You are on page 1of 17

THIS STANDARD IS: STD NO : 13-61-16

Updated INDEX : 9.6


DESIGN STANDARD DATE : 11 AUG 2003
OWNER : 9810
PAGE : 1 OF 17

SUBJECT : FIELD WELDING DATA SHEETS AND LOCATION DRAWINGS

PURPOSE : To provide a written procedure, charts, graphs and forms for completing
field welding data sheets and location drawings.

DRAWING : See Page 3

REMARKS: This Standard to be effective immediately.

NOTES: 1. See Page 2 for Versions.


2. See Page 3 for list of Arrangement and Detail drawings.

SR. ENGINEERING TECHNICIAN


PREPARED BY: S. GARCIA STANDARDS ENGINEERING - 9809
MANAGER
APPROVED FOR CONTENT: W. RICE PRESSURE PARTS ENGINEERING - 9810
PROGRAM MANAGER
APPROVED FOR PUBLICATION: T. MISKELL STANDARDS ENGINEERING - 9809

This document contains proprietary data and shall not be reproduced


or disclosed without the permission of ALSTOM Power Inc.
SUBJECT: Field Welding Data Sheets STD. NO. : 13-61-16
and Location Drawings INDEX : 9.6
DATE : 11 AUG 2003
OWNER : 9810
PAGE : 2 of 17
______________________________________________________________________________________________________

UNITS: n ENGLISH; o METRIC; o BOTH; o NONE

PRODUCT LINE: CHECK THE PRODUCT LINE THE STANDARD IS APPLICABLE TO:

o ALL; n A = CONTROLLED CIRC. BOILERS o H = HEAT RECOVERY STEAM GENERATORS


n B = SUPERCRITICAL BOILERS (HRSG)
n C = VU40 AND VU60 BOILERS o P = PULVERIZERS - MILLING SYSTEM
o E = FLUIDIZED BED BOILERS (CFB) o R = CHEMICAL RECOVERY BOILERS
n F = NATURAL CIRC. BOILERS (UTILITY) o S = SERVICES (AFTER MARKET USE)

Versions

Ver. 14 - Updated Standard format; added


list of Arrangement and Detail drawings;
Standard has been completely updated
and revised.

Ver. 15 – Revised Charts I, II, III and


Attachment F.

Ver. 16 - Updated standard format; name


change to ALSTOM Power Inc.
SUBJECT: Field Welding Data Sheets STD. NO. : 13-61-16
and Location Drawings INDEX : 9.6
DATE : 11 AUG 2003
OWNER : 9810
PAGE : 3 of 17
______________________________________________________________________________________________________

List of Arrangement Drawings

Drawing No. Title

FB-3213 Field Welding Data Head Sheet

FB-3214 Field Welding Data Sheet

FB-3215 Field Welding Pressure Attachment

List of Detail Drawings

Drawing No. Title

D-980-0103 Detail of 1” Diameter Hole and Plug for Radiographing of Field


SUBJECT: Field Welding Data Sheets STD. NO. : 13-61-16
and Location Drawings INDEX : 9.6
DATE : 11 AUG 2003
OWNER : 9810
PAGE : 4 of 17
______________________________________________________________________________________________________

1.0 Scope procedure is applicable. All revisions to the field


weld data sheets shall be reviewed by
To provide a standard procedure for Construction Services Welding Engineering.
completing the field welding data forms.
2.4 All field weld data forms and location
2.0 General drawings shall be assigned contract drawing
numbers.
2.1 The field welding data sheets are
issued by Design Engineering to provide the field 3.0 Instructions Utilizing Location
with additional information covering field welds Drawings
involving ALSTOM Power pressure parts, hi-crown
roof seals and non-pressure part welds. 3.1 Standard B-size drawing sheets are
utilized for this application and therefore, no
2.2 The field weld data sheets package standard form is needed.
normally consists of the following:
3.2 Location drawings are schematic
2.2.1 Field Welding Location single line sketches used to readily locate and
Drawings identify field welds. Other methods, such as
arrangement or detail drawings, may also be
For this application a standard B- used for this purpose.
size drawing sheet is used and therefore, no form
number is provided. 3.3 Pressure part welds and terminal
welds are normally shown on the field welding
2.2.2 Field Welding Data Head Sheet location drawings.
Drawing
3.4 The following pressure part welds are
See Drawing FB-3213. not normally shown on field welding location
drawings: water column valves and piping, soot
2.2.3 Field Welding Data Sheet blower valves and piping, water cooled spacers,
Drawing miscellaneous piping and valves around pumps,
etc. These welds are usually grouped on data
See Drawing FB-3214. sheets and cross referenced by a note saying
welds ---- through --- cover water column, see
2.2.4 Field Welding Pressure Construction Drawing ---------------.
Attachment Drawing
3.5 Attachment welds and hi-crown roof
See Drawing FB-3215. welds shown on FB-3215 do not require location
drawings, but may be used is needed.
2.3 Although Design Engineering is
responsible for issuing the field weld data 3.6 Welds requiring radiography shall be
package, Construction Services Welding shown on location drawings using an
Engineering has agreed to input field welding identification system that is prefixed by a letter
procedure specification information required on followed by a number, starting with 1 and
the field weld data sheets FB-3214 and FB-3215. followed by a " R ". The letter prefix will identify the
This will permit Construction Services to select the boiler section, as outlined below. More than one
most appropriate field welding procedure when section may be included on the same location
more than one welding drawing.
SUBJECT: Field Welding Data Sheets STD. NO. : 13-61-16
and Location Drawings INDEX : 9.6
DATE : 11 AUG 2003
OWNER : 9810
PAGE : 5 of 17
______________________________________________________________________________________________________

