REQUEST FOR PROPOSAL (RFP)

For

132kV Current Transformers (CT)

Issued by

ib vogt Solar India Pvt Ltd.

5th Floor, North Tower, M3M Tee Point, Sector 65, Golf Course Extension Road
Gurugram, Haryana INDIA – 122018

R0 26-12-2023 HD OBS
Rev. Date Prepared by Reviewed by Approved by
132kV Current Transformer (CT)
REQUEST FOR PROPOSAL

Section 1: Project Specific Data


Sr.No. Description Details
1 Owner Ib vogt Solar India Pvt. Ltd.
2 Location of the plant Sangarh, Rajasthan
3 Transport (Nearest locations) Client to share
4 Plant Elevation <1000m MSL
5 Design Temperature 50ºC
6 Normal Operating Voltage 132 kV
7 Highest Operating Voltage 145 kV
8 Frequency 50 Hz
9 Corrosion Level C3
10 Seismic Data As per IS-1893 latest issue
10.1 Zone Zone-III
2.5 for Electrical Equipment, 1.5 for
10.2 Co-efficient
others.
10.3 Importance Factor As per IS 875-III latest issue
11 Wind Data 47m/s
11.1 Zone As per IS Code
11.2 Terrain Category As per IS 1893 Latest issue
11.3 Wind Speed Zone-III
12 Topicalization
The equipment shall be given tropical and biocidal/fungicidal treatment in view of the
12.1
above-mentioned climatic conditions.

Tropical protection shall conform to BS: CP 1014 dated 15-06-1980, entitled “Protection
12.2
of Electrical Power Equipment against climatic condition.”

IP 42 for indoor application IP 65 for


13 Enclosure Protection Class
outdoor application or as per DISCOM

14 Creepage (Ph-E) 25 mm/kV


15 Auxiliary Power Supply
AC Power Supply System for Station 415V AC, 3-phase, 4-wire solidly
15.1
Auxiliaries grounded system
240V, 1-phase, 2 wire, 50Hz AC supply
AC Power Supply System for Lighting fixtures
15.2 with neutral lead grounded derived
and space Heaters
from 15.1
240 V, 1-phase, 50 Hz, 2-wire, AC
15.3 Uninterrupted Power Supply
supply
DC Power Supply System for Protection and 110 V DC, 2-wire ungrounded DC
15.4
Control supply
The above voltages may vary as follows:
15.5 All devices shall be suitable for continuous operation over the entire range of voltage
and frequency indicated below without any change in their performance.

Page 2 of 3
132kV Current Transformer (CT)
REQUEST FOR PROPOSAL

· AC supply Voltage variation ±10%.


· Frequency variation ± 5%.
· Combined voltage & frequency variation ±10%.

Page 3 of 3
Doc No

50 MVA, 33/132 KV SUBSTATION AT, SANGARH, RAJASTHAN IBVSI/RJ/SANGRAH/EE/TS


/CT/01

Approved: CAT B
By OBS
Date :20/12/2023

TITLE : 132kV CT SPECIFICATION

ib vogt SOLAR INDIA Pvt. Ltd.


CLIENT : GURUGRAM, HARYANA INDIA – 122018

SHAKTI ENGINEERS AND CONSULTANTS,


CLIENT
BANGALORE-560097.
CONSULTANT :

0 18.11.2023 AC HP AC 11 FOR APPROVAL

NO. OF
REV. DATE PREPARED BY. CHECKED BY. APPROVED BY. REMARKS
SHEETS
50MVA, 33/132kV Substation, Document No: Rev No: 00
Rajasthan Project
Sangarh, Rajasthan , India IBVSI/RJ/SANGRAH/EE/TS/CT/01

