ARCHITECTURAL

DRAWINGS
CONTENTS
USE OF ARCHITECTURAL DRAWINGS
INDEX OF DRAWINGS BY DETAIL NUMBER
GENERAL DETAILS
B26 Product Technical Data 3
B27 Minimum Pitch Table 3
B28 Rafter Length Table 4
MT01 Sarked Ceiling - Exposed Rafters 4
MT25 Fire Wall Detail 5
RIDGE DETAILS
B12 Ridge Detail 5
B13 Roof/Wall Ridge - Detail/Clerestorey 6
MT02 Steep Pitched Ridge 6
MT03 Butt Jointed Ridge 7
MT04 Flexible Pointing 7
BARGE DETAILS
B05 Barge Tile Detail 8
B06 Bed & Point Finish 8
B07 Small Panel Metal Detail 9
MT05 Barge Detail With Secret Gutter - Flat Tile 9
MT06 Verge - Secret Gutter 10
MT07 Verge - No Overhang Scribed Fillet 10
MT08 Verge - No Overhang Concrete Block 11
MT09 Flashing At Junction Of Metal Roof & Tile 11
MT11 Barge Detail With Z Flashing - Flat Tile 12
MT12 Barge Detail With Banbury Flashing - Flat Tile 12
B30 Bed & Point Finish - Flat Tile 13
APRON DETAILS
B01 Apron Details - Parallel Flashing Without Underlay 14
B02 Apron Details - Parallel Flashing With Underlay 14
B03 Apron Details - Transverse Flashing Without Underlay 15
B04 Apron Details - Transverse Flashing With Underlay 15
B25 Spreader For Roof Discharge 16
B29 Kickout Flashing 16
MT13 Stepped Cover Flashing 17
MT14 Flashing To Brick Abutment 17
MT15 Dutch Gable Detail 18
MT16 Vertical Tiling 18
PITCH CHANGE DETAILS
B08 Change In Pitch -35 Degrees Or Less 19
B09 Change In Pitch - Greater Than 35 Degrees 19
MT10 Mansard Detail 20
EAVES DETAILS
B19 Timber Fascia Eaves Detail - Without Underlay 20
B20 Timber Fascia Eaves Detail - With Underlay 21
B21 Internal Fascia Gutter Detail 21
B22 External Fascia Gutter Detail 22
B23 Eaves Exposed Rafters 22
B24 Eaves & Rafter Detail With Sarking 23
MT23 Eaves Standard Gutter 23
MT24 Fascia Height 24
VALLEY DETAILS
B10 Valley Detail Without Underlay 24
B11 Valley Detail With Underlay 25
MT21 Hip Gutter 25
MT22 Steep Pitch Roof Valley 26
PENETRATION DETAILS
B14 Plan View Of Three Sided Penetration 26
B15 Abutment Detail For Framed Penetration 27
B16 Elevation/Section View Of Three Sided Penetration 27
B17 Cross Section Of Hidden Gutter 28
B18 Pipe Penetration Detail 28
MT17 Cross Section Hidden Gutter - Flat Tile 29
MT18 Chimney Tray 29
MT19 Chimney Flashing 30
MT20 Pipe Penetration Detail - Flat Tile 30
USE OF ARCHITECTURAL DRAWINGS
Monier roofing systems provide contemporary
and innovative design solutions that benefit IMPORTANT INFORMATION FOR DISCLAIMER
from the time proven effectiveness and SPECIFICATION, PREPARATION
sustainability of tiles. This manual contains a & INSTALLATION This information is intended solely as a guide
for use of Monier products. Before using
broad range of roofing details and applications
enabling architects and specifiers to easily Monier products you should ensure that the
This manual has been prepared by Monier to
access and assess the suitability of design for product is suitable for use in the specific
assists the architect, builder and installer to
their client. application. Nothing in this information
specify, prepare and install roof tiles.
constitutes a statement of fitness for particular
While it is not possible to detail every
purpose - appropriate expert advice should
MONIER DETAIL DRAWINGS condition that may be encountered, Monier
will assist to advise on any special situations
always be obtained. Monier makes no warranty
NOW ONLINE that may occur.
regarding the use of this information with
non-Monier products.
This manual has been written as a working
© 2010 The copyright of this document is the
Monier roofing detail drawings are available guide for industry, however it is not intended
property of CSR Building Products (NZ) Ltd
in multiple CAD formats and as enlarged PDF to replace good trade practice and experience
trading as Monier and shall not be reproduced,
files at monier.co.nz. essential to obtaining a quality roof
copied, loaned or disposed of directly, or
installation. Nor does this manual override
indirectly, nor used for any purpose other
The information provided in the drawings specific advice received from Monier fixing
than that for which it is specifically furnished
provide reference information on the typical services.
without prior consent.
use of the Monier product. The information Architects and specifiers should ensure
provided in this reference guide is generic in that the details provided in this manual are
nature; it does not contain the full details followed and determined to their own
required for construction, nor does it satisfaction that the job is complete to an
constitute an express statement as to fitness acceptable standard of trade practice. All
for a particular purpose. Professional advice care has been taken in the compilation of this
is required to take into account all site and manual. However, Monier accepts no
design specific influences. Designers and responsibility or liability for the contents
specifiers will typically provide details specific of the manual (including any printing or
to particular projects: these should always be typographical errors) and recommends that
referred to in preference to the default system all standards and recommendations are
of drawings. The instructions and details independently checked.
available refer to both concrete and terracotta
tiles (except where specifically noted).
SPECIFICATIONS
MONIER COMPLIANCE WITH THE While information contained in this manual is
NEW ZEALAND BUILDING CODE correct at the time of creation, specifications
are subject to change without notice.
When installed according to the manufacturers
instructions, Monier products will meet the
Durability performance requirements of NZBC
B2 and E2.
Methods used for verifying compliance with
the relevant performances of the New Zealand
Building Code, include testing and assessment
by a laboratory, ease of installation
1
assessment, assessment of data provided by
the manufacturer and the inservice history
ARCHITECTURAL DRAWINGS