The following letter prefixes shall apply: 4.2.2 Nondestructive Examination

“D” - Downtakes D-1R, D-2 R, etc. A check mark is required in the


“P” - Pump suction & discharge lines legend for NDE if this examination is required for
(including valves); P-1 R, P-2 R, etc. any weld listed on drawings using FB-3214.
“W” – Water wall headers and section; W-1 R,
W-2 R, etc. 4.3 The revision number on the head
"E" - Economizer headers and section; E-1 R, sheet will be changed and the head sheet revised
E-2 R, etc. and re-issued when any of the drawings listed on
“S” – Superheater headers and section; 1 R, the head sheet are revised.
S-2 R, etc.
"R" - Reheater headers and section; R-1 R, 5.0 Instructions for Completing Field
R-2 R, etc. Welding Data Sheet –Drawing
"M" - All other sections; M-1 R, M-2 R, etc. FB-3214

3.7 Non-radiograph pressure part welds 5.1 Drawing FB-3214 shall be used to
shall be identified by a number only. cover all welds joining pressure parts to pressure
parts.
3.8 The weld location drawings shall
cross reference the applicable field weld data 5.2 Pressure part welds connecting
sheets. ALSTOM Power furnished material require all the
field welding data sheet columns completed. All
4.0 Instructions for Completing Field welds requiring radiography must be listed
Welding Head Sheet - FB-3213 separately, other identical welds may be grouped.

4.1 The field weld data head sheet 5.3 Pressure part terminal inlet and outlet
consists of general note, a legend and column for connections, joining ALSTOM Power furnished
listing the field weld location drawings, the field material to customers furnished material, shall
weld data sheet drawings and the field weld have the following columns completed covering
pressure attachment drawings. the ALSTOM Power furnished material: Drawing
Number, Weld Number, Location of Weld, Size,
4.2 Legend Material Specification, Maximum Carbon where
necessary, and Number of Welds.
The legend shall be followed in
completing the field weld data package. 5.4 The temperature and pressure
information must be filled in for piping designed
4.2.1 Codes under ASME B31.1 Code but is not necessary for
piping under the ASME Code Section I technical
Refer to Figures 100.1.2 (A and responsibility and jurisdiction.
B) of the ASME B31.1 Code and Figures
PG-58.3.1 and PG-58.3.2 of the ASME Code 5.5 Drawing FB-3214 is divided into two
Section I for the piping diagrams showing the parts by vertical double lines, and although
Code jurisdictional limits for piping. Design Engineering is responsible for issuing this
form, the responsibility for completing this form
will be as follows:
SUBJECT: Field Welding Data Sheets STD. NO. : 13-61-16
and Location Drawings INDEX : 9.6
DATE : 11 AUG 2003
OWNER : 9810
PAGE : 6 of 17
______________________________________________________________________________________________________

