Site Number 1336 Report A – 21st November 2017
14 – 16 Prowse Street, West Perth
CONTENTS
1.0- Preamble
Page 2 of 11
Site Number 1336 Report A – 21st November 2017
14 – 16 Prowse Street, West Perth
1.0-Preamble
Fire and Civil WA 21st November 2017
Company: SMF Projects Pty Ltd Email: greg@fireandcivil.com
Mobile: 041 111 5060
Address: U7, 405-407 Oxford Street, Mt Hawthorn Phone: 9364 4488
Dear Daniel,
We thank you for your instructions to undertake a residual flow and pressure test/s at the above site.
Fire and Civil (WA) is pleased to provide the following report.
The results particularised herein were obtained by measuring the water residual flow and pressure at
the listed test location/s (see page 5). Our comments and findings set out herein meet the requirements
of, or are within the acceptable parameters of the following (as and if applicable): DTS (Deemed to
Satisfy) provisions of the Building Code of Australia (BCA) 2016 (Vol. 1) Part E 1.3 and/or
Australian Standards 2419.1-2005.
Please Note: The residual flow and pressure test results, set out in this report are indicative only and
obtained solely for design/maintenance purposes.
The test results show residual flow and pressure rates for the time and date on which the tests were
performed only. No representation is made or warranty given that the same result/s can be achieved in
any further, or additional test/s on account of flow and pressure being affected or compromised by
factors including, but not limited to:
1) Time of day/week/year of water test
2) Increased demand on infrastructure (internal/external)
3) Age/maintenance of infrastructure (internal/external)
4) Infrastructure modifications (internal/external)
5) Installation of backflow prevention device/s etc.
6) Local demand variations (internal/external) etc.
7) Water Corporation Pressure Management Programme
8) Service Performance Standards for Water Corporation supplied water is set out in Schedule 2,
Sections 1.1 and 1.2 ( http://www.erawa.com.au/water ) for the Perth Metropolitan area being -
minimum 15m head static (147 kPa) @ 20L/minute flow.
Should you require any further information, contact Greg Lock on 041 111 5060.
Regards
Page 3 of 11
Site Number 1336 Report A – 21st November 2017
14 – 16 Prowse Street, West Perth
2.0- Measuring Instruments Used
Please note: Current calibration certificates are displayed on the last page/s of the
report where applicable.
Page 4 of 11
Site Number 1336 Report A – 21st November 2017
14 – 16 Prowse Street, West Perth
3.0-Site Map of Test Location/s Specified
Page 5 of 11
Site Number 1336 Report A – 21st November 2017
14 – 16 Prowse Street, West Perth
LOCATION ONE
LOCATION ONE
Page 6 of 11
Site Number 1336 Report A – 21st November 2017
14 – 16 Prowse Street, West Perth
Location ONE
See 3.0 Site Map and 4.0 - Photograph/s of Test Location/s Specified
Note:
1. Refer to 2.0- Measuring Instruments Used for Instrument Details.
2. Depending on test requirements, when multiple testing instruments are used the residual flow is measured
in Litres per Second (L/s) and pressure measured in Kilopascals (kPa), the results are the average of the
interpreted combined numerical data generated.
3. No flow is required for a static pressure test.
The table below reports the residual flow and coinciding pressure testing results interpreted in 5 L/s
increments, or part thereof, and pressure readings in (kPa).
Test: Test 1
Time: 11:08
Date: 21/11/17
Instruments used: 3&4
Brief Current On site fire
Description: service
Flow Rate
(L/s)
Static 0 375
5 360
10 340
15 330
20 320
25 300
30
35
40
See graph/s below when applicable
Test No. 1
600
500
Pressure (kPa)
400
300
200
100
0
0 5 10 15 20 25 30
Flow (L/Second)
Page 7 of 11
Site Number 1336 Report A – 21st November 2017
14 – 16 Prowse Street, West Perth
6.0-Calibration Certificates