Commissioning Manual

Air Handling Unit


Application Software name: Airstream

D-EOM
AHU – COMMISSIONING MANUAL 2

Index
1. Air Handling Unit Safety Information ........................................................................................................ 3
2. Introduction ............................................................................................................................................... 4
2.1 Revision History ................................................................................................................................. 4
3. AHU Configuration screen ......................................................................................................................... 5
4. Unit Type Configuration............................................................................................................................. 6
5. Components Configuration........................................................................................................................ 8
6. Functions Configuration .......................................................................................................................... 12
7. Fans Configuration ................................................................................................................................... 17
AHU – COMMISSIONING MANUAL 3

1. Air Handling Unit Safety Information


Observe all safety directions and comply with the corresponding general safety regulations in order to
prevent personal injury and damage to property.

• Safety devices may not be removed, bypassed or taken out of operation.


• Apparatus and system components may only be used in a technically fault-free state. Faults that
can affect safety must be rectified immediately.
• Observe the required safety instructions against excessively high contact voltages.
• The plant may not be in operation if the standard safety devices are out of operation or if their
effects are influenced in some other way.
• All handling that affects the prescribed disconnection of the protective extra-low voltage (AC 24 V)
must be avoided.
• Disconnect the supply voltage before opening the apparatus cabinet. Never work when the
power is on!
• Avoid electromagnetic and other interference voltages in signal and connection cables.
• Assembly and installation of system and plant components may only be performed in accordance
with corresponding installation instructions and instructions for use.
• Every electric part of the system must be protected against static charging: electronic components,
open printed circuit boards, freely accessible connectors and apparatus components that are
connected with the internal connection.
• All equipment that is connected to the system must be CE marked and comply with the Machine
Safety Directive.
AHU – COMMISSIONING MANUAL 4

2. Introduction
This commissioning manual provides the information needed to configure the Daikin Air Handling Unit
(AHU), both Modular and Professional models.
Please note that the following manual always refers to the latest official released software version of the
unit.
Refer to D-AHU operating manual for detailed information about control functions and how to operate on
AHU controller.

2.1 Revision History


AHU Commissioning Manual (Airstream) First release March 2015
AHU Commissioning Manual (Airstream)_r1 Revision one March 2015
AHU Commissioning Manual (Airstream)_r2 Revision two April 2015
AHU Commissioning Manual (Airstream)_r3 Revision three May 2016
AHU Commissioning Manual (Airstream)_r4 Revision four July 2016
AHU – COMMISSIONING MANUAL 5

3. AHU Configuration screen


Through the AHU Configuration screen the user can access to all sub-menus necessary to properly
configure the AHU.
NOTE! In order to access the “AHU Configuration” screen, the user must enter the service level
password, otherwise the “Commissioning” item is not shown on the “Main Menu” screen.

HMI Path: Main Menu  Commissioning  AHU Configuration

The following table shows all the items needed for AHU configuration and the sections where they are
described.
Menu item Section
Config unit type Display and configure AHU type and coils
(Section number 4)
Config components Display and configure installed components
(Section number 5)
Config functions Display and configure available functions
(Section number 6)
Config fan Display and configure AHU fans type and sensors.
(Section number 7)

IMPORTANT! The AHU configuration procedure must be executed following the “AHU
Configuration” menu item order (i.e. Config Unit Type -> Config Components -> Config functions ->
Config fan), because some menu items are strictly dependent on how the AHU has been
configured in previous sections.
AHU – COMMISSIONING MANUAL 6

4. Unit Type Configuration


This page allows to configure the AHU type and to choose which kind of coil is used for both heating and
cooling mode. Please refer to the I/O map for the detailed description of all input and output available with
different AHU type.

NOTE! When the configuration in this page is finished, the menu item “Configuration” must be set
to “Done” and “Apply Changes!” must be executed so that the changes can take effect.

