Professional Documents
Culture Documents
24
32
considered to ply on the same carriageway. No wind, seismic, footway live load) shall be considered to ply on the same carriageway.
(Refer amendments
temperature gradient, braking force and dynamic impact on the live Effect of wind, seismic, temperature gradient need not be considered
published in Indian
load need to be considered as the SV shall move at a speed not for load combinations with SV loading. In addition, tractive force
Notifications
Highways – January
exceeding 5 kmph over the bridge. For the load combination with / braking force and dynamic impact on live load need not be
2018 issue)
special vehicle, the partial safety factor on SV load for verification considered on the carriageway carrying SV loading. For the load
of equilibrium and structural strength under Ultimate Limit State combination with special vehicle, the partial safety factor on SV load
(Basic Combination) and for verification of Serviceability Limit for verification of equilibrium (as per Table B.1), structural strength
State (Rare Combination) shall be taken as 1.15 and 1.0 respectively. (as per Table B.2) and strength of foundation (as per combination 1
For other accompanying loads, partial safety factors shall be taken of Table B.4) under Ultimate Limit State (Basic Combination) shall
from Annex-B. be taken as 1.15. For verification under Serviceability Limit State
and for other accompanying loads, including the live load surcharge
loading, Table B.3 shall be followed with partial safety factors on
SV load taken as 1.0 under Rare Combination (For stress check)
and 0.75 under Frequent Combination (For deflection and crack
width checks as applicable). Fatigue check is not required under
Load Combination with SV loading.
Note : The movement of Special Vehicle shall be regulated /
monitored to ensure that it moves at a speed less than 5 Kmph and Note : The movement of Special Vehicle shall be regulated /
also does not ply on the bridge on a high wind condition monitored to ensure that it moves at a speed less than 5 Kmph and
also does not ply on the bridge on a high wind condition
3 Sr. No. 4 of FIG. 6B Add a sentence in 2nd column under “No. of Lanes and Carriageway Add following at the end in next para :
(Refer amendments configurations” (Load combinations & partial safety factors as given in clause
published in Indian 204.5.4 shall apply for superstructure carrying SV loading and for
Highways – January 2018 substructure and foundation)
issue)
4 Sr. No. 5 of FIG. 6B Add a sentence in 2nd column under “No. of Lanes and Carriageway Add following at the end in next para :
(Refer amendments configurations” (Load combinations & partial safety factors as given in clause
published in Indian
Highways – January 2018
204.5.4 shall apply for the entire structure)
issue)
5. 206.6 Crash barriers are designed to withstand the impact of vehicles of Crash barriers are designed to withstand the impact of vehicles of
certain weights at certain angle while travelling at the specified certain weights at certain angle while travelling at the specified
Crash Barriers
speed as given in Table 9. They are expected to guide the vehicle speed as given in Table 9. They are expected to guide the vehicle
(Page 26-28) back on the road while keeping the level of damage to vehicle as back on the road while keeping the level of damage to vehicle as
well as to the barriers within acceptable limits. well as to the barriers within acceptable limits.
Table 9: Application for design of Crash Barrier Table 9: Application for design of Crash Barrier
P-1: Normal Bridges carrying expressway, 15 kN vehicle at 110 km/h, P-1: Normal Bridges carrying 15 kN vehicle at
Containment or equivalent and 20o angle of impact Containment Expressway, National & 110 km/h and
(Cast-in-situ or State Highway or Road of 20o angle of impact
P-2: Low All other bridges except 15 kN vehicle at 80 km/h Precast as per equivalent standard except
Containment bridge over railways and 20o angle of impact Fig. 1,2 & 5 of over railways and high-risk
IRC:5-2015) locations
P-3: High At hazardous and high risk 300 kN vehicle at 60 km/h
Containment locations, over busy railway and 20o angle of impact
P-2: High At hazardous and high-risk 300 kN vehicle at
lines, complex interchanges, etc. Containment locations ie, over busy 60 km/h and
(Cast-in-situ railway lines, stretches 20o angle of impact
Notifications
The barriers can be of rigid type, using cast-in-situ/precast as per Fig. 3 of on curves having radius
reinforced concrete panels, or of flexible type, constructed using IRC:5-2015) less than 100 meters and
metallic cold-rolled and/or hot-rolled sections. The metallic type, complex interchanges, etc
called semi-rigid type, suffers large dynamic deflection of the order The crash barriers can be of rigid type, using cast-in-situ/precast
of 0.9 to 1.2 m due to impact, whereas the ‘rigid’ concrete type reinforced concrete panels, or of flexible type, constructed using
suffers comparatively negligible deflection. The efficacy of the metallic cold-rolled and/or hot-rolled sections. The metallic type,
two types of barriers is established on the basis of full-size tests called semi-rigid type, suffers large dynamic deflection of the order
carried out by the laboratories specializing in such testing. Due to of 0.9 to 1.2 m due to impact, whereas the ‘rigid’ concrete type
the complexities of the structural action, the value of impact force suffers comparatively negligible deflection. The efficacy of the two
cannot be quantified.
INDIAN HIGHWAYS
concrete
3) Minimum thickness of R 175 175 250 mm
using the equivalent static nominal loadings from Table 10.
C wall (at top) mm mm
4) Minimum moment of 15 7.5 100 kNm/m for
resistance at base of the kNm/m kNm/m end section and
wall [see note (i)] for 75 kNm/m for
bending in vertical plane intermediate
section [see note
33
(iii)]
34
Types of Crash Barrier Table 10: Equivalent static nominal loads in situ and precast
S. P-1 P-2 P-3 concrete barriers applicable to panel lengths (L) 2.0 m to 3.5 m
Requirement In-situ/ In-situ/ In-situ
No
Precast Precast Barrier Containment Panel nominal Panel nominal shear
INDIAN HIGHWAYS
minimum.
resistance at vertical joints kN/m kN/m
between precast panels, or at of joint of joint ii) Panel Length (L) for cast-in-situ barrier shall not exceed 3.5 m.
vertical joints made between iii) H=Vertical distance in meters from top of barrier to the horizontal
Notifications
lengths of in-situ crash barrier. section where shear force is considered.
iv) Gaps between panels shall be 20 mm. Gaps shall be covered or sealed
8) Minimum 900 mm 900 mm 1550 mm and filled with a durable soft joint filler.
v) *The bending moment to be resisted produced by applying
Notes : transversely a horizontal continuous, uniformly distributed nominal
i) The base of wall refers to horizontal sections of the parapet within 300 load to the top of panel.
mm above the adjoining paved surface level. The minimum moments of vi) **The nominal shear force to be resisted by any transverse section of
resistance shall reduce linearly from the base of wall value to zero at top a panel.
of the parapet. vii) In addition to the main reinforcement on traffic face, secondary
ii) In addition to the main reinforcement, in items 4 & 5 above, distribution reinforcement of area not less than 50 percent of the main
steel equal to 50 percent of the main reinforcement shall be provided in reinforcement shall be provided. The area of reinforcement on outer
the respective faces. face, both vertical and horizontal, shall not be less than 50% of that
iii) For design purpose the crash barrier Type P-3 shall be divided into end in the traffic face. Spacing of reinforcement bars on any face shall not
sections extending a distance not greater than 3.0 m from ends of the exceed 200 mm.
crash barrier and intermediate sections extending along remainder of the viii) If concrete barrier is used as a median divider, the reinforcement is
crash barrier. required to be placed on both sides.
iv) If concrete barrier is used as a median divider, the steel is required to be ix) For in-situ panels, the joint between panels shall extend from the top of the
placed on both sides. panel down to not more than 25mm above the level of paved surface.
v) In case of P-3 In-situ type, a minimum horizontal transverse shear x) Specialist literature may be referred for design of attachment systems
resistance of 135 kN/m shall be provided. and anchorages and their loading for precast concrete parapet panels.
xi) Equivalent static loading as given in Table-10 are also applicable to crash
barrier supported on friction slabs and friction slab too can be designed
for same static loading.
