Reference
Sl.
Name of Test Standard
No.
IEC Std. No.
03 Analyzer Test
Power Frequency Voltage Test:
Standard Actual Data
Phase Test Time Applied
Date Frequency Current Result
Selection Voltage Duration Voltage
(Hz) (mA)
(kV) (Min) (kV)
72 15 72.2 231
R 132 3 132.2 149.2 424 Withstood
235 1 235 750
72 15 72.2 227
12-10-2021 Y 132 3 132.2 148.9 421 Withstood
235 1 235 748
72 15 72.2 228
B 132 3 132.2 150.4 416 Withstood
235 1 235 742
Leakage Current Calculation for Power Frequency Voltage Test:
𝑈𝑥
Current, Ix = = 2*3.1416*fx*Cx*Ux
𝑋𝑐
=2*3.1416*149.2*0.000473*10−6 *235000
=0.1042 A
=104.2 mA
Analyzer Test:
Date Phase Closing Time (msec) Opening Time(msec) Result
R 60.35 25.20 Satisfactory
12-10-2021 Y 60.20 25.00
B 60.15 25.10
Test Witnessed by
Engr. Kazi Ariful Hoque Md. Faruk Hossain Md. Fasiul Alam
Project Director Executive Engineer, Executive Engineer,
Chandpur Power Generation Ltd. RTS, PGCB Telecom & RTU Division
and Chattogram, PGCB
Executive Engineer,
Chandpur 150 MW CCPP, BPDB, Chandpur