org International Engineering Research Journal (IERJ) Special Issue 3 Page 152-157, 2016, ISSN 2395-1621

ISSN 2395-1621 Design of Ejector Parameters and


Geometry for Ejector Expansion
Refrigeration System- A Review
#1
Akshay R. Ghotkar, #2Prof. Nitin V. Sali

1
akshayghotkar2@gmail.com
2
nvsali@rediffmail.com

#12
Mechanical Engineering Department, Shivaji University, Kolhapur,
Government College of Engineering, Karad, Maharashtra, India

ABSTRACT ARTICLE INFO

From last few decades, the use of efficient ejector in refrigeration systems has been Article History
paid a lot of attention. This paper presents literature studies on recent development in Received: 28th February 2016
ejector cooling system and also the enhancement of the coefficient of performance.
Some of researches have conducted and categorized in simulation and mathematical Received in revised form :
modelling of the ejector, geometrical parameters and operation conditions
1st March 2016
optimization. Most of the experimental work which have been done in last two
decades are insufficient compared with simulation modelling results. Hence, there is Accepted: 3rd March 2016
need of more experimental studies and big scale work in order to come out with good
results in real application. Published online :
5th March 2016
Keywords—working fluid, cooling system, operating conditions ejector design, area ratio-
geometry,

Fig. 2 shows a basic vapour compression refrigeration


I. INTRODUCTION system. It mainly consists of a compressor, an evaporator, a
The ejector show in fig.1 is a component that expands a condenser, expansion device, ejector and separator. In this
high-pressure primary liquid refrigerant to absorb a system, high pressure (primary fluid) liquid refrigerant
secondary vapour refrigerant at a pressure slightly above the flows through the motive nozzle of the ejector and entrains
low pressure reached by the primary substance. In this vapour from evaporator at low pressure (secondary fluid).
refrigeration cycle, the two-phases of refrigerant are The primary and secondary fluid then mix in the mixing
identical, so both flows mix together, and there is pressure section and recover a pressure in the diffuser.
increase due to the change of the flows momentum. An
ejector is made up of two components a motive nozzle and a
body. The nozzle is having convergent divergent shapes
with a throat that defines the primary refrigerant mass flow
rate. The role of the nozzle is to create a low-pressure flow
of liquid refrigerant with high momentum, so it converts the
pressure potential energy into kinetic energy.

Fig. 2 Ejector Expansion Refrigeration system


Fig. 1 Ejector Geometry

© 2015, IERJ All Rights Reserved Page 1


www.ierjournal.org International Engineering Research Journal (IERJ) Special Issue 3 Page 152-157, 2016, ISSN 2395-1621