Notifications
Table B.2 Partial Safety Factor for Verification of Structural Strength
For Read
Loads Ultimate Limit State Loads Ultimate Limit State
Basic Combination Accidental Seismic Basic Combination Accidental Seismic
Combination Combination Combination Combination
(1) (2) (3) (4) (1) (2) (3) (4)
Table B.3 Partial Safety Factor for Verification of Serviceability Limit State
For Read
OCTOBER 2019
For Read
Loads Combination Combination Seismic Accidental Loads Combination Combination Seismic Accidental
INDIAN HIGHWAYS
2.1
Add new 1.35 1.0 1.35 1.0
c) Construction live load
Notifications
4.0 Construction
Dead Loads
(weight. of
launching girder, 1.35 1.0 1.0 1.0 4.0 Construction Dead Load 1.35 1.0 1.35 1.0
truss or cantilever
construction
equipment)
5.1 Water Current 1.0 or 0 1.0 or 0 1.0 or 0 5.1 Water Current 1.0 or 0 1.0 or 0 1.0 or 0 1.0 or 0
5.2 Wave Pressure 1.0 or 0 1.0 or 0 1.0 or 0 5.2 Wave Pressure 1.0 or 0 1.0 or 0 1.0 or 0 1.0 or 0
6 Buoyancy 6 Buoyancy
a) For Base
1.0 1.0 1.0 a) For Base Pressure 1.0 1.0 1.0 1.0
Pressure
b) For Structural
0.15 0.15 0.15 b) For Structural Design 0.15 0.15 0.15 0.15
Design
Notifications
(iii) R
CC Wall piers and abutments in longitudinal
(ii) RCC Wall piers and abutments 1.0 1.0 3.0
direction (where hinges can develop)
transverse direction (where plastic
hinge cannot develop) (iv) RCC Single Column 3.0
(iii) R
CC Wall piers and abutments in 3.0 2.5 (v) RCC/PSC Frame ( Refer Note VII) 3.0
longitudinal direction (where hinges
can develop) (vi) Steel Framed 3.0
(iv) RCC Single Column 3.0 2.5 (vii) Steel Cantilever Pier 1.5
(v) RCC/PSC Frame ( Refer Note VI) 3.0 2.5
Bearings and Connections (see note(VI) also) 1.0
(vi) Steel Framed 3.0 2.5
INDIAN HIGHWAYS
ii. Response reduction factor is not to be applied for calculation of ii) Response reduction factor is not to be applied for calculation of
displacements of elements of bridge as a whole. displacements of elements of bridge as a whole.
iii) When elastomeric bearings are used to transmit horizontal
iii. When elastomeric bearings are used to transmit horizontal
seismic forces, the response reduction factor (R) shall be taken
seismic forces, the response reduction factor (R) shall be taken
as 1.0 for all substructure.
as 1.0 for all substructure. In case substructure and foundation
will remain in elastic state, no ductile detailing is required.
37
S. Clause No. & For Read
38
No Page No.
iv. Ductile detailing is mandatory for piers of bridges located in iv) In case substructure & foundations are designed with R=1, no
seismic zones III, IV and V where plastic hinges are likely to form ductile detailing is required.
INDIAN HIGHWAYS
and when adopted for bridges in seismic zone II, for which “R v) Where plastic hinges are likely to be formed in any seismic zone
value with ductile detailing” as given in Table 4.1 shall be used. (including zone II), ductile detailing is mandatory at locations
v. Bearings and connections shall be designed to resist the lesser of plastic hinges.
of the following forces, i.e., (a) design seismic forces obtained vi) Bearings and connections shall be designed to resist the lesser of the
by using the response reduction factors given in Table 4.1 and following forces, i.e., (a) design seismic forces obtained by using
(b) forces developed due to over strength moment when hinge the response reduction factors given in Table 4.1 and (b) forces
is formed in the substructure. For calculation of overstrength developed due to over strength moment when hinge is formed in
moments, (Mo) shall be considered as Mo=γ0 MRd γ0 = the substructure. For calculation of overstrength moments, (Mo)
Overstrength factor & MRD is plastic moment of section, for shall be considered as Mo=γ0 MRd γ0 = Over-strength factor
detail refer Chapter 7 . Over-strength factors for Concrete & MRD is plastic moment of section, for detail refer Chapter 7 .
members: γ0= 1.35 & for Steel members: γ0 = 1.25 Over-strength factors for Concrete members: γ0= 1.35 & for Steel
OCTOBER 2019
members: γ0 = 1.25
vi. The shear force for over strength moments in case of cantilever
vii) The shear force for over strength moments in case of cantilever
piers shall be calculated as MRD/h, “h” is height shown in Fig
Notifications
piers shall be calculated as Mo/h, “h” is height shown in
7.1 in Chapter 7. In case of portal type pier capacity of all
Fig. 7.1 in Chapter 7. In case of portal type pier capacity of all
possible hinges need to be considered.
possible hinges need to be considered.
vii Capacity Design should be carried out where plastic hinges are viii) Capacity Design should be carried out where plastic hinges are
likely to form. likely to form.
ix) The R factor for ductile behavior specified in Table 4.1 may
be used only if the location of relevant plastic hinges are
accessible for inspection and repair. Otherwise, under situation
of inaccessibility of plastic hinges the Factor R given in Table
4.1 shall be multiplied by 0.6; however, R value less than 1.0
need not be used.
3 Title of Clause 4.7 Seismic Effects on Earth Pressure & Dynamic Component 4.7 Lateral Earth Pressure under Seismic Condition & Seismic in
4.7 For seismic effects on earth pressure and dynamic component the clause Embedded portion of Structure
(Page 30) 214.1.2 of IRC-6-2017 shall be referred. 4.7.1 Lateral Earth Pressure under Seismic Condition
The modified earth pressure forces described in above clause need not For seismic effects on earth pressure, the clause 214.1.2 of IRC-6-2017
be considered on the portion of the structure below scour level. shall be referred.
For embedded portion of foundation at depths exceeding 30 m below The modified earth pressure forces described in above clause need not
scour level, the seismic force due to foundation mass may be computed be considered on the portion of the structure below scour level.
using design seismic coefficient equal to 0.5Ah. For portion of foundation 4.7.2 Seismic in Embedded portion of Structure
between the scour level and up to 30 m depth, the seismic force due
For embedded portion of foundation at depths exceeding 30 m below
to that portion of foundation mass may be computed using seismic
scour level, the seismic force due to foundation mass may be computed
coefficient obtained by linearly interpolating between Ah at scour level
using design seismic coefficient equal to 0.5Ah. For portion of foundation
and 0.5Ah at a depth 30 m below scour level.
between the scour level and up to 30 m depth, the seismic force due
to that portion of foundation mass may be computed using seismic
coefficient obtained by linearly interpolating between Ah at scour level
and 0.5Ah at a depth 30 m below scour level.
S. Clause No. & For Read
No Page No.
4 Fig 5.1 (a) & (b) Natural period T,5 Natural period T, secs
(Page 35)
5 5.3 In bridges where pier height are high……. In bridges where pier heights are high……
(Page 38)
6 6.3.1 Sr. V, v. The capacity protected regions of substructure/foundation can be v. The capacity protected regions of substructure may be designed
(Page 41) designed elastically without ductility provisions. without ductility provisions.
7 6.3.2, Force demands for essentially elastic components adjacent to ductile Force demands for essentially elastic components adjacent to plastic
(Page 42) components should be determined by capacity-design principle, that is, hinges should be determined by capacity-design principle, that is, joint-
joint-force equilibrium conditions; considering plastic hinge capacity force equilibrium conditions; considering plastic hinge capacity at hinge
at hinge location multiplied by over strength factor. The over strength location multiplied by over strength factor in-principal direction of
factors should not be used where plastic hinges are not likely to be earthquake. The over strength factors should not be used where plastic
formed. Force demands calculated from linear elastic analysis should hinges are not likely to be formed. Force demands calculated from linear
not be used in capacity protected regions elastic analysis should not be used in capacity protected regions
8 6.4.3 (v) v. Wherever the elastomeric bearings are used, these bearing shall v. In case, in-plane horizontal seismic forces are to be transmitted using
Notifications
(Page 43) accommodate imposed deformations and normally resist only non- elastomeric bearings, they shall be checked using minimum dynamic
seismic actions. The resistance to seismic action is provided by structural frictional value and minimum vertical loads, including combined effect
connections of the deck to piers or abutments through suitable means. of vertical and horizontal components of earthquake. In such cases
In case, in-plane horizontal seismic forces are to be transmitted using these suitable devices for preventing dislodgement of superstructure shall be
elastomeric bearings, they shall be checked using minimum dynamic provided.
frictional value and minimum vertical loads, including combined effect Where high damping elastomeric bearings are used to resist seismic
of vertical and horizontal components of earthquake. In such cases action, these may be designed to act as seismic isolation bearing for
suitable devices for preventing dislodgement of superstructure shall be which Chapter-10 shall be referred.
provided.
INDIAN HIGHWAYS
10 7.3 (e) The final step in the design is to determine the forces in the members The final step in the design is to determine the forces in the members
( Page 47) adjacent to plastic hinge which are to remain elastic, by capacity design adjacent to plastic hinge which are to remain elastic, by capacity design
procedure explained in the following section. This includes sections of procedure explained in the following section. This includes sections of
pier outside the plastic hinge and the foundations pier outside the plastic hinge and the foundations. For this purpose, the
combination of component of motion as given clause 4.2.2 for capacity
design effects is not applicable
39
S. Clause No. & For Read
40
No Page No.
11 Fig 7.2
(Page 56)
INDIAN HIGHWAYS
OCTOBER 2019
Notifications
12. 8.3.2 Cl. 8.3.2 Force Transfer mechanism from bearing to abutment Cl. 8.3.2 Force Transfer mechanism from bearing to abutment
(Page 58) and pier and pier
The transfer of force through connection between substructure and The transfer of force through connection between substructure and
superstructure is an important aspect in design of substructure. superstructure is an important aspect in design of substructure.
