Automated Boiler Controls and Systems
An extensive range of boiler controls and systems is available.
Whether it is a new installation or a retrofit application, Spirax Sarco will have the answer.
Air Vent
To
Drain
Level
Alarm
Boiler TDS
Control
System
Level
Control
Heat
Recovery
System
Sample
Cooler
2
■ Boiler TDS control system ■ Condensate contamination
As steam forms it leaves behind impurities detection systems
and dissolved solids in the boiler water that Even low levels of contamination can cause
will concentrate unless blown down. The TDS foaming, scaling and corrosion in the boiler.
(total dissolved solids) in the boiler must be The contamination detection system moni-
controlled accurately. High TDS will result in tors the conductivity of the condensate and
carryover of boiler water and impurities causing will raise an alarm and divert it to drain if a
problems with production and plant. Low TDS pre-set limit is passed.
due to too much blowdown will be expensive
in fuel costs and water treatment chemical
losses. Systems are available for firetube
and watertube boilers.
User benefits
● Single source supplier for boiler
controls and steam system.
3
Heat recovery system
Recover heat and water from TDS blowdown to increase
energy efficiency and cut costs.
Make-up
Steam boilers need to be blown water
down to control the level of total
dissolved solids (TDS) in the boiler
water. This is best achieved by using
a TDS control system which will
open a valve to allow boiler water to
discharge when the TDS level rises
above a pre-set limit. Relatively low
TDS feedwater then replaces the
discharged boiler water.
Up to 80% of the heat in this
discharged boiler water can be
recovered with a properly
designed heat recovery system.
Blowdown inlet from
TDS control valve(s)
How the system works
Flash steam is released from the
hot blowdown water when the pres-
sure drops after the TDS blowdown
control valve. This mixture of flash
steam and blowdown water is
allowed to separate in the flash
vessel. The design of the vessel
ensures that flow velocities are low to
promote good separation. The dry
flash steam is then introduced at low
pressure into the deaerator. A float
trap fitted to the outlet of the flash
vessel drains the residual blowdown
water.
From the float trap the residual
blowdown water, which is still hot at
this point, is allowed to pass into the
heat exchanger where it gives up its
heat to the circulating cold make-up
water. The cooled blowdown water
then flows safely to drain. Residual
blowdown to drain
4
Return of
condensate
Safety
Valve
Pressure
Gauge
Float
Trap
User benefits
● Can recover up to 80% of the heat
from blowdown.
5
Level control system components
LP 20 probe and LC2200 Level Controller (Electric)
PA 20 pre-amplifier LC2500 Level Controller LC2300 Level Controller (Pneumatic)
The LP 20 probe consists of a
stainless steel rod completely insulated Control and alarm
from the water by teflon. As the water levels can be
level rises, the capacitance between adjusted without
shutting down
the rod and the ground boiler protection the boiler.
tube or probe chamber increases. The
capacitance is measured by the pream-
plifier and is transmitted as a dc signal
to the controller. Control and alarm lev- Alternative input
els are set in the controller. from 4-20mA
transmitter.
Adjustment
potentiometers on
front panel for
Simple plug easy access.
connection.
All electronics
are housed in The LC2500 controller is a dual The LC2200 and LC2300
the controller. voltage unit with two channels, controllers are proportional level
designated A and B. Either of the controllers with adjustable set points
channels can be set to provide a high and adjustable proportional bands.
or low alarm, and Channel B can also Features:
provide adjustable on/off control.
Probe can be Wave filter
used for Features: This prevents over-frequent relay
applications up to Wave filter operation in turbulent conditions.
465 psig (32 bar).
This prevents over-frequent relay
operation in turbulent conditions.
Out of range alarm
This can warn of damage to the
wiring or other problems that
could lead to potentially dangerous
situations.
User benefits
● Can provide information to 4-20mA to
management system
management systems. or remote indicator
● Can be used as direct
replacement for old and outdated
controls (modulating and on-off).
● Three stage level wave filter to Where remote signal representing water level is required (4-20mA isolated
mainatain a stable signal. signal) an LT2010 can also be connected to the level probe. The transmitter
range can be set, for example, to represent the boiler level gauge glass. It can
of course be set to represent any range of levels along the probe.
● Suitable for pressure up to
The transmitter output can be used to provide information to a management
465 psi (32 bar). system or connected to a remote display unit such as the DS 1000.
6
Level control applications
Deaerator
and feedwater
application
High
alarm
Boiler application
Level
control
probe
Level controller
Electric or
Pneumatic Level controller
control
valve Level
control
probe
Electric or
Pneumatic Make-up
control valve water
High level alarm
7
High integrity, self-monitoring low level alarm
for the automated steam boilers
Performance and safety
Today’s boilers are designed to extract the max-
imum possible heat from their fuel. With larger heat LEDs
transfer areas and smaller steam spaces than earli- LC3000
Controller Test
er designs they are capable of achieving increasing- button
ly high outputs from more compact designs. This
high performance demands control systems to
match, particularly in the important area of boiler
water level controls and alarms where failure to
achieve proper operation could have grave safety
implications.
