Professional Documents
Culture Documents
CLB 21303
PROCESS INSTRUMENTATION & CONTROL
EXPERIMENT 3
Level Measurement & Calibration
SEMESTER
Sept/Oct 2022
1 Fill-up water in Tank T2 up to its overflow level. Make sure that drain valve is
FULLY CLOSED.
2 At the front panel, make sure the heater and pump (P) are OFF.
3 Then switch ON the main power supply at the front panel. The panel instruments
should all lit up.
4 Check that the pump suction valve and all pump discharge valves are FULLY
OPEN.
5 Open ONE TURN of the pump by-pass valve (BV) first BEFORE starting the pump
(P). After pump start-up, FULLY CLOSE BV. This is a good practice to avoid any
hydraulic shock to the pump (P).
Note: During the experiment, if the water of tank T2 is at the low level, the level switch
(LS) will automatically SWITCH OFF the heaters and pump (P). In this case,
TOP UP more water into tank T2 from external water supply.
1. Refer to the START-UP procedures and check that the procedures are DONE before
the experiment is carried out.
2. For tank T1, FULLY OPEN top vent (V) and overflow manual valves.
3. Make sure bottom gate valve is FULLY OPENED and globe valve is FULLY
CLOSED.
4. Make sure air inlet manual isolation valve is CLOSED (with 900 position at the air
supply inlet tubing). The top space of tank T1 is at atmospheric pressure, as
monitored by the pressure gauge (PG).
5. Open ONE TURN of the pump by-pass valve (BV) first BEFORE starting the pump
(P)
7. After the pump already starts, CLOSE the pump by-pass valve (BV).
8. ADJUST the flowrate by using Variable Area Flowmeter (FI) to about 2.5m3/hr. Let
the water circulate throughout tanks T1 and T2.
9. At the sight millimetre scale (LG), OBSERVE the level in tank T1 rise until it
overflows to make sure that both of the wet legs at the Differential Pressure/Level
Transmitter (LT) is filled with water.
10. CLOSE the manual discharge gate valve at tank T1. STOP the pump (P).
1. Refer to the START-UP procedures and check that the procedures are DONE before
the experiment is carried out
3. Open ONE TURN of the pump by-pass valve (BV) first BEFORE starting the pump
(P). Start pump (P) by pressing the GREEN pushbutton at the front panel. After
pump start-up, check that the pump by-pass valve (BV) is FULLY CLOSED.
4. Adjust the flowrate by using Variable Area Flowmeter (FI) to about 2.5m3/hr. Let the
water circulate throughout tanks T1 and T2.
5. At the sight millimetre scale (LG), observe the level in tank T1 rise until it
OVERFLOWS to make sure that both of the wet legs at the Differential Pressure/Level
Transmitter (LT) is filled with water.
6. CLOSE the manual discharge gate valve at tank T1. STOP the pump (P).
1. Refer to the START-UP procedures and check that the procedures are DONE before
the experiment is carried out.
2. For tank T1, FULLY OPEN top vent (V) and overflow manual valves.
3. Make sure bottom gate valve is FULLY OPENED and globe valve is FULLY
CLOSED.
4. Make sure air inlet manual isolation valve is CLOSED (position 900 at the air supply
inlet tubing). The top space of tank T1 is at atmospheric pressure, as monitored by
the pressure gauge (PG).
5. Open ONE TURN of the pump by-pass valve (BV) first BEFORE starting the pump
(P). Start pump (P) by pressing the GREEN pushbutton at the front panel. After
pump start-up, CLOSE the pump by-pass valve (BV).
6. Adjust the flowrate by using Variable Area Flowmeter (FI) to about 2.5m3/hr. Let
the water circulate throughout tanks T1 and T2.
7. At the sight millimetre scale (LG), observe the level in tank T1 rise until it
OVERFLOWS to make sure that both of the wet legs at the Differential
Pressure/Level Transmitter (LT) is filled with water.
9. Let the water to circulate throughout tanks T1 and T2 until the water temperature
reaches to about 500C.
Note:
TIC has an ON/OFF ALARM with hysteresis of 0.50C.
Say the temperature set point is at 50.00C, the heater is switched ON until the
water temperature reaches 50.00C. TIC will then switch the heater OFF. The
water temperature will continue to rise and then drop to below 50.00C.
Once the water temperature drops BELOW 49.50C, TIC will switch the heater
ON again to heat the water up to the set point temperature again.
This will CONTINUE throughout as long as the heater switch at the front panel
stays ON.
11. CLOSE the manual discharge gate valve at tank T1. STOP the pump (P).
1. Refer to the START-UP procedures and check that the procedures are DONE before
the experiment is carried out.
2. Check that tank T1 is still operated as an OPEN tank.
Make sure that the top vent (V) and overflow manual valve are FULLY
OPENED.
Make sure that the manual discharge valves i.e. bottom gate valve is FULLY
OPENED and globe valve is FULLY CLOSSED.
The pressurising air inlet manual isolation valve handle is 900 to the air supply
inlet tubing.
3. Open ONE TURN of the pump by-pass valve (BV) first BEFORE starting the pump
(P).Start pump (P) by pressing the GREEN pushbutton at the front panel. After
pump start-up, check that the pump by-pass valve (BV) is FULLY CLOSED.
4. Adjust the flowrate by using Variable Area Flowmeter (FI) to about 2.5m3/hr. Let
the water circulate throughout tanks T1 and T2.
6. Switch ON the heater on the front panel. Let the water to circulate throughout tanks
T1 and T2 until the water temperature reaches to about 500C.
Note:
a. TIC has an ON/OFF ALARM with hysteresis of 0.50C.
b. Say the temperature set point is at 50.00C, the heater is switched ON until
the water temperature reaches 50.00C. TIC will then switch the heater OFF.
The water temperature will continue to rise and then drop to below 50.00C.
c. Once the water temperature drops BELOW 49.50C, TIC will switch the
heater ON again to heat the water up to the set point temperature again.
d. This will continue throughout as long as the heater switch at the front
panel stays ON.
8. CLOSE the manual discharge gate valve at tank T1. STOP the pump (P).
9. OPEN the bottom globe valve of tank T1 to allow the water in the tank to flow out
into tank T2 until the level at LG reads to about 750mm. CLOSE the bottom globe
valve.
After ALL of the experiments have been completed, do the following steps:
1. Make sure that BOTH the heater and pump (P) are switched OFF.
3. FULLY OPEN the overflow manual valve and the top vent (V) valve of tank
T1.
4. DRAIN out all of the water in tank T1 by OPENING the manual discharge
valve i.e. the gate valve. After that, FULLY CLOSE BOTH the gate valve
and globe valve.
5. DRAIN out all of the water in tank T2 by OPENING its manual drain valve.
2.0 RESULTS
REMARKS:
B: Read from the sight glass with millimetre scale (LG).
C: Read from the level indicator (LI) on the front panel.
D: Read from the temperature gauge (TG) mounted on level tank T1.
1. Level is measured in many of the processes in the industry. List and explain the most
common reasons for measuring level.
3. How the depth of a liquid does correspond to changes in liquid pressure? Can a
pressure transmitter be used to measure level?
4. The differential pressure transmitter is used to measure level in an open tank or closed
tank system. Discuss how this is done.
5. Discuss briefly the possible errors affecting the accuracy in pressure / level
measurement as observed in the experiment.
4.0 REFERENCE
1. Experiment Manual LMC 200. QDR Marketing Sdn Bhd