. May not be copied, scanned, or duplicated, in whole or in part. Due to electronic rights, some third party content may be suppressed from the eBook and/or eChapter(s).
Editorial review has deemed that any suppressed content does not materially affect the overall learning experience. Cengage Learning reserves the right to remove additional content at any time if subsequent rights restrictions require it.