You are on page 1of 8

THIS STANDARD IS: STD NO : 57-75-01

Updated INDEX : 1.9


DESIGN STANDARD DATE : 9 JULY 2003
OWNER : MEDS
PAGE : 1 OF 8

SUBJECT : DESIGN RULES FOR SUPERHEATER AND REHEATER TERMINALS, LINK


PIPING, DOWNCOMERS AND HANGERS FOR CONTROLLED AND NATURAL
CIRCULATION UNITS

PURPOSE : To advise Design Graphics of various temperatures and temperature


differences for use in determining allowable stresses, expansion stresses
and expansion movements of various components.

REMARKS: This Standard to be effective immediately.

NOTES: 1. This standard is being issued for historical purposes only.

SR. ENGINEERING TECHNICIAN


PREPARED BY: S. GARCIA STANDARDS ENGINEERING - 9809
PROGRAM MANAGER
APPROVED FOR CONTENT: T. MISKELL STANDARDS ENGINEERING - 9809
PROGRAM MANAGER
APPROVED FOR PUBLICATION: T. MISKELL STANDARDS ENGINEERING - 9809

This document contains proprietary data and shall not be reproduced


or disclosed without the permission of ALSTOM Power Inc.
SUBJECT: Design Rules for Superheater and STD NO. : 57-75-01
Reheater Terminals, Link Piping, INDEX : 1.9
Downcomers and Hangers for DATE : 9 JULY 2003
Controlled and Natural Circulation Units OWNER : MEDS
PAGE : 2 OF 8
______________________________________________________________________________________________________

UNITS: n ENGLISH; o METRIC; o BOTH; o NONE

PRODUCT LINE: CHECK THE PRODUCT LINE THE STANDARD IS APPLICABLE TO:

o ALL; n A = CONTROLLED CIRC. BOILERS o H = HEAT RECOVERY STEAM GENERATORS


o B = SUPERCRITICAL BOILERS o P = BOWL MILLS (PULVERIZERS)
o C = VU40 AND VU60 BOILERS o R = CHEMICAL RECOVERY BOILERS
o E = FLUIDIZED BED BOILERS (CFB) n S = SERVICES (AFTER MARKET USE)
n F = NATURAL CIRC. BOILERS (UTILITY)

Versions

Ver. 0 - Issued for historical purposes only.

Ver. 1 - Updated standard format; name change


to ALSTOM Power Inc.
SUBJECT: Design Rules for Superheater and STD NO. : 57-75-01
Reheater Terminals, Link Piping, INDEX : 1.9
Downcomers and Hangers for DATE : 9 JULY 2003
Controlled and Natural Circulation Units OWNER : MEDS
PAGE : 3 OF 8
______________________________________________________________________________________________________

1.0 Temperatures for Analysis of c. Hot Startup


Headers, Links and Terminals Above
the Roof Same as full load operation.

1.1 Hanger Rods in Roof Enclosure 1.2.2 For design criteria of drum
hanger roads, see Standard No. 18-65, Index
1.1.1 Temperature for expansion and 2.6.2.
flexibility analysis.
1.3 Division Panel Inlet and Outlet
a. Cold Startup Headers

While raising pressure use 1.3.1 Temperature for expansion and


100o F below steam-cooled roof temperature. At flexibility analysis.
10% load use 100o F above steam-cooled roof
temperature. Steam-cooled roof temperatures a. Cold Startup (before any flow)
are given in Paragraph 2.1.1.
Use 500o F for the division panel
b. Full Load Operation inlet and outlet header temperature and 700o F
for the steam-cooled roof temperature.
Same as division panel outlet
temperature. If not division panel, use steam- b. Full Load Operation
cooled roof temperature +100o F.
Refer to the Predicted
c. Hot Startup Performance Sheet of the Superheater, Reheater
and Economizer Section of the Design
Same as full load operation. Performance Letter.

1.2 Drum Hangers 1.3.2 Temperature for establishing


allowable stresses.
1.2.1 Temperatures for expansion and
flexibility analysis. Use the design temperature
taken from the sheets titled "Headers, Piping and
a. Cold Startup Miscellaneous Data" of the Superheater, Reheater
and Economizer Section of the Design
Rods up to 4" in diameter will lag Performance Letter.
enclosure temperature by 50o F. Rods over 4" in
diameter will lag enclosure temperature by 1.4 Superheater Outlet Header
100o F.
1.4.1 Temperatures for expansion and
b. Full Load Operation flexibility analysis.