overseas and in New Zealand. Details are


available from Monier.
INDEX OF DRAWINGS BY DETAIL NUMBER
Detail Category Page
B01 Apron Details - Parallel Flashing Without Underlay Apron Details 14
B02 Apron Details - Parallel Flashing With Underlay Apron Details 14
B03 Apron Details - Transverse Flashing Without Underlay Apron Details 15
B04 Apron Details - Transverse Flashing With Underlay Apron Details 15
B05 Barge Tile Detail Barge Details 8
B06 Bed & Point Finish Barge Details 8
B07 Small Panel Metal Detail Barge Details 9
B08 Change In Pitch - 35 degrees Or Less Pitch Change Details 19
B09 Change In Pitch - Greater Than 35 Degrees Pitch Change Details 19
B10 Valley Detail Without Underlay Valley Details 24
B11 Valley Detail With Underlay Valley Details 25
B12 Ridge Detail Ridge Details 5
B13 Roof/Wall Ridge - Detail/Clerestorey Ridge Details 6
B14 Plan View Of Three Sided Penetration Penetration Details 26
B15 Abutment Detail For Framed Penetration Penetration Details 27
B16 Elevation/Section View Of Three Sided Penetration Penetration Details 27
B17 Cross Section Of Hidden Gutter Penetration Details 28
B18 Pipe Penetration Detail Penetration Details 28
B19 Timber Fascia Eaves Detail - Without Underlay Eaves Details 20
B20 Timber Fascia Eaves Detail - With Underlay Eaves Details 21
B21 Internal Fascia Gutter Detail Eaves Details 21
B22 External Fascia Gutter Detail Eaves Details 22
B23 Eaves Exposed Rafters Eaves Details 22
B24 Eaves & Rafter Detail With Sarking Eaves Details 23
B25 Spreader For Roof Discharge Apron Details 16
B26 Product Technical Data General Details 3
B27 Minimum Pitch Table General Details 3
B28 Rafter Length Table General Details 4
MONIER ARCHITECTURAL DRAWINGS

B29 Kickout Flashing Apron Details 16


B30 Bed & Point Finish - Flat Tile BargeDetails 13
MT01 Sarked Ceiling - Exposed Rafters General Details 4
MT02 Steep Pitched Ridge Ridge Details 6
MT03 Butt Jointed Ridge Ridge Details 7
MT04 Flexible Pointing Ridge Details 7
MT05 Barge Detail With Secret Gutter - Flat Tile Barge Details 9
MT06 Verge - Secret Gutter Barge Details 10
MT07 Verge - No Overhang Scribed Fillet Barge Details 10
MT08 Verge - No Overhang Concrete Block Barge Details 11
MT09 Flashing At Junction Of Metal Roof & Tile Barge Details 11
MT10 Mansard Detail Pitch Change Details 20
MT11 Barge Detail With Z Flashing - Flat Tile Barge Details 12
MT12 Barge Detail With Banbury Flashing - Flat Tile Barge Details 12
MT13 Stepped Cover Flashing Apron Details 17
2 MT14 Flashing To Brick Abutment Apron Details 17
MT15 Dutch Gable Detail Apron Details 18
SECTION 8

MT16 Vertical Tiling Apron Details 18


MT17 Cross Section Hidden Gutter - Flat Tile Penetration Details 29
MT18 Chimney Tray Penetration Details 29
MT19 Chimney Flashing Penetration Details 30
MT20 Pipe Penetration Detail - Flat Tile Penetration Details 30
MT21 Hip Gutter Valley Details 25
MT22 Steep Pitch Roof Valley Valley Details 26
MT23 Eaves Standard Gutter Eaves Details 23
MT24 Fascia Height Eaves Details 24
MT25 Fire Wall Detail General Details 5
GENERAL DETAILS
B26 PRODUCT TECHNICAL DATA
This drawing is to be read in conjunction with Monier technical literature.

