: 81-80-02
Updated INDEX : 2.4
DESIGN STANDARD DATE : 11 MAR 2002
OWNER : MEDS
PAGE : 1 OF 11
PRODUCT LINES: CHECK THE PRODUCT LINES THAT THE STANDARD IS APPLICABLE TO
Versions
None
SUBJECT: Damper Selection for Balanced STD. NO. : 81-80-02
Draft Utility Boilers INDEX : 2.4
DATE : 11 MAR 2002
OWNER : MEDS
PAGE : 4 of 11
______________________________________________________________________________________________________
1.1 This standard provides the standard A damper for regulating the flow of
selection of damper locations, types of dampers primary air to the pulverizer from the primary air
and various specific functions of dampers. fan.
Table "A"
Item No. Damper Description and Location Location Preference on Type of Damper Damper Function Remarks
Figures 1, 2, 3 and 4
Secondary Air/Gas System Figure 1
1 Forced Draft Fan - Inlet Vane Damper 1 Radial Vane Control the flow Fan Vendor
of air
2 Forced Draft Fan - Outlet Damper to 2 Parallel Blade Louvre Shut-off/Isolation Guillotine type
Air Preheater Damper of air damper may be used
if space is available.
3 * Air Preheater - Outlet Damper 3 Parallel Blade Louvre Shut-off/Isolation Guillotine type
Damper of air damper may be used
if space is available.
4 At Windbox - Hot Secondary Air 4 Opposite Blade Control
Damper Louvre Damper
5 * Air Preheater - Gas Inlet Damper 5 Parallel Blade Louvre Shut-off/Isolation Guillotine type can be
Damper of gas used.
6 Inducted Draft Fan - Inlet Vane 6 Radial Vane Control Gas Flow
Damper
7 Induced Draft Fan - Outlet Damper to 7 Parallel Blade Louvre Shut-off/Isolation Guillotine type can be
Stack Damper used.
Primary Air System Figure 2
8 Primary Air Fan - Outlet Damper 8 Parallel Blade Louvre Shut-off/Isolation
Damper
9 Tempering Air to Mill (Slide Gate) 9 Slide Gate Shut-off Isolation Tight shut-off or zero
Inlet leakage.
* The purpose of these dampers is to avoid a forced outage is case there is damage to the air heater, precipitator or I. D. fan. ALSTOM normal
practice is not to provide "shut-off" dampers in the air heater gas or air inlets or outlets but to provide 28" straight duct for adding ALSTOM damper
later.
SUBJECT: Damper Selection for Balanced Draft Utility Boilers STD. NO. : 81-80-02
INDEX : 2.4
DATE : 11 MAR 2002
OWNER : MEDS
PAGE : 7 of 11
_____________________________________________________________________________________________________________________________________________
Item No. Damper Description and Location Location Preference on Type of Damper Damper Function Remarks
Figures 1, 2, 3 and 4
Primary Air System Figure 2
10 Tempering Air Inlet to Mills 10 Opposite Blade Control Tight shut-off for high
Louvre Type moisture control.
11 * Air Preheater - Premiary Air Inlet 11 Parallel Blade Louvre Shut-off/Isolation
Type
12 * Air Preheater - Primary Hot Air 12 Parallel Blade Louvre Shut-off/Isolation
Outlet to Mills Type
13 Hot Air to Mills (Slide Gate) Inlet 13 Slide Gate Shut-off/Isolation Tight shut-off or zero
leakage
14 Hot Air to Mills - Inlet 14 Opposite Blade Control
Louvre Damper
Seal Air Systems Figure
15 Seal Air Supply to Various 15 Butterfly or Louvre Shut-Off Suggest standby
Components Type Small Damper bypass seal air path.
16 16 Butterfly Control
Ignitor Air/Scanner Air Figure 4
17 Ignitor Air Supply to Ignition System 17 Butterfly Control
18 Scanner Emergency Air Damper 18 Butterfly Shut-Off
* The purpose of these dampers is to avoid a forced outage is case there is damage to the air heater, precipitator or I. D. fan. ALSTOM normal
practice is not to provide "shut-off" dampers in the air heater gas or air inlets or outlets but to provide 28" straight duct for adding ALSTOM damper
later.
Note: Parallel blade and opposite blade louvre type, slide gate and butterfly type damper are typical ALSTOM standard construction dampers shown
on Drawings C-981-0226 and E-981-0076.
SUBJECT: Damper Selection for Balanced Draft Utility Boilers STD. NO. : 81-80-02
INDEX : 2.4
DATE : 11 MAR 2002
OWNER : MEDS
PAGE : 8 of 11
_____________________________________________________________________________________________________________________________________________
Figure 1 - Flow Paths: Secondary Air to Furnace and Gas Flow from Furnace to Atmosphere
SUBJECT: Damper Selection for Balanced Draft Utility Boilers STD. NO. : 81-80-02
INDEX : 2.4
DATE : 11 MAR 2002
OWNER : MEDS
PAGE : 9 of 11
_____________________________________________________________________________________________________________________________________________
Figure 2 - Flow Path: Hot and Cold Primary Air to Mills (Both Sides)
SUBJECT: Damper Selection for Balanced Draft Utility Boilers STD. NO. : 81-80-02
INDEX : 2.4
DATE : 11 MAR 2002
OWNER : MEDS
PAGE : 10 of 11
_____________________________________________________________________________________________________________________________________________