TECHNICAL SUBMITTAL

FOR
VENTILATION FANS
Manufactured by:

Project:
BEL AIR CLUSTER

Client:
M/S DAMAC CRESCENT PROPERTIES LLC
Consultant:
M/S ARIF AND BINTOAK
Main Contractor:
M/S DELTA AL EMARATE BUIULDING CONTR. LLC
MEP Contractor:
M/S NASCON ENGINEERING CONTRACTING LLC

Submitted By:
ENERGY INTERNATIONAL
P.O. Box 45217, Abu Dhabi - U.A.E.
22-Jun-22
TABLE OF CONTENT

1. Project Specification & Compliance Statement


2. List of Items

3. Warranty Certificate
4. Catalogue & Technical Data
5. Company Profile and Trade License
6. Vendor List

7. Certificates

8. Approval Certificates
1.
Project Specification &
Compliance Statement
Project Specification
GOLF COMMUNITY

15830 - FANS

Contents
1.0 GENERAL .................................................................................................................................. 2
1.1 REFERENCE ............................................................................................................................... 2
1.2 DESCRIPTION OF WORK.......................................................................................................... 2
1.3 QUALITY ASSURANCE ............................................................................................................ 2
1.4 SUBMITTALS ............................................................................................................................. 3
1.5 MAINTENANCE DATA ............................................................................................................. 3
1.6 PRODUCT DELIVERY, STORAGE AND HANDLING .............................................................. 3
2.0 PRODUCT .................................................................................................................................. 4
2.1 CENTRIFUGAL FANS .............................................................................................................. 4
3.0 EXECUTION..... ...................................................................................................................... . 5
3.1 INSTALLATION..... ............................................................................................................... .. 5
3.2 PRE-OPERATION MAINTENANCE. .................................................................................... .. 5
3.3 START-UP AND INSTRUCTIONS ......................................................................................... .. 5
3.4 TESTING, BALANCING AND COMMISSIONING.......................................................................... 5

Mechanical Specification
15830 – Fans Rev 0 Page 1
GOLF COMMUNITY

1.0 GENERAL

1.1 Reference

Conform to General Requirements for Mechanical Services of Division 15.

1.2 DESCRIPTION OF WORK

1.2.1 Furnish and install fans as indicated on drawings and schedule of equipment

1.2.2 Types of centrifugal fans required for project may include the following:

A. Inline – Centrifugal fans

1.2.3 Refer to other Division 15 sections for vibration control units used in conjunction with fans.

1.2.4 Refer to other Division 15 sections for testing, adjusting, and balancing work
required in conjunction with fans.

1.2.5 Refer to Division 16 sections for the following work:

A. Power supply wiring from power source to power connection on unit. Include starters,
disconnects, and required electrical devices, except where specified as furnished, or factory
installed by manufacturer.

B. Interlock wiring between electrically operated equipment units and between equipment and
field installed control devices.

1.3 QUALITY ASSURANCE

1.3.1 Manufacturer's Qualifications: Firms regularly engaged in manufacture's of


fans of types and sizes required, whose products have been in satisfactory use in
similar service for not less than 5 years.

1.3.2 Codes and Standards:

A. Fans shall be performance tested in accordance with BS EN ISO 5136.


B. Motors shall comply with BS 5000.
C. Impellers shall be dynamically balanced to ISO 1940 Grade 6.3.
D. AMCA Compliance: Provide centrifugal fans bearing the AMCA Certified ratings sea.
Sound rate centrifugal fans in accordance with AMCA 300 "Test Code for Sound rating air
moving devices".
E. ASHRAE Compliance: Test and rate fans in accordance with ASHRAE 51 (AMCA 210)
"Laboratory Methods of Testing Fans for Rating".

1.4 SUBMITTALS

1.4.1 Product Data : Submit manufacturer's technical product data for fans including specifications,
capacity ratings, fan performance, curves with operating point clearly indicated, gages and finishes
of materials, and installation instruction.

Mechanical Specification
15830 – Fans Rev 0 Page 2
GOLF COMMUNITY

1.4.2 Shop Drawings : Submit assembly-type shop drawings showing unit dimensions, weight
loadings, required clearances, construction details, and field
connection details.

1.4.3 Wiring Diagrams : Submit manufacturer's electrical requirements for power supply wiring to fans.
Submit manufacturer's ladder-type wiring diagrams for interlock and control wiring. Clearly
differentiate between portions of wiring that are factory - installed and portions to be field- installed.

