Confirming to R=5, Special moments resisting frames

S.N Description Reference Clause


A General
1 Minimum grade of concrete Pre-Analysis
a Building Height Pre-Analysis
b Exposure condition Pre-Analysis
2 Steel reinforcement Fe-500 (14.5%)
3 Lintel beam integrated (Yes or no)??? Pre-Analysis
4 Plinth beam and staricase beams included (Yes or no)??? Pre-Analysis
5 Irregularities Present (IS 1893 : Part I) ??? Pre-Analysis
B Beams
1 factored axial compressive stress/fck
2 B/D Pre-Analysis
3B Pre-Analysis
4 Column Dimension
B Pre-Analysis
D Pre-Analysis
5 Mimimum rebar 2-12 dia bottom and top
Mimimum longitudinal rebar
Maximum longitudinal rebar 2.50%
6 Ast Bottom/Ast Top
7 Astmid/Ast end 0.25
8 Anchorage length, X (bottom and top) Ld+10dia
9 Link spacing at laps <=150mm Lap splices
10 Lap length >=Development lenght
11 Lap splices avoided @
a Joint
b Distance 2D from face of volumn
c 0.25L from flexural yielding
d Not more than 50% lapped
12 Use vertical links only Tranverse rebar
13 Hooks should alternate, cross ties hook on slab side
14 Min dia of links 8mm
15 Shear force capacity of beams
16 Close spacing of links within 2d <=d/4 or 8dia or 100mm
17 First links at 50mm from face
18 Rest portion spacing of link >d/2
C Columns
1 Shall apply to
factored axial compressive stress/fck >0.08
Another criteria
2 Minimum dia of rebar Miminum dimension of column
Min/max dimension >=0.45
3 Relative strength of beams and columns at joint