When outside of roof housing, a. One consideration in the design


use drum saturated steam temperature up to top of the terminals should be to design the terminals
of drum and room temperature (assume 100o F) for the sum of the maximum expansion difference
above top of drum. When inside of roof housing, between the end of the terminal at the header
use drum saturated steam temperature. and the anchor of the terminal, during startup
and full load operation.
SUBJECT: Design Rules for Superheater and STD NO. : 57-75-01
Reheater Terminals, Link Piping, INDEX : 1.9
Downcomers and Hangers for DATE : 9 JULY 2003
Controlled and Natural Circulation Units OWNER : MEDS
PAGE : 4 OF 8
______________________________________________________________________________________________________

b. Superheater outlet header During startup, use a ∆ T


temperatures (header located in doghouse). between superheater outlet header and water
wall of 250o F. This assumes the superheater
Use 300o F for the header outlet header at 170o F and the water wall at
temperature during start up. 420o F.

For full load operation, refer to For full load operation, use the
the Predicted Performance Sheet of the design temperature taken from the sheets titled
Superheater, Reheater and Economizer Sections "Headers, Piping and Miscellaneous Data" of the
of the Design Performance Letter. Boiler Circulation System Section and the
Superheater, Reheater and Economizer Section of
c. Peg fin steam-cooled roof the Design Performance letter.
construction (superheater outlet header in
doghouse). 1.4.2 Temperatures for establishing
allowable stresses.
Side-to-side and front-to-rear
anchor movement is governed by the water wall These temperatures are to be the
temperature. The water wall temperatures are as design temperatures taken from the sheets titled
follows: "Headers, Piping and Miscellaneous Data" of the
Superheater, Reheater and Economizer Section of
At startup (with flow), use 500o F. the Design Performance Letter.

For full load operation, use the 1.5 Reheater Outlet Headers
design temperature taken from the sheets titled
"Headers, Piping and Miscellaneous Data" of the 1.5.1 Temperature for expansion and
Boiler Circulation System Section in the Design flexibility analysis.
Performance Letter.
a. One consideration in the design
d. Fin welded roof construction of the terminals should be to design the terminals
(superheater outlet header in doghouse). for the sum of the maximum expansion difference
between the end of the terminal at the header
Side-to-side and front-to-rear and the anchor of the terminal, during startup
anchor movement is governed by the roof and full load operation.
temperature. Refer to Paragraph 2.0 for the
temperatures of the steam-cooled roof at various b. Temperature for reheater outlet
loads. header located in doghouse.

e. Superheater outlet header in Use 325o F for the reheater


front enclosure. outlet header temperature during startup.

Anchor movement is governed For full load operation, refer to


by water wall temperatures. the Predicted Performance Sheet of the
Superheater, Reheater and Economizer Section of
the Design Performance Letter.
SUBJECT: Design Rules for Superheater and STD NO. : 57-75-01
Reheater Terminals, Link Piping, INDEX : 1.9
Downcomers and Hangers for DATE : 9 JULY 2003
Controlled and Natural Circulation Units OWNER : MEDS
PAGE : 5 OF 8
______________________________________________________________________________________________________

c. Peg fin steam-cooled roof These temperatures are to be the


construction (reheater outlet header in doghouse). design temperatures taken from the sheets titled
"Header, Piping and Miscellaneous Data" of the
Side- to-side and front-to-rear Superheater, Reheater and Economizer Section in
anchor movement is governed by the water wall the Design Performance Letter.
temperature. The water wall temperatures are as
follows: 1.6 All intermediate headers and link
piping (including divisional panel
At startup (with flow), use 500o F. links).