Contents
1 Project Brief ...................................................................................................................................2
2 Items to be Procured ......................................................................................................................2
3 Delivery ..........................................................................................................................................3
4 Compliance ....................................................................................................................................3
5 Conflict ...........................................................................................................................................3
6 Scope of Work ...............................................................................................................................4
7 Inspection and Testing ...................................................................................................................5
8 Exceptions and Deviations .............................................................................................................5
9 Current Transformer ......................................................................................................................5
9.1 Quality certification..................................................................................................................5
9.1.1 Type and Duty .................................................................................................................7
9.1.2 Constructional Features ...................................................................................................7
9.1.3 Terminal...........................................................................................................................8
9.1.4 Grounding ........................................................................................................................8
9.1.5 General requirement ........................................................................................................8
9.2 Pre-dispatch Quality and Testing ............................................................................................8
9.3 Specific Erection Requirement ................................................................................................9
9.4 Onsite Testing.........................................................................................................................9
9.5 Packing and Dispatch ...........................................................................................................10
10 Submission ...............................................................................................................................10
11 List of Attachment .....................................................................................................................11

Rev. 0 Page 1
50MVA, 33/132kV Substation, Document No: Rev No: 00
Rajasthan Project
Sangarh, Rajasthan , India IBVSI/RJ/SANGRAH/EE/TS/CT/01

1 Project Brief
Project 50MVA, 33/132kV Switchyard

Owner (Purchaser) ib vogt SOLAR INDIA Pvt. Ltd

EPC -

Consultant SHAKTI ENGINEERS AND CONSULTANTS (SEC)

Project Location Sangarh, Rajasthan, India

2 Items to be Procured
Following Items (material and services), required for above mentioned Project in Clause 1 in line with
Procurement Specifications.

Sr.No. Item Description Quantity


Design, engineering, manufacture, inspection, testing and performance of
132kV Current transformer (101-CT)

CT 250-500/1-1-1-1A

Core-1: Cl:0.2S, 15VA


1 3 Nos.
Core-2: PS Class

Core-3: 5P20, 30VA

Core-4: PS Class

Design, engineering, manufacture, inspection, testing and performance of


132kV Current transformer (102-CT)

CT 250-500/1-1-1-1A

Core-1: Cl:0.2S, 15VA


2 Core-2: PS Class 3 Nos.

Core-3: 5P20, 15VA

Core-4: PS Class

Design, engineering, manufacture, inspection, testing and performance of


132kV Metering Current transformer.
3 3 Nos.
Equipment Tag: 101-MCT

Rev. 0 Page 2
50MVA, 33/132kV Substation, Document No: Rev No: 00
Rajasthan Project
Sangarh, Rajasthan , India IBVSI/RJ/SANGRAH/EE/TS/CT/01

Sr.No. Item Description Quantity


CT Ratio: 250-500/1-1A

Core-1: Cl:0.2S, 10VA

Core-2: Cl:0.2S, 10VA

Construction & Commissioning Spare


4 Supply of Manufacturer’s recommended construction and commissioning 1 Lot
spare along with itemized list and unit rate for each supplied spare item.
Operation & Maintenance Spare
5 List of two-year spares for normal operation and maintenance which is 1 Lot
required but not covered in mandatory spare list.
Special tools and tackles
6 Supply of special tools and tackles as per Manufacturer’s recommendation 1 Lot
along with list and unit price of all special tools/tackles.

3 Delivery
Manufacturer is expected to deliver above specified item in clause 2 by Q1 of 202X. Manufacturing
time would be around six months from date of ordering.

4 Compliance
Manufacturer shall submit compliance statement, attached with this requisition, duly filled in along with
the offer as attached as Annexure-02 with this document.

5 Conflict
The technical specification shall be read in conjunction with all other Specifications and documents
attached. During resolving conflicts, the following order precedence:
1. Statutory Regulations:
− Applicable Act/Legal Requirement of Specific Country and Region.
− The Factory Act if applicable.
− Requirements of the statutory bodies.
2. Equipment Specifications.
3. Codes & Standards.
During order execution stage, in the event of conflict, actual or implied, amongst documents relating to
this requisition or enquiry or order, the more stringent requirement(s) shall apply. Manufacturer shall
identify and state such conflict(s) in the course of engineering / manufacturing to obtain Client’s
concurrence.