1.4.4 Pressure Calculations

Submit pressure drop calculations based on shop drawings for approval by the Consultant before final
selection of the unit.

1.5 MAINTENANCE DATA

Submit maintenance data parts list for each type of fan accessory, and control. Include this data,
product data, shop drawings, and wiring diagrams in maintenance manual.

1.6 PRODUCT DELIVERY, STORAGE AND HANDLING

1.6.1 Deliver fans with factory installed shipping skids and lifting lugs, pack components in factory
fabricated protective containers.

1.6.2 Handle fans carefully to avoid damage to components, enclosures, and finish.
Do not install damaged components; replace and return damaged components to
air handling unit manufacturer.

1.6.3 Store fans in clean dry place and protect from weather and construction traffic.

1.6.4 Comply with manufacturer's rigging and installation instructions for unloading fans and moving
them to final location.

2.0 PRODUCT

GENERAL REQUIREMENTS

A. Contractor shall provide a detailed external static pressure calculations along with the
respective isometrics for approval, during the fans selection and prior to place any order.
B. Fan sound power and vibration levels should be analyzed to determine the required acoustic
and vibration measures. Refer to acoustic study requirements in Section: Mechanical Sound,
Vibration and Seismic Control.
C. When selecting the fan; assure that air velocity at the fan does not exceed 15 m/s.
D. Fan shall be selected such that the duty point on the fan curve falls within 30% of the best
efficiency area of the curve.
E. All fans shall be supplied with a lubrication nipples/means, lifting lugs/eyes, motor access &
mounting base.

2.1 CENTRIFUGAL FANS – General.

Mechanical Specification
15830 – Fans Rev 0 Page 3
GOLF COMMUNITY

2.1.1 Furnish, install and connect up complete, all supply, return, exhaust, transfer and exhaust fans.
All fans shall be of the non-overloading centrifugal type.

2.1.2 Fans shall have direction of rotation, discharge direction indicated on the casing. Fan
arrangement shall be selected to suit the space conditions.

2.1.3 Fan housing shall be rigidly built and braced. Where fan scroll is 480 mm or more in width,
provide access door with frame and gasket. All access doors shall be so fabricated that the inner
surface is flush with the inside of the scroll. Raised frame doors of the pan type shall be
provided on all fans where insulation is required. The doors shall be secured to the frame by
hand-grip latches and shall be provided with lift handles. Bolted doors are not acceptable,

2.1.4 Fans shall not produce excessive noise as compared to units of like size and power when used
in conjunction with the specified vibration isolation. Fan manufacturers shall furnish for
approval for each fan, certified sound power ratings with an octave band analysis and also the
volume-horsepower-pressure characteristic curves from shut-off to free delivery. Wheels shall
have ample strength and shall be statically and dynamically balanced to avoid vibration and
shall have blades designed to ensure quiet efficient operation.

2.1.5 Each fan motor shall be sized to drive it's respective fan when fan is operating at a speed (due
to pulley adjustment) of 10% in excess of that required to meet fan performance, and when the
fan requires the maximum power at this speed.

2.1.6 All fans shall carry the AMCA, or similar approved Certification Association performance and
construction seal.

2.1.7 All fans shall be factory coated with one coat of primer and one coat of machine enamel. The
interior of all fans and all wheels shall be painted as per manufacturer's standard.

2.1.8 All fans discharging directly up through the roof shall be equipped with a 38 mm casing drain
which shall be piped to the nearest floor drain.

2.1.9 All fans scheduled to be arranged as belted vent sets shall have overhung wheels and motors
mounted on a common base with the bearings. All such belted vent sets shall be furnished with
weatherproof motor housings where located outdoors.

2.1.10 All double width, double inlet fans shall be provided with galvanized steel inlet guard screens.

2.6 DUCTED INLINE CENTRIFUGAL EXTRACT FANS

Provide multi-blade centrifugal fans, statically and dynamically balanced, galvanized steel housing
with inlet and outlet collars, and internal service access door. Design fans to overlap the fan venturi.

Housing shall be of heavy gauge, spun steel with baked epoxy finish inside and outside. Impellers
shall be forward curved centrifugal design driven by speed controllable motors with integral
thermal protection. Motors shall be squirrel. Bearings shall be ball type, sealed for life. Speed
controllers shall be supplied by fan manufacturer when required.

Mechanical Specification
15830 – Fans Rev 0 Page 4
GOLF COMMUNITY

3.0 EXECUTION

3.1 INSTALLATION

3.1.1 Install as shown on the drawings, as detailed, and according to manufacturer's installation
instructions. On units provided with a drain connection, reduce drain connection down to inch
fitting and leave open.

