AHU – COMMISSIONING MANUAL 2
Index
1. Air Handling Unit Safety Information ........................................................................................................ 3
2. Introduction ............................................................................................................................................... 4
2.1 Revision History ................................................................................................................................. 4
3. AHU Configuration screen ......................................................................................................................... 5
4. Unit Type Configuration............................................................................................................................. 6
5. Components Configuration........................................................................................................................ 8
6. Functions Configuration .......................................................................................................................... 12
7. Fans Configuration ................................................................................................................................... 17
AHU – COMMISSIONING MANUAL 3
2. Introduction
This commissioning manual provides the information needed to configure the Daikin Air Handling Unit
(AHU), both Modular and Professional models.
Please note that the following manual always refers to the latest official released software version of the
unit.
Refer to D-AHU operating manual for detailed information about control functions and how to operate on
AHU controller.
The following table shows all the items needed for AHU configuration and the sections where they are
described.
Menu item Section
Config unit type Display and configure AHU type and coils
(Section number 4)
Config components Display and configure installed components
(Section number 5)
Config functions Display and configure available functions
(Section number 6)
Config fan Display and configure AHU fans type and sensors.
(Section number 7)
IMPORTANT! The AHU configuration procedure must be executed following the “AHU
Configuration” menu item order (i.e. Config Unit Type -> Config Components -> Config functions ->
Config fan), because some menu items are strictly dependent on how the AHU has been
configured in previous sections.
AHU – COMMISSIONING MANUAL 6
NOTE! When the configuration in this page is finished, the menu item “Configuration” must be set
to “Done” and “Apply Changes!” must be executed so that the changes can take effect.
HMI Path: Main Menu Commissioning AHU Configuration Config Unit Type
Heating = Water
AH-W-U
Cooling = Water
Heating = Water
AH-WDX-U
Cooling = Dx
Unit Type
Heating = Dx
AH-DX-U
Cooling = Dx
5. Components Configuration
This page allows to configure the type and number of components installed on the AHU. This step must be
executed only after the configuration of the AHU type.
NOTE! When the configuration in this page is finished, the menu item “Configuration” must be set
to “Done” and “Apply Changes!” must be executed so that the changes can take effect.
Cooling pump - No Specify the presence of an enabling pump contact for the cooling
(only available if - Yes water coil.
“Water” is selected
as Cooling coil)
Water Coil Type - Separated Specify if the heating and cooling water coils are separated or
(only available if - Combined combined.
“Water” is selected Based on the value selected, consider different I/O on the controller:
as both Heating
Value selected Cooling coil Heating Coil
and Cooling coil) Pump = Q53 (POL638) Pump = Q33 (POL955-B)
Separated Signal = X6 (POL638) Signal = X7 (POL955-A)
Alarm = X4 (POL955-A) Alarm = X5 (POL955-B)
Pump = Q53 (POL638) Pump = Q53 (POL638)
Combined Signal = X6 (POL638) Signal = X6 (POL638)
Alarm = X4 (POL955-A) Alarm = X4 (POL955-A)
AHU – COMMISSIONING MANUAL 9
Num of Dx step 0..3 Specify the number of steps of the direct expansion coil.
(only available if
“Dx” is selected as
Heating or Cooling
coil)
Num of ERQ 0..2 [Modular] Specify the number of Daikin ERQ condensing units.
(only available if 0..4 [Pro]
“ERQ” is selected
as Heating or
Cooling coil)
Fan Snsr Type - 0 – 10 V Specify the voltage range of fan pressure sensors installed.
- 0.5 – 4.5 V
Supply temp - No Specify the presence of the supply air temperature sensor.
- Yes
Outside temp - No Specify the presence of the external air temperature sensor.
- Yes
Return temp - No Specify the presence of the return air temperature sensor.
- Yes
AHU – COMMISSIONING MANUAL 10
Pre-Heat temp - No Specify the presence of the pre-heating air temperature sensor.
- Yes
NOTE! Only one type of pre-heating can be enabled at a
time.
Frost Switch - No Specify the presence of the frost protection switch for the heating
(only available if - Yes coil.
“ERQ+Water” or
“Water” is selected
as Heating coil)
Other Sns 1. No Specify the type of other sensors installed on the AHU:
(only available for 2. CO2
1. No: no other sensor is present in the AHU;
AHU “Modular” 3. Humidity
2. CO2: the air quality (CO2) sensor is present;
model)
3. Humidity: the room humidity sensor is present;
Air qual (CO2) - No Specify the presence of the air quality (CO2) sensor.
(only available for - Yes
AHU “Professional”
model)
Electric htg - No Specify if the AHU is provided with a post-heating electric coil and its
- 1 Step number of activation stages:
- 2 Steps
1. No: no post-heating electric coil is present in the AHU;
- Modulate(*)
2. 1 Step: the post-heating electric coil features only one
activation stage;
3. 2 Steps: the post-heating electric coil features two
activation stages.