HMI Path: Main Menu  Commissioning  AHU Configuration  Config Unit Type

Menu item Value Description


AHU Model 1. Professional Display the actual AHU model. This parameter is automatically
(read only) 2. Modular configured according to the controller used:
1. Professional: AHU Professional model.
In this case POL638 controller is being used.
2. Modular: AHU Modular model.
In this case POL687 controller is being used.
Unit Type 1. AH-W-U Modify the type of AHU based on the external devices used to
2. AH-WDX-U produce cooling or heating. This setting specifies the I/O map that
3. AH-DX-U will be used:
4. AH-ERQ-U
1. AH-W-U: the AHU is connected to a water coil;
2. AH-WDX-U: the AHU is connected to a water coil and a
generic direct expansion coil. The water coil is used to produce
heating, while the DX coil produces cooling;
3. AH-DX-U: the AHU is connected to a generic direct expansion
coil;
4. AH-ERQ-U: the AHU is connected with the Daikin ERQ
condensing unit*.
*Select this unit type if it is also present a water heating coil.
AHU – COMMISSIONING MANUAL 7

Menu item Value Description


NOTE! If both heating and cooling coils are not present,
select “AH-W-U” as unit type.
Cooling 1. No Specify the type of AHU coil used to produce cooling:
2. Water
1. No: no cooling coil is present;
3. ERQ
2. Water: the device used to produce cooling is a water coil*;
4. Dx
3. ERQ: the device used to produce cooling is the ERQ;
4. Dx: the device used to produce cooling is a generic direct
expansion coil.
*If “Unit Type = AH-WDX-U” choose “Dx” cooling coil (if present).
Heating 1. No Specify the type of AHU coil used to produce heating:
2. Water
1. No: no heating coil is present;
3. ERQ
2. Water: the device used to produce heating is a water coil;
4. ERQ+Water
3. ERQ: the device used to produce heating is the ERQ;
5. Dx
4. ERQ+Water: the devices used to produce heating are both
ERQ and water coil*.
5. Dx: the device used to produce heating is a generic direct
expansion coil**.
*In this case “Unit Type” must be set to “AH-ERQ-U”.
**If “Unit Type = AH-WDX-U” choose “Water” heating coil (if
present).
Manuf. Place 1. EU Specify the manufacturing place of the AHU:
2. Asia
1. EU: AHU produced in EU; all controller expansion modules
considered.
2. Asia: AHU produced in Asia; ERQ defrost expansion module
for Professional unit not considered.
Unit S/N Enter Data Specify the Serial Number of the AHU by typing it in the “Enter Data”
string.

Below a diagram that summarizes all available AHU type configurations:

Heating = Water
AH-W-U
Cooling = Water

Heating = Water
AH-WDX-U
Cooling = Dx
Unit Type
Heating = Dx
AH-DX-U
Cooling = Dx

Heating = ERQ / Water / ERQ+Water


AH-ERQ-U
Cooling = ERQ
AHU – COMMISSIONING MANUAL 8

5. Components Configuration
This page allows to configure the type and number of components installed on the AHU. This step must be
executed only after the configuration of the AHU type.

NOTE! When the configuration in this page is finished, the menu item “Configuration” must be set
to “Done” and “Apply Changes!” must be executed so that the changes can take effect.

HMI Path: Main Menu  Commissioning  AHU Configuration  Config components

Menu item Value Description


Heating pump - No Specify the presence of an enabling pump contact for the heating
(only available if - Yes water coil.
“Water” is selected
as Heating coil)

Cooling pump - No Specify the presence of an enabling pump contact for the cooling
(only available if - Yes water coil.
“Water” is selected
as Cooling coil)

Water Coil Type - Separated Specify if the heating and cooling water coils are separated or
(only available if - Combined combined.
“Water” is selected Based on the value selected, consider different I/O on the controller:
as both Heating
Value selected Cooling coil Heating Coil
and Cooling coil) Pump = Q53 (POL638) Pump = Q33 (POL955-B)
Separated Signal = X6 (POL638) Signal = X7 (POL955-A)
Alarm = X4 (POL955-A) Alarm = X5 (POL955-B)
Pump = Q53 (POL638) Pump = Q53 (POL638)
Combined Signal = X6 (POL638) Signal = X6 (POL638)
Alarm = X4 (POL955-A) Alarm = X4 (POL955-A)
AHU – COMMISSIONING MANUAL 9

Menu item Value Description


Pre Htg Wtr - No Specify whether there is a water type pre-heating coil.
- Yes

Num of Dx step 0..3 Specify the number of steps of the direct expansion coil.
(only available if
“Dx” is selected as
Heating or Cooling
coil)

Num of ERQ 0..2 [Modular] Specify the number of Daikin ERQ condensing units.
(only available if 0..4 [Pro]
“ERQ” is selected
as Heating or
Cooling coil)

Fan Snsr Type - 0 – 10 V Specify the voltage range of fan pressure sensors installed.
- 0.5 – 4.5 V

Return Fan - No Specify the presence of the return fan.


- Yes

Fans for chn 1, 2 Specify the number of fans per channel.


