Instruksi Pemasangan DSE4210-DSE4220
Instruksi Pemasangan DSE4210-DSE4220
The LED above the () button flashes to indicate that the editor is 20 Seconds
active. 30 Seconds
The first five LEDs on the top row of the module’s fascia indicate the
60 Seconds
current parameter. The last three LEDs indicate the parameter’s value. 180 Seconds
Value
Immediate Warning Close on Fault
To edit the parameter, press the () button. TABLE OF OUTPUT FUNCTIONS
Press the (+) button or the (-) button to adjust the value to the
required setting. Value Polarity
Press the () button the save the current value. Not Used
Energise
(DSE4210)
If an invalid parameter has been entered via PC Configuration, the LEDs
Close Mains
De-Energise
used to indicate the parameter value begin to flash. (DSE4220)
Pre-Heat During
Pre-Heat Timer
Energise
NOTE: Terminals 8, 9, 25, 26, 27 and 28 are fitted to DSE4220
only. For DSE4210, Gen Breaker Close is set to Output C (terminal 6).
EXITING THE FRONT PANEL EDITOR Close Generator Energise
Press and hold the () button to save and exit the editor. The LED Common Warning Energise
Common Shutdown Energise
NOTE: For a larger version of the typical wiring diagram, refer to above the button ceases flashing.
DSE publication: 057-181 DSE4210 & DSE4220 Operators Manual, System in Auto Energise
which can be obtained from www.deepseaplc.com. Press and hold the (-) button to exit the editor without saving. The LED Common Alarm Energise
NOTE 1,2 50 Hz
Nominal Frequency
60 Hz
NOTES:
1) When the Front Panel Editor changes more than one setting, only the setting being edited is checked to determine if it matches the
stored configuration.
2) When the Nominal Frequency is edited, automatically the Under Frequency Shutdown Trip is set to -20%, Under Frequency Pre-Alarm
Warning is set to -16%, Loading Frequency is set to -10%, Over Frequency Pre-Alarm Warning is set to +10%, Over Frequency Shutdown
Trip is set to +14% and Over Frequency Overshoot is set to +25%.
3) When edited, the Charge Fail alarm is set to 66% (2/3) of the Nominal DC Voltage setting.
5) The parameter is only available if a digital input is assigned to Remote Start On Load, Remote Start Off Load or Simulated Mains. The
parameter is not available if digital inputs are assigned for both Remote Start and Simulated Mains.
6) The parameter is only available if a digital input is assigned to Remote Start On Load or Remote Start Off Load. The parameter is not
available if digital inputs are assigned for both Remote Start On Load and Remote Start Off Load.