For full load operation, use the 1.6.1 Temperature for expansion and
design temperature taken from the sheets titled flexibility analysis.
"Header, Piping and Miscellaneous Data" of the
Boiler Circulation System Section in the Design a. One consideration in the design
Performance Letter. of the terminals should be to design the terminals
for the sum of the maximum expansion difference
d. Fin welded roof construction between the end of the terminal at the header
(reheater outlet header in doghouse). and the anchor of the terminal during startup and
full load operation.
Side-to-side and front-to-rear
anchor movement is governed by the roof b. Intermediate headers and link
temperature. Refer to Paragraph 2.0 for the piping temperatures.
temperatures of the steam-cooled roof at various
loads. For cold startup (before any
flow), use 100o F below the water wall
e. Reheater outlet header in front temperature. The water wall temperature is
enclosure. 300o F.

Anchor movement is governed For full load operation, refer to


by water wall temperatures. the Predicted Performance Sheet of the
Superheater, Reheater and Economizer Section of
During startup, use a ∆ t between the Design Performance Letter.
reheater outlet header and water wall of 300o F.
This assumes the reheater outlet header at 120o F c. Peg fin steam-cooled roof
and the water wall at 420o F. construction (headers in doghouse).

For full load, use the design Side-to-side and front-to-rear


temperature taken from the sheets titled anchor movement is governed by the water wall
"Headers, Piping and Miscellaneous Data" of the temperature. The water wall temperatures are as
Boiler Circulation System Section and the follows:
Superheater, Reheater and Economizer Section in
the Design Performance Letter. At startup (before flow), use
300o F.
1.5.2 Temperatures for establishing
allowable stresses.
SUBJECT: Design Rules for Superheater and STD NO. : 57-75-01
Reheater Terminals, Link Piping, INDEX : 1.9
Downcomers and Hangers for DATE : 9 JULY 2003
Controlled and Natural Circulation Units OWNER : MEDS
PAGE : 6 OF 8
______________________________________________________________________________________________________

For full load, use the design a. Cold Startup


temperature taken from the sheets titled
"Headers, Piping and Miscellaneous Data" of the Use 475o F for the steam-cooled
Boiler Circulation System Section in the Design wall temperature and 225o F for the feed water
Performance Letter. inlet temperature.

d. Fin welded roof construction b. Partial Load Operation


(headers in doghouse).
Use 675o F for the steam-cooled
Side-to-side and front-to-rear wall temperature and 300o F for the economizer
anchor movement is governed by the roof outlet temperature. (With the high pressure feed
temperature. Refer to Paragraph 2.0 for the water heater out of service, this 300o F
temperatures of the steam-cooled roof at various temperature could be attained with a 225o F feed
loads. water inlet temperature).

e. Headers in front enclosure. c. Full Load Operation

Anchor movement is governed Use 700o F for the steam-cooled


by water wall temperatures. wall temperature and 425o F for the economizer
outlet temperature. (With the feed water heaters
At startup (before any flow) use out of service, this 425o F temperature could be
200o F for the header and 450o F for the front attained.)
water wall temperature.
2.0 Temperature for Analysis of Steam-
At start of turbine (with flow), use Cooled Roof
275o F for the reheater inlet header temperature
and 500o F for the front water wall temperature. 2.1 Temperature for expansion and
flexibility analysis.
For full load operation, refer to
the Predicted Performance Sheet of the 2.1.1 At startup (before any flow), the
Superheater, Reheater and Economizer Section of design temperatures to be used at various
the Design Performance Letter. sections of the roof are:

1.6.2 Temperatures for establishing a. Roof section in front of platen


allowable stresses. assembly - 700o F.

These temperatures are to be the b. Roof section between front of


design temperatures taken from the sheets titled platen assembly and the water wall rear hanger
"Headers, Piping and Miscellaneous Data" of the tubes - 600o F.
Superheater, Reheater and Economizer Section of
the Design Performance Letter. c. Roof section between water wall
rear hanger tubes and back pass steam-cooled
1.7 Economizer wall hanger tubes - 500o F.

1.7.1 Temperature for expansion and 2.1.2 At startup (with flow, the roof will
flexibility analysis. be 60o F above water wall temperature. The
water wall temperature at this time is 500o F.
SUBJECT: Design Rules for Superheater and STD NO. : 57-75-01
Reheater Terminals, Link Piping, INDEX : 1.9
Downcomers and Hangers for DATE : 9 JULY 2003
Controlled and Natural Circulation Units OWNER : MEDS
PAGE : 7 OF 8
______________________________________________________________________________________________________

2.1.3 For full load operation, the roof 4.1 Temperature for expansion and
temperature will be the same as first inlet header flexibility analysis.
temperature after drum (saturation temperature).
4.1.1 At startup (before any flow), the
2.2 Temperature for establishing temperature of the front water wall tubes will rise
allowable stresses from 100o F to 500o, while the radiant reheat
tubes will rise from 500o F to 700o F. The design
2.2.1 The same as full load operation temperature differential to be used at startup is
temperature (Paragraph 2.1.3) +50o F. 400o F.