3.1.2 Align fan and motor sheaves to allow belts to run true and straight.

3.1.3 Bolt equipment to curbs with galvanized lag bolts.

3.1.4 Install thrust restraints in accordance with the requirements of following


Sections:

A. Section 15060, HANGERS AND SUPPORTS


B. Section 15070, MECHANICAL SOUND, VIBRATION & SEISMIC CONTROL

3.2 PRE-OPERATION MAINTENANCE

3.2.1 Grease bearings.

3.2.2 Rotate impeller by hand and check for shifting during shipment and check all
bolts, collars, and other parts for tightness.

3.3 START-UP AND INSTRUCTIONS

3.3.1 Check vibration and correct as necessary for air balance work.

After air balancing is complete and permanent sheaves are in place perform necessary field
mechanical balancing to meet vibration tolerance in Section 15070, MECHANICAL SOUND,
VIBRATION & SEISMIC CONTROL

3.4 TESTING, BALANCING AND COMMISSIONING

3.4.1 Testing, Balancing and Commissioning shall be as detailed in manufacturers


commissioning literature and in standards listed in this Section as well as per Section 15950
Testing, Adjusting and Balancing.

3.4.2 Coincidentally with the above test, all medium and high pressure ductwork systems as defined
by SMACNA shall be tested for air leakage.
3.4.3 Provide notice of any test to the Consultant in writing in accordance with Contract
requirements so that, where he deems necessary, the Consultant or his representative shall witness
the test. The test rig and all necessary blanks for the purpose of sealing the ductwork under test shall
be provided, and blanks shall be removed after the test has been approved for each section of the
ductwork.
– End of Section –

Mechanical Specification
15830 – Fans Rev 0 Page 5
Compliance Statement
2.
LIST OF ITEMS
3.
WARRANTY CERTIFICATE
4.
CATALOGUE &
TECHNICAL DATA
External Static Pressure (ESP)
TEF-06 ESP CALCULATION

EQUIVALENT HEAD LOSS FACTOR TOTAL HEAD


SN FITTINGS DUCT SIZE (mm) FLOW (L/s)
LENGTH (m) (Pa/m) LOSS(Pa)

1 DISC VALVE DIA 100 25 - - 7.00


2 FLEXIBLE DUCT DIA 100 25 1.50 1.8 2.70
3 FLEXIBLE CONNECTOR 150x150 25 - - 2.50
4 ELBOW 150x150 25 0.00
5 ELBOW 150x150 25 0.00
6 ELBOW 150x151 25 0.00
7 STRAIGHT DUCT 150x150 25 6.50 0.16 1.04

Gose Neck and


8 150x150 25
Screen Wire Mesh
- - 5.00
PRESSURE (Pa) 18.24
15% SAFETY FACTOR 2.74
TOTAL STATIC PRESSURE (Pa) 20.98
TEF-06 ESP CALCULATION

EQUIVALENT HEAD LOSS FACTOR TOTAL HEAD


SN FITTINGS DUCT SIZE (mm) FLOW (L/s)
LENGTH (m) (Pa/m) LOSS(Pa)

1 DISC VALVE DIA 100 25 - - 7.00


2 FLEXIBLE DUCT DIA 100 25 1.50 1.8 2.70
3 FLEXIBLE CONNECTOR150x150 25 - - 2.50
4 ELBOW 150x150 25 0.00
5 ELBOW 150x150 25 0.00
6 ELBOW 150x151 25 0.00
7 STRAIGHT DUCT 150x150 25 9.00 0.16 1.44

Gose Neck and


8 150x150 25
Screen Wire Mesh
- - 5.00
PRESSURE (Pa) 18.64
15% SAFETY FACTOR 2.80
TOTAL STATIC PRESSURE (Pa) 21.44
TEF-05 ESP CALCULATION

EQUIVALENT LENGTH HEAD LOSS FACTOR TOTAL HEAD


SN FITTINGS DUCT SIZE (mm) FLOW (L/s)
(m) (Pa/m) LOSS(Pa)

1 DISC VALVE DIA 100 25 - - 7.00


2 FLEXIBLE DUCT DIA 100 25 1.50 1.8 2.70
3 FLEXIBLE CONNECTOR 150x150 25 - - 2.50
4 ELBOW 150x150 25 0.00
5 ELBOW 150x150 25 0.00
6 STRAIGHT DUCT 150x150 25 5.00 0.16 0.80