Simple plug
Productivity and safety connection.
All electronics
Requirements for greater productivity have led are housed in
to increasing boiler house automation and limited the controller. FM
levels of supervision. This, in turn, has demanded
APPROVED
safety devices that are self-monitoring and will give
warnings of system faults and allow safe shutdown
of plant.
8
High integrity, self-monitoring high level alarm
for the automated steam boilers
Level control standards User benefits
The danders of a low water level in steam boilers are
● High integrity self-monitoring high alarm ensures
well known and boiler operating standards around the world
require stringent safety measures to be taken to guard safe operation.
against this potentially dangerous condition.
The more advanced of these standards require two inde- ● Low maintenance from solid state components
pendent high integrity, self-monitoring low water level alarms —no floats or linkages.
which periodically carry out a self-checking routine.
● Avoids overfilling the boiler which can lead to
High water level—the risks waterhammer and plant damage.
What are the dangers of too high a water level in a
steam boiler? ● Avoids contamination of product with boiler water.
• Increased carry over of water into the steam will result in
poor operation and/or malfunction of the steam system
components due to dirt.
• Wet and dirty steam can contaminate or spoil the product
where it is used directly.
• Wet steam can lower processing temperatures, perhaps
interfering with proper sterilization of food products or pro- FM
cessing of pharmaceuticals, causing wastage. At best,
lower process and production efficiency will increase APPROVED
process time and unit costs.
• Overfilling the boiler can lead to water hammer in the Advanced
steam system, risking damage to plant and even injury to controller with
personnel. built in cyclic
test facilities.
High level alarm system
For this reason, Spirax Sarco has developed a high
integrity, self-monitoring high water level alarm system. It is suit-
able for steam boilers, particularly for those operating with only
limited supervision, and can also be used with other vessels. Cable
socket
Time Time
10
control systems
BCS 1 blowdown control system
BC 1100 The BCS 1 blowdown system is suitable for
controler horizontal and vertical shell boilers. BCS 1 has
blowdown flowrates up to 1300 lbs/hr (590 kg/h) and
can handle boiler pressures up to 150 psig (14 barg).
Boiler
Blowdown
valve
Sensor
chamber
Boiler BCV 31
blowdown
valve
To heat
recovery
CP30 system or
blowdown
vessel
Check
S11 Sensor valve
Chamber
BCV 31 Sample
blowdown valve Cooler
Stop valves to
isolate system
Water for
flushing
and
Temperature calibration
Compensation
Sensor
Dump Valve
12
Automatic boiler blowdown system
A time controlled bottom blowdown system for single or multiple boiler installations.
Even after careful feedwater Manual blowdown is also No batteries are needed.
treatment, boiler water still contains dis- time consuming for multi boiler Settings are stored in the
solved and suspended solids, installations. There should be an memory even when the
which must be removed. interval between blowdowns, to power is switched off.
Control systems are often fitted to avoid thermal overload of the
remove boiler water with high levels blowdown vessel. Furthermore,
of total dissolved solids (TDS). Boilers a skilled boiler operator may Clear 4-digit LED
also contain suspended solids such as not always be available. For display which shows
scale and oxide particles which if safety reasons, only one boiler the amount of time till
allowed to build up in the bottom blowdown valve must be open at the next blowdown.
of the boiler, my cause: a time.
• Blocked blowdown connections. Therefore, the Spirax Sarco
automatic boiler blowdown
• Impaired heat transfer. system offers considerable
• Subsequent hotspots and boiler advantages. The system Two push buttons
damage. comprises a BT 1000 cyclic for straightforward
Therefore all boilers are fitted with timer and a pneumatically setting or viewing.
a valve at the lowest point, which actuated ABV 20 blowdown
allows the build-up of sludge to be valve.
flushed regularly from the boiler:
daily or once per shift.
The traditional manual valve
is an acceptable solution as
long as the blowdown
procedure is:
• Carried out at the right time
and at regular intervals.
• Is not forgotten, or repeated
by another operator.
Spring-to-close
pneumatic actuator.
Solenoid valve
Blowdown control
Most authorities recommend that
intermittent bottom blowdown is carried
out in “short sharp bursts”. It is normal
practice in a well managed boilerhouse
to blowdown regularly a small quantity
of boiler water to clear any build up of
sludge.
Excessive bottom blowdown is very
costly in terms of both lost heat energy
and water treatment chemicals, so it is
important that it is kept to a minimum.
To minimize energy loss and ensure
that the total dissolved solids (TDS)
level is monitored and kept within design
limits, the fitting of an automatic TDS
control is also recommended.
Cast carbon steel body available
in sizes 1" to 2-1/2" for boiler
pressures up to
250 psig (17.25 barg).
User benefits
● Purpose designed for boiler
blowdown applicaitons.
14
Conductivity Meter
MS1 Conductivity meter, the essential instrument for every boilerhouse.