The connections between supporting and supported members The connections between supporting and supported members
shall be designed in order to ensure structural integrity and shall be designed in order to ensure structural integrity and
avoid unseating under extreme seismic displacements. The piers avoid unseating under extreme seismic displacements. The piers
shall be designed to withstand shear forces corresponding to shall be designed to withstand shear forces corresponding to
the pier’s plastic hinge capacity. The maximum induced shear the pier’s plastic hinge capacity. The maximum induced shear
S. Clause No. & For Read
No Page No.
in the piers shall be limited to the plastic hinge moment (or moments) in the piers shall be limited to the plastic hinge moment (or moments)
divided by the height of pier as ascertained in Chapters 4 and 7. divided by the height of pier as ascertained in Chapters 4 and 7.
For Seismic Zone IV and V, use of elastomeric bearings for resisting For use of elastomeric bearing in seismic zone IV&V reference shall be
horizontal seismic actions by shear deformation, shall not be permitted. made to clause 3.4.2
In such cases PoT, POT Cum PTFE and Spherical Bearings shall be
In seismic design, the fixed bearing shall be checked for full seismic force
adopted over elastomeric bearings for resisting seismic loads.
along with braking / tractive force, ignoring the relief due to frictional
In seismic design, the fixed bearing shall be checked for full seismic force
forces in other free bearings. The structure under the fixed bearing shall
along with braking / tractive force, ignoring the relief due to frictional
be designed to withstand the full seismic and design braking / tractive
forces in other free bearings. The structure under the fixed bearing shall be
force.
designed to withstand the full seismic and design braking / tractive force.
13 Table 5.3 Table 5.3 Method of Analysis of Various Type of Bridges Replace existing Table 5.3 with new table as given below:
(Page 40)
Table 5.3 :- Method of Analysis on various Type of Bridges
Span Length/ Pier Height Method of analysis in Seismic Zone
Type of Bridge Remarks
Notifications
Condition II & III IV & V
Simply Supported individual span 0 to 60m Up to 30m ESAM/ERSM ESAM/ERSM
Above 30 m ERSM ERSM
Simply Supported individual span 60 to 150m Up to 30m ESAM/ERSM ERSM
Above 30 m ERSM ERSM
Right Individual Span > 150m Up to 30m ESAM ERSM
Bridge or Above 30 m ERSM ERSM
Skew Up to <150m between All heights ERSM ERSM
30 ◦ or Continuous/Integral Bridges/Extradosed exp. joints.
curved
INDIAN HIGHWAYS
bridges >150m between All heights ERSM ERSM* Spatial Variation of ground motion
span exp. joints to be considered
having Bridges Located on Geological discontinuity All Spans All heights ERSM* ERSM* Refer Note 3
radius more
Major Bridges in "Near field or Bridges on
than 100m
soils consisting of marine clay or loose sand
All Spans All heights ERSM* ERSM# #site Specific Spectrum preferable
( eg where soil up to 30m depth has an avg
SPT value≤10)
Filled up Arch - ESAM/ERSM ESAM/ERSM
Arch Bridges -
All other Arch ERSM ERSM
Difference in Pier Heights/Stiffness Large All heights ERSM ERSM Refer Note 4
Curved in Plan < 100 m radius All heights ERSM ERSM*
OCTOBER 2019
Bridge
With Skew Angle >30 ◦ All heights ERSM ERSM*
Cable Stay, Suspension spans Main Span #site Specific Spectrum for zone IV
All heights ERSM* ERSM#
<600m & V preferable
Evaluation of liquefaction potential
Bridges founded on site with sand or poorly graded sand with
All heights ERSM ERSM shall be carried out as given in
little or no fines or in liquefiable soil in all seismic zones
Appendix A5
Bridges with shock transmission units (STU), Seismic #site Specific Spectrum preferable
All heights ERSM# ERSM#
isolation devices or Seismic dampers etc
41
42
S. Clause No. /
For Read
NO Page No.
14 9.2.3 9.2.3 Load and Load Combinations 9.2.3 Load and Load Combinations
(Page 79-80) 1. Earthquake loads and response reduction factor shall be as 1. Earthquake loads and response reduction factor shall be as per these
INDIAN HIGHWAYS
Notifications
to design axial compressive strength (without elastic buckling) of member shall be taken as greater of (a) & (b) below:
Pd (i.e., Pr / Pd ) is greater than 0.4, the required axial compressive a) Factored compressive load. Pr as per Table B.2 of IRC:6
strength of member in the absence of applied moment shall also b) Minimum of (i) & (ii) below
be determined from the load combination given in 9.2.3. The i) Strength required using load combination given in clause 9.2.3.
required strength so determined need not exceed the maximum ii) Direct factored load on column + maximum load transferred to column
load transferred to the member considering 1.25 times over by connected beams and/or bracings considered over strength (1.25 times
strength of the connecting beam or bracing element. nominal strength ) of such beam/bracing.
Where Pd is design axial compressive strength without elastic buckling
17 9.2.7.1 9.2.7.1 Moment resisting frames shall be designed so that plastic 9.2.7.1 Moment resisting frames shall be designed so that plastic hinges form at the
(Page 85) hinges form in the beams or in the connections of the beams to base of column or in the beams not supporting the superstructure or in their connection
the columns, but not in the columns. Depending on the detailing, a to column. Plastic hinge should not form in the beam directly supporting superstructure
moment resisting frame can be classified as either an ordinary moment or at other location in the column. Depending on the detailing, a moment resisting
frame (OMF) or a special moment frame (SMF). Moment resisting frame can be classified as either an ordinary moment frame (OMF) or a special
frames are usually provided in the steel piers, end diaphragms of moment frame (SMF). Moment resisting frames are usually provided in the steel
girder bridges and end portals (for wind) of through open web girder piers, end diaphragms of girder bridges and end portals (for wind) of through open
bridges. A higher value of R is assigned to the SMF but more stringent web girder bridges. A higher value of R is assigned to the SMF but more stringent
ductility detailing requirements need to be satisfied so as to achieve ductility detailing requirements need to be satisfied so as to achieve the required
the required plastic joint rotation θp (see Fig. 9.6) plastic joint rotation θp (see Fig. 9.6).
18 9.2.7.2 iii) The rigid and semi-rigid connections should be designed to iii) The rigid and semi-rigid connections should be designed to withstand a
(iii), below withstand a shear resulting from the load combination 1.2 DL + shear resulting from the load combination 1.35 DL + 1.75 Surfacing + 0.2 LL
second para- 0.5 LL plus the shear corresponding to the design moment defined plus the shear corresponding to the design moment defined above in (i) and (ii)
(Page 86) above in (i) and (ii) respectively. respectively.
19 9.2.7.3 The connection shall be designed to withstand a shear resulting The connection shall be designed to withstand a shear resulting from the load
third para from the load combination combination
(Page 87) 1.2DL + 0.5LL plus the shear resulting from the application of 1.35 DL + 1.75 Surfacing + 0.2LL plus the shear resulting from the application of
1.2MP in the same direction, at each end of the beam (causing 1.2MP in the same direction, at each end of the beam (causing double curvature
double curvature bending). The shear strength need not exceed the bending). The shear strength need not exceed the required value corresponding to
required value corresponding to the load combination in 9.2.3 the load combination in 9.2.3.
S.NO Clause No.
For Read
/ Page No.
20 Chapter 10,
Title, SEISMIC ISOLATION DEVICE SEISMIC ISOLATION & DAMPING DEVICES
( Page 89)
This chapter deals with the design of bridges incorporating Seismic This chapter deals with the design of bridges incorporating Seismic base
Insolation Devices. Some of the currently known seismic Isolation & damping devices. Some of the currently known seismic isolation
isolation devices are: devices are:
i) Hydraulic Viscous Damper i) Low damping Elastomeric Bearing
ii) Elastomeric Bearing Damper (Low Damping Elastomer) ii) High Damping Rubber Bearing (HDR)
iii) High Damping Elastomeric Bearing Damper iii) Lead-Rubber Bearing (LRB)
iv) Lead-Rubber Bearing Damper iv) Friction Pendulum System ( FPS)
v) Friction Damper Following types of damping devices in isolation system may be adopted:
Provision of isolation devices is optional and it may be decided i) Viscous Damper
by the designer on a case to case basis. Various types of isolation ii) Friction Damper
devices have different mechanism of seismic force reduction. iii) Visco Elastic Damper
Seismic Isolation devices covered in this chapter are permitted to iv) Hysteresis damper
Notifications
be used for comparatively rigid structures where fundamental time Provision of isolation devices is optional and it may be decided by the designer
period ‘T’ of the structure without incorporation of seismic isolation on a case to case basis. Seismic Isolation devices covered in this chapter are
devices is less or equal to 1.0 sec. In the case of Type III soft soil, permitted to be used for comparatively rigid structures where fundamental time
seismic isolation devices shall be avoided. period ‘T’ of the structure without incorporation of seismic isolation devices
Reduction of response is achieved through either of the following is less or equal to 1.0 sec. In the case of Type III soft soil, seismic isolation
phenomena: devices shall be avoided.