Ridge Tile
Horizon, Georgian,
Madison Profile Roof Tile

Tapered Barge Tile

20mm
20mm
Hacienda Profile Roof Tile

Valley Tray

Monier Concrete Roofing Tiles are manufactured in accordance with


NZS 4206: 1992 'Concrete Interlocking Roofing Tiles'
b26 monier product technical data.dwg
Monier Roofing
PO Box 188,
Takanini,
Monier Tile Detail: B26 planstomonier@csr.co.nz
www.monier.co.nz

B27 MINIMUM PITCH TABLE


Auckland 2245 Product Technical Data Issue 1
20 January 2015
Not To Scale
Disclaimer: This information is intended solely as a guide for use of Monier products. Before using Monier products you should ensure that the product is suitable for use in the specific application. Nothing in this information constitutes a statement of fitness for
Technical Help particular purpose - appropriate expert advice should always be obtained. Monier makes no warranty regarding the use of this information with non-Monier products. © 2014. The copyright of this document is the property of CSR Building Products (NZ) Ltd
0800 851 588 trading as Monier and shall not be reproduced, copied, loaned or disposed of directly, or indirectly, nor used for any purpose other than that for which it is specifically furnished without prior consent.

Minimum Pitches for Concrete & Clay Tiles


Tile Material Minimum Pitches
Profile Type forWith
Concrete & Clay
Underlay (Refer NoteTilesWithout Underlay
Tile Material Minimum Pitches
Type I*
Profile Type for Concrete 15° (Refer NoteTilesWithout20°
With Underlay & Clay Underlay
Concrete Tiles
Tile Material Profile
TypeType
Type II
I* With Underlay
20° (Refer Note
15° Without20°
Underlay
-
Type III 25° -
Concrete Tiles Type I*
II* 15°
20° 20°
-
Type I 20° 25°
Concrete Tiles Type
Type III
II 25°
20°
20 -
Clay Tiles Type
Type III
TypeIII 20°
25°
20° --
25°
Type III 25° -
Clay Tiles Type III
Type 20° 25°
-
* Monier Hacienda & Villa profile concrete roof tiles conform to the "Type 1" profile type.
Clay Tiles Type
Type III II 25°
20° -
Type I Type 1: Double tiles having two distinct watercourses with a minimum watercourse depth of 18mm.
* *Monier
MonierHacienda
Hacienda & Villa
Type III profile
profile concrete
concrete roof
roof tiles
tiles conform
conform totothe
25° the"Type
"Type I"1"profile
profile type. -
Type II Single profile tiles having one watercourse a minimum of 25mm in height
* **
Type Monier
I Type
Monier Horizon,
1: Double
Hacienda Georgian,
& Villa tiles having
profile Madison profile
two distinct
concrete roof concrete
watercourses
tiles roof
conform to thetiles
with a conform
minimum
"Type to type.
the “Type
watercourse
1" profile III” profile
depth of 18mm.type.
Type III Tiles not fitting the Type I or Type II categories, and includes flat tiles and those resembling slated, shakes
Type
TypeIII Single 1:profile
Typeshingles.
Double tiles having
tiles having one watercourse
two a minimumwith
distinct watercourses of 25mm in height
a minimum watercourse depth of 18mm.
3
and
Type
TypeIII Tiles not
II Single fittingtiles
profile thehaving
Type I one
or Type II categories,
watercourse and includes
a minimum of 25mmflatintiles and those resembling slated, shakes
height
ARCHITECTURAL DRAWINGS

Type III and


Tilesshingles.
not fitting the Type I or Type II categories, and includes flat tiles and those resembling slated, shakes
and shingles.

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
B28 RAFTER LENGTH TABLE

Maximum
Maximum RafterLengths
Rafter LengthsFor
For Concrete
Concrete Tiles
TilesCompared
ComparedToTo
Roof Pitch
Roof Pitch
Hacienda Profile Hacienda Profile Horizon, Georgian & Madison Profiles
With Underlay Without Underlay
- With Underlay - Without Underlay - With Underlay
Roof Pitch Max. Rafter Length Roof Pitch Max. Rafter Length
Roof Pitch Max. Rafter Length Roof Pitch Max. Rafter Length Roof Pitch Max. Rafter Length
15° 4.5M 20° 4.5M
15° 4.5M 20° 4.5M 20° 4.5M
16° 5.0M 21° 5.0M
16° 5.0M 21° 5.0M 21° 5.0M
17° 17° 5.5M 5.5M 22° 5.5M 22° 22° 5.5M 5.5M
18° 18° 6.0M 6.0M 23° 6.0M 23° 23° 6.0M 6.0M
19° 19° 6.5M 6.5M 24° 6.5M 24° 24° 6.5M 6.5M
20° 20° 7.0M 7.0M 25° 7.0M 25° 25° 7.0M 7.0M
21° 21° 7.5M 7.5M 26° 7.5M 26° 26° 7.5M 7.5M
22° 22° 8.0M 8.0M 27° 8.0M 27° 27° 8.0M 8.0M
23° 23° 8.5M 8.5M 28° 8.5M 28° 28° 8.5M 8.5M
24° 24° 9.0M 9.0M 29° 9.0M 29° 29° 9.0M 9.0M
25° 25° 9.5M 9.5M
30° 9.5M 30° 30° 9.5M
9.5M
26° 10.0M 31° 10.0M 31° 10.0M
26° 10.0M 31° 10.0M
27° 10.5M 32° 10.5M 32° 10.5M
27° 10.5M 32° 10.5M
28° 11.0M 33° 11.0M 33° 11.0M
28° 11.0M 33° 11.0M
29° 11.5M 34° 11.5M 34° 11.5M
30° 29° 12.0M 11.5M 35° 12.0M 34° 35° 11.5M12.0M
31° 30° 12.5M 12.0M 36° 12.5M 35° 36° 12.0M12.5M
32° 31° 13.0M 12.5M 37° 13.0M 36° 37° 12.5M13.0M
33° 32° 13.5M 13.0M 38° 13.5M 37° 38° 13.0M13.5M
34° 33° 14.0M 13.5M 39° 14.0M 38° 39° 13.5M14.0M
35° 34° 14.5M 14.0M 40° 14.5M 39° 40° 14.0M14.5M
35° 14.5M 40° 14.5M

