Professional Documents
Culture Documents
This trip circuit supervision scheme is also quite simple. The only difference is
that here in this scheme, one NC contact of same auxiliary switch is connected
across the auxiliary NO contact of the trip circuit. The auxiliary NO contact is
closed when CB is closed and auxiliary NC contact is closed when CB is open and
vice versa. Hence, as shown in the figure below when the circuit breaker is closed
the trip circuit supervision network is completed via auxiliary NO contact but when
the circuit breaker is open the same supervision network is completed via NC
contact. The resistor is used series with the lamp for preventing unwanted tripping
of circuit breaker due to internal short circuit caused by failure of the lamp.
Trip Circuit Supervision
So far whatever we have discussed it is only for locally controlled installation
but for a distance control installation, relay system is necessary. The figure
below shows the trip circuit supervision scheme wherever a remote signal is
required.
Trip Circuit Supervision
When trip circuit is healthy and circuit breaker is closed, relay A is energized
which closes the NO contact A1 and hence relay C is energized. Energized relay C
keeps NC contact in open position. Now if the circuit breaker is open, relay B is
energized which closes No contact B1 hence relay C is energized. As C is energized,
it keeps the NC contact C1 in open position. While CB is closed, if there is any
discontinuity in the trip circuit relay A is de-energized which opens contact A1
and consequently relay C is de-energized and which make the NC contact C1 in close
position and hence alarm circuit is actuated. Trip circuit supervision is
experienced by relay B with the circuit breaker is open in a similar manner as
relay A with the circuit breaker is closed. Relays A and C are time-delayed by
copper slugs to prevent spurious alarms during tripping or closing operations. The
resistors are mounted separately from the relays and their values are chosen such
that if any one component is inadvertently short-circuited, a tripping operation
will not take place.
The alarm circuit supply should be separated from main trip supply so that the
alarm can be actuated even the trip supply failed.