i) By lengthening of the fundamental period of the structure The Reduction of response and control of displacement in isolation system can
10.1-
(effect of period shift in the response spectrum), which be achieved by following methods:
General,
reduces forces but increases displacements; i) By lengthening of the fundamental period of the structure (effect of
from 2nd
ii) By increasing the damping, which reduces displacements and period shift in the response spectrum), which reduces forces but increases
INDIAN HIGHWAYS
para-
may reduce forces; displacements;
(Page 89)
iii) By a combination of the two effects (preferred). ii) By introducing a damping device in parallel with isolation devices, the
Isolation Devices provide single or combination of the following displacement at the isolation level can be limited and arrived at acceptable
functions: level.
iv) Vertical-load carrying capability, combined with high lateral iii) Instead of introducing separate damping device one may adopt HDR or
flexibility and high vertical rigidity; LRB which can serve both as isolation bearing as well as a damping
v) Energy dissipation (hysteretic, viscous, frictional); device. Similarly FPS can serve both the purpose of period elongation as
vi) Lateral restoring capability; well as damping.
vii) Horizontal restraint(sufficient elastic stiffness) under non- Isolation Devices provide single or combination of the following functions:
seismic service horizontal loads i) Vertical-load carrying capability, combined with high lateral flexibility
Strength and integrity of the Isolation Device used is of utmost and high vertical rigidity;
OCTOBER 2019
importance, due to the critical role of its displacement capability for ii) Energy dissipation (hysteretic, viscous, frictional);
the safety of the bridge. For all types of Isolation Devices excepting iii) Lateral restoring capability;
simple elastomeric low damping bearings and flat sliding bearings, iv) Horizontal restraint (sufficient elastic stiffness) under non-seismic service
the design properties shall be verified through established test horizontal loads
methods. Strength and integrity of the Isolation Device used is of utmost importance, due
to the critical role of its displacement capability for the safety of the bridge.
For all types of Isolation Devices excepting simple elastomeric low damping
bearings and flat sliding bearings, the design properties shall be verified through
43
24
OCTOBER 2019
Notifications
Fig. 10.2,
Title,
(Page 92)
Fig. 10.2: Acceleration and displacement spectra Fig. 10.2: Acceleration Spectra
25 Note 2 Note 2: Maximum Teff shall be restricted to 4 sec. Brides with higher Note 2: Maximum Teff shall be restricted to 4 sec. Bridges with higher Teff need
(Page 92) Teff need special precautions due to very low stiffness against special precautions due to very low stiffness against horizontal action
horizontal action
Fig. 10.3,
Replace existing Fig 10.3
(Page 93)
Notifications
designing each isolator ‘i’ for increased displacement dbi,a
displacement after incorporating the device into the structure etc
are needed for the design of structure incorporating Friction Sliding dbi,a = y ISdbi,d Eq. 10.15
Dampers Where y Is is an amplification factor (taken as 1.50) that is applied only on the
design displacement dbi,d in each isolation device i resulting from one of the
procedures specified in 10.2.
The maximum total displacement of each isolation device in each direction shall
be obtained by adding to the above increased design seismic displacement, the
offset displacement potentially induced by:
a) the permanent actions
b) the long-term deformations (post-tensioning, shrinkage and creep for
INDIAN HIGHWAYS
properties of components lead to higher design forces and lesser properties lead
to larger displacements. Hence, two sets of values, namely upper bound design
properties (UBDP) and Lower bound design properties (LBDP) need to be
considered in the analysis and design. However, in case the design displacements
calculated using Fundamental mode analysis based on UBDP and LBDP do not
differ by more than ±15%, response spectrum analysis or Time-history analysis
may use nominal design properties.
For determination of variation in properties, if required to be used in the
analysis, specialist literature may be followed.
45
46
27 10.8 10.8 Verification of Bridge Sub-structure and Superstructure 10.8 Verification of Bridge Sub-structure and Superstructure with
(Page 95-97) with Isolating System Isolating System
dbi,a = y ISdbi,d Eq. 10.15 The Seismic internal forces EEA, derived from analysis, in the substructures and
superstructure due to the design seismic action alone, shall be derived from the
INDIAN HIGHWAYS
Where y Is is an amplification factor (taken as 1.50) that is applied results of an analysis in accordance with 10.2. The design seismic forces EE due
only on the design displacement dbi,d in each isolation device i to the design seismic action alone, may be derived from the forces EEA, after
resulting from one of the procedures specified in 10.2. division by the Response Reduction Factor ‘R’ =1, i.e. FE = FE.A/R with R = 1.0.
The maximum total displacement of each isolation device in each All members of the structure should be verified to have an essentially elastic
direction shall be obtained by adding to the above increased design behaviour as per the relevant clauses. The design horizontal forces of supporting
seismic displacement, the offset displacement potentially induced members (piers or abutments) carrying sliding bearings shall be derived from the
by: maximum friction values as per relevant clauses of the bearing design code.
d) the permanent actions In the case of sliding bearings as mentioned above and when the same supporting
e) the long-term deformations (post-tensioning, shrinkage and member also carries viscous fluid dampers, then the design horizontal seismic
creep for concrete decks) of the superstructure, and force of the supporting member in the direction of the action of the damper should
be increased by the maximum seismic force of the damper, refer eqn. 10.16.
OCTOBER 2019
Notifications
supported on the same supporting elements(s), the phase difference between
displacements.
the maxima of the elastic and the viscous elements may be taken into account,
Note: The maximum reaction of hydraulic viscous dampers (see by the following approximation. The seismic force should be determined as the
10.11) corresponding to the increased displacement dbi,a may be most adverse of those corresponding to the following characteristic states:
estimated by multiplying the reaction resulting from the analysis
a. At the state of maximum displacement. The damper forces are then
times y IS α b / 2 where α b is the exponent of velocity of viscous equal to zero.
damper. b. At the state of maximum velocity and zero displacement, when the
Isolation devices consisting of simple low-damping elastomeric maximum damper forces should be determined by assuming the
bearings should be verified for the action effects in accordance with maximum velocity to be:
relevant clauses of the bearing design code, taking partial factor for ν max = 2πdbdbd //TTeffeff Eq. 10.16
material y m = 1.15. For simple low damping elastomeric bearings,
Where dbd is the maximum damper displacement corresponding to the design
in addition to the above verification, the following condition should
displacement dcd of the isolating system.
be verified:
c At the state of the maximum inertial force on the superstructure, that
εq,d ≤ 2.0 Eq. 10.16
should be estimated as follows:
Where εq,d is the shear strain calculated in accordance with relevant Fmax = ( f1 + 2ξ b f 2 )Se M d Eq. 10.17
clauses of the bearing design code. In this context the movements
Where Se is determined from Table 10.1
ν x.d and νydyd should be taken equal to the maximum total relative
displacements in the horizontal directions x and y. f1 = cos[arctan(2ξb)] Eq. 10.18a
No uplift of isolators carrying vertical force shall be permitted in f 2 = sin[arctan(2ξb)] Eq. 10.18b
the seismic design combination.
Sliding elements shall be designed as per relevant clauses of the Where ξb is the contribution of the dampers to the effective damping ξ eff
bearing design code. of Eq. 10.1.
The Seismic internal forces EEA, derived from analysis, in the At this state the displacement amounts to f d and the velocity of the dampers
1 ccd
d
substructures and superstructure due to the design seismic action
alone, shall be derived to ν = f 2ν max
from the results of an analysis in accordance with 10.2. The design In isolating systems consisting of a combination of fluid viscous dampers and
seismic forces EE due to the design seismic action alone, may elastomeric bearings, without sliding elements, the design horizontal force
be derived from the forces EEA, after division by the Response acting on supporting element(s) that carry both bearings and dampers for non-
Reduction Factor ‘R’ =1, i.e. FE = FE.A/q with R = 1.0. All members seismic situations of imposed deformation actions (temperature variation, etc.)
of the structure should be verified to have an essentially elastic should be determined by assuming that the damper reactions are zero.
behaviour as per the relevant clauses. The design horizontal forces of
supporting members (piers or abutments) carrying sliding bearings
shall be derived from the maximum friction values as per relevant
clauses of the bearing design code.