MT01 SARKED CEILING - EXPOSED RAFTERS

Counter batten
Monier tile

Batten
Underlay

Insulation

4
ARCHITECTURAL DRAWINGS

Electrical Services Duct located at bottom of Counter Batten

Rafter

Sarked Ceiling

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
MT25 FIRE WALL DETAIL

120mm 120mm

Monier tile

Tile batten

Underlay

Galvanised steel strap 25mm x


1mm or equivalent angle fixed
between battens

Mortar bedding or KAOWOOL


placed to fill space between
underside of tile and top surface
of fire wall

Rafter

Fire separation wall

RIDGE DETAILS
B12 RIDGE DETAIL

Monier Ridge Tile

Mortar bedding

Batten Mortar pointing with weep


holes at the pan of each
tile

Monier tile

Underlay where required

5
ARCHITECTURAL DRAWINGS

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
B13 ROOF/WALL RIDGE - DETAIL CLERESTORY

Proprietary capping tile


Mortar bedding

Mortar pointing with weep


holes at the pan of each tile Fixing point
Top of barge board 70mm
above rafter

Monier tile

70mm
Batten
Barge board
Underlay where required
Horizontal cavity batten

Cladding

Cladding cavity

Rafter

MT02 STEEP PITCHED RIDGE

Steep pitch ridge

Ridge beam & apex battens chamfered

Bedding mortar with weep holes

Monier tile

Tile batten
6
ARCHITECTURAL DRAWINGS

Underlay
Rafter

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
MT03 BUTT JOINTED RIDGE

Monier ridge tiles

Underflashing

Silicone joins Mortar bedding with weep holes

Monier tile
Underlay

MT04 FLEXIBLE POINTING

Ridge tile

Bedding material

Flexible pointing

Note:
When mechanical fixing is not used - flexible
pointing is required at all times

Monier ridge tile


Fasteners to hold tile in place
during testing
7
Mortar bedding with weep holes
ARCHITECTURAL DRAWINGS

Positive Pressure Chamber

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
BARGE DETAILS
B05 BARGE TILE DETAIL

* Where an over roll cannot be achieved, a Monier tile


Mortar finish
Zincalume® type Z flashing is to be installed.

Over roll upstand of tile under


barge tile as required *
Barge tile
50mm

Batten

Underlay where
Fixing point required
Outrigger
Barge board

Eaves lining

B06 BED & POINT FINISH

50mm Bedding mortar


Monier Tile 100mm painted fibre cement
strip installed by builder and
to overhang fascia by 50mm
m
m
Vaiable according to wind zone.

15
50x50mm batten
Refer to E2/AS1 Table 7
50-70mm

100mm

Underlay where required.


Zincalume® type Z
Anti-ponding boards required
flashing (Installed under
for roof pitch less than 20°
the fibre cement strip)
Barge
8
100x50mm Fly rafter
ARCHITECTURAL DRAWINGS

Soffit
Cladding
Cladding cavity

Wall framing
* 100mm

* Bed & Point finish requires a minimum soffit


width of 100mm past cladding

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
B07 SMALL PANEL METAL DETAIL

Mortar finish

Over roll upstand of tile under


* Where an over roll cannot be achieved, a Monier tile
barge tile as required *
Zincalume® type Z flashing is to be installed.
Barge tile

Fixing point
50mm

Batten

Proprietary Metal Barge Underlay where


(Incorporated in metal required
fascia/spouting system)
Outrigger -
100x50mm on flat

Eaves lining

MT05 BARGE DETAIL WITH SECRET GUTTER - FLAT TILE

This drawing is to be read in conjunction with Monier technical literature.


Variable according to wind zone.