(only available for
AHU “Modular”
model)

Mix Damper - No Specify if the mixing damper is being controlled by a modulating


- Yes actuator.
NOTE! This value must be set to “No” if the mixing damper
is controlled by an On/Off actuator or not controlled at all.

Outs Dampers - No Specify if the outside dampers (fresh/exhaust/return) are being


- Yes controlled by On/Off actuators.

Rec Device 1. No Specify the type of the recovery device:


2. Wheel
1. No: no recovery device is present in the AHU;
3. Cube
2. Wheel: the recovery device is a Heat-Wheel;
4. Water
3. Cube: the recovery device is a Heat-Cube;
4. Water: the recovery device is a RAR type.

Supply temp - No Specify the presence of the supply air temperature sensor.
- Yes

Outside temp - No Specify the presence of the external air temperature sensor.
- Yes

Return temp - No Specify the presence of the return air temperature sensor.
- Yes
AHU – COMMISSIONING MANUAL 10

Menu item Value Description


Room temp - No Specify the presence of the room unit device (POL822).
- 1 Unit

Pre-Heat temp - No Specify the presence of the pre-heating air temperature sensor.
- Yes
NOTE! Only one type of pre-heating can be enabled at a
time.

Frost Switch - No Specify the presence of the frost protection switch for the heating
(only available if - Yes coil.
“ERQ+Water” or
“Water” is selected
as Heating coil)

Other Sns 1. No Specify the type of other sensors installed on the AHU:
(only available for 2. CO2
1. No: no other sensor is present in the AHU;
AHU “Modular” 3. Humidity
2. CO2: the air quality (CO2) sensor is present;
model)
3. Humidity: the room humidity sensor is present;

Room hum - No Specify the presence of the room humidity sensor.


(only available for - Yes
AHU “Professional”
model)

Air qual (CO2) - No Specify the presence of the air quality (CO2) sensor.
(only available for - Yes
AHU “Professional”
model)

Electric htg - No Specify if the AHU is provided with a post-heating electric coil and its
- 1 Step number of activation stages:
- 2 Steps
1. No: no post-heating electric coil is present in the AHU;
- Modulate(*)
2. 1 Step: the post-heating electric coil features only one
activation stage;
3. 2 Steps: the post-heating electric coil features two
activation stages.
4. Modulate*: the post-heating electric coil features a
modulating control of its heat capacity.

(*) Only available for “Professional” AHU model.

NOTE! This value strictly depends on “Pre Htg Elect”


stages number: the sum of the steps from both pre/post
heating electric coil cannot exceed two stages.

Pre Htg Elect - No Specify if the AHU is provided with a pre-heating electric coil and its
- 1 Step number of activation stages:
- 2 Steps 1. No: no pre-heating electric coil is present in the AHU;
2. 1 Step: the pre-heating electric coil features only one
activation stage;
AHU – COMMISSIONING MANUAL 11

Menu item Value Description


3. 2 Steps: the pre-heating electric coil features two
activation stages.

NOTE! This value strictly depends on “Electric htg” stages


number: the sum of the steps from both pre/post heating
electric coil cannot exceed two stages.
Humidifier 1. No Configure the humidification device:
2. On/Off
1. No: no humidifier is present in the AHU;
3. Modulate(*)
2. On/Off: the humidifier is an On/Off device;
3. Modulate(*): the humidifier is a modulating device.

(*) only available for AHU “Professional” model.

Energy Meter 1. No Configure the Energy Meter device:


2. 1-Phase
1. No: no Energy Meter device installed;
3. 3-Phase
2. 1-Phase: the Energy Meter is installed and the AHU is power
supplied with a mono-phase connection;
3. 3-Phase: the Energy Meter is installed and the AHU is power
supplied with a three-phase connection;
AHU – COMMISSIONING MANUAL 12

6. Functions Configuration
This page allows to configure the control functions that can be performed by the AHU. This step must be
executed only after the configuration of AHU components.

NOTE! When the configuration in this page is finished, the menu item “Configuration” must be set
to “Done” and “Apply Changes!” must be executed so that the changes can take effect.

HMI Path: Main Menu  Commissioning  AHU Configuration  Config functions

Menu item Value Description


Fan ctrl mode 1. Direct Specify the control mode for supply/return fans:
2. Fix Speed
1. Direct: supply/return fans On/Off controlled.
3. Pressure
By selecting this mode, no fans setpoints are used;
4. Air Flow
2. Fix Speed: supply/return fans open loop controlled with a
fixed speed value. By selecting this mode, fans setpoints are a
percentage of max fan speed [%];
3. Pressure: supply/return fans closed loop controlled by a
pressure value. By selecting this mode, fans setpoints
measurement unit is in Pascal [Pa];
4. Air Flow: supply/return fans closed loop controlled by an air-
flow value . By selecting this mode, fans setpoints
measurement unit is in cube meters per hour [m3/h].