Notifications
and fluid viscous dampers supported on the same supporting
elements(s), the phase difference between the maxima of the elastic
and the viscous elements may be taken into account, by the following
approximation. The seismic force should be determined as the most
adverse of those corresponding to the following characteristic
states:
a. At the state of maximum displacement. The damper forces are
then equal to zero.
b. At the state of maximum velocity and zero displacement,
INDIAN HIGHWAYS
Fmax
OCTOBER 2019
f1d ccdd
INDIAN HIGHWAYS
29 Appendix A-1 Illustration of elastic seismic acceleration method Replace existing Appendix A-1 with new
Notifications
30 Appendix A-2 Illustration of elastic response spectrum method Replace existing Appendix A-2 with new
31 Appendix A-3 Illustration of Seimic Acceleration Method Preamble Replace existing Appendix A-3 with new
32 Appendix A-4 Illustration of hydrodynamic Pressure on Bridge Piers Replace existing Appendix A-4 with new
33 Appendix A-5 Illustration of Liquefaction of soil Replace existing Appendix A-5 with new
Notifications
CALCULATE TIME
DEFINE SEISMIC
PARAMETERS DEFINE MEMBER
IDEALIZATION DEFINE MEMBER
STIFFNESS DEFINE MEMBER
LOADS PERIOD & BASE
SHEAR
Note:
For the purpose of this analysis, pier is assumed to be
fixed at top of open foundation and mass is lumped at top
of bearing i.e., 10.05 m above top of open foundation.
Step 3: Define member stiffness
Fig. A1.1: Typical Elevation The stiffness of Elastomeric bearing is calculated based on
the Shear rating of the bearing as follows: obtained by vectoral addition of vX & vY (for stiffness
computation – unit deflection)
RXY = Resultant of the forces resisting to translatory
motion, Te = Total thickness of elastomer in shear = 50 mm
RXY/vXY = (n A G)/Te (refer IRC 83 Part-II)
n = Total number of bearings on pier cap = 4
A = Total plan area of bearing = 500 x 500 = 4x500 x 500 x 0.7
50
G = Shear modulus of bearing (IRHD 50) = 0.7 Mpa = 14000 N/mm
vXY = Maximum resultant horizontal relative displacement = 14000 kN/m
Ixx / Iyy
Foundation Depth 1.5 m Area 16.0 m2
Width 4.0 m Ixx 21.33 m4 35 32
Length 4.0m Iyy 21.33 m 4
F = 11188.3/1000 = 0.87
Note:
The stiffness of pier cap is not considered separately for the =
sake of simplicity.
The length L is taken from the top of bearing to the top of
foundation.
Calculate the dead load idealized as a lumped mass:
= 0.084
The dead load idealized as a lumped mass, D
Calculate base shear:
= Mass from superstructure +
Mass of pier cap + S. Component Loads Design seismic Seismic
Half mass of pier No. (kN) acceleration force
coefficient (Ah) (kN)
= 6050 + 420 + 333.6
= 6803.6 kN 1 Super 5000.0 0.084 418.60
structure
The time period based on the approximate method, T 2 Crash barrier 480.0 0.084 40.19
3 Wearing 570.0 0.084 47.72
course
4 CWLL 0.0 0.084 0.00
5 Pier cap 420.0 0.084 35.16
6 Pier above 588.8 0.084 49.29
= 1.56 sec GL (7.5m)
Calculation of Base shear: 7 Pier below 78.5 0.083 6.52
Since time period is 1.56 sec, as per clause 5.2.1: Sa/g GL (1m)
= 1.36 / T; 0.55s < T < 4.00s 8 Foundation 600.0 0.081 48.77
Base Shear: 646.24
Calculate Sa/g =
In this example, a bridge with two span continuous example illustrates the mathematical modelling, member
superstructure resting on fixed and free bearings is properties for analysis, loading, determination of natural
analyzed for assessment of seismic forces with ERSM as frequency, mode shapes and calculation of base shear by
per clause 5.2.2 and Fig. 5.1(b) of Chapter 5. Fig. A.2.1.1 using a commercial software.
shows the bridge elevation with pile foundation. The
CALCULATE TIME
DEFINE SEISMIC
PARAMETERS DEFINE MEMBER
IDEALIZATION DEFINE MEMBER
STIFFNESS DEFINE MEMBER
LOADS PERIOD & BASE
SHEAR
WORK FLOW FOR CALCULATING THE BASE Direction for Seismic Analysis = Longitudinal
SHEAR WITH ERSM
Zone factor, Z
Step 1: Define Seismic parameters
The variables involved in finding out the seismic coefficient The bridge is located in zone III.
are as follows: Therefore, as per Table 4.2: Z = 0.16
Importance factor, I
The bridge is categorized as Seismic class
"Important bridges".
Therefore, as per Table 4.3: I = 1.2
Response reduction factor, R
As per Table 4.1: R =3
Average response acceleration coefficient, Sa/g
The soil strata is categorized as Medium stiff soil
sites.
Therefore, as per clause 5.2.2: Sa/g
= 1 + 15T : T < 0.10s Fig. A2.1.3: Fig. A2.1.4:
Variation of Seismic Coefficient Member Idealization
= 2.5 ; 0.10s < T < 0.55s
= 1.36 / T ; 0.55s < T < 4.00s
Notes:
= 0.34 ; T > 4.00s
The depth of fixity is calculated based on IS 2911 (Part
Step 2: Define member Idealization
1/Sec 2). In this example it is assumed as 6m from base
of pile cap.
The pile is modelled as a free-standing element from
bottom of pile cap to depth of fixity.
The base of pile is assumed as fixed at the depth of fixity.
Step 3: Define member stiffness
Summary of member stiffness:
1.5
Depth Area 12.6 m2
m
Notes:
The stiffness of pier is reduced by 25% to cater for cracking of the
element during seismic case. The same can be modified based on
the actual cracked stiffness with the help of rigorous analyses.
All other components are assumed to be uncracked. The same
can be modified based on the actual cracked stiffness with the
help of rigorous analyses.
Step 4: Define Member Loads
Mass of superstructure (including deck slab)
= 5000 kN x 2
= 10000 kN
Mode Shape – 1 Mode Shape –2
Mass of crash barrier = 480 kN x 2
Summary of Time period & Modal participation factor:
= 960 kN Participation Design
Mass of wearing course = 570 kN x 2 Frequency Time factor (%) seismic
Mode (Cycles/ Period Sa/g acceleration
= 1140 kN Sec) (Sec) Individual Cumulative coefficient
(Ah)
Mass of CWLL (as applicable) = N.A.
1 0.48 2.10 85.01 85.01 0.65 0.021
Total mass from superstructure = 12100 kN
2 7.29 0.14 14.97 99.98 2.50 0.080
Mass of pier cap = 12.60 x 1.50 x 25
The shear force & bending moment diagram as output
= 472.5 kN from the commercial software is shown below:
Mass of pier = 4.91 x 1.0 x 25
= 122.8 kN/m
Mass of pile cap = 26.01 x 1.80 x 25
= 1170.5 kN Shear force at pier
base: 283kN
Mass of pile = 1.13 x 1.0 x 25
= 28.3 kN/m
Step 5: Calculate time period & Base shear
Calculation of time period by commercial software:
The number of modes to be used in the analysis for
earthquake shaking along a considered direction,
should be such that the sum total of modal masses of Bending moment at pier
these modes considered is at least 90 percent of the base: 5724 kNm
total seismic mass.
The mode shapes, time periods & participation factor are For foundation design, capacity design shall be done as per
calculated with the help of a commercial software. Clause 7.3.4.3 (iv) of IRC:114
This example illustrates the Elastic Response Spectrum pier height of 45m resting on open foundation. The spans
Method for computation of seismic forces as per clause resting on pier are supported on fixed bearings on one side
5.2.2 and Spectra shown in Fig.5.1(b) of IRC:SP:114. and free bearings on other side of pier center. The example
The bridge analyzed is a simply supported bridge with a illustrates the mathematical modelling, determination of
natural frequency, mode shapes, lateral seismic forces and I longitudinal @ top = 4.17 m4
base shear in longitudinal and transverse directions using I transverse @ top = 39.17 m4
a commercial software.
Section at Node 2:
Design Data
Area of Pier section @ m2 = 10.16 m2
Self-weight of Superstructure I longitudinal @ m2 = 9.54 m4
+ SIDL = 10000 kN I transverse @ m2 = 52.38 m4
Self-weight of Pier cap = 1200 kN Section at Node 1:
Live Load on superstructure = 1500 kN Area of Pier section @ m1 = 12.51 m2
I longitudinal @ m1 = 18.23 m4
Seismic Zone = III
I transverse @ m1 = 66.98 m4
Zone Factor Z = 0.16
Section 4 at base:
Importance Factor I = 1.5
Area of Pier section @ bottom = 15.04 m2
Response Reduction Factor R = 3.0 I longitudinal @ bottom = 31.11 m4
Grade of concrete fck = 25 MPa I transverse @ bottom = 82.84 m4
Stiffness of pier in Transverse direction, k3 Total horizontal load at m3 [DL + SIDL + wt. of pier
= 9.16E+05 kN/m (7.5m ht.)] = 12870 kN
Total horizontal load at m2 [Wt. of pier (15m ht.)]
For Member 2
= 3755 kN
Area for section of member 2 Total horizontal load at m1 [Wt. of pier (15m ht.)]
