Site Number 1336 Report A – 21st November 2017

14 – 16 Prowse Street, West Perth

Fire and Civil


(WA)

14 – 16 Prowse Street, West Perth


Residual Flow and Pressure Test Report
-Site Number 1336-
Report A

21st November 2017

Page 1 of 11
Site Number 1336 Report A – 21st November 2017
14 – 16 Prowse Street, West Perth
CONTENTS

1.0- Preamble

2.0- Measuring Instruments Used

3.0- Site Map of Test Location/s Specified

4.0- Photograph/s of Test Location/s Specified

5.0- Performance Evaluation Data

6.0- Calibration Certificates

Page 2 of 11
Site Number 1336 Report A – 21st November 2017
14 – 16 Prowse Street, West Perth
1.0-Preamble
Fire and Civil WA 21st November 2017
Company: SMF Projects Pty Ltd Email: greg@fireandcivil.com
Mobile: 041 111 5060
Address: U7, 405-407 Oxford Street, Mt Hawthorn Phone: 9364 4488

Attention: Daniel Gwyther-Jones Postal: P O Box 7083


Applecross North
Site Address: 14-16 Prowse Street, West Perth WA 6153

Project: ABN: 65 009 442 648

Dear Daniel,

We thank you for your instructions to undertake a residual flow and pressure test/s at the above site.
Fire and Civil (WA) is pleased to provide the following report.

The results particularised herein were obtained by measuring the water residual flow and pressure at
the listed test location/s (see page 5). Our comments and findings set out herein meet the requirements
of, or are within the acceptable parameters of the following (as and if applicable): DTS (Deemed to
Satisfy) provisions of the Building Code of Australia (BCA) 2016 (Vol. 1) Part E 1.3 and/or
Australian Standards 2419.1-2005.

Please Note: The residual flow and pressure test results, set out in this report are indicative only and
obtained solely for design/maintenance purposes.

The test results show residual flow and pressure rates for the time and date on which the tests were
performed only. No representation is made or warranty given that the same result/s can be achieved in
any further, or additional test/s on account of flow and pressure being affected or compromised by
factors including, but not limited to:
1) Time of day/week/year of water test
2) Increased demand on infrastructure (internal/external)
3) Age/maintenance of infrastructure (internal/external)
4) Infrastructure modifications (internal/external)
5) Installation of backflow prevention device/s etc.
6) Local demand variations (internal/external) etc.
7) Water Corporation Pressure Management Programme
8) Service Performance Standards for Water Corporation supplied water is set out in Schedule 2,
Sections 1.1 and 1.2 ( http://www.erawa.com.au/water ) for the Perth Metropolitan area being -
minimum 15m head static (147 kPa) @ 20L/minute flow.
Should you require any further information, contact Greg Lock on 041 111 5060.
Regards

Plumber’s Licence No. 5247


Restricted G Class Gas Licence No. GF019069
Water Corporation Contractor ID: 35725
Backflow Prevention No. 2676
PVC Handling Licence No. 2215
White Card Holder 11th July 2013
Butt Weld PE Plastic Pipes and Electrofusion Weld PE Pipes No. BEC830

Page 3 of 11
Site Number 1336 Report A – 21st November 2017
14 – 16 Prowse Street, West Perth
2.0- Measuring Instruments Used

Whenever practicable to obtain accuracy in measurements contributing to a


high degree of certainty in test results issued, Fire and Civil (WA) utilises
multiple flow measuring instruments and multiple pressure gauge instruments in
its testing protocols. In addition to being recalibrated annually, such instruments
are regularly cross-checked against other calibrated instruments either before,
during or after being utilised in a measurement and test undertaking to promote
consistency of outcomes in Fire and Civil (WA)’s multiple measurement and the
resulting reports.

Please note: Current calibration certificates are displayed on the last page/s of the
report where applicable.