30
Refer to E2/AS1 Table 7

mm
Gable cap flashing manufactured to barge height
*Note:
This drawing applies to Monier Horizon,
50-90mm

Madison and Georgian profiles


70mm
mm
10

75mm

Abutment underflashing
Option A:
Gable cap flashing Option B:
10mm notch out of every alternate
Additional support nog
batten as a maximum spacing
Gable cap flashing Intervening battens require
minimum 25mm support on rafter

Monier flat tile Monier flat tile


130 mm min

130 mm min
height

height

9
ARCHITECTURAL DRAWINGS

Fixing point Fixing point

Barge board Batten Barge board Batten

Rafter double Rafter double


to accommodate Underlay where to accommodate Underlay where
flashing and batten required flashing and batten required

Eaves lining Eaves lining

Outrigger Outrigger

mt05 monier barge detail with secret gutter - flat tile.dwg


Monier Roofing
PO Box 188,
Takanini,
Monier Tile Detail: MT05 planstomonier@csr.co.nz
www.monier.co.nz

Auckland 2245 Barge Detail With Secret Gutter - Monier Flat Tile Range Issue 3
22 December 2014
Scale 1:5
Disclaimer: This information is intended solely as a guide for use of Monier products. Before using Monier products you should ensure that the product is suitable for use in the specific application. Nothing in this information constitutes a statement of fitness for
Technical Help particular purpose - appropriate expert advice should always be obtained. Monier makes no warranty regarding the use of this information with non-Monier products. © 2014. The copyright of this document is the property of CSR Building Products (NZ) Ltd
0800 851 588 trading as Monier and shall not be reproduced, copied, loaned or disposed of directly, or indirectly, nor used for any purpose other than that for which it is specifically furnished without prior consent.

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
MT06 VERGE - SECRET GUTTER

Tile batten
Pre-primed metal
capping 75mm

Monier tile
120mm

Pre-primed metal
secret gutter

Barge board

Outrigger
Flying rafter

MT07 VERGE - NO OVERHANG SCRIBED FILLET

Fixing point Monier tiles

Z Flashing Batten

Treated scribed fillet

10
Building paper
ARCHITECTURAL DRAWINGS

Cladding

Rafter

Stud wall

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
MT08 VERGE - NO OVERHANG CONCRETE BLOCK

Monier tile
Mortar bedding

Batten
Fixing point

Mortar bedding

Exterior plaster finish carried


under tiles
Top cord

Treated fillet to take tile fixing

MT09 FLASHING AT JUNCTION OF METAL ROOF & TILE

Metal roof decking

Metal flashing

Acrylead / Lead flashing

Monier tile

Top plate
11
ARCHITECTURAL DRAWINGS

Stud

Tile batten

Rafter

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
MT11 BARGE DETAIL WITH Z FLASHING - FLAT TILE

10mm
100mm

10
Monier Horizon tile

mm
Mortar finish

Gable flashing Gable Flashing Dimensions

Barge tile
50mm

Batten

Underlay where
Fixing point required
Outrigger
Barge board

Eaves lining

Note:
Use this detail when barge board is above batten

MT12 BARGE DETAIL WITH BANBURY FLASHING - FLAT TILE

100mm
10mm

10

Monier Horizon tile


mm

Mortar finish

Gable flashing Gable Flashing Dimensions

Barge tile
50mm

Batten
12
Underlay where
Fixing point required
ARCHITECTURAL DRAWINGS

Outrigger
Barge board

Eaves lining

Note:
Use this flashing when barge board is flush with
batten

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
B30 BED & POINT FINISH - FLAT TILE

This drawing is to be read in conjunction with Monier technical literature.

Bedding mortar with flexible


Monier flat tile 50mm pointing finish
*Note: 100mm painted fibre cement
This drawing applies to Batten notched 10mm to strip installed by builder and
Monier Horizon, Madison fit flashing to overhang fascia by 50mm
and Georgian profiles
m
m

Variable according to wind zone.


15
50x50mm batten

Refer to E2/AS1 Table 7


50-90mm
100mm

Underlay where required.


Anti-ponding boards required Zincalume ® type Z
for roof pitch less than 20° flashing (Installed under
the fibre cement strip)
Barge
100x50mm Fly rafter
Soffit
Cladding
Cladding cavity

Wall framing
* 100mm

* Bed & Point finish requires a minimum soffit


width of 100mm past cladding

b30 monier bed & point finish.dwg


Monier Roofing
PO Box 188,
Takanini,
Monier Tile Detail: B30 planstomonier@csr.co.nz
www.monier.co.nz

Auckland 2245 Bed & Point Finish - Monier Flat Tile Range Issue 1
1 December 2014
Scale 1:5
Disclaimer: This information is intended solely as a guide for use of Monier products. Before using Monier products you should ensure that the product is suitable for use in the specific application. Nothing in this information constitutes a statement of fitness for
Technical Help particular purpose - appropriate expert advice should always be obtained. Monier makes no warranty regarding the use of this information with non-Monier products. © 2010 . The copyright of this document is the property of CSR Building Products (NZ) Ltd
0800 851 588 trading as Monier and shall not be reproduced, copied, loaned or disposed of directly, or indirectly, nor used for any purpose other than that for which it is specifically furnished without prior consent.