4. Modulate*: the post-heating electric coil features a
modulating control of its heat capacity.
Pre Htg Elect - No Specify if the AHU is provided with a pre-heating electric coil and its
- 1 Step number of activation stages:
- 2 Steps 1. No: no pre-heating electric coil is present in the AHU;
2. 1 Step: the pre-heating electric coil features only one
activation stage;
AHU – COMMISSIONING MANUAL 11
6. Functions Configuration
This page allows to configure the control functions that can be performed by the AHU. This step must be
executed only after the configuration of AHU components.
NOTE! When the configuration in this page is finished, the menu item “Configuration” must be set
to “Done” and “Apply Changes!” must be executed so that the changes can take effect.
Fan Fdbk 1. No Specify the sensor feedback type for supply/return fans:
2. Pressure
1. No: no feedback is received by the controller;
3. Air Flow
2. Pressure: the feedback for fan control logic is a pressure
value [Pa];
AHU – COMMISSIONING MANUAL 13
Fan Compensation 1. None Specify the compensation type for supply/return fans:
2. Temperature
1. None: no compensation function selected;
3. CO2(*)
2. Temperature: fan temperature compensation function
selected.
By enabling this function, fans setpoints are dynamically
reduced in order to increase the heating/cooling effect of the
selected coil type;
3. CO2(*): CO2 compensation function selected.
By enabling this function, fans setpoints are dynamically
increased in order to reduce CO2 concentration in the air.
MxDmp St - Open Specify mixing damper state during AHU “Ventilation” mode.
Ventilation - Close
(only available if a
“Mix Damper” is
selected )
Tmp ctrl mode 1. Supply Specify the temperature controlled by the regulation logic:
2. Room
1. Supply: the regulation logic controls the supply air
3. Return
temperature;
2. Room: the regulation logic controls the room temperature
provided by the room unit (POL822);
3. Return: the regulation logic controls the return air
temperature.
Tmp stpt sel 1. Htg+Dz Specify the type of temperature setpoints used in heating/cooling
2. Htg/Clg modes:
3. +/- 1/2Dz
1. Htg+Dz: direct control over heating setpoint with a
4. Clg-Dz
deadzone for cooling setpoint;
2. Htg/Clg: direct control over both heating and cooling
setpoints;
3. +/- 1/2Dz: temperature control over a central temperature
and a deadzone setpoints for both heating and cooling;
4. Clg-Dz: direct control over cooling setpoint with a deadzone
for heating setpoint.
Recovery Type 1. On/Off Specify the control logic for the recovery device:
(only available if a 2. Modulate
1. On/Off: the heat recovery can either have a fixed speed
“Rec Device” is
device (wheel), a damper (cube) or a water pump enabling
selected)
contact (RAR) and it is controlled by an On/Off contact;
2. Modulate: the heat recovery is a variable speed/opening
device controlled by a modulating signal.
AHU – COMMISSIONING MANUAL 14
MxDmp cmp CO2 - No Specify the activation of the CO2 compensation logic for the mixing
(only available if - Yes damper.
“Mix Damper” and By enabling this function, the maximum aperture of the mixing
“Air qual (CO2)” damper is being dynamically limited in order to facilitate room air
sensor are exchange.
selected)
Post Htg DeHum 1. No Specify the type of the post-heating coil used for dehumidification
(only available if 2. Water control logic:
“DeHum” or 3. Electric
1. No: no post-heating coil for dehumidification is present;
“Hum+DeHum” is
2. Water: the post-heating coil for dehumidification control is a
selected as
water type coil;
humidity control
3. Electric: the post-heating coil for dehumidification is an
type)
electric type coil.
Fan Alarm 1. No Select the fan for which the respective alarm is being enabled:
2. Supply
1. No: no fan alarms;
3. Return
2. Supply: alarm active only for supply fan;
4. Sply+Ret
3. Return: alarm active only for return fan;
4. Sply+Ret: alarm active for both supply and return fans.
Fan Alm Type 1. Inverter Specify the type of the supply/return fan alarm:
2. DPS
1. Inverter: alarm is generated by an external fan inverter (not
3. Both
for EBM-Papst fan);
AHU – COMMISSIONING MANUAL 15
Fan Alm Dly 0…180 sec Specify the delay time for the activation of the supply/return fan
alarm.
Fan Dev Alm 1. No Select the fan for which the respective setpoint deviation alarm is
2. Supply being enabled:
3. Return
1. No: no fan setpoint deviation alarms;
4. Sply+Ret
2. Supply: setpoint deviation alarm active only for supply fan;
3. Return: setpoint deviation alarm active only for return fan;
4. Sply+Ret: setpoint deviation alarm active for both supply
and return fans.