Rev. 0 Page 3
50MVA, 33/132kV Substation, Document No: Rev No: 00
Rajasthan Project
Sangarh, Rajasthan , India IBVSI/RJ/SANGRAH/EE/TS/CT/01

Similarly, if there is a conflict between the printed enclosures / catalogues / Specifications and other
statements of Manufacturer/Developer’s quotation, superior Specification advantageous to the
Purchaser/Developer shall prevail.

6 Scope of Work
Manufacturer’s Scope of Work / Supply has been broadly defined as under. Manufacturer to note that,
in no case shall their scope of supply / work is limited to content of this requisition only.
It is Manufacturer’s responsibility to verify the selection of type of item, material of construction of each
component as per the data mentioned in individual Specifications / data sheets / this Procurement
Specification. Manufacturer to suggest an alternative, in case not found suitable. They shall stand
guarantee for all items supplied by them, including their bought-out items. Manufacturer shall be
completely responsible to supply all required materials and services, including that of sub-
Manufacturer for satisfying the functional / operational requirements stated in this Specifications and
this Material Requisition.
Items not indicated clearly in Manufacturer’s offer, but required for technical requirements shall be
considered as included in Manufacturer’s scope of supply. Any deviation proposed by the sub-
Manufacturer for such items shall not be taken into account. Such items shall be considered to be
completed by Manufacturer on his full responsibility.

− Design & Engineering.


− Manufacturing.
− Painting.
− Type Testing.
− Supply of material as per this procurement specification.
− Packing and forwarding.
− Delivery Ex Work (EXW).
− Supply of services as specified in procurement specification.
− Field services for supervision of Erection, Installation & Pre-commissioning (Per day rate
separate for engineer and Technician).
− Field services for Inspection and field Testing (Per day rate separate for engineer and
Technician).
− Field services for Start-up and Commissioning (Per day rate separate for engineer and
Technician).
− Supply of construction and commissioning spares.
− Supply of mandatory spares.
− List of consumables as per Manufacturer’s recommendation.

Rev. 0 Page 4
50MVA, 33/132kV Substation, Document No: Rev No: 00
Rajasthan Project
Sangarh, Rajasthan , India IBVSI/RJ/SANGRAH/EE/TS/CT/01

− Documentation (Hard copy and optical disk also for long storage).
− Factory Acceptance Testing (FAT) and Inspection of ex-factory items.
− Site Acceptance Testing (SAT).
− Statutory Approval.
− Training (Per day rate for Manufacturer’s shop as well as at Field).
− Special tools and tackles.
− Logistic support for supply of spares for next 5 years.

7 Inspection and Testing


Manufacturer shall submit Quality Assurance Plan for manufacturing, testing and Inspection for
Client/Owner’s Engineer review and approval. To fulfil the quality assurance requirement Manufacturer
shall accept free access of Client/Owner’s Engineer review representatives at any time until shipment.
Shop Inspection and tests shall be carried out in accordance with the procurement specification and
relevant codes and standard.

8 Exceptions and Deviations


As such total compliance to specification and its attachment / addendum is required and no
deviations/exceptions are expected. In rare and unavoidable cases, where deviations/exceptions are
inevitable solely due to technical reasons Manufacturer may propose the same in attached format for
Client /Owner’s Engineer review and acceptance.
Any clarification/deviation/exceptions shall be submitted in consolidated in the format (Annexure-01) in
pre-order stage. Clarification/deviation/exceptions specified anywhere in offer or in other document
shall not to be considered. It will be construed that Manufacturer confirm in totality to the requirement
specified in Procurement Specification.
In case of no deviation, Manufacturer shall mention ’NO DEVIATION/CLARIFICATION/EXCEPTIONS”
with sign and stamp. Manufacturer to note that no post-order deviations/clarifications/exceptions shall
be accounted.

9 Current Transformer
This section herein describes the specific construction and erection requirement of Solar plant onsite
switchyard 132kV current transformer.