13
ARCHITECTURAL DRAWINGS

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
APRON DETAILS
B01 APRON DETAILS - PARALLEL FLASHING NO UNDERLAY

* Where cladding manufacturer requires more than


75mm of apron upstand under cladding, cladding
supplier to supply and install over flashing to suit
their requirements. Cladding cavity
For details refer to cladding manufacturer.

* Cladding
Continuous Support to
Acrylead
Acrylead / Lead
/ Lead flashing
flashing dressed
dressed with flashing
into pan,
150mm min. 150mm minthe
cover over cover
tile
Monier tile

75mm
35mm
Minimum nog size ex
Batten 100x50mm

Square off rafter 230mm


to top of nog

Rafter

B02 APRON DETAILS - PARALLEL FLASHING WITH UNDERLAY

* Where cladding manufacturer requires more than


75mm of apron upstand under cladding, cladding
supplier to supply and install over flashing to suit
their requirements. Cladding cavity
For details refer to cladding manufacturer.

* Cladding
Continuous Support to
Acrylead
Acrylead / Lead/ Lead flashing
flashing dressed
dressed with flashing
into min.
150mm pan, cover
150mm minthe
over cover
tile
Monier tile
75mm
35mm

Minimum nog size ex


Batten 100x50mm

14
Square off rafter 230mm
ARCHITECTURAL DRAWINGS

to top of nog
Underlay where required

150mm min. lap

Rafter

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
B03 APRON DETAILS - TRANSVERSE FLASHING WITHOUT UNDERLAY

* Where cladding manufacturer requires more than Cladding cavity Continuous Support to
75mm of apron upstand under cladding, cladding flashing
supplier to supply and install over flashing to suit * Cladding
their requirements.
For details refer to cladding manufacturer.

Acrylead / Lead flashing dressed Minimum nog size ex


into pan, 150mm min cover 100x50mm

230mm
Monier tile Square off rafter 230mm
to top of nog

Batten

Rafter

B04 APRON DETAILS - TRANSVERSE FLASHING WITH UNDERLAY

* Where cladding manufacturer requires more than Cladding cavity


75mm of apron upstand under cladding, cladding Continuous Support to
supplier to supply and install over flashing to suit * Cladding flashing
their requirements.
For details refer to cladding manufacturer.
75mm

Acrylead / Lead flashing dressed Minimum nog size ex


into pan, 150mm min cover 100x50mm
35mm

230mm

Monier tile Square off rafter 230mm


to top of nog

Batten p 15
in. la
mm
75m
ARCHITECTURAL DRAWINGS

Underlay where required

Rafter

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
B25 SPREADER FOR ROOF DISCHARGE

Notes:
1. Hole positions to avoid joints in roofing.
Downpipe 2. Hole positions to discharge into pans of tile.
3. When downpipe is located in a corner, spreader is
to be "L" shaped.
T Junction 4. 600mm min spreader discharge pipe length.
5. For rectangular (or other profile) downpipes use
the same design principle as shown.
6. Underlay must be installed below spreader from
under apron to gutter line across at least 300mm
Holes half the diameter of from edge of spreader to the next truss/rafter.
the downpipe 7. Block ends of pipes.

600mm min

B29 KICKOUT FLASHING

Upstand 110mm behind wrap


and cladding

150mm minimum cover,


dressed into pan

Lead side flashing with tapered


stop end
Cladding to cover upstand by
75mm minimum

Clout

Fold bend behind upstand

Edge trimmed as required


16
ARCHITECTURAL DRAWINGS

10mm gap required between


wall and gutter end

50 x 50mm transition tray


flashing

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
MT13 STEPPED COVER FLASHING

Brick work
Over flashing

Acrylead / Lead Cover flashing

Monier tile

Tile batten

Rafter

Top plate

Framing

MT14 FLASHING TO BRICK ABUTMENT

Brick work

Acrylead / Lead flashing

Monier tile

Tile batten

17
ARCHITECTURAL DRAWINGS

Rafter

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
MT15 DUTCH GABLE DETAIL

Bedding and pointing


Finish to verge

Weatherboard

Barge board

Monier tile

Turn up lower edge of


Acrylead / Lead flashing
under hip tile

Hip capping

Monier tile

Tile batten

Rafter

MT16 VERTICAL TILING

Building wrap

Monier tile

Tile batten
Nogging to support flashing

Acrylead / Lead flashing

Monier tile
Underlay
18
ARCHITECTURAL DRAWINGS

Rafter Timber frame

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
PITCH CHANGE DETAILS
B08 CHANGE IN PITCH - 35 DEGREES OR LESS

in
mm
200m

Top roof pitch 35 ° or less

Monier tile
Rafters

Batten

Underlay where
required

Framing

B09 CHANGE IN PITCH - GREATER THAN 35 DEGREES

Fix Acrylead / Lead flashing to


special batten ex 75x50mm
Top pitch greater than
35° but less than 60°
d
0m hin ea
11 las d / L
m g
n
mi