3.0 Temperature for Analysis of Radiant 4.1.2 At start of turbine (with flow), use
Reheater Inlet Header (In front of 275o F for the radiant reheat tube temperature
furnace with a fixed "welded" seal and 500o F for the front water wall temperature.
construction)
4.1.3 For full load operation, refer to
3.1 Temperature for expansion and the Predicted Performance Sheet of the
flexibility analysis. Superheater, Reheater and Economizer Section of
the Design Performance Letter.
3.1.1 At startup (before any flow) use
200o F for radiant reheater inlet temperature and 5.0 Temperature for Analysis of
450o F for the front water wall temperature. Downcomer

3.1.2 At start of turbine (with flow) use 5.1 Controlled Circulation Units
275o F for the reheater inlet header temperature
and 500o F for the front water wall temperature. The design temperature to be used is
25o F below saturated steam temperature.
3.1.3 For full load operation, refer to
the Predicted Performance Sheet of Superheater, 5.2 Natural Circulation Units
Reheater and Economizer Section of the Design
Performance Letter. The design temperature to be used is
125o F below saturated steam temperature.
3.2 Temperature for establishing
allowable stresses. 5.3 If the pump is out of service, the
temperature between the inlet and outlet values
These temperatures are to be the will be 200o F.
design temperatures taken from the sheets titled
"Headers, Piping and Miscellaneous Data" of the 6.0 Mean Metal Temperature of Water
Superheater, Reheater and Economizer Section of Wall Tubes for Determining
the Design Performance Letter. Allowable Stresses

4.0 Temperature for Analysis of Radiant Use saturation temperature +50o F except
Reheat Tubes Inside the Furnace in firing panel area where saturation temperature
+100o F is to be used.
(The roof seal is to be a flexible
construction to permit vertical movement of
radiant reheat outlet header in both directions).
SUBJECT: Design Rules for Superheater and STD NO. : 57-75-01
Reheater Terminals, Link Piping, INDEX : 1.9
Downcomers and Hangers for DATE : 9 JULY 2003
Controlled and Natural Circulation Units OWNER : MEDS
PAGE : 8 OF 8
______________________________________________________________________________________________________

7.0 Temperature Difference Between 10.0 Temperature Difference Between


Water Wall Outlet Header and Steam-Cooled Wall Inlet Header and
Nipples the Steam-Cooled Wall

For the purpose of calculating the thermal For the purposes of thermal expansion
expansion difference between header and calculations at the point where the weld between
nipples, use: the wall tube fin stops (provided the point is
above the roof), use:
∆T = T (nipples) -T (header) = + 15o F
based on a drum saturated temperature change ∆T = T (wall) -T (header) = 40o F startup
rate of 400o F/hr.
∆T = T (wall) -T (header) = 20o F cool
∆T = T (nipples) -T (header) = + 23 Fo
down
based on drum saturated temperature change
rate of 600o F/hr. (Sliding pressure operation.) 11.0 Temperature Difference Between
Extended Side Steam-Cooled Wall
8.0 Temperature Difference Between and Water Wall Prior to
Economizer Outlet Tubing and Syncronization
Reheat Inlet Header
∆T = Steam Cooled Wall (525o F -water
8.1 The reheat inlet header will lag wall (505o F) = 20o F
economizer outlet tubing by 300o F prior to steam
flow.

8.2 If there is a trip during operation, the


reheat inlet header will be hot while the
economizer outlet tubing will be running at
300o F. Refer to the Predicted Performance Sheet
of the Superheater, Reheater and Economizer
Section of the Design Performance Letter for the
reheater inlet temperature.

9.0 Temperature Difference Between


Center Wall and Outer Wall

For the purposes of thermal expansion


calculations, use:

∆T = T (center wall) -T (outer wall) = 20o F

You might also like