Fan Fdbk 1. No Specify the sensor feedback type for supply/return fans:
2. Pressure
1. No: no feedback is received by the controller;
3. Air Flow
2. Pressure: the feedback for fan control logic is a pressure
value [Pa];
AHU – COMMISSIONING MANUAL 13

Menu item Value Description


3. Air Flow: the feedback for fan control logic is an air flow
value [m3/h];

Fan Compensation 1. None Specify the compensation type for supply/return fans:
2. Temperature
1. None: no compensation function selected;
3. CO2(*)
2. Temperature: fan temperature compensation function
selected.
By enabling this function, fans setpoints are dynamically
reduced in order to increase the heating/cooling effect of the
selected coil type;
3. CO2(*): CO2 compensation function selected.
By enabling this function, fans setpoints are dynamically
increased in order to reduce CO2 concentration in the air.

(*) only available when “Air Qual (CO2)” sensor is selected.


Fan Defrst Limit - No Enable of the fan defrost limitation logic.
- Yes

MxDmp St - Open Specify mixing damper state during AHU “Ventilation” mode.
Ventilation - Close
(only available if a
“Mix Damper” is
selected )

Tmp ctrl mode 1. Supply Specify the temperature controlled by the regulation logic:
2. Room
1. Supply: the regulation logic controls the supply air
3. Return
temperature;
2. Room: the regulation logic controls the room temperature
provided by the room unit (POL822);
3. Return: the regulation logic controls the return air
temperature.

Tmp stpt sel 1. Htg+Dz Specify the type of temperature setpoints used in heating/cooling
2. Htg/Clg modes:
3. +/- 1/2Dz
1. Htg+Dz: direct control over heating setpoint with a
4. Clg-Dz
deadzone for cooling setpoint;
2. Htg/Clg: direct control over both heating and cooling
setpoints;
3. +/- 1/2Dz: temperature control over a central temperature
and a deadzone setpoints for both heating and cooling;
4. Clg-Dz: direct control over cooling setpoint with a deadzone
for heating setpoint.
Recovery Type 1. On/Off Specify the control logic for the recovery device:
(only available if a 2. Modulate
1. On/Off: the heat recovery can either have a fixed speed
“Rec Device” is
device (wheel), a damper (cube) or a water pump enabling
selected)
contact (RAR) and it is controlled by an On/Off contact;
2. Modulate: the heat recovery is a variable speed/opening
device controlled by a modulating signal.
AHU – COMMISSIONING MANUAL 14

Menu item Value Description


ERQ Wtr Priority 1. Auto Specify the activation sequence of the ERQ and water coils for
(only available if 2. ERQfirst heating mode:
“ERQ+Water” is 3. Waterfirst
1. Auto: the activation sequence is automatically determined
selected as Heating
from the comparison between a threshold temperature
coil)
(changeable) and the outside air temperature:
Tout > Ttreshold -> ERQ first
Tout < Ttreshold -> Water first
2. ERQfirst: the ERQ is activated first;
3. Waterfirst: the water coil is activated first.

MxDmp cmp CO2 - No Specify the activation of the CO2 compensation logic for the mixing
(only available if - Yes damper.
“Mix Damper” and By enabling this function, the maximum aperture of the mixing
“Air qual (CO2)” damper is being dynamically limited in order to facilitate room air
sensor are exchange.
selected)

Adiabatic Recovery - No Specify the activation of the adiabatic recovery function.


(only available if - Yes
“On/Off” is
selected as
Humidifier type)

Humidity ctrl 1. No Specify the type of the humidification control functions:


(only available if a 2. Hum
1. No: no humidification/dehumidification control selected;
“Room hum” 3. DeHum
2. Hum: only humidification control selected;
and/or a 4. Hum+DeHum
3. DeHum: only dehumidification control selected;
“Humidifier” are
4. Hum+DeHum: both humidification/dehumidification
selected)
controls selected.

Post Htg DeHum 1. No Specify the type of the post-heating coil used for dehumidification
(only available if 2. Water control logic:
“DeHum” or 3. Electric
1. No: no post-heating coil for dehumidification is present;
“Hum+DeHum” is
2. Water: the post-heating coil for dehumidification control is a
selected as
water type coil;
humidity control
3. Electric: the post-heating coil for dehumidification is an
type)
electric type coil.