Filter alarm 1. No Select the filters for which the respective alarm is being enabled:
2. Supply
1. No: no filter alarms;
3. Return
2. Supply: filter alarm active only for supply fan;
4. Sply+Ret
3. Return: filter alarm active only for return fan;
4. Sply+Ret: filter alarm active for both supply and return fans.
ERQ Alm Type 1. Stop Specify the behavior of the ERQ alarms management:
2. Display
1. Stop: the AHU is stopped only if all ERQs are in alarm,
otherwise only a visualization on the HMI appears;
2. Display: the AHU is never stopped and only a visualization
on the HMI appears;
Recovery Alm - No Specify the presence of the heat recovery digital input alarm.
(only available for - Yes
“Modular” AHU
model)
Htg Pump Alm - No Specify the presence of the heating coil pump digital input alarm.
(only available if a - Yes
“Htg Pump” is
selected)
Clg Pump Alm - No Specify the presence of the cooling coil pump digital input alarm.
(only available if a - Yes
“Clg Pump” is
selected)
Clg Dx Alarm - No Specify the presence of the direct expansion cooling coil digital
(only available if - Yes input alarm.
“Dx” is selected as
cooling coil)
El htg alarm - No Specify the presence of the electrical heating digital input alarm.
(only available if an - Yes
electrical heating
coil is selected)
AHU – COMMISSIONING MANUAL 16
Fire Alarm Type 1. NO Specify the type of physical digital input value for the fire alarm
2. NC device used:
1. NO: Normally Open, the alarm is given when the fire alarm
digital input is closed;
2. NC: Normally Closed, the alarm is given when the fire alarm
digital input is open;
Fire dmp ctrl 1. No Specify the presence and the behavior of the fire damper when a
(only available for 2. Yes fire alarm occurs:
“Professional” AHU 3. FollowUnit
1. No: no fire damper is present;
model)
2. Yes: the fire damper is present and it will close when a fire
alarm occurs;
3. FollowUnit: the fire damper is present and it will close when
a fire alarm occurs, but follows the behavior of the AHU when
not in alarm.
AHU – COMMISSIONING MANUAL 17
7. Fans Configuration
This page allows to configure AHU supply and return (if present) fans, together with fans sensors scales.
This is the last AHU configuration step and must be executed only after the configuration of AHU functions.
Aluminium 250, 280, 310, Specify the size of the EBM-Papst aluminium type supply fan.
355, 400, 450, Depending on the fan size the conversion factor “K” will be
500, 560, 630, automatically determined.
710, 800, 900
NOTE! Consider this menu item only if fan “Type” is set to
“EC-Aluminium”.
AHU – COMMISSIONING MANUAL 18
K-Custom 0…10000 Specify the value of the conversion factor “K” for custom supply
fan type.
K-Actual 0…10000 Display the actual value of the conversion factor “K” that will be
(read only) used in supply fan control logic.
Sply Prs Scale 0…10000 Specify the value of the supply fan pressure sensor scale.
(only available if
“Fan fdbk” is set to
“Pressure”)
Sply Flow Scale 0…100000 Specify the value of the supply fan airflow sensor scale.
(only available if
“Fan fdbk” is set to
“Air Flow”)
Aluminium 250, 280, 310, Specify the size of the EBM-Papst aluminium type return fan.
355, 400, 450, Depending on the fan size the conversion factor “K” will be
500, 560, 630, automatically determined.
710, 800, 900
NOTE! Consider this menu item only if fan “Type” is set to
“EC-Aluminium”.
AHU – COMMISSIONING MANUAL 19
K-Custom 0…10000 Specify the value of the conversion factor “K” for custom return
fan type.
K-Actual 0…10000 Display the actual value of the conversion factor “K” that will be
(read only) used in return fan control logic.
Rtrn Prs Scale 0…10000 Specify the value of the return fan pressure sensor scale.
(only available if
“Fan fdbk” is set to
“Pressure”)
Rtrn Flow Scale 0…100000 Specify the value of the return fan airflow sensor scale.
(only available if
“Fan fdbk” is set to
“Air Flow”)
AHU – COMMISSIONING MANUAL 20
The present publication is drawn up by of information only and does not constitute an offer binding upon Daikin Applied Europe S.p.A..
Daikin Applied Europe S.p.A. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is
given for the completeness, accuracy, reliability or fitness for particular purpose of its content, and the products and services presented
therein. Specification are subject to change without prior notice. Refer to the data communicated at the time of the order. Daikin Applied
Europe S.p.A. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use
and/or interpretation of this publication. All content is copyrighted by Daikin Applied Europe S.p.A..