9.1 Quality certification


Current Transformers and allied accessories shall comply with the requirements of the latest editions
of IEC/IS Standards with updated amendments. Local Standards and Regulations shall also be
followed. Below table indicates non-exhaustive list of standards to which all the Current transformer
should conform.

Rev. 0 Page 5
50MVA, 33/132kV Substation, Document No: Rev No: 00
Rajasthan Project
Sangarh, Rajasthan , India IBVSI/RJ/SANGRAH/EE/TS/CT/01

Standard Description

IS 2705 Current Transformer

IEC 60028:1925 International standard of resistance for copper

IEC 60038:1983 IEC standard voltages

Instrument transformers – Part 5: Requirements for protective current


IEC 60044-6:1992
transformers for transient performance

International Electro technical Vocabulary – Chapter 321: Instrument


IEC 60050 (321):1986
transformers

IEC 60060-1:1989/ High-voltage test techniques – Part 1: General definitions and test
IS 2071 requirements

IEC 60071-1:1993 Insulation co-ordination – Part 1: Definitions, principles and rules

Recommendation for commercial annealed aluminum electrical conductor


IEC 60085:1984
wire

IEC 60270:1981 Partial discharge measurements

Guide for the sampling of gases and of oil from oil-filled electrical equipment
IEC 60567:1992
and for the analysis of free and dissolved gases

Interpretation of the analysis of gases in transformers and other oil-filled


IEC 60599:1978
electrical equipment in service

IEC 60721 Classification of environmental conditions

IEC 60815:1986 Guide for the selection of insulators in respect of polluted conditions

Standard | Coupling capacitors and capacitor dividers - Part 3: AC or DC


IEC 60358-3:2013
coupling capacitor for harmonic-filters applications

General requirements and test methods for current transformers used for
IEC 60044-1
measurement and protection.

IEC 61869-2 Additional specifications for current transformers used for protection purposes

IEC 61869-3 Standard specifies the requirements for current transformers used for specific
applications, such as electronic voltage transformers, current transformers for
digital protection relays, and current transformers for transient performance
measurements.

Rev. 0 Page 6
50MVA, 33/132kV Substation, Document No: Rev No: 00
Rajasthan Project
Sangarh, Rajasthan , India IBVSI/RJ/SANGRAH/EE/TS/CT/01

Standard Description

IEEE C57.13 Guidelines for the design, testing, and application of current transformers used
in power systems.

IS 335 New Insulating oil

IS 3618 Phosphate Treatment of Iron and Steel for Protection Against Corrosion

IS 4201 Application Guide For Current Transformer

IS/IEC 60529 Degrees of protection provided by enclosures (IP CODE)

9.1.1 Type and Duty


− The Current Transformers shall be oil immersed, self-cooled and hermetically sealed type live
tank / dead tank.
− Current Transformers shall have single primary - ring type or hair pin type. Each current
transformer shall be furnished with a number of independent cores with ratios and other ratings
as specified in the specification. The rated extended primary current shall be 120% on all cores
of the CT.
− Different ratios of each core specified shall be achieved by secondary taps only and primary
reconnection is not acceptable.

9.1.2 Constructional Features


− The current transformer shall be single pole unit, designed for upright mounting on steel
structure and furnished complete with fixing hardware.
− Insulator shall be of wet process porcelain, brown glazed and free from imperfections. All metal
parts and hardware’s shall be hot dip galvanized.
− Current transformer shall be provided with oil level gauge, drain plug and pressure relief
device. An inert gas cushion/ stainless steel bellow shall be provided on top for expansion of
the oil.
− Current transformer shall be so constructed as to ensure that the oil does not flow out or leak
out even when the current transformer is used continuously at the maximum allowable
temperature.
− Polarity shall be marked on each primary and secondary terminal, provision of short circuiting
and grounding CT secondary terminals shall be made in terminal box.
− The current density adopted for the design of terminal connector shall in no case exceed 1.6 A/
mm2 for copper and 1.0 A/ mm2 for terminal contactor made of other material.
− Metering CT shall maintain the required accuracy for current ranging from 5% to 120% of rated
current or specified rated extended current whichever is higher and for 0.2S class CT accuracy
Rev. 0 Page 7
50MVA, 33/132kV Substation, Document No: Rev No: 00
Rajasthan Project
Sangarh, Rajasthan , India IBVSI/RJ/SANGRAH/EE/TS/CT/01