5.5.1 Design Engineering will complete 6.2.2 Design Engineering will then
all columns to the left of the vertical double lines forward the form to Construction Services
and the "No. of Welds” column only on the right Welding Engineering for completing the
side of the double vertical lines. remaining columns to the right side. The form will
then be returned to Design Engineering for
5.5.2 Design Engineering will then issuing.
forward the Form to Construction Services
Welding Engineering for completing the 6.2.3 Paragraphs 6.2.1 and 6.2.2 also
remaining columns to the right of the double apply to revisions.
vertical lines. The form will then be returned to
Design Engineering for issuing. 6.3 This form will cross reference the
applicable location drawings. Use the remarks
5.5.3 Paragraphs 5.5.1 and 5.5.2 also block for this purpose.
apply to revisions.
6.4 Additional information for
5.6 This form will cross reference the completing this form is shown on the attached
applicable location drawings. Use the remarks marked copy of this form.
block for this purpose.
6.5 To electronically add lines of data to
5.7 Additional information for FB-3215, insert block “FW01” at the desired
completing this form is shown on the attached location on the AutoCad form.
marked copy of this form.
7.0 Attachments A through F are to be used for
6.0 Instructions for Completing Field estimating field weld weights. Types “B” and “D”
Welding Pressure Attachment Sheet - butt welds shown in Attachment A are typical weld
Drawing FB-3215 profiles for estimating purposes. For minimum /
maximum dimensioning requirements of these
6.1 Drawing FB-3215 will be used to welds refer to Standard No. 53-75, Index 9.4.
show the following welds:

6.1.1 Attachments to tubing and


pressure parts as shown on Charts I and II.

6.1.2 Non-pressure part, hi-crown roof


seal butt and fillet welds as shown on Chart III.
These welds should be listed separately and not
mixed in with attachment welds, Paragraph 6.1.1.

6.2 This Form is divided into two parts


and although Design Engineering is responsible
for issuing this form, the responsibility for
completing this form will be as follows:

6.2.1 Design Engineering will complete


all columns to the left side and the "No. of Welds"
column only on the right side.
SUBJECT: Field Welding Data Sheets and Location Drawings STD. NO. : 13-61-16
INDEX : 9.6
DATE : 11 AUG 2003
OWNER : 9810
PAGE : 7 of 17
______________________________________________________________________________________________________________________________________________________________

Field Welded Attachments to Tubing


Type of Fillet Welds A- Girth Weld With Throat Thickness 0.5" or Less
B - Longitudinal Weld 4" Long or Less, Weld Throat 0.50" or less
Chart I C - Longitudinal Weld Over 4", Weld Throat 0.50" or Less
Limitations: Tubing 4" O. D. Max., Also See Limitations on Chart
TUBING ATTACHMENT MATERIAL (0.50" MAX. THK.)
MATERIAL Car. Stl. Car. Moly 1 to 1.25 Cr - .5 Mo 2.25 Cr - Mo 5Cr-Mo-Ti 9Cr-Mo 12 to 15 Cr Stn. Steel
P1 P3 P4 P5A P5B P5B P6: P7 P8
MAX. O. D. 4" AISI 1020 AISI 6120 SA-182 F11 SA-182 F22 AISI 502 SA-213 T9 AISI 405, 430, AISI 304, 308,
A-36 SA-217 WC1 SA-217 WC6 SA-217 WC9 P5B1 409, 410 309, 321, 347
ASME FILLET FILLET SA-515 SA-387 GR. 11 SA-387 GR. 22 SA-240 429 A-297 HH
GRP. SPEC. MAX. WELD WELD A-572 GR. 50 SA-387 GR. 12 P5F2 P6E1 SA-351 CH20
NO. NO. THK. TYPE REQMTS. P1G1 CORTEN
P1 SA-178A, C & D 0.75 A FLD. WELD 1.1Z-304 1.3Z-301 1.4Z-304 1.5Z-302 1.8Z - 302
SA-192 B PROC.
SA-210 C NO. WELD 11 13 14 15 18
GR. A-1 & C CODE
SA-226
P3 SA-209 0.5 A FLD. WELD 1.3Z-300 3.3Z-300 3.4Z-300 3.5Z-300
T1 B PROC.
T1a NO. WELD 31 33 34 35
T1b CODE
P4 SA-213 0.5 A FLD. WELD 1.4Z-305 4.4Z-300 4.5Z-300 4.8Z-300
T11 & T12 B PROC.
SA-423 NO. WELD 41 44 45 48
Gr. 1 CODE
P5A SA-213 0.5 A FLD. WELD 4.5Z-302 5.5Z-300 5.8Z-300
T22 B PROC.
CC2199-1 (T23) NO. WELD 54 55 58
CODE
P8 SA-213 0.5 A FLD. WELD 8.8Z-300
TP-321H PROC.
TP-304H NO. WELD 88
TP-316H CODE
TP-347H
SA-213 0.5 B FLD. WELD 4.8Z-300 8.8Z-302
TP-304H PROC.
NO. WELD 83 88
CODE
Notes: 1. Design Engineering to show No. Weld Code on Field Weld Data Sheet FB-3215.
2. Contact Standards Engineering or Welding Engineering regarding field welds not covered by this Chart.
SUBJECT: Field Welding Data Sheets STD. NO. : 13-61-16
and Location Drawings INDEX : 9.6
DATE : 11 AUG 2003
OWNER : 9810
PAGE : 8 of 17
______________________________________________________________________________________________________