The combined fluid flows to the separator. And then duct effectiveness, wall friction, momentum loss, ejector
separates liquid and vapour. Vapour flows through geometry, shock waves as well as the acceleration of the
compressor and then through condenser. Then liquid flows induced flow in the conical part of the mixing section. The
through the expansion device and enters the evaporator, usual assumption of mixing at constant pressure over the
where it is evaporated to vapour. The vapour is finally mixing chamber cross section was not that of a constant
entrained into the ejector again, thus finishing the ejector mixing chamber cross section were made. A comparison
refrigeration cycle. with available experimental data as well as other
computation methods from the literature was presented. The
II. LITERATURE REVIEW performance was influenced by the ejector geometry.
DA-WEN SUN etal. [5] reviewedthat refrigeration and air-
G. Grazzini, A. Milazzo, D. Paganini [1]presented a conditioning units powered by low-grade thermal energy
design procedure for ejector compression refrigeration have economic advantages. However, the current market is
system, based on a one-dimensional simulation. Heat dominated by electrically worked mechanical vapour-
exchangers were included in the calculation, accounting for compression systems. Ejector-refrigeration cycles offer a
temperature differences between thefluids and for pressure low-cost and reliable option for saving low-grade thermal
losses. The ideal gas assumption, which is quite common in energy. Recent studies were shown that for achieving
the literature concerning ejector systems, was avoided in optimal performance variable geometry ejectors play an
this paper. Furthermore, the supersonic diffuser was important role. Unfortunately, in the public domain the
designed with a continuous profile,without cylindrical piece, detailed design information is not available. Here, we
controlling the variation of momentum along the flow path analyses the effect of ejector geometries on performance.
and accountingfor friction. At design conditions, this should Technical data including flow rates, entrainment ratio and
reduce the irreversibility due to the normal shock.A ejector geometry were provided for a 5kW steam-jet
comparison between different operating fluids is presented refrigerator. These data may serve as guides in designing
and R245fa was selected. The results of thedesign procedure ejector-cycle refrigerators with other cooling capacities.
and the expected performance, in terms of first and second Praitoon Chaiwongsa, Somchai Wongwises*
law efficiency, werepresented. [6]investigatedthe performance of the refrigeration cycle
B.J. Huang*, J.M. Chang, C.P. Wang, V.A. Petrenko using a two-phase ejector as an expansion device
[2]presented a 1-D analysis for the prediction of ejector experimentally. Refrigerant R-134a was used as working
performance at critical-mode operation. In constant-area fluid. Motive nozzles having three different outlet diameters
section of the ejector, constant pressure mixing was were tested. New experimental data on external parameters
assumed. The entrained flow at choking condition was that have never been seen before were presented. Effect of
analyzed. They also carried out an experiments using 11 heat sink and heat source temperatures on the coefficient of
ejectors and R141b as the working fluid to verify the performance and various relevant parameters were presented
analytical results with experimental results. The test results i.e. primary mass flow rate of the refrigerant, secondary
were used to determine the coefficients such as , , mass flow rate of the refrigerant, recirculation
and defined in the 1-D model by matching the test data ratio,compressor ratio, average evaporator pressure,
with the analytical results. The1-D analysis using the discharge temperature and cooling capacity. The effects of
empirical coefficients can accurately predict the size of the motive nozzle outlet on the system performance
performance of the ejectors was proved. were also discussed.
Abdelouahid Dahmania, Zine Aidounb, Nicolas H. Kursad Ersoy, Nagihan Bilir Sag [7]investigatedthe
Galanisa,*[3] presenteda design methodology for simple use of an ejector as an expansion device instead of an
ejector refrigeration systems applied for a particular expansion valve for expansion work recovery in a vapor-
combination of four parameters like generator, ejector, compression cycle was experimentally. Under the same
condenser and the evaporatorof fixed cooling capacity external conditions,the coefficient of performance (COP)
operating with fixed temperatures. The existence of values for both conventional and ejector systems were
optimum values for the refrigerant pressure in the generator experimentally investigated. It was observed that, in the
(PG) and the temperature difference in the heat exchangers conventional system the pressure drop picks up to 133 kPa
( T) which minimize the total thermal conductance of the although the drop in the refrigerant pressure in the
system were established.These optimum values of PG and T evaporator of the ejector system was almost negligible.
were particularly interesting since they yield high values for Depending on the operating conditions,in the ejector it was
the coefficient of performance and the exergetic efficiency found that the work recovery was between 14% and 17%. It
of the system. They had been determined for four was also found that the refrigeration system with an ejector
refrigerants (R134a, R152a, R290, and R600a). For first as the expander exhibited a COP that was 6.2%–14.5%
approximation an objective function is proportional to the higher than that of the conventional system. The
product of the capital and operational costs was defined and approximated error were found within 10% when
used to compare the performance of the system with above experimental results were compared with theoretical results.
refrigerants. Praitoon Chaiwongsa, Somchai Wongwises* [8]presented
K. Cizungua,*, M. Grolla, Z.G. Linga [4] formulateda one the experimental study of the performance of the two-phase
dimensional compressible flow model, which was based on ejector expansion refrigeration cycle. In this study, three
the control volume approach, and in a jet cooling system it two-phase ejectors were used as an expansion device in the
optimize two-phase ejectors in steady-state operation with refrigeration cycle. Also presented the effects of throat
particular reference to their deployment. The working fluid diameter of the motive nozzle, on the coefficient of
can be both single-component (NH3) and two component performance, primary mass flow rate of the refrigerant,
(NH3–H2O). The developed model takes into account the secondary mass flow rate of the refrigerant, recirculation