Ensure nose of tile has 10mm


F a
e
ryl

clearance off Acrylead / Lead


Ac

Acrylead / Lead Flashing


dressed into the pan, 150mm
n

cover
mi
m

Monier tile Rafters


19
0m
11

ARCHITECTURAL DRAWINGS

Batten

Underlay where
required

Framing

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
MT10 MANSARD DETAIL

Batten to support tile and flashing

Monier tile

Tile batten

Acrylead / Lead flashing

Tile

Rafter

EAVES DETAILS
B19 TIMBER FASCIA EAVES DETAIL - WITHOUT UNDERLAY

Monier tile

50x50mm tile batten

Rafter
*75

20
mm

Fascia board
ARCHITECTURAL DRAWINGS

Note:
Anti-ponding boards required for pitches
below 17°
Refer minimum Pitch Table for tile types
* This fascia board measurement to and roof pitches requiring roof
be 25mm higher than the batten underlays
height
(e.g. 50x50mm batten = 75mm
fascia height)

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
B20 TIMBER FASCIA EAVES DETAIL - WITH UNDERLAY

Monier tile

Tile batten
250mm anti-ponding board
(for low pitches see note *)
(installed by builder)
Underlay where required Rafter

Fascia board * Note:


Anti-ponding boards – to be fitted in accordance with
E2/AS1,8.2.5
Masonry roofs with pitches less than 17° shall have
anti-ponding boards installed. Where anti-ponding boards
are used, these shall be set to a minimum fall of 5° towards
the fascia and shall be treated in accordance with NZS 3602.

B21 - INTERNAL FASCIA GUTTER DETAIL

Monier tile

Tile batten

Underlay where required. Anti-ponding


board where underlay used

25mm Packer installed by builder


Rafter

Underlay

21
ARCHITECTURAL DRAWINGS

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
B22 EXTERNAL FASCIA GUTTER DETAIL

Monier tile

Tile batten

Underlay where required (see note *).


Anti-ponding board required where underlay used

25mm Packer installed by builder


where required Rafter

Underlay

* Note: Refer minimum Pitch Table for


tile types and roof pitches requiring roof
underlays.

B23 EAVES EXPOSED RAFTERS

Monier tile

50x50mm tile batten


250mm anti-ponding board
(See Note *)

Underlay where required


(See Note *)

Rafter

22
Cavity
Fascia purlin
ARCHITECTURAL DRAWINGS

(Fascia purlin & eaves lining,


where installed, on top of truss to
be 25mm higher than tile batten)

Rafter * Note:
Anti-ponding boards – to be fitted in accordance with
E2/AS1,8.2.5
Eaves lining notched into rafters Masonry roofs with pitches less than 17° shall have
or resting on top of truss anti-ponding boards installed. Where anti-ponding
boards are used, these shall be set to a minimum fall
Exterior cladding
of 5° towards the fascia and shall be treated in
accordance with NZS 3602.

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
B24 EAVES & RAFTER DETAIL WITH SARKING

Monier tile

50x50mm tile batten


250mm anti-ponding board
See Note *

Underlay mandatory over


sloping ceilings Rafter

*75m
m

Ceiling Lining

* Note:
Fascia board Anti-ponding boards – to be fitted in accordance
with E2/AS1,8.2.5.
Masonry roofs with pitches less than 17° shall
have anti-ponding boards installed. Where
anti-ponding boards are used, these shall be
set to a minimum fall of 5° towards the fascia
and shall be treated in accordance with NZS
*75mm to top of anti-ponding board off top of counter batten. 3602.

MT23 EAVES STANDARD GUTTER

Monier tile

Rafter

Underlay

Anti-ponding board
m
55m
50 - hang
over

23
ARCHITECTURAL DRAWINGS
75m
m

Eaves lining
Standard gutter

Nogging

Fascia

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
MT24 FASCIA HEIGHT

Tile batten
50 x 50 softwood

Fascia height 25mm

Gutter Rafter

VALLEY DETAILS
B10 VALLEY DETAIL WITHOUT UNDERLAY

100mm cover over valley


tray Monier tile

50mm min
m
20m

100 mm
100
50mm min

mm

24
ARCHITECTURAL DRAWINGS

Splay batten 50x50mm

Underlay between valley tray & valley board


is mandatory (for separation) If metal valley Valley boards 25x150mm
tray is used with CCA treated valley boards.

Valley tray

250mm min. gutter width

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
B11 VALLEY DETAIL WITH UNDERLAY

100mm cover over


valley tray Monier tile

50mm min

100 mm
mm 100

m
50mm min

20m
Underlay where required

Splay batten 50x50mm

Underlay between valley tray and valley


board is mandatory (for separation) If metal
valley tray is used with CCA treated valley Valley boards 25x150mm
boards.
Valley tray

250mm min. gutter width

MT21 HIP GUTTER

Mortar bedding Valley run-off at hip

Fibre cement strip


Expanded mesh
Monier tile

25
ARCHITECTURAL DRAWINGS

Rafter Nogging

Valley boards

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
MT22 STEEP PITCH ROOF VALLEY

Top chord

Tile batten

Tile batten

Valley tray on boards


and underlay

Top chord Valley batten Water diversion rib

PENETRATION DETAILS
B14 PLAN VIEW OF THREE SIDED PENETRATION

Gutter Framing

Framed penetration See cross section detail b15


(e.g. chimney)