Chart II
Field Welded Attachments to
Pressure Parts
For: Carbon Steel Lines, Links over 4"
O. D. & Headers
Limitations: Pressure Part - Max. Thickness 4"
Fillet Weld - Max. Throat 0.5"
ATTACHMENT MATERIAL
Pressure Part FILLET A-36, P1G1 SA-387-12 SA-387-22
Material WELD SA-515 Gr. 70
Max. Thickness 4" REQMTS.
Headers FLD. WELD 1.1Z-304 1.4Z-304 1.5Z-302
SA-106 Gr. B PROCESS
ALPHA NO. A11 A14 A15
WELD CODE
Lines & Links Only FLD. WELD 1.1Z-304 1.4Z-304 1.5Z-302
SA-106 Gr. B or C PROCESS
SA-216 Gr. WCB ALPHA NO. B11 B14 B15
SA-515 Gr. 70 WELD CODE

Notes: 1. Design Engineering to show ALPHA - No. Weld Code


on Field Weld Data Sheet Form FB-3215.
2. Contact Standards Engineering or Welding Engineering
regarding field welds not covered by this Chart.
SUBJECT: Field Welding Data Sheets STD. NO. : 13-61-16
and Location Drawings INDEX : 9.6
DATE : 11 AUG 2003
OWNER : 9810
PAGE : 9 of 17
______________________________________________________________________________________________________

Chart III
Field Welded Non-pressure Part Butt & Fillet Welds
For: Hi-Crown Roof Seals, End Bars & Collector Plates
Limitations: Maximum Material Thickness 1.50"
Mat'l Combinations Butt & Carbon Stl Low Alloy 2-1/4 Cr - 1 Mo 2-1/4 Cr - 1 Mo
Fillet A-36 A387-12 A387-22 A387-22
Seal, Cross Bars Weld A515-70 A287-11 Max. Thickness Thickness Over
& Collector Plates Reqmts. P1G1 Corten A, B 0.375 0.375
Carbon Steel AWS
A-36, A-515 SMA-PROC. 1.1V-303 1.4V-301 1.5V-301 1.5V-301
P1G1 Alpha
Weld Code AA AB AC AD
Low Alloy AWS
A387-11, 12 SMA-PROC. 1.4V-301 4.4V-302 4.5V-302 4.5V-302
Corten A, B Alpha
Weld Code BA BB BC BD
2-1/4 Cr - 1 Mo AWS
A387-22 SMA-PROC. 1.5V-301 4.5V-302 5.5V-302 5.5V-302
Max. Thickness Alpha
0.375 Weld Code CA CB CC CD
2-1/4 Cr - 1 Mo AWS
A387-22 SMA-PROC. 1.5V-301 4.5V-302 5.5V-302 5.5V-302
Thickness Over Alpha
0.375 Weld Code DA DB DC DD

Notes: 1. Design Engineering to show ALPHA Weld Code


on Field Weld Data Sheet Form FB-3215.
2. Contact Standards Engineering or Welding Engineering
regarding field welds not covered by this Chart.
SUBJECT: Field Welding Data Sheets STD. NO. : 13-61-16
and Location Drawings INDEX : 9.6
DATE : 11 AUG 2003
OWNER : 9810
PAGE : 10 of 17
______________________________________________________________________________________________________

Attachment A
SUBJECT: Field Welding Data Sheets STD. NO. : 13-61-16
and Location Drawings INDEX : 9.6
DATE : 11 AUG 2003
OWNER : 9810
PAGE : 11 of 17
______________________________________________________________________________________________________

Attachment B

10

6
2
ANET - IN

2 C R O SS SEC TIO N AL AR EA
O F TYPE "B" W ELD G R O O VE
A N ET
Vs
1 M IN IM U M W ALL TH IC KN ESS
t M IN > .75"

0
0 1 2 3 4 5 6 7
M IN IM U M W A L L T H IC K N E S S t M IN . - IN C H E S
SUBJECT: Field Welding Data Sheets
STD. NO. : 13-61-16
and Location Drawings
INDEX : 9.6
DATE : 11 AUG 2003
OWNER : 9810
PAGE : 12 of 17
______________________________________________________________________________________________________