© 2015, IERJ All Rights Reserved Page 2


www.ierjournal.org International Engineering Research Journal (IERJ) Special Issue 3 Page 152-157, 2016, ISSN 2395-1621

ratio, average evaporator pressure, compressor pressure and cooling coefficient of performance (COP)for any
ratio, discharge temperature and cooling capacity, which operating temperature. The improvement ratio in COP rises
have never before appeared in open literature. The effects of whereas ejector area ratio drops, when the difference
the heat sink and heat source temperatures on the system between condenser and evaporator temperatures increases.
performance are also discussed. The minimum COP improvement ratio in the investigated
Somjin Disawas, Somchai Wongwises* [9]presentedthe work was 10.1%, while its maximum was 22.34%. Even in
new experimental data on the performance of a never before the case of an off-design operation, the COP of a system
seen two-phase ejector refrigeration cycle. In this with ejector is higher than that of the basic system.
refrigeration cycle, a two-phase ejector was used as an Jianyong Chen, Hans Havtun*, Björn Palm
expansion device. The results were compared with those of [13]presentedan ejector model to determine the optimum
the conventional refrigeration cycle (CRC). The effects of performance as well as obtaining the design of an area ratio
heat sink and heat source temperatures on the system of an ejector in a refrigeration system. Auxiliary dynamic
performance were discussed. Over the whole range of equations andworking fluid properties were used to model
experimental conditions the results show that the coefficient the processes in the ejector. In the mixing chamber, the
of performance of the TPERC is higher than that of the normal compression shock was considered. To validate the
CRC. This is due to a higher refrigerant-side heat transfer model experimental data from literature were used, and the
coefficient in the evaporator, resulting from the higher agreement with the model at different optimum operating
refrigerant mass flow rate passing through the evaporator. conditions was very good. The deviation between the
However, the heat sink temperature increasesthe increase in experimental data and the model at non-optimum conditions
COP becomes relatively smaller. was slightly larger.A study shows that the working
M. Hassanain, E. Elgendy, M. Fatouh [10] presenteduse conditions for refrigerants R123 and R141b indicates that
of a two-phase flow ejector as an expansion device in vapor the condenser temperature has more influence on area ratio
compression refrigeration systems is one of the efficient and the entrainment ratio in the ejector than the generator
ways to enhance its performance. This work aims to design and evaporator temperatures on the area ratio. As operating
a constant-area two phase flow ejector and to evaluate conditions are changed area ratios need to keep up the pace
performance characteristics of the ejector expansion with the variation of entrainment ratio. To ensure that the
refrigeration system working with R134a. A simulation ejector refrigeration system operates at its optimum
program was developed and effects of operating conditions conditions a variable-geometry ejector seems a very
and ejector internal efficiencies on the system performance promising alternative. Ejector efficiencies play a very
were investigated using EES software. Comparison between important role in this model, and the influence of the
published experimental data and present data revealed that efficiencies on the ejector performance was investigated.
the developed model can predict the system COP with a Szabolcs Vargaa, Armando C. Oliveiraa,*, Bogdan
maximum error of 2.3%. As evaporation temperature Diaconua.b [14]determined ejector efficiencies for the
changed from -10°C to 10°C, the system COP increased by primary nozzle, suction, mixing and diffuser for the first
87.5%. Finally, the correlations regarding ejector main time by using an axi-symmetric CFD model. Water was
diameters as a function of operating conditions, system considered as working fluid and the operating conditions
cooling capacity and ejector internal efficiencies were were selected in a range that would be suitable for an air-
reported. conditioner powered by solar thermal energy. Ejector
Khaled Ameur, Zine Aidoun, Mohamed Ouzzane performance was estimated for constant section area ratios
[11]presented a modeling procedure of liquid-vapour and different nozzle throat. Depending on operating
ejectors for refrigeration, heat pumps and several other conditions,the results indicated the existence of an optimal
potential industrial applications. The modeling relies on a ratio. Ejector efficiencies were calculated for different
thermodynamic approach where properties of real operating conditions. It was found that while nozzle
refrigerantsandconservation equationswere used.Refrigerant efficiency can be considered as constant, the efficiencies
liquid and vapour phases were assumed to be in related to the suction, mixing and diffuser sections of the
homogeneous equilibrium.Fluid flow in the ejector is two- ejector were depend on operating conditions.
phase and compressible. The design of primary and Jahar Sarkar* et al. [15]presented thermodynamic analyses
secondary nozzles was performed by maximizing the mass and comparison of ammonia, propane and isobutane based
flow rate at their respective throats, thus the approximate vapour compression refrigeration cycles using constant area
determination of the velocity of sound and the Mach number mixing ejector as an expansion device. Optimization of
in a two-phase flow environment. In the mixing chamber, ejector geometric parameter based on the performance
wall friction is taken in the momentum balance equation. improvement and maximum cooling COP for different
The result of computations by the present model matches operating conditions was studied. Results show that the
fairly with experimental data from a dedicated test bench as optimum geometric parameter increases with decrease in
well as with those found in the available literature. condenser temperature and increase in evaporator
Computations were performed using this model for an temperature, whereas the COP improvement over basic
ejector in typical conditions of a refrigeration application. expansion cycle increases with decrease in evaporator
Nagihan Bilir and H. Kursad Ersoy* [12]investigatedthe temperature and the increase in condenser temperature.
performance of a vapour compression system that uses an Expressions for optimum ejector geometric parameters were
ejector as an expansion device. In the analysis, a two-phase developed, which offer useful guidelines for operation and
constant area ejector flow model was used. R134a was optimal design. Study shows that the COP improvement as
selected as the refrigerant. According to the obtained results, well as optimum parameters using ejector as expansion
there are different optimum values of pressure drop in the device are strongly dependent on the operating conditions as
suction chamber, ejector area ratio, ejector outlet pressure well as therefrigerant properties. The optimum geometric