Gose Neck and


7 150x150 25
Screen Wire Mesh
- - 5.00
PRESSURE (Pa) 18.00
15% SAFETY FACTOR 2.70
TOTAL STATIC PRESSURE (Pa) 20.70
TEF-04 ESP CALCULATION

EQUIVALENT HEAD LOSS FACTOR TOTAL HEAD


SN FITTINGS DUCT SIZE (mm) FLOW (L/s)
LENGTH (m) (Pa/m) LOSS(Pa)

1 DISC VALVE DIA 100 25 - - 7.00


2 FLEXIBLE DUCT DIA 100 25 1.50 1.8 2.70
3 FLEXIBLE CONNECTOR150x150 25 - - 2.50
4 ELBOW 150x150 25 0.00
5 ELBOW 150x150 25 0.00
6 ELBOW 150x150 25 0.00
7 STRAIGHT DUCT 150x150 25 14.00 0.16 2.24

Gose Neck and


8 150x150 25
Screen Wire Mesh
- - 5.00
PRESSURE (Pa) 19.44
15% SAFETY FACTOR 2.92
TOTAL STATIC PRESSURE (Pa) 22.36
TEF-03 ESP CALCULATION

HEAD LOSS FACTOR


SN FITTINGS DUCT SIZE (mm) FLOW (L/s) EQUIVALENT LENGTH (m) TOTAL HEAD LOSS(Pa)
(Pa/m)

1 DISC VALVE DIA 100 25 - - 7.00


2 EXHAUST DIFFUSER 150x150 15 - 12 12.00
3 FLEXIBLE DUCT DIA 100 25 1.50 1.8 2.70
4 FLEXIBLE CONNECTOR 150x150 25 - - 2.50
5 STRAIGHT DUCT 150x150 15 2.00 0.065 0.13
6 VCD 150x150 15 - 5.00
7 VCD 150x150 25 - 5.00
8 STRAIGHT DUCT 150x150 40 15.00 0.38 5.70
9 ELBOW 150x150 40 - - 0.00
10 ELBOW 150x150 40 - - 0.00
11 ELBOW 150x150 40 0.00
12 ELBOW 150x150 40 - - 0.00
Gose Neck and Screen Wire
13 150x150 40
Mesh - - 7.00
PRESSURE (Pa) 47.03
15% SAFETY FACTOR 7.05
TOTAL STATIC PRESSURE (Pa) 54.08
TEF-02 ESP CALCULATION

HEAD LOSS FACTOR


SN FITTINGS DUCT SIZE (mm) FLOW (L/s) EQUIVALENT LENGTH (m) TOTAL HEAD LOSS(Pa)
(Pa/m)

1 DISC VALVE DIA 100 25 - - 7.00


2 FLEXIBLE DUCT DIA 100 25 1.50 1.8 2.70
3 FLEXIBLE CONNECTOR 150x150 25 - - 2.50
4 ELBOW 150x150 25 0.00
5 ELBOW 150x150 25 0.00
6 VCD 150x150 25 5.00
7 STRAIGHT DUCT 150x150 25 9.00 0.16 1.44
Gose Neck and Screen Wire
8 150x150 25
Mesh - - 5.00
PRESSURE (Pa) 23.64
15% SAFETY FACTOR 3.55
TOTAL STATIC PRESSURE (Pa) 27.19
TEF-01 ESP CALCULATION

HEAD LOSS FACTOR


SN FITTINGS DUCT SIZE (mm) FLOW (L/s) EQUIVALENT LENGTH (m) TOTAL HEAD LOSS(Pa)
(Pa/m)

1 DISC VALVE DIA 100 25 - - 7.00


2 FLEXIBLE DUCT DIA 100 25 1.50 1.8 2.70
3 FLEXIBLE CONNECTOR 150x150 25 - - 2.50
4 STRAIGHT DUCT 150x150 25 12.00 0.16 1.92
5 ELBOW 150x150 25 - - 0.00
6 ELBOW 150x150 25 - - 0.00
7 ELBOW 150x150 25 - - 0.00
8 VCD 150x150 25 5.00
Gose Neck and Screen Wire
9 150x150 25
Mesh - - 5.00
PRESSURE (Pa) 24.12
15% SAFETY FACTOR 3.62
TOTAL STATIC PRESSURE (Pa) 27.74
KEF-01 ESP CALCULATION