Attachment C

Sheet 1 of 2

100

N o m in a l P ip e S ize s

36

30
WEIGHT OF DEPOSITED FILLER METAL LBS

26
22

18

10 14

10

W E IG H T O F F IL L E R M E T A L
Vs
M IN IM U M W A L L T H IC K N E S S
W G T ≅ 0 .2 8 3 A N E T π d
OR
0 .8 9 0 A N E T d
W H E R E d = A C T U A L O .D .
F O R T Y P E "B " W E L D S

1
0 0 .5 1 1 .5 2 2 .5 3 3 .5
M IN IM U M T H IC K N E S S t M IN . - IN C H E S
SUBJECT: Field Welding Data Sheets
STD. NO. : 13-61-16
and Location Drawings
INDEX : 9.6
DATE : 11 AUG 2003
OWNER : 9810
PAGE : 13 of 17
______________________________________________________________________________________________________

AT T AC H M E N T "C "
SHEET 2 OF 2

1000

N om inal P ipe S izes

36

30
WEIGHT OF DEPOSITED FILLER METAL LBS

26

22

18

100 14

W E IG H T O F F ILLE R M E T A L
Vs
M IN IM U M W A LL T H IC K N E S S
W G T ≅ 0.283 A N E T π d
OR
0.890 A N E T d
W H E R E d = A C T U A L O .D .
F O R T Y P E "B " W E LD S

10
2 2.2 2.4 2.6 2.8 3 3.2 3.4 3.6 3.8 4 4.2 4.4 4.6 4.8 5
M IN IM U M W AL L T H IC K N E S S t M IN . - IN C H E S
SUBJECT: Field Welding Data Sheets STD. NO. : 13-61-16
and Location Drawings INDEX : 9.6
DATE : 11 AUG 2003
OWNER : 9810
PAGE : 14 of 17
______________________________________________________________________________________________________

Attachment D

1
ANET - IN²

0 .1

C ro s s S e c tio n a l A re a
o f T y p e "D ' W e ld G ro v e
ANET
Vs
M in im u m W a ll T h ic k n e s s
t M in . < = .7 5 "

0 .0 1
0 .1 0 0 0 .2 0 0 0 .3 0 0 0 .4 0 0 0 .5 0 0 0 .6 0 0 0 .7 0 0 0 .8 0 0

M in im u m W a ll T h ic k n e s s t M in . - In c h e s
SUBJECT: Field Welding Data Sheets STD. NO. : 13-61-16
and Location Drawings INDEX : 9.6
DATE : 11 AUG 2003
OWNER : 9810
PAGE : 15 of 17
______________________________________________________________________________________________________

Attachment E

10

A c tu a l O u ts id e D ia m e te r

30
24
22
18
14
1 2 .7 5
1 0 .7 5
8 .6 2 5
6
5
0 .1
4

W e ig h t o f F ille r M e ta l
2
Vs
1 .5
M in im u m W a ll T h ic k n e s s
1 .2 5 WGT ≅ 0 .2 8 3 A N E T d
Or
≅ 0 .8 9 0 A N E T d
W h e re d = A c tu a l O .D .
F o r T y p e " D " W e ld s

0 .0 1
0 0 .1 0 .2 0 .3 0 .4 0 .5 0 .6 0 .7 0 .8
M in im u m W a ll T h ic k n e s s t M in . - In c h e s
SUBJECT: Field Welding Data Sheets STD. NO. : 13-61-16
and Location Drawings INDEX : 9.6
DATE : 11 AUG 2003
OWNER : 9810
PAGE : 16 of 17
______________________________________________________________________________________________________

Attachment F

O.D.

Weld Volume = π/2 (A2D + A3) in3


Weight Deposited = .283 π/2 (A2D + A3) lbs.
= .445 (A2D + A3) lbs.