Fan Alarm 1. No Select the fan for which the respective alarm is being enabled:
2. Supply
1. No: no fan alarms;
3. Return
2. Supply: alarm active only for supply fan;
4. Sply+Ret
3. Return: alarm active only for return fan;
4. Sply+Ret: alarm active for both supply and return fans.

Fan Alm Type 1. Inverter Specify the type of the supply/return fan alarm:
2. DPS
1. Inverter: alarm is generated by an external fan inverter (not
3. Both
for EBM-Papst fan);
AHU – COMMISSIONING MANUAL 15

Menu item Value Description


2. DPS: alarm is generated by a Differential Pressure Switch
(DPS) or by the EMB-Papst fan;
3. Both: both alarms type available.

Fan Alm Dly 0…180 sec Specify the delay time for the activation of the supply/return fan
alarm.

Fan Dev Alm 1. No Select the fan for which the respective setpoint deviation alarm is
2. Supply being enabled:
3. Return
1. No: no fan setpoint deviation alarms;
4. Sply+Ret
2. Supply: setpoint deviation alarm active only for supply fan;
3. Return: setpoint deviation alarm active only for return fan;
4. Sply+Ret: setpoint deviation alarm active for both supply
and return fans.

Filter alarm 1. No Select the filters for which the respective alarm is being enabled:
2. Supply
1. No: no filter alarms;
3. Return
2. Supply: filter alarm active only for supply fan;
4. Sply+Ret
3. Return: filter alarm active only for return fan;
4. Sply+Ret: filter alarm active for both supply and return fans.

ERQ Alm Type 1. Stop Specify the behavior of the ERQ alarms management:
2. Display
1. Stop: the AHU is stopped only if all ERQs are in alarm,
otherwise only a visualization on the HMI appears;
2. Display: the AHU is never stopped and only a visualization
on the HMI appears;

Recovery Alm - No Specify the presence of the heat recovery digital input alarm.
(only available for - Yes
“Modular” AHU
model)
Htg Pump Alm - No Specify the presence of the heating coil pump digital input alarm.
(only available if a - Yes
“Htg Pump” is
selected)
Clg Pump Alm - No Specify the presence of the cooling coil pump digital input alarm.
(only available if a - Yes
“Clg Pump” is
selected)
Clg Dx Alarm - No Specify the presence of the direct expansion cooling coil digital
(only available if - Yes input alarm.
“Dx” is selected as
cooling coil)
El htg alarm - No Specify the presence of the electrical heating digital input alarm.
(only available if an - Yes
electrical heating
coil is selected)
AHU – COMMISSIONING MANUAL 16

Menu item Value Description


Fire Alarm 1. No Specify the presence and the type of the fire alarm:
2. Alm
1. No: no fire alarm active;
3. Tmp
2. Alm: fire alarm active as a physical digital input value;
4. Alarm+Tmp
3. Tmp: fire alarm active as a monitoring function on the
controlled temperature (supply or return);
4. Alarm+Tmp: both fire alarm types active.

Fire Alarm Type 1. NO Specify the type of physical digital input value for the fire alarm
2. NC device used:
1. NO: Normally Open, the alarm is given when the fire alarm
digital input is closed;
2. NC: Normally Closed, the alarm is given when the fire alarm
digital input is open;

Fire dmp ctrl 1. No Specify the presence and the behavior of the fire damper when a
(only available for 2. Yes fire alarm occurs:
“Professional” AHU 3. FollowUnit
1. No: no fire damper is present;
model)
2. Yes: the fire damper is present and it will close when a fire
alarm occurs;
3. FollowUnit: the fire damper is present and it will close when
a fire alarm occurs, but follows the behavior of the AHU when
not in alarm.
AHU – COMMISSIONING MANUAL 17

7. Fans Configuration
This page allows to configure AHU supply and return (if present) fans, together with fans sensors scales.
This is the last AHU configuration step and must be executed only after the configuration of AHU functions.

HMI Path: Main Menu  Commissioning  AHU Configuration  Config fan

Menu item Value Description


Supply Fan
Type 1. EC-Aluminium Specify model and material type of the supply fan.
2. EC-Plastic
According to this value, the Pressure/AirFlow conversion factor
3. Other
“K” that is considered will be the one of the selected fan type (i.e.
if “Type = EC-Aluminium” -> “K-Actual” modified by “Aluminium”
value):
1. EC-Aluminium: EBM-Papst supply fan of aluminium type;
“K-Actual” modified by “Aluminium” menu item value.
2. EC-Plastic: EBM-Papst supply fan of plastic type;
“K-Actual” modified by “Plastic” menu item value.
3. Other: custom supply fan (not EBM-Papst);
“K-Actual” equal to “K-Custom” menu item value.