© 2015, IERJ All Rights Reserved Page 3


www.ierjournal.org International Engineering Research Journal (IERJ) Special Issue 3 Page 152-157, 2016, ISSN 2395-1621

parameter was minimum for isobutane, whereasmaximum comparison of the different ejector cycles was presented.
for ammonia. Using ejector as an expansion device, Also theoretical COP was presented and used to show that
isobutane yields maximum COP improvement of 21.6%, they have the same theoretical COP. Numerical models
propane (17.9%) and ammonia (11.9%). were used to further compare the cycles in terms of
K.O. Shestopalova, b,*, B.J. Huanga, V.O. Petrenkoa, b, availability destruction andtheoretical COP. The results
O.S. Volovyka [16]presentedthe ejector refrigeration show that the standard two-phase ejector cycle has higher
machine (ERM) offers several advantages over other heat- Second Law efficiency andlower availability destruction
driven refrigeration machine, including simplicity in design than the alternate ejector cycles despite having the same
and operation, high reliability and low installation cost. It theoretical COP. Some advantages and disadvantages of the
enable its wide application in the refrigeration. In this paper different ejector cycles that are not accounted for in the
the ejector refrigeration cycle performance and theoretical theoretical COP were discussed in this paper.
analysis of ejector design was presented. ERM performance J.M. Abdulateef*, K. Sopian, M.A. Alghoul*, M.Y.
characteristics is stronglydepend on the operating Sulaiman [19] reviewed the literature on solar-driven
conditions, the efficiency of the ejector used, and the ejector refrigeration systems and to give useful guidelines
thermodynamic properties of the refrigerant used. A 1-D regarding operating principles and background of ejector.
model for the prediction of the entrainment ratio, and an The development of solar-driven ejector refrigeration
optimal design for ejectors with cylindrical and conical- systemshistory and recent progress were reported. It shows
cylindrical mixing chambers are presented. It is necessary that solar-driven ejector refrigeration technologies are not
first of all to improve the performance of the ejector, in only can serve the needs for cooling requirements, but also
order to increase ERM performance values. can meet demand for energy conservation and environment
Krzysztof Banasiakb,*, Michał Palacza, Armin Hafnerb, protection. For these reasons, to solve the crucial points of
Zbigniew Bulinskia, Jacek Smołkaa, Andrzej J. Nowaka, the research activities in this sector are still increasing that
Adam Fica[17] presented a CFD-based numerical analysis make these systems not yet ready to compete with the well-
of the flow irreversibility in R744 ejectors. A validated CFD known vapour compression system. However, a lot of
was used to investigate three cases that were differentiated research work still needs to be done for the replacement of
by the massflow rate per unit area (mass flux) that passed conventional refrigeration machines andfor large-scale
through the mixer, which represented threedissimilar flow applications in industry.
patterns. To evaluate the ejector performance a new factor Jahar Sarkar et al. [20]revieweda literature on two-phase
wasproposed based on the reference entropy increase in ejectors and their applications in vapour compression
aclassic expansion valve. The mixer mass flux was found to refrigeration and heat pump systems. Also summarised
significantly affect the ejectorperformance. To assess geometry, modelling and operation of ejector, and effects of
thecontribution of the local irreversibilities to the overall various geometric and operatingparameters. Also
entropy increasean original approach was introduced. In categorised the refrigerant varieties on the ejector
addition, the influence of the mixer diameter and length on performances as well as performance characteristics of both
theejector performance was numerically analyzed, which subcritical and trans-critical vapour compression systems
showed that the effects of bothgeometric parameters are with various cycle configurations. Moreover, system control
very important. In the conditions considered, andoptimal operation to get maximum performance by using
bothenlargement of the mixer cross section area by 33.3% as ejector as an expansion device were also discussed.
well as shortening the mixerlength by 17.4%resulted in the However, a lot of research work still needs to be done for
increase of the overall entropy growth rate by5.4% large-scale applications in industry and for the
and8.9%, respectively. replacement/modification of heat pump machines
Neal Lawrence, Stefan Elbel*[18] presentedthe andconventional refrigeration. Also discussed the
comparison between the standard two-phase ejector performance improvement along with several advantages in
refrigeration cycle withless commonly considered two- installation, operation and control with ejector stimulates the
phase ejector refrigeration cycles and also compared a commercialization of ejector enhanced refrigeration and
liquid-vapor separator to two alternate, as well as to a heat pump systems.
conventional cycle with an expansion valve. An analytical