HEAD LOSS FACTOR


SN FITTINGS DUCT SIZE (mm) FLOW (L/s) EQUIVALENT LENGTH (m) TOTAL HEAD LOSS(Pa)
(Pa/m)

1 EXHAUST DIFFUSER 150X150 50 - - 12.00


2 STRAIGHT DUCT 150x150 50 18.00 0.56 10.08
3 ELBOW 150x150 50 0.00
4 ELBOW 150x150 50 0.00
5 ELBOW 150x150 50 0.00
6 ELBOW 150X150 50 0.00
7 FLEXIBLE CONNECTOR 150x150 50 - - 2.50
8 FLEXIBLE CONNECTOR 150x150 50 - - 2.50
Gose Neck and Screen Wire
9 150x150 50
Mesh - - 7.00
PRESSURE (Pa) 34.08
15% SAFETY FACTOR 5.11
TOTAL STATIC PRESSURE (Pa) 39.19
TEF-06 ESP CALCULATION

EQUIVALENT HEAD LOSS FACTOR TOTAL HEAD


SN FITTINGS DUCT SIZE (mm) FLOW (L/s)
LENGTH (m) (Pa/m) LOSS(Pa)

1 DISC VALVE DIA 100 25 - - 7.00


2 FLEXIBLE DUCT DIA 100 25 1.50 1.8 2.70
3 FLEXIBLE CONNECTOR150x150 25 - - 2.50
4 ELBOW 150x150 25 0.00
5 ELBOW 150x150 25 0.00
6 ELBOW 150x151 25 0.00
7 STRAIGHT DUCT 150x150 25 6.00 0.16 0.96

Gose Neck and


8 150x150 25
Screen Wire Mesh
- - 5.00
PRESSURE (Pa) 18.16
15% SAFETY FACTOR 2.72
TOTAL STATIC PRESSURE (Pa) 20.88
TEF-05 ESP CALCULATION

EQUIVALENT LENGTH HEAD LOSS FACTOR TOTAL HEAD


SN FITTINGS DUCT SIZE (mm) FLOW (L/s)
(m) (Pa/m) LOSS(Pa)

1 DISC VALVE DIA 100 25 - - 7.00


2 FLEXIBLE DUCT DIA 100 25 1.50 1.8 2.70
3 FLEXIBLE CONNECTOR 150x150 25 - - 2.50
4 ELBOW 150x150 25 0.00
5 ELBOW 150x150 25 0.00
6 STRAIGHT DUCT 150x150 25 5.00 0.16 0.80

Gose Neck and


7 150x150 25
Screen Wire Mesh
- - 5.00
PRESSURE (Pa) 18.00
15% SAFETY FACTOR 2.70
TOTAL STATIC PRESSURE (Pa) 20.70
TEF-04 ESP CALCULATION

EQUIVALENT HEAD LOSS FACTOR TOTAL HEAD


SN FITTINGS DUCT SIZE (mm) FLOW (L/s)
LENGTH (m) (Pa/m) LOSS(Pa)

1 DISC VALVE DIA 100 25 - - 7.00


2 FLEXIBLE DUCT DIA 100 25 1.50 1.8 2.70
3 FLEXIBLE CONNECTOR150x150 25 - - 2.50
4 ELBOW 150x150 25 0.00
5 ELBOW 150x150 25 0.00
6 STRAIGHT DUCT 150x150 25 8.00 0.16 1.28

Gose Neck and


7 150x150 25
Screen Wire Mesh
- - 5.00
PRESSURE (Pa) 18.48
15% SAFETY FACTOR 2.77
TOTAL STATIC PRESSURE (Pa) 21.25
TEF-03 ESP CALCULATION

HEAD LOSS FACTOR


SN FITTINGS DUCT SIZE (mm) FLOW (L/s) EQUIVALENT LENGTH (m) TOTAL HEAD LOSS(Pa)
(Pa/m)

1 DISC VALVE DIA 100 25 - - 7.00


2 FLEXIBLE DUCT DIA 100 25 1.50 1.8 2.70
3 FLEXIBLE CONNECTOR 150x150 25 - - 2.50
4 STRAIGHT DUCT 150x150 15 1.00 0.065 0.07
5 VCD 150x150 15 - 5.00
6 VCD 150x150 25 - 5.00
7 STRAIGHT DUCT 150x150 40 12.00 0.38 4.56
8 ELBOW 150x150 40 - - 0.00
9 ELBOW 150x150 40 - - 0.00
10 ELBOW 150x150 40 - - 0.00
Gose Neck and Screen Wire
11 150x150 40
Mesh - - 7.00
PRESSURE (Pa) 33.83
15% SAFETY FACTOR 5.07
TOTAL STATIC PRESSURE (Pa) 38.90
TEF-02 ESP CALCULATION