Aluminium 250, 280, 310, Specify the size of the EBM-Papst aluminium type supply fan.
355, 400, 450, Depending on the fan size the conversion factor “K” will be
500, 560, 630, automatically determined.
710, 800, 900
NOTE! Consider this menu item only if fan “Type” is set to
“EC-Aluminium”.
AHU – COMMISSIONING MANUAL 18

Menu item Value Description


Plastic 250, 280, 310, Specify the size of the EBM-Papst plastic type supply fan.
355, 400, 450, Depending on the fan size the conversion factor “K” will be
500, 560, 630 automatically determined.

NOTE! Consider this menu item only if fan “Type” is set to


“EC-Plastic”.

K-Custom 0…10000 Specify the value of the conversion factor “K” for custom supply
fan type.

NOTE! Consider this menu item only if fan “Type” is set to


“Other”.

K-Actual 0…10000 Display the actual value of the conversion factor “K” that will be
(read only) used in supply fan control logic.

Sply Prs Scale 0…10000 Specify the value of the supply fan pressure sensor scale.
(only available if
“Fan fdbk” is set to
“Pressure”)

Sply Flow Scale 0…100000 Specify the value of the supply fan airflow sensor scale.
(only available if
“Fan fdbk” is set to
“Air Flow”)

Return Fan (only available if “Return Fan” component is selected)


Type 1. EC-Aluminium Specify model and material type of the return fan.
2. EC-Plastic
According to this value, the Pressure/AirFlow conversion factor
3. Other
“K” that is considered will be the one of the selected fan type (i.e.
if “Type = EC-Aluminium” -> “K-Actual” modified by “Aluminium”
value):
1. EC-Aluminium: EBM-Papst return fan of aluminium type;
“K-Actual” modified by “Aluminium” menu item value.
2. EC-Plastic: EBM-Papst return fan of plastic type;
“K-Actual” modified by “Plastic” menu item value.
3. Other: custom return fan (not EBM-Papst);
“K-Actual” equal to “K-Custom” menu item value.

Aluminium 250, 280, 310, Specify the size of the EBM-Papst aluminium type return fan.
355, 400, 450, Depending on the fan size the conversion factor “K” will be
500, 560, 630, automatically determined.
710, 800, 900
NOTE! Consider this menu item only if fan “Type” is set to
“EC-Aluminium”.
AHU – COMMISSIONING MANUAL 19

Menu item Value Description


Plastic 250, 280, 310, Specify the size of the EBM-Papst plastic type return fan.
355, 400, 450, Depending on the fan size the conversion factor “K” will be
500, 560, 630 automatically determined.

NOTE! Consider this menu item only if fan “Type” is set to


“EC-Plastic”.

K-Custom 0…10000 Specify the value of the conversion factor “K” for custom return
fan type.

NOTE! Consider this menu item only if fan “Type” is set to


“Other”.

K-Actual 0…10000 Display the actual value of the conversion factor “K” that will be
(read only) used in return fan control logic.

Rtrn Prs Scale 0…10000 Specify the value of the return fan pressure sensor scale.
(only available if
“Fan fdbk” is set to
“Pressure”)
Rtrn Flow Scale 0…100000 Specify the value of the return fan airflow sensor scale.
(only available if
“Fan fdbk” is set to
“Air Flow”)
AHU – COMMISSIONING MANUAL 20

The present publication is drawn up by of information only and does not constitute an offer binding upon Daikin Applied Europe S.p.A..
Daikin Applied Europe S.p.A. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is
given for the completeness, accuracy, reliability or fitness for particular purpose of its content, and the products and services presented
therein. Specification are subject to change without prior notice. Refer to the data communicated at the time of the order. Daikin Applied
Europe S.p.A. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use
and/or interpretation of this publication. All content is copyrighted by Daikin Applied Europe S.p.A..

DAIKIN APPLIED EUROPE S.p.A.


Via Piani di Santa Maria, 72 - 00040 Ariccia (Roma) - Italia
Tel: (+39) 06 93 73 11 - Fax: (+39) 06 93 74 014
http://www.daikinapplied.eu

You might also like