User benefits
The MS1 meter Using the MS1 meter ● Easy to use, lightweight, portable
The Spirax Sarco MS1 is a Operating the instrument is very instrument.
compact, battery powered con- straightforward. Ideally, the neutralized
ductivity meter designed for use sample temperature should be as near to ● Automatic temperature compen-
in the boilerhouse and is particu- 77°F as possible, but any temperature up sation saves time cooling the
larly suitable for measuring the to a maximum of 115°F is satisfactory. sample.
conductivity of boiler water, feed The instrument has three range
water, or condensate samples in switches, 0-200µS/cm, 0-2mS/cm and 0- ● Wide, selectable range for accu-
order to estimate TDS levels. 20mS/cm. Light emitting diodes indicate rate readings.
The instrument is fitted with the range selected. Simply select the
a permanently wired carbon highest range to start with, (right hand ● Automatic switch off saves
electrode sensor with integral button), then switch to the lower ranges batteries.
temperature sensor, and can be to obtain a more accurate reading. The
used for sample temperatures up display will automatically indicate “1” if an ● Can check operation of conduc-
to 115°F, though it is more usual inappropriately low range is selected. tivity probe installed in boiler.
to cool samples to around 77°F If a result in ppm is required, multiply
before testing, using a sample the µS/cm result by 0.7 for a neutral sam- ● Protective case included.
cooler. ple at 77°F.
15
SC 20 Sample Coolers Vent Heads
A sample cooler that is quick to fit, safe to use Simple and effective vent heads for increased
and simple to operate. For accurate sampling safety and environmental protection.
of high pressure and high temperature water Spirax Sarco vent heads are designed for fitting to
and process liquors. vertical open-ended steam vent pipes.
The vent head incorporates an internal baffle which
The SC 20 is used to take samples of water and process separates entrained water from the steam, safely
liquids at high temperature and pressure, preventing “flash- discharging dry steam at decreased velocity to atmosphere,
ing-off” or high temperatures which can be dangerous and protecting personnel from injury, buildings from damage
could result in an inaccurate sample. Its 316L stainless steel and minimizing the nuisance of water spray.
construction with counter current flow provides accurate,
contamination free samples. The compact,
maintenance-free design makes it ideal for
either permanent or mobile installation.
Applications
To be sure that a boiler is operating Applications
at the desired concentration of total • Vented pump
dissolved solids (TDS) it is necessary to receivers
take a sample of boiler water and test it. • Blowdown
This should b done even if an auto- vessels
matic TDS control system is fitted since • Flash tanks
any automatic system should be checked • Hot water
at intervals. storage tanks
When a sample of water is taken
from a boiler its pressure reduces and
flash steam is formed.
If this flash steam were to escape to
atmosphere without being condensed the
resulting sample would show a greater
concentration of TDS than actually exist-
ed in the boiler water. To obtain accurate
Vent Head overview
and safe samples it is therefore essential Model Inlet Size Connections Drain Size NPT Construction
that sufficient cooling is carried out to VH2S 2" 3
/4"
fully condense any flash steam that is VH3S 3" NPT 3
/4"
formed prior to discharge. VH3 3" 3
/4"
The sample cooler reduces boiler VH4 4" 1" 300 Series
water temperature to around 80°F ready VH6 6" 1" Stainless Steel
for immediate analysis. VH8 8" ANSI 150 11/2"
VH10 10" 11/2"
VH12 12" 2"
● Compact and maintenance free design. ● No moving parts eliminate maintenance requirements.
Regional Offices
Northeast Mid-Atlantic Midwest West
Spirax Sarco, Inc. Spirax Sarco, Inc. Spirax Sarco, Inc. Spirax Sarco, Inc.
209 W. Central St. 1125 S. Cedar Crest Blvd. 2806 Centre Circle Drive 1930 East Carson St.
Suite 228 Suite 101 Downers Grove, IL 60515 Suite 102
Natick, MA 01760 Allentown, PA 18103 Phone: (630) 268-0330 Long Beach, CA 90810
Phone: (508) 651-3200 Phone: (610) 432-4557 Fax: (630) 268-0336 Phone: (510) 549-9962
Fax: (508) 655-9434 Fax: (610) 432-2595 Fax: (510) 549-7909 1150 Northpoint Blvd.
Blythewood, SC 29016
Southeast Southwest
Spirax Sarco, Inc. Spirax Sarco, Inc. Spirax Sarco, Inc. 1-800-883-4411
7760 Olentangy River Rd. 200 Centre Port Drive 203 Georgia Ave. www.spiraxsarco.com/us
Suite 120 Suite 170 Deer Park, TX 77536
Columbus, OH 43235 Greensboro, NC 27409 Phone: (281) 487-4002
Phone: (614) 436-8055 Phone: (336) 605-0221 Fax: (281) 478-4615
Fax: (614) 436-8479 Fax: (336) 605-1719 Printed in USA 02/02. Copyright 2002 Spirax Sarco, Inc.