= 11.33 m2 = 4618 kN
Moment of Inertia in Longitudinal direction, I longitudinal
Basic Steps in Response Spectrum Method:
= 13.89 m4
Cracked I longitudinal (Assuming 75% of uncracked) Step-1 Frame Mass Matrix, M
= 13.89 x 0.75 = 10.42m4 m1 0 0
Stiffness of pier in Longitudinal direction, k2 M = 0 m2 0
= 2.78E+05 kN/m 0 0 m3
Moment of Inertia in transverse direction, I transverse
= 59.68 m4 Step-2 Frame Stiffness Matrix, K
Cracked I transverse (Assuming 75% of uncracked) k1+k2 -k2 0
= 59.68 x 0.75 = 44.76 m4 K = -k2 k2+k3 -k3
Stiffness of pier in Transverse direction, k2 0 -k3 k3
= 11.94E+05 kN/m
Step-3 Determine Eigenvalues, ω2 by [K-ω2M]
For Member 1
= 0 for each Mode=ω12, ω22, ω32
Area for section of member 1
= 13.77 m2 Step-4 Determine Natural Frequency for each Mode
Moment of Inertia in Longitudinal direction, I longitudinal =ω1, ω2 & ω3
= 24.67 m4
Cracked I longitudinal (Assuming 75% of uncracked) Step-5 Determine Natural Time Period, T for each mode
= 24.67 x 0.75 = 18.50 m4 T1=2π/ω1
Stiffness of pier in Longitudinal direction, k1 T2=2π/ω2
= 4.93E+05 kN/m T3=2π/ω3
Moment of Inertia in transverse direction, I transverse
= 74.91 m4 Step-6 Determine Eigenvectors φ (mode shapes) at each
Cracked I transverse (Assuming 75% of uncracked) Node for each mode, by [K-Mw^2] φ=0 for each Mode
=74.91 x 0.75 = 56.18 m4 φ11, φ21, φ31 for Mode 1
Stiffness of pier in Transverse direction, k1 φ12, φ22, φ32 for Mode 2
= 14.98E+05 kN/m φ13, φ23, φ33 for Mode 3
Average properties for member 1, 2 & 3 are provided as
Step-7 Determination of Modal Participation Factors for
given in the table below: each Mode, Pk
Member I longitudinal (m4 ) I transverse (m4 ) Area (m2)
1 18.50 56.18 13.77
2 10.42 44.76 11.33
3 5.14 34.33 9.08
Step-8 Determination of Modal Mass for each Mode,
Load calculation: Mk
Transverse seismic load
Total horizontal load at m3 [DL + SIDL +20% LL+ wt. of
pier (7.5m ht.)] = 13170 kN
Total horizontal load at m2 Where,
[Wt. of pier (15m ht.)] = 3755 kN g = acceleration due to gravity,
Total horizontal load at m1
[Wt. of pier (15m ht.)] = 4618 kN φik = mode shape coefficient at node i in mode k,
Longitudinal seismic load Wi = seismic weight at node i of the structure, and
Modal
Frequency Time
Mode Contribution
(Hz) Period (sec)
%
1 0.51 1.98 78.61
2 4.20 0.238 15.62
3 11.97 0.084 5.77
M1 = 1702 kN
M2 = 337 kN
M3 = 124 kN
Nodal
Modal Contribution of various Modes Mode-1 Mode-2 Mode-3 SRSS
Shear
Mode 1= 100.M1/M = 78.60 % V3 390 kN -158 kN 23 kN 421.5 kN
Mode 2= 100.M2/M = 15.58 % V2 442 kN 134 kN -74 kN 468.2 kN
Mode 3= 100.M3/M = 5.74 % V1 459 kN 331 kN 110 kN 578.3 kN
I
Z = 0.16
I = 1.5
R = 3.0
Response Spectra is chosen for Medium Stiff Soil Type
Ref: Cl.5.2.2 and Fig. 5.1(b) of IRC:SP:114-2018
Qik = AkØikPkWi
Where,
Ak =design horizontal acceleration spectrum value as per
Cl.5.2.2 using natural period of Tk of mode k obtained
from dynamic analysis Fig. A.2.2.4: Shear Force Diagram
Z= 0.16
I= 1.5
Mode-1 Mode-2 Mode-3 R= 3.0
φ31 1.00 φ32 -0.18 φ33 -0.06
Response Spectra is chosen for Medium Stiff Soil Type
φ21 0.50 φ22 1.00 φ23 0.78 Ref: Cl. 5.2.2 of IRC:SP:114-2018 and Fig.5.1(b)
φ11 0.14 φ12 0.67 φ13 -1.00 Qik = AkØikPkWi
Fig. A.2.2.5: Eigenvectors Where,
Calculation of Modal Mass Ak = design horizontal acceleration spectrum value as per
5.2.2 using natural period Tk of mode k obtained from
W3 = 13170 kN dynamic analysis
W2 = 3755 kN Mode-1 Mode-2 Mode-3
Tk 1.06 Sec 0.11 Sec 0.041 Sec
W1 = 4618 kN
Sa/g 1.28 2.50 1.62
Total (M)= 21543 kN Ak 0.051 0.10 0.065
APPENDIX –A-3
(Reference Clause 7.3)
ILLUSTRATION OF CAPACITY DESIGN METHOD FOR MEMBERS WITH DUCTILE BEHAVIOUR
This Appendix includes worked out example for Capacity
¾¾ Capacity Design Effects shall be treated as Ultimate
Design to be followed for checking the member sections loads
adjacent to ductile components/plastic hinges in accordance
with method described in Chapter 7. A typical pier analysed and designed for Capacity Design
is shown in Fig.A3.1 and Fig.A3.2.
The procedure for Capacity design mainly includes the
following steps:
¾¾ Design of Section with IRC:112 for Load
Combinations of IRC:6 by Limit State Method
¾¾ Design of Plastic Hinge including its location, height
and ductile detailing as specified in Clause 7.5.2 &
7.5.4 of Guidelines
¾¾ Determination of MRd, Design Flexural Strength of
section in Longitudinal and Transverse directions
at location of plastic hinge for reinforcement and
dimensions provided
¾¾ Computation of Over Strength Moment Mo by
multiplying MRd with Over Strength Factor γ o
SIDL (Surfacing)
3 SIDL-V-Each 620 0 0 0 0
side
4 Live load (LL) Reaction Without Impact Factor
Pmax(LL)
i 1982 0 0 238 3164
Q1
Max MT(LL)
ii 1321 0 0 159 4416
Q2
Max ML(LL)
iii 1326 0 0 1061 2121
Q3
Where,
SIDL -Super Imposed Dead Load
P -Axial Force
HT
-Horizontal Force along Transverse
Direction
HL -Horizontal Force along Longitudinal
Direction
MT -Transverse moment
ML -Longitudinal moment
Pmax(LL) -Maximum Vertical load case
Fig.A3.2: Section in Longitudinal Direction
Max MT(LL) -Maximum Transverse moment case
(both bearings fixed)
Max ML(LL) -Maximum Longitudinal moment case
1. Material Properties:
Superstructure Mass for longitudinal seismic
Grade of concrete for Substructure fck = 45 N/mm2
(DL + SIDL) = 18060 KN
Grade of concrete for Pile foundation fck = 35 N/mm2
Superstructure Mass for transverse seismic
Grade of steel reinforcement for
fy = 500 N/mm2 (DL+SIDL+0.2 x LL) = 9426 KN
Substructure and Pile foundation
Clear Cover to reinforcement for Pile T, Time Period of the system along Longitudinal
c = 75 mm Direction = 1.18 sec
foundation
Clear Cover to reinforcement for T, Time Period of the system along Transverse Direction
c = 40 mm
Substructure = 0.75 sec
Gross Area of Pier section Ac = 3570000 mm2 Taking
2. Calculation of Seismic Forces: Zone factor = 0.24
Importance factor = 1.2
Table 1: Un-Factored loads from Superstructure at bearing
level Response Reduction factor, R = 3
Considering medium type soil
S. P HL HT ML MT
N. Description
Ah Long = 0.164
(kN) (kN) (kN) (kNm) (kNm)
Ah Trans = 0.263
1 Dead Load Load Factor for Seismic
(DL) – Each 7710 0 0 0 0
Superstructure Combination = 1.5
Base Shear un-factored Seismic Combination in Longitudinal
SIDL (permanent)
Direction:
2 SIDL-F-Each 700 0 0 0 0
side Due to superstructure= 987.3 KN with lever arm=10.5m above
pier base
Sl. P HL HT ML MT
Description
No (kN) (kN) (kN) (kNm) (kNm)
1 Earthquake along Longitudinal Direction
1.35
(DL+SIDL-F) +
a 1.75 (SIDL-V) 14347 1630 416 16745 5546
+ 0.2(Q1) +
0.2(Fb) + 1.5Feq At the base of Pier
1.35(DL
+SIDL-F) +
b 1.75(SIDL-V) 14215 1614 416 16569 5797
+0.2(Q2) +
0.2(Fb) + 1.5Feq
1.35(DL
+SIDL-F) +
c 1.75(SIDL-V) 14216 1630 416 16909 5338
+0.2(Q3) +
0.2(Fb) +1.5Feq
2 Earthquake along Transverse Direction
1.35(DL
+SIDL-F) +
a 1.75(SIDL-V) 14347 529 1387 4878 17011
+ 0.2(Q1) +
0.2(Fb) + 1.5Feq At curtailment level
Figure A3. 3: Reinforcement Detailing of the Pier Section
6.2 For Capacity Design Shear Vc in Pier Checks should be carried out to ensure that the plastic
As per section 7.8 of this Guideline, the increase of hinge region, pier sections beyond plastic hinge region
moments of plastic hinges, ΔM, is obtained by deducting and foundation have shear strength greater than the Final
the moment due to non-seismic actions, i.e. live load and Capacity Design shear Vc of the section along both the
braking force (considering appropriate load factors) from directions.