Note: Quantities calculated above are net deposited metal. To allow for normal loss due
to spatter, stub ends, and weight of coating, increase losses as follows:

For shielded Metal Arc (SMA) Procedures in P-1 and P-2 Material Groups: Net x 2.0

For shielded Metal Arc (SMA) Procedures in P-4, P-5 and P-8 Material Groups: Net x 4.0
SUBJECT: Field Welding Data Sheets and Location Drawings STD NO. : 13-61-16
INDEX : 9.6
DATE : 11 AUG 2003
OWNER : 9810
PAGE : 17 of 17
______________________________________________________________________________________________________________________________________________________

Attachment F (Cont.)
O. D. inches Socket Weld Fillet Leg Size inches
Pipe or Tube 0.120 0.150 0.180 0.200 0.220 0.240 0.260 0.280 0.300 0.320 0.340 0.360 0.380 0.400 0.420 0.440 0.460 0.480 0.500
0.800 0.006 0.010 0.014 0.018 0.022 0.027 0.032 0.038 0.044 0.051 0.059 0.067
1.000 0.007 0.012 0.017 0.021 0.026 0.032 0.038 0.045 0.052 0.060 0.069 0.078 0.089 0.100
1.050 0.007 0.012 0.018 0.022 0.027 0.033 0.039 0.046 0.054 0.062 0.072 0.081 0.092 0.103 0.115
1.125 0.008 0.013 0.019 0.024 0.029 0.035 0.042 0.049 0.057 0.066 0.075 0.086 0.097 0.109 0.121
1.250 0.009 0.014 0.021 0.026 0.032 0.038 0.045 0.053 0.062 0.072 0.082 0.093 0.105 0.117 0.131 0.146 0.161 0.177 0.195
1.315 0.009 0.015 0.022 0.027 0.033 0.040 0.047 0.056 0.065 0.075 0.085 0.097 0.109 0.122 0.136 0.151 0.167 0.184 0.202
1.500 0.010 0.017 0.024 0.030 0.037 0.045 0.053 0.062 0.072 0.083 0.095 0.107 0.121 0.135 0.151 0.167 0.185 0.203 0.223
1.625 0.011 0.018 0.026 0.032 0.040 0.048 0.057 0.066 0.077 0.089 0.101 0.114 0.129 0.144 0.161 0.178 0.196 0.216 0.236
1.660 0.011 0.018 0.027 0.033 0.040 0.049 0.058 0.068 0.078 0.090 0.103 0.116 0.131 0.147 0.163 0.181 0.200 0.219 0.240
1.750 0.012 0.019 0.028 0.035 0.042 0.051 0.060 0.071 0.082 0.094 0.108 0.122 0.137 0.153 0.170 0.189 0.208 0.229 0.250
1.875 0.013 0.020 0.030 0.037 0.045 0.054 0.064 0.075 0.087 0.100 0.114 0.129 0.145 0.162 0.180 0.199 0.220 0.241 0.264
1.900 0.013 0.021 0.030 0.037 0.046 0.055 0.065 0.076 0.088 0.101 0.115 0.130 0.147 0.164 0.182 0.202 0.222 0.244 0.267
2.000 0.014 0.022 0.031 0.039 0.048 0.057 0.068 0.080 0.092 0.106 0.120 0.136 0.153 0.171 0.190 0.210 0.232 0.254 0.278
2.125 0.014 0.023 0.033 0.041 0.051 0.061 0.072 0.084 0.097 0.111 0.127 0.143 0.161 0.180 0.200 0.221 0.243 0.267 0.292
2.375 0.016 0.025 0.037 0.046 0.056 0.067 0.079 0.093 0.107 0.123 0.140 0.158 0.177 0.198 0.219 0.243 0.267 0.293 0.320
2.500 0.017 0.027 0.039 0.048 0.059 0.070 0.083 0.097 0.112 0.129 0.146 0.165 0.185 0.206 0.229 0.253 0.279 0.306 0.334
2.875 0.019 0.030 0.044 0.055 0.067 0.080 0.094 0.110 0.127 0.146 0.165 0.187 0.209 0.233 0.259 0.286 0.314 0.344 0.375
3.000 0.020 0.032 0.046 0.057 0.069 0.083 0.098 0.114 0.132 0.151 0.172 0.194 0.217 0.242 0.268 0.296 0.326 0.357 0.389
3.500 0.023 0.037 0.053 0.066 0.080 0.096 0.113 0.132 0.152 0.174 0.198 0.223 0.249 0.278 0.308 0.339 0.373 0.408 0.445
4.000 0.026 0.042 0.060 0.075 0.091 0.109 0.128 0.149 0.172 0.197 0.223 0.251 0.281 0.313 0.347 0.383 0.420 0.459 0.501

Chart – Weight of Deposited Weld Metals in Lbs.

Note: For Shielded Metal Arc (SMA) Procedures in P-1 and P-3 Material Groups, multiply above values by 2.
For Shielded Metal Arc (SMA) Procedures in P-4, P-5 and P-8 Material Groups, multiply above values by 4.

You might also like