HEAD LOSS FACTOR


SN FITTINGS DUCT SIZE (mm) FLOW (L/s) EQUIVALENT LENGTH (m) TOTAL HEAD LOSS(Pa)
(Pa/m)

1 DISC VALVE DIA 100 25 - - 7.00


2 FLEXIBLE DUCT DIA 100 25 1.50 1.8 2.70
3 FLEXIBLE CONNECTOR 150x150 25 - - 2.50
4 ELBOW 150x150 25 0.00
5 ELBOW 150x150 25 0.00
6 STRAIGHT DUCT 150x150 25 8.00 0.16 1.28
Gose Neck and Screen Wire
7 150x150 25
Mesh - - 5.00
PRESSURE (Pa) 18.48
15% SAFETY FACTOR 2.77
TOTAL STATIC PRESSURE (Pa) 21.25
TEF-01 ESP CALCULATION

HEAD LOSS FACTOR


SN FITTINGS DUCT SIZE (mm) FLOW (L/s) EQUIVALENT LENGTH (m) TOTAL HEAD LOSS(Pa)
(Pa/m)

1 DISC VALVE DIA 100 25 - - 7.00


2 FLEXIBLE DUCT DIA 100 25 1.50 1.8 2.70
3 FLEXIBLE CONNECTOR 150x150 25 - - 2.50
4 STRAIGHT DUCT 150x150 25 11.00 0.16 1.76
5 ELBOW 150x150 25 - - 0.00
6 ELBOW 150x150 25 - - 0.00
7 ELBOW 150x150 25 - - 0.00
Gose Neck and Screen Wire
8 150x150 25
Mesh - - 5.00
PRESSURE (Pa) 18.96
15% SAFETY FACTOR 2.84
TOTAL STATIC PRESSURE (Pa) 21.80
KEF-01 ESP CALCULATION

HEAD LOSS FACTOR


SN FITTINGS DUCT SIZE (mm) FLOW (L/s) EQUIVALENT LENGTH (m) TOTAL HEAD LOSS(Pa)
(Pa/m)

1 EXHAUST DIFFUSER 150X150 42 - - 12.00


2 STRAIGHT DUCT 150x150 42 10.00 0.42 4.20
3 ELBOW 150x150 42 0.00
4 ELBOW 150x150 42 0.00
5 ELBOW 150X150 42 0.00
6 FLEXIBLE CONNECTOR 150x150 42 - - 2.50
7 FLEXIBLE CONNECTOR 150x150 42 - - 2.50
Gose Neck and Screen Wire
8 150x150 42
Mesh - - 6.00
PRESSURE (Pa) 27.20
15% SAFETY FACTOR 4.08
TOTAL STATIC PRESSURE (Pa) 31.28
5.
COMPANY PROFILE & TRADE
LICENSE
6.
VENDOR LIST
Bid of Nascon Engineering Contracting DH - BEL AIR - V23.V27 MEP TENDER
BOQ Document Version: V1 Reference: T1
Bid not submitted yet

Item No. Code Code Item Description and Remarks Quantity Units Unit Rate Adj Total Price Documenter Bidder Image
descripti Image
on

1.4.2.1.2.1 D3050.5 kef-01 1.0 No 0.00 --- ---


0.23300
0

1.4.2.2 Toilet Exhaust Fans × 0.00 --- ---

1.4.2.2.1 Supply of Toilet Exhaust fan, high × 0.00 --- ---


temperature single inlet centrifugal
type with control panel and controls ,
anti-vibration steel base, electrical
connections, all in accordance with the
specifications and drawings.Approved
Makes:System Air, Penn, S & P, Dynair,
Flakt woods, Greenheck,Elta,Nuaire and
Elektrovent

1.4.2.2.1.1 D3050.5 tef-01 1.0 No 0.00 --- ---


0.23300
0

1.4.2.2.1.2 D3050.5 tef-02 1.0 No 0.00 --- ---


0.23300
0

1.4.2.2.1.3 D3050.5 tef-03 1.0 No 0.00 --- ---


0.23300
0

1.4.2.2.1.4 D3050.5 tef-04 1.0 No 0.00 --- ---


0.23300
0

Page 53 (of 134) Powered by


7.
Certificates
AMCA Certificate
Test Report
8.
APPROVAL CERTIFICATES

You might also like