the over-strength moment of the section along both the 6.3 Bearings:
directions. The increase in moment of plastic hinge is:
Bearings and connections are to be designed for lesser of
Along Longitudinal Direction, ΔML the following forces:
= 37341 - 632 = 36709 kNm i) Seismic forces obtained using Response reduction
Along Transverse Direction, ΔMT factor,
= 39677 - 634 = 39043 kNm R=1 as applicable for assessment of bearings.
As per clause 7.3.4.2 (e), Capacity Design shear ii) Forces developed due to over strength moment when
corresponding to this increase in moment is Obtained as: hinge is formed in the substructure
Vc = (∑ΔM) / h where ∑ΔM =∑Mo Hence the design seismic forces for bearing design are:
Shear Along Longitudinal Direction Along Longitudinal Direction, lesser of (1) and (3)
= ΔML / h = 36709/10.25 = 3582 kN (3) = 3582 kN
Shear Along Transverse Direction
Along Transverse Direction, lesser of (2) and (4)
= ΔMT / h =39043/10.25 = 3810 kN (4)
= 3735 kN
The factored shear due to non-seismic actions (braking
force for this example) is then added to the shear due to 6.4 Capacity check for Pile Foundation:
design seismic forces so as to obtain the Final Capacity The foundation is capacity protected by designing it for
design shear along both the directions. Over strength Moment Mo and Capacity Design Shear Vc
Final Capacity Design Shear in in both the directions separately. The summary of forces
= 3639 kN acting at the base of pile cap for the considered maximum
Longitudinal Direction = 3582+ 57
vertical load case in Longitudinal and Transverse is given
Final Capacity Design Shear in Transverse
= 3810 kN in Table 4. The number of piles is considered as 4 at a
Direction
spacing of 4.5 m in both directions.
Table 4: Summary of forces at the base of Pile cap
Hor. Load on
P HL HT ML MT Reactions on Pile in kN
Description Pile in kN
kN kN kN kNm kNm P1 P2 P3 P4
Longitudinal Seismic
17218* 3639 0 37341 634 8524 8383 226 -85 910
Case
Transverse Seismic
17157* 57 3810 48 39677 8704 -115 8693 -125 953
Case
*Including soil weight above pile cap
The depth of fixity is assumed to be 9 m from the pile cap The pile diameter is assumed to be 1.2 m and the corresponding
bottom. The reduction factor for fixed head pile is assumed reinforcement assumed is 19 numbers of (32+20mm) bundled
to be 0.8 as per Fig. 5 of IS 2911(Part 1/Sec 2).
bars. For the above said pile, the capacity at the minimum axial
Maximum moment on a pile is observed to be load i.e. -85 kN and -125 kN along longitudinal and transverse
Along Longitudinal Direction direction respectively is found out to be 3575 kNm and
= 910 x 9/2x 0.8 = 3276 kNm 3484 kNm respectively. The capacity of the Pile for longitudinal
Along Transverse Direction and transverse seismic case is more than the maximum moment
= 953 x 9/2x 0.8 = 3431 kNm on the pile.
APPENDIX - A4
(Reference Clause 4.8)
ILLUSTRATION OF HYDRODYNAMIC FORCES ON BRIDGE
SUBSTRUCTURE & FOUNDATION
Example : Calculation of hydrodynamic forces in case = C3F1 \
of a bridge with Well Foundation, located in Seismic = 1.0 x 2.464t = 2.464t
Zone IV, with design horizontal seismic coefficient, Ah
= (Z/2) x (I/R) x (Sa/g) = 0.12 [i,e. Assuming Sa/g = 2.5; Point of application of resultant force from base of pier
I=1.2; Z=0.24; R=3.0 : Ah = (0.24/2) x (1.2/3.0) x 2.5] = C4h = 0.4286 X 6.218 = 2.665m
Bending moment at the base of pier (Well cap level) due
Design parameters : Pier Diameter, d1 = 2.4m; Pier
to hydrodynamic force on pier
Height below HFL, h = 6.218m, Well Diameter, d2 = 5.5m,
Overall height from HFL to Scour Level, H = 31.09m, = 2.464 x 2.665 = 6.566tm
Well Height upto scour level = (H-h) = 24.872m [Refer The force distribution is worked out in Table 1, below, and
Fig. A4-1] shown in Fig. A4-2
Table 1: Force Distribution on pier
(Refer portion A-B-C in Fig. A4-4)
C1 C1h C2 C2 Pb1 (t/m)
0.1 0.6218 0.410 0.195
0.2 1.2436 0.673 0.319
0.3 1.8654 0.832 0.395
0.4 2.4872 0.922 0.438
0.5 3.1090 0.970 0.460
0.6 3.7308 0.990 0.470
0.8 4.9744 0.999 0.474
1.0 6.2180 1.000 0.475
Fig. A4.1
Hydrodynamic force on pier, F1 = CeαhWe
Pier Portion:
For pier portion consider enveloping cylinder of height h
and radius r1. Fig. A4.2
For pier portion, (b) Well Portion:
(Refer Table 4.4) For well portion consider enveloping cylinder of height
Weight of water in enveloping cylinder for pier H and radius r2. Deduct from it the enveloping cylinder of
height h and radius r2 to determine hydrodynamic effect
on well portion only. Thus hydrodynamic force on well
portion is obtained as follows:
Hydrodynamic force on pier, F1 = Ceαh We1
For well foundation,
F1 = 0.73 x 0.12 x 28.129 = 2.464t
For Pier,
Resultant force at base of pier
64 INDIAN HIGHWAYS OCTOBER 2019
Notifications
Hydrodynamic force on well portion only= F2 –F3, Table 2: Force Distribution on well
Where:
C1 C1h C2 C2 Pb2(t/m)
F2 = force acting on complete height H, enveloping radius
0.2 0.6218 0.673 1.680
r2 (Refer portion A-B-D in Fig. A4.4
0.3 9.3270 0.832 2.077
F3 = force acting on pier height h, enveloping radius
r2(Refer portion A-E-F in Fig. A4.4 0.4 12.436 0.922 2.302
F2 = Ceαh We2 0.5 15.545 0.970 2.422
We2 = π x 2.752 x 31.09 = 738.645 t 0.6 18.654 0.990 2.472
F2 = 0.73 x 0.12 x 738.645 = 64.705 t 0.8 24.872 0.999 2.472
Point of application of F2 (resultant on H) from scour level 1.0 31.090 1.000 2.497
(C1 = 1.0),
C4H = 0.4286 x 31.09 = 13.325 m
Resultant force on height h (for C1 = h/H = 0.2)
F3 = C3 F2
F3 = 0.093 x 64.705 = 6.017 t
Point of application F3 (resultant on h) from scour level
(for C1 = 0.2)
= C4 H = 0.8712 x 31.09 = 27.085 m
The net hydrodynamic force acting on well portion only
F2 – F3 = 64.705-6.017 = 58.688 t
Bending moment at scour level due to hydrodynamic
force on well
=F2 x 13.325 - F3 x 27.085 Fig. A4.3
= 64.705 x 13.325 – 6.017 x 27.085
Fig. A4-4 below shows the final forces acting in pier and
= 699.224tm well foundation
Total shear force and bending moment at scour level
Total shear force at scour level
= Hydrodynamic force on pier + Hydrodynamic force
on well
= 2.464 + 58.688 = 61.152 t
Total bending moment at scour level
= Moment of force F1 + Net Moment of force F2 and F3
= 2.464 (2.665 + 24.872) + 699.224
= 67.851 + 699.224 = 767.075t
The force distribution for well portion (C1 = 0.2 to C1 = 1.0)
is worked out in Table 2 and also shown in Fig. A4-3.