Edge battens

A A Roof line edge


See cross section
detail b17

Roof line edge


Cladding 26
Gutter
ARCHITECTURAL DRAWINGS

Also see details:


b15 monier abutment detail for framed penetration.dwg
b16 monier elevation-section view of three sided penetration.dwg
b17 monier cross section of hidden gutter.dwg for details

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
B15 ABUTMENT DETAIL FOR FRAMED PENETRATION

Cladding cavity

100mm min
Cladding Cladding lap over upstand

Monier tile

75mm Min Lap


To designer's specification but
cladding must finish 50mm
minimum above gutter lining
Underlay

50mm min Deep


Nog for upstand
Bottom of gutter to discharge
into side hidden gutter (then into
spouting) see detail b17

Tile batten

250mm anti-ponding board laid


to fall - See note *
Butyl, EPDM lining carried over
anti-ponding board and up
abutment frame on nog to suit.
Dress around sides of Gutter board at abutment
Also see details: on nogs to suit
penetration at ends
b14 monier plan view of three sided penetration.dwg
b16 monier elevation-section view of three sided penetration.dwg
b17 monier cross section of hidden gutter.dwg for details
* Note:
Anti-ponding boards – to be fitted in accordance with E2/AS1,8.2.5
Masonry roofs with pitches less than 17° shall have anti-ponding boards installed. Where anti-ponding boards are used, these shall
be set to a minimum fall of 5° towards the fascia and shall be treated in accordance with NZS 3602.

Cross Section BB
(from B14 Monier Plan View Of Three Sided Penetration)

B16 ELEVATION/SECTION VIEW OF THREE SIDED PENETRATION

See detail mt15 for further information

Monier tile

Chimney

Hidden gutter discharging


into gutter

27
Gutter
ARCHITECTURAL DRAWINGS

Rafter

Fascia board

Also see details:


b14 monier plan view of three sided penetration.dwg
b15 monier abutment detail for framed penetration.dwg
b17 monier cross section of hidden gutter.dwg for details

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
B17 CROSS SECTION OF HIDDEN GUTTER

Cladding cavity

Cladding

100mm min Support Nog

Monier tile E2/AS1 Approved


membrane on substrate

200mm min.
Tile Batten

100mm
Underlay where required

Edge Batten

Also see details: Rafter


b14 monier plan view of three sided penetration.dwg
b15 monier abutment detail for framed penetration.dwg
b16 monier elevation-section view of three sided penetration.dwg for details

Cross Section A-A


(from b14 Monier Plan View Of Three Sided Penetration)

B18 PIPE PENETRATION DETAIL

Stack/vent pipe with


venting cap carried
through tile
Dress Acrylead / Lead sleeve
100mm up pipe and solder to
Collar sealed to pipe over Acrylead / Lead flashing over tile
Acrylead / Lead flashing

Acrylead / Lead dressed down


over bottom edge of tile or
Acrylead / Lead carried to top 150mm, whichever is less
edge of the tile under the
overlap

Monier Concrete Tiles

28
ARCHITECTURAL DRAWINGS

Acrylead / Lead flashing dressed


to roof tile min 150mm all round
and carried up to edge of tile

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
MT17 CROSS SECTION HIDDEN GUTTER - FLAT TILE

Building wrap
Support Nog
Cladding cavity
Abutment flashing
Cladding dimensions

Monier

200mm
Acrylead / Lead
Horizon tile

200mm min.

50mm
100mm
Tile Batten

50mm
50mm
Abutment flashing
Underlay where
extension to continue
required 50mm
through to centre line
Edge Batten

Abutment underflashing

Rafter - double to
accommodate flashing
and batten

MT18 CHIMNEY TRAY

Chimney tray

Chimney tray
Weep hole

Over flashing

Back gutter

Monier tile
Stop flashing

Rafter
29
ARCHITECTURAL DRAWINGS

Tile batten

Boarding block to
support back gutter

NOT TO SCALE. ALL TECHNICAL FILES IN THIS MANUAL ARE SUBJECT TO OUR DISCLAIMER - SEE PAGE 1.
MT19 CHIMNEY FLASHING

Over flashing

Back gutter
Stop flashing
Monier tile

Rafter

Tile batten

Boarding block to
support back gutter

MT20 PIPE PENETRATION DETAIL - FLAT TILE

Stack/vent pipe with


venting cap carried
through tile

Dress Acrylead / Lead sleeve


100mm up pipe and solder to
Collar sealed to pipe over
lead flashing over tile
Acrylead / Lead flashing

Apply silicon to complete


perimeter of opening before fitting
Acrylead / Lead flashing

30
Monier tiles
ARCHITECTURAL DRAWINGS

Acrylead / Lead carried to top edge


of the tile under the overlap
(upper tiles lifted to illustrate)

Acrylead / Lead flashing dressed to


roof tile min 150mm all round and
carried up to edge of tile
Acrylead / Lead dressed down
over bottom edge of tile or
150mm, whichever is less