shall be maintained between 1% to 120% of rated current. CT burden shall not be less than
15VA to achieve required 0.2S accuracy class.
− The instrument security factor of metering core shall be low enough but not greater than 5.

9.1.3 Terminal
− Primary terminals shall be made of non-ferrous corrosion resistant material and provided with
bimetallic terminal connectors, and the terminal connectors required for connection of the
Instrument Transformer shall be an integral part of it. These terminal connectors shall be
suitable for connecting ACSR equivalent.
− Secondary terminals shall be brought out to a terminal box and suitable for connection to 2 x
2.5mm2 stranded copper conductors per way.
− All primary and secondary terminals shall be clearly and indelibly identified as per relevant
standard.
− The terminal box shall be of 3mm thick sheet steel, IP-55, weather proof and dust-tight,
complete with gasketted front access cover and removable gland plate at bottom for cable
entry.

9.1.4 Grounding
− Each current transformer shall be provided with two ground pads for connection to station
ground mat.
− The ground pad shall comprise buffed metal surface with two holes, M10 G.I. bolts and spring
washers to receive 75x12mm G.S flat.

9.1.5 General requirement


− CT shall be type tested from ERDA / CPRI.

9.2 Pre-dispatch Quality and Testing


Following are some of the key factory test parameters that are expected to be carried out under an
independent engineer’s witness.

− Verification of terminal marking and polarity.


− Power frequency dry withstand tests for one minute.
− Over voltage interturn test.
− Composite error test.
− Knee point voltage test.
− Determination of errors.
− Partial discharge test.
− Tan delta and capacitance test.
Rev. 0 Page 8
50MVA, 33/132kV Substation, Document No: Rev No: 00
Rajasthan Project
Sangarh, Rajasthan , India IBVSI/RJ/SANGRAH/EE/TS/CT/01

9.3 Specific Erection Requirement


Safety instructions

− Always consider transformer as a part of the circuit to which it is connected and do not touch
the leads and terminals or other parts of the transformer unless they are known to be
grounded.
− Always ground the metallic bases of instrument transformer.
− Always ground one secondary terminal of the transformer, except if the windings are connected
to open delta. When the secondary of transformer is interconnected, there should be only one
grounded point to prevent accidental paralleling with system grounding wire. In case of
disconnection from the ground, the grounding screw has to be removed from the secondary
terminal.
− Always short-circuit the secondary of the current transformer, which is not currently in use to
prevent secondary voltages which may be hazardous to personnel or damaging to the
transformers secondary.
− In case of the current transformer with voltage indication (coupling electrode included) is
secondary terminal box equipped with PE terminal, which is connected with earthing screw to
the base plate, which must be generally earthed.

9.4 Onsite Testing


The CT shall be fully tested on site prior into putting into service to ensure that all items are in proper
working condition, correctly installed and free from damage.
An authorized testing Professional Engineer shall be engaged by the contractor to perform the site
testing and commissioning.
Following tests shall be performed at site:

− Power frequency test on primary winding.


− Insulation Resistance Test for primary and secondary.
− Polarity test.
− Ratio and phase angle error identification test - checking of all ratios on all cores by primary
injection of current.
− Dielectric test of oil (wherever applicable).
− Magnetizing characteristics test.
− Tan delta and capacitance measurement.
− Secondary winding resistance measurement.
− Contact resistance measurement (wherever possible/accessible).