66
INDIAN HIGHWAYS
OCTOBER 2019
Notifications
Notifications
Notification No. 26
Amendment No.8/Irc:112/August, 2019 (effective from 31th October, 2019)
To
Irc:112-2011 “code of practice for concrete road bridges”
and, (εuk ; ft), where fyk ; ft, εuk are the minimum and, (εuk ; ft), where fyk ; ft, εuk are the minimum
values required by relevant IS Codes referred to in values required by relevant IS Codes referred to in
Section 18.2.1 (Table 18.1). The factored idealised Section 18.2.1 (Table 18.1). The factored idealised
design diagram is obtained by factoring design diagram is obtained by factoring stress
stress
values by, that is by taking, values by, that is by taking,
6. 10.2.2.1 In case of direct support [Fig. 10.1 (b)], a fan In case of direct support [Fig. 10.1 (b)], a fan
(Page 81) like compression field exists. When structure is like compression field exists. When structure is
subjected to predominantly uniformly distributed subjected to predominantly uniformly distributed
loads, in area, confined by the beam end and the loads, in area, confined by the beam end and the
steepest inclination (θmax= 45º) of the compression steepest inclination (θmax= 45º) of the compression
field (generally within a distance equal to field (generally within a distance equal to effective
effective depth from centre of support), no shear depth from face of support or centre of bearing
reinforcement is required. where flexible bearings are used), no shear
reinforcement is required.
For concentrated loads the steepest inclination
may the taken as 26.5º (measured with respect For concentrated loads the steepest inclination may
to vertical face of beam end, generally within a the taken as 26.5º (measured with respect to vertical
distance of half the effective depth from centre of face of beam end, generally within a distance of half
support) and for loads within this distance no shear the effective depth from face of support) and for
reinforcement is required. It is however, necessary loads within this distance no shear reinforcement
to extend the shear reinforcement up to the support is required. It is however, necessary to extend the
from the section within this region 'A' (distance shear reinforcement up to the support from the
d or half of d, as the case may be) and provide section within this region ‘X1' (distance d or half
tensile reinforcement for resisting the horizontal of d, as the case may be, see figure 10.1(b)) and
components of these internal compressive forces provide tensile reinforcement, adequately anchored
in addition to the steel provided for bending. beyond bearing point, for resisting the horizontal
components of these internal compressive forces in
addition to the steel provided for bending.
7. 10.2.3 (1) In case of direct support, shear force VNS acting In case of direct support, shear force VNS acting
(Page 84) at section d (effective depth) away from centre at section d (effective depth) away from face
of support, when the member is subjected of support (or centre of bearing where flexible
predominately uniformly distributed load and at bearings are used) when the member is subjected
a distance d/2 away when member is subjected to predominantly uniformly distributed load and at
concreted loads – may be used for design of shear a distance d/2 away when member is subjected to
reinforcement in the region between support to d concentrated loads – may be used for design of shear
or support to d/2 as the case may be. For checking reinforcement in the region between support to d
crushing of concrete compression strut VNS shall be or support to d/2 as the case may be. For checking
taken at the centre of the support. crushing of compression strut VNS shall be taken at
centre of support.
8. 10.3.3.2, fywd is the design strength of web reinforcement to fywd is the design strength of web reinforcement to
(Page 91) resist shear = fyk / γm resist shear (and torsion) = fyk / γmwhile the value
of fyk is limited to 500 MPa.
9. 10.3.3.3 (5) For non-grouted ducts, grouted plastic ducts and For non-grouted ducts and unbonded tendons the
(Page 92) unbonded tendons the nominal web thickness is: nominal web thickness is:
bw,nom= bw - 1.2Σ Φ Eq.10.15 bw,nom= bw - 1.2Σ Φ Eq.10.15
The value 1.2 In Eq.10.15 is introduced to take The value 1.2 In Eq.10.15 is introduced to take
account of splitting of the concrete struts due account of splitting of the concrete struts due
to transverse tension. If adequate transverse to transverse tension. If adequate transverse
reinforcement is provided this value may be reinforcement is provided this value may be
reduced to 1.0 reduced to 1.0
13. Table 14.1 Table 14.1 Classification of Service Environment Table 14.1 Classification of Service Environment
(Page 141)
S. S.
Environment Exposure Condition Environment Exposure Condition
No. No.
Concrete dry or permanently Concrete dry or permanently
wet; concrete continuously under wet; concrete continuously under
(1) Moderate
water; (1) Moderate water; low humidity (Relative
humidity <50%); humid
Wet, rarely dry; humid (relative (Relative humidity >70 %)
humidity > 70 %), completely
Wet, rarely dry; moderate
(2) Severe submerged in sea water below
humidity (relative humidity ≥
mid-tide level; concrete exposed
50% and ≤70 %), completely
to coastal environment. (2) Severe submerged in sea water below
moderate humidity (relative mid-tide level; concrete exposed
humidity 50-70 percent); to coastal environment.
(3) Very severe Concrete exposed to air-borne Concrete exposed to air-borne
chloride in marine environment; (3) Very severe chloride in marine environment;
freezing conditions while wet. freezing conditions while wet.
Cyclic wet and dry, concrete Cyclic wet and dry, concrete
exposed to tidal, splash and spray exposed to tidal, splash and spray
zones in sea, concrete in direct zones in sea, concrete in direct
(4) Extreme contact with aggressive sub-soil/ (4) Extreme contact with aggressive sub-soil/
ground water, concrete in contact ground water, concrete in contact
with aggressive chemicals. with aggressive chemicals.
14. 16.7.1 (1) (1) Corbels may be designed by using strut and tie (1) Corbels may be designed by using strut and tie
model. The inclination of strut with respect to model. The inclination of strut with respect to
(Page 185) axial direction of the member to which corbel the “main” tie should lie between 45° and 68°.
is attached, should lie between 22o and 45o. The strut shall be dimensioned such that the
concrete compression stress does not exceed
that given in clause 6.4.2.8. Horizontal forces,
HEd when applied in addition to the vertical load
FEd, will require additional reinforcement in the
tie. The effects of torsion, if any, have to be
catered to in accordance with clause 10.5.2.1
15. 16.7.1 (3), As,link> 0.25 As,main As,link> 0.50 As,main(to be provided in upper two-
Eq. 16.11 third of the corbel depth)
(Page 185)
16. 16.7.1 (4), (4) In corbels with ac> 0.5 hcand (4) In corbels where aclies between 0.5 hcand hc and
(Page 185) FEd>VRd.c(Refer section 10), closed vertical stirrups FEd>VRd.c(Refer clause 10.3.2 and 10.3.3), closed
with area As.stirrupshall be provided in addition to vertical stirrups with area As.stirrupshall be provided
the main tension reinforcement as shown in Fig. in addition to the main tension reinforcement and
16.7(b), where: the closed horizontal or inclined links, as shown in
As.stirrup ≥ 0.5 FEd / fyd Fig. 16.7(b), where:
As.stirrup ≥ 0.5 FEd / fyd
In addition check against crushing of strut shall be
made in accordance with Eq 10.5
17. Additional New clause added (5) If ac>hc the design shall be carried out as a
clauses (5) flexural member. The shear check shall be carried
to (7) to be out as per Eq 10.5 of 10.3.2 (5) for checking against
added in clause crushing of concrete as well as 10.3.3.3(7) and
16.7.1, 10.3.3.3(8) for arriving at the shear reinforcement.
(Page 186) (6) The bearing area on a corbel shall not project
either beyond the straight portion of the main
tension bars or beyond the interior face of any
transverse anchor bar.
(7) In the case of corbels with varying depth, Fig
16.7(c), the depth at the outside edge of the bearing
area shall not be less than half the depth at the
face of the support. The favourable contributions
from inclined compression chord and tensile chord
(clause 10.2.3) shall not be considered.
18. 17.1 (1) Ductile detailing shall be carried out for bridges Ductile detailing shall be carried out for the bridges
(Page 192) located in zones III, IV and V of seismic zone map located in Zones III, IV and V of the seismic Zone
of IRC:6. map of IRC : 6 if they are designed for Response
reduction factor R > 1.0
19. 17.2.2 (3) (3) The minimum amount of transverse ties shall be Change the clause no. from 17.2.2 (3) to 17.2.2.(2)
(Page198) determined as follows: (c), with following revision :
(c) The minimum amount of transverse ties shall be
determined as follows:
where
Al is the area of one tie leg, in mm2.
ST is the transverse distance between tie legs, in m; where
ΣAS is the sum of the areas of the longitudinal bars Al is the area of one tie leg, in mm .
2
21. 17.2.2 (3), New Clause to replace existing clause (3) Along Circular section boundaries, restraining
(Pge 198) of longitudinal bars should be achieved through
circular ties determined by:
A1 1 fys
= x ρ D2 x
fyt (mm /m) Eq. 17.9
2
SL 12.8 l
23. 18.2.3.3 Properties of stainless steel reinforcement Stainless steel reinforcement shall conform to
(Page 202) shall not be inferior to those of carbon steel IS:16651:2017.
reinforcement of corresponding strength class.
For bond properties, the relevant code may Properties of stainless steel reinforcement shall not
be inferior to those of carbon steel reinforcement of
be referred or they may be established on the
corresponding strength class.
basis of tests.