TABLE I
Two phase flow ejector length and angles (Refer fig.3)
Reference Refrigerant

Banasiak et al. (2014) R744 1.59 15 - 1 - 21 10 4.3 2.5


Lee et al. (2014) R744 1.53 15 4.8 2 - - 12 5.2 3
Liu et al. (2012) R744 - - - - - - 6.5 2.7 7
Nakagawa et al. (2012) R744 - - 14.4 0.5 - - 6 3.8 5.2
Disawas and Wongwises R134a 1 23 8 2.3 1 18.4 11 4 3.8
(2004)
Chainwongsa and Wongwises R134a 1 23 8 2.3 1 18.4 11 4 3.8
(2008)
Chainwongsa and Wongwises R134a 1 23 11.11 1.3 1 18.4 11 4 3.8
(2007)

© 2015, IERJ All Rights Reserved Page 4


www.ierjournal.org International Engineering Research Journal (IERJ) Special Issue 3 Page 152-157, 2016, ISSN 2395-1621

[3] Abdelouahid Dahmania, Zine Aidounb, Nicolas


Galanisa,*,‖ Optimum design of ejector refrigeration systems
with environmentally benign fluids‖, International Journal
of Thermal Sciences 50 (2011) 1562e1572.
[4] K. Cizungua,*, M. Grolla, Z.G. Linga,‖ Modelling and
optimization of two-phase ejectors for cooling systems‖,
Applied Thermal Engineering 25 (2005) 1979–1994.
[5] DA-WEN SUN et al.,‖ variable geometry ejectors and
Fig.3 Ejector parameters their applicationsin ejector refrigeration systems‖, Energy
Vol. 21, No. IO. PP. 919-929, 1996.
IV CONCLUSION [6] Praitoon Chaiwongsa, Somchai Wongwises*,‖
Experimental study on R-134a refrigeration system usinga
1. This paper presents the principles for the recent two-phase ejector as an expansion device,‖ Applied Thermal
enhancements and development and ejector design in ejector Engineering 28 (2008) 467–477.
refrigeration technologies. [7] H. Kursad Ersoy, Nagihan Bilir Sag,‖ Preliminary
2. Research on ejector refrigeration systems over the last experimental results on the R134a refrigeration system
two decades involve system modelling, design, and system using a two-phase ejector as an expander‖, International
optimization. Journal of RefrigerationS0140-7007(14)00082-6.
3. The optimal geometry parameters of ejectors depend on [8] Praitoon Chaiwongsa, Somchai Wongwises*,‖ Effect of
the operating conditions andworking fluids. throat diameters of the ejector on the performance of the
4. Other parameters such as the length of the constant area refrigeration cycle using a two-phase ejector asan expansion
mixing section and the converging angle of the constant device,‖ International Journal of Refrigeration 30 (2007)
pressure mixing section are less studied because of their 601-608.
small influence on ejector performance. [9] Somjin Disawas, Somchai Wongwises*,‖ Experimental
5. The research and development are focuses on feasibility investigation on the performance of the refrigeration cycle
enhancement and performance by combining the ejector using a two-phase ejector as an expansion device,‖
refrigeration system with other systems. International Journal of Refrigeration 27 (2004) 587–594.
The following conclusions are obtained on the basis of the [10] M. Hassanain, E. Elgendy, M. Fatouh,‖ Ejector
reviewed studies: expansion refrigeration system: ejector design and
1. Ejector refrigeration systems are have low investment performance evaluation,‖ International Journal of
costs and mechanically simple. However, such refrigeration RefrigerationS0140-7007(15)00157-7.
systems have relatively low COP than other conventional [11] Khaled Ameur, Zine Aidoun, Mohamed Ouzzane,‖
refrigeration technologies. Modeling and Numerical Approach for the Design and
2. At any given evaporator, condenser, and generator Operation of Two-phase Ejectors,‖ Applied Thermal
temperatures, only one unique geometry will result in the EngineeringS1359-4311(14)01020-5.