Rev. 0 Page 9
50MVA, 33/132kV Substation, Document No: Rev No: 00
Rajasthan Project
Sangarh, Rajasthan , India IBVSI/RJ/SANGRAH/EE/TS/CT/01

− Dissolved gas analysis to be carried out at the time of commissioning. CTs must have
adequate provision for taking oil samples from the bottom of the CT without exposure to
atmosphere.

9.5 Packing and Dispatch


− All the equipment shall be divided into several sections for protection and ease of handling
during transportation. The equipment shall be properly packed for selected mode of
transportation i.e. by ship/rail or trailer. The equipment shall be wrapped in polythene sheets
before being placed in crates/cases to prevent damage to finish.
− Crates/cases shall have skid bottom for handling. Special notations such as 'Fragile', 'This side
up', 'Centre of gravity', 'Weight', 'Owner's particulars', 'PO nos.' etc., shall be clearly marked on
the package together with other details as per purchase order.
− The equipment may be stored outdoors for long periods before installation. The packing shall
be completely suitable for outdoor storage in areas with heavy rains/high ambient temperature
unless otherwise agreed.

10 Submission
Manufacturer shall submit following documents for current transformer. Manufacturer / supplier shall
submit valid type test certificates issued by a National or International Testing Authority.

− Complete technical literature giving complete product specifications.


− Mounting arrangements, installation manual and operation and maintenance manual shall be
shared.
− Makes and specifications, certifications of all components.
− Schematic diagram.
− General arrangement drawings.
− Secondary box, porcelain insulator drawings.
− Bill of material.
− Primary and secondary terminal drawings.
− Rating and connection plate details.
− Oil level indicator, oil drain plug and nitrogen valve details.
− Wiring diagram.
− Packing list.
− Quality assurance plan

Rev. 0 Page 10
50MVA, 33/132kV Substation, Document No: Rev No: 00
Rajasthan Project
Sangarh, Rajasthan , India IBVSI/RJ/SANGRAH/EE/TS/CT/01

11 List of Attachment

Sr.No. Attachment Number Revision Title

1 Annexure-01 0 Deviation/Clarification/Exception List

2 Annexure-02 0 Manufacturer’s compliance

3 Annexure-03 0 Project Specific Details

Rev. 0 Page 11
Doc No
50 MVA, 33/132 KV SUBSTATION AT, SANGARH, RAJASTHAN
IBVSI/RJ/SANGRAH/EE/CT
/GTP/01

Approved: CAT B
By OBS
Date : 20/12/2023

TITLE : 132KV CT DIAGRAM & GTP

ib vogt SOLAR INDIA Pvt. Ltd.


CLIENT : GURUGRAM, HARYANA INDIA – 122018

SHAKTI ENGINEERS AND CONSULTANTS,


CLIENT
BANGALORE-560097.
CONSULTANT :

0 15.11.2023 AC HP AC 8 FOR APPROVAL

NO. OF
REV. DATE PREPARED BY. CHECKED BY. APPROVED BY. REMARKS
SHEETS
Document: GTP of 132kV Current Transformer
Document Number: IBVSI/RJ/SANGRAH/EE/CT/GTP/01

Vendor Data Vendor Data


Sr.No. Description Requirement
101-CT 102-CT

A Current Transformer (as per SLD) 101-CT (3Nos.)

CT Ratio 250-500/1-1-1-1 A

Core-1 CL-0.2S, 15 VA

Core-2 CL-PS

Core-3 5P20, 30 VA

Core-4 CL-PS

B Current Transformer (as per SLD) 102-CT (3Nos.)

CT Ratio 250-500/1-1-1-1 A

Core-1 CL-0.2S, 15 VA

Core-2 CL-PS

Core-3 5P20, 15 VA

Core-4 CL-PS

Page 1 Rev. 0
Vendor Data Vendor Data
Sr.No. Description Requirement
101-CT 102-CT

1 Nominal System Voltage 132 kV

2 Maximum System Voltage 145 kVrms

3 Rated Frequency (Hz) 50 Hz

4 No. of Poