E2 Zero-crossingsignal error
E3 Indoor fan speed has been out of control
E5 Open or short circuit of outdoor temperature sensor or outdoor unit EEPROM
parameter error
Display Operation lamp flash times Timer lamp Failure CCI 2ªG
E0 1 X EEPROM error
E1 2 X Indoor and outdoor communication
error
E2 3 X Zero crossing detection error
E3 4 X Indoor fan speed has been out of
control
E4 5 X Indoor room temperature sensor T1
open
circuit or short circuit
E5 6 X Evaporator coil temperature sensor T2
open
circuit or short circuit
EC 7 X Refrigerant leak detection error
F1 2 O Outdoor temperature sensor T4 open
circuit or
short circuit
F2 3 O Condenser coil temperature sensor T3
open
circuit or short circuit
F3 4 O Compressor discharge temperature
sensor T5
open circuit or short circuit
F4 5 O Outdoor EEPROM parameter error
P0 1 ☆ IPM malfunction or IGBT over-strong
current
P1 2 ☆ Over voltage or too low voltage
protection
P2 3 ☆ Temperature protection of compressor
top(only for 24k models)
P4 5 ☆ Inverter compressor drive error
O(light)X(off)
☆(flash)
CSC9K-18K MD / B
Operation Timer
Failure phenomenon
lamp lamp
Indoor fan speed has been out of control for over 1 minute ☆ X
Indoor room temp. or evaporator sensor is open circuit or short circuit ☆ On
Over current protection of the compressor occurs 4 times X ☆
EEROM error On ☆
No over-zero signal ☆ ☆
Extinguish ☆ Flash at 5Hz
CSC24K-30K-MD / B
Operation Timer Defrosting Auto
Failure phenomenon
lamp lamp lamp lamp
Over current protection of the compressor occurs 4 times ☆ ☆ ☆ ☆
Indoor room temp. sensor is open circuit or short circuit X ☆ X X
Temp. sensor on indoor evaporator is open circuit or short
☆ X X X
circuit
Temp. sensor on outdoor condenser is open circuit or short
X X ☆ X
circuit (without cooling only models)
Outdoor unit protects(outdoor compressor current, phase
X X ☆ ☆
order etc)
EEROM error X ☆ X ☆
Indoor unit communication error X X X ☆
Extinguish ☆ Flash at 5Hz
BAR-2
Comprobación de sensores
➢ chequeo de sensor de temperatura
Desconecte el sensor de temperatura desde la placa electrónica, mida el valor de resistencia con un multimetro.
Sensores de temperatura
➢ Sensor de temperatura ambiente interno, (T1).
➢ Sensor de temperatura evaporador. (T2).
➢ Sensor de temperatura condensador, T3).
➢ Sensor de temperatura ambiente externo, (T4).
➢ Sensor de temperatura descarga de compresor (T5).
Mida la resistencia de cada alambrado en cada uno de los sensores hacienda uso de multi metro
Tabla 1: use la siguiente tabla para los sensores: T1, T2, T3 y T4.
Temperatura (°C) 5 10 15 20 25 30 40 50 60
Valor de Resistencia (KΩ) 26.9 20.7 16.1 12.6 10 8 5.2 3.5 2.4
T5
Operation Timer
Display +Error Information
Lamp Lamp
1 time OFF E0 Indoor unit EEPROM parameter error
2 times OFF E1 Indoor / outdoor unit communication error
3 times OFF E2 Zero-crossing signal detection error(for some models)
4 times OFF E3 The indoor fan speed is operating outside of the normal range
5 times OFF E4 Indoor room temperature sensor T1 is in open circuit or has shortcircuit
Evaporator coil temperature sensor T2 is in open circuit or has short
6 times OFF E5 circuited
9 times OFF E7 Indoor PCB / Display board communication error
7 times OFF EC Refrigerant leak detected
1 times ON F0 Current overload protection
Outdoor room temperature sensor T4 is in open circuit or has short
2 times ON F1 circuited
Condenser coil temperature sensor T3 is in open circuit or has short
3 times ON F2 circuited
Compressor discharge temperature sensor TP is in open circuit or has
4 times ON F3 short circuited
5 times ON F4 Outdoor unit EEPROM parameter error
The outdoor fan speed is operating outside of the normal range(for
6 times ON F5 some models)
1 times FLASH P0 IPM malfunction or IGBT over-strong current protection
2 times FLASH P1 Over voltage or over low voltage protection
3 times FLASH P2 High temperature protection of IPM module
5 times FLASH P4 Inverter compressor drive error