highest COP and entrainment ratio of the ejector. [12] Nagihan Bilir and H. Kursad Ersoy* ,‖ Performance
3. Dry fluid refrigerants, such as butane, isobutane,R113, improvement of the vapour compression refrigeration cycle
R114, and R141b, require less excessive energy for by a two-phase constant area ejector,‖ International Journal
superheating than wet fluids and yield better performance Of Energy ResearchInt. J. Energy Res. 2009; 33:469–480.
and isentropic fluids at the same operating temperatures. [13] Jianyong Chen, Hans Havtun*, Björn Palm,‖
4. The area ratio between primary nozzles is an important Investigation of ejectors in refrigeration system: Optimum
non-dimensional factor that affects ejector performance. The performance evaluation and ejector area ratios
optimum area ratio depends on the refrigerant type perspectives,‖ Applied Thermal Engineering 64 (2014) 182-
andoperating conditions. 191.
5.With increasing generator temperaturethe optimum value [14] Szabolcs Vargaa, Armando C. Oliveiraa,*, Bogdan
of the primary nozzle diameter decreases. Diaconua.b,‖ Numerical assessment of steam ejector
6.The optimum primary nozzle position or converging angle efficiencies using CFD,‖ International Journal of
cannot be predefined to meet all operating conditions. Refrigeration 32 (2009) I203-I2II.
Whereas from the design point the operating conditions are [15] Jahar Sarkar* et al.,‖ Geometric parameter optimization
different. To maximize ejector performance nozzle exit of ejector-expansion refrigeration cycle with natural
position should be adjusted. refrigerants,‖ International Journal of Energy Research, Int.
7.Constant area section length has no effect on entrainment J. Energy Res. 2010; 34:84–94.
ratio. [16] K.O. Shestopalova, b,*, B.J. Huanga, V.O. Petrenkoa, b,
8.Variable area geometry ejectors based on CRMC methods O.S. Volovyka,‖ Investigation of an experimental ejector
are operate at high critical condenser pressures. refrigeration machine operating with refrigerantR245fa at
design and off-design working conditions. Part 1.
REFRENCES Theoretical analysis,‖ international journal of refrigeration
[1] G. Grazzini, A. Milazzo, D. Paganini, ―Design of an 55 (2015) 201-211.
ejector cycle refrigeration system‖,Energy Conversion and [17] Krzysztof Banasiakb,*, Michał Palacza, Armin Hafnerb,
Management 54 (2012) 38–46. Zbigniew Buli nskia, Jacek Smołkaa, Andrzej J. Nowaka,
[2] B.J. Huang*, J.M. Chang, C.P. Wang, V.A. Petrenko,‖ A Adam Fica,‖ A CFD-based investigation of the energy
1-D analysis of ejector performance‖, International Journal performance of two-phase R744 ejectors to recover the
of Refrigeration 22 (1999) 354–364. expansion work in refrigeration systems: An irreversibility

© 2015, IERJ All Rights Reserved Page 5


www.ierjournal.org International Engineering Research Journal (IERJ) Special Issue 3 Page 152-157, 2016, ISSN 2395-1621

analysis,‖ international journal of refrigeration 40 (2014)


328-337.
[18] Neal Lawrence, Stefan Elbel*,‖ Theoretical and
practical comparison of two-phase ejector refrigeration
cycles including First and Second Law analysis,‖
international journal of refrigeration 36 (2013) 1220-1232.
[19] J.M. Abdulateef*, K. Sopian, M.A. Alghoul*, M.Y.
Sulaiman,‖ Review on solar-driven ejector refrigeration
technologies,‖ Renewable and Sustainable Energy Reviews
13 (2009) 1338–1349.
[20]Jahar Sarkar et al.,‖ Ejector enhanced vapour
compressionrefrigeration and heatpumpsystems—A review,‖
Renewable and Sustainable Energy Reviews 16 (2012)
6647–6659.