Measuring Instruments Used by Fire & Civil (WA)


Instrument Measuring instruments Size Comments Date of Last
Number Calibration
1 Flowmaster-Serial Number: 65mm A) Mag flow with Data Logging 06/12/2016
1815
B) Pressure Gauge with Data Logging 23/03/2017

2 Flowmaster-Serial Number: 65mm A) Mag flow with Data Logging 01/12/2016


1828
B) Pressure Gauge with Data Logging 22/03/2017

3 Flowmaster-Serial Number: 65mm A) Mag flow with Data Logging 29/11/2016


1845
B) Pressure Gauge with Data Logging 22/03/2017

4 Flowmaster-Serial Number: 65mm A) Mag flow with Data Logging 01/12/2016


1846
B) Pressure Gauge with Data Logging 22/03/2017

5 GF+ SIGNET- Serial Number: 65mm Paddle Wheel Sensor 07/12/2016


123852
6 MANUFLO- Serial Number: 65mm Paddle Wheel Sensor 04/10/2017
303-622
7 ADT680 Pressure Gauge- 100mm Digital Pressure Gauge 28/09/2017
S/No: 218130C0001 (0-2000kPa)
8 ADT680 Pressure Gauge- 100mm Digital Pressure Gauge 27/09/2017
S/No: 218130C0046 (0-2000kPa)
9 ADT680W Pressure Gauge- 100mm Digital Pressure Gauge With Data 23/11/2016
S/No: 218150D0012 Logging (0-2000kPa)
10 ADT680W Pressure Gauge- 100mm Digital Pressure Gauge With Data 23/11/2016
S/No: 21815010045 Logging (0-2000kPa)
11 Stewart Buchanan- 100mm Analogue Pressure Gauge Only 27/09/2017
S/No: 131101/20 (0-2500 kPa)
12 Ambit 300DGC- 115 mm Analogue Differential Pressure Gauge 18/09/2017
S/No: HC-5445 Only (0-100 kPa)

Page 4 of 11
Site Number 1336 Report A – 21st November 2017
14 – 16 Prowse Street, West Perth
3.0-Site Map of Test Location/s Specified

Page 5 of 11
Site Number 1336 Report A – 21st November 2017
14 – 16 Prowse Street, West Perth

4.0-Photograph/s of Test Location/s Specified

LOCATION ONE

LOCATION ONE

Page 6 of 11
Site Number 1336 Report A – 21st November 2017
14 – 16 Prowse Street, West Perth

5.0-Performance Evaluation Data

Location ONE
See 3.0 Site Map and 4.0 - Photograph/s of Test Location/s Specified
Note:
1. Refer to 2.0- Measuring Instruments Used for Instrument Details.
2. Depending on test requirements, when multiple testing instruments are used the residual flow is measured
in Litres per Second (L/s) and pressure measured in Kilopascals (kPa), the results are the average of the
interpreted combined numerical data generated.
3. No flow is required for a static pressure test.
The table below reports the residual flow and coinciding pressure testing results interpreted in 5 L/s
increments, or part thereof, and pressure readings in (kPa).
Test: Test 1
Time: 11:08
Date: 21/11/17
Instruments used: 3&4
Brief Current On site fire
Description: service
Flow Rate
(L/s)
Static 0 375
5 360
10 340
15 330
20 320
25 300
30
35
40
See graph/s below when applicable

Test No. 1
600

500
Pressure (kPa)

400

300

200

100

0
0 5 10 15 20 25 30
Flow (L/Second)

Page 7 of 11
Site Number 1336 Report A – 21st November 2017
14 – 16 Prowse Street, West Perth

6.0-Calibration Certificates

Page 8 of 11
Site Number 1336 Report A – 21st November 2017
14 – 16 Prowse Street, West Perth

Page 9 of 11
Site Number 1336 Report A – 21st November 2017
14 – 16 Prowse Street, West Perth

Page 10 of 11
Site Number 1336 Report A – 21st November 2017
14 – 16 Prowse Street, West Perth

Page 11 of 11