Professional Documents
Culture Documents
Purpose
Introduction
Cummins Confidential
Figure 1 - PSMS Location in CIB
Discussion
The PSMS circuit board main fuses are rated at 15 amps and are labeled as F1
& F2 on the circuit board. The root cause of the main fuse tripping behavior is
due to a circuit within the PSMS circuit board. The circuit creating the issue is in
place to protect CIB components from an over-voltage condition.
There have been two versions of the PSMS circuit board released into
production. Both versions have an over-voltage protection circuit, which is the
culprit in tripping the main fuses. These circuit boards can be identified by part
number 4927265 or 4978808. They may also be visually compared to those
shown Figures 2 & 3 below.
Page 2 of 5
The recommended temporary corrective action is to disable the over-voltage
protection circuit within the PSMS module. Please follow the procedure below to
perform the repair.
Procedure:
• Disconnect power from panel
• Verify power is off by testing for voltage at terminals 300 through
303 with a volt meter
o Tips
Removal of module main fuses F1 & F2 is not
recommended due to exposed terminals and the
potential for shorting
The module may also be removed from the panel to
ease modification, but be sure to mark wire
termination locations before removal to simplify
reinstallation
• Cut the diodes labeled D1 & D2 (see circled items in Figure 1).The
diodes are black cylindrical components marked with a silver band
at one end. Trim as close to the circuit board as possible. Take
care not to damage any other nearby components. A small pair of
side cut pliers is recommended.
• Remove the diode completely, to prevent shorting or re-insertion
into the circuit.
• Modification is now complete. Reinstall any removed wires and
apply power as normal.
Page 3 of 5
Figure 2 – PSMS Circuit Board (P/N 4927265)
Conclusion
Page 4 of 5
Change Log
Revising Author’s
Date Change Page
Name
3/12/2009 MSA Created All Jay McKinney
Distribution of this document is intended for Cummins personnel and distributors. The information contained in this
document is only considered valid while published on the Marine Website. Copies and archived documents are not
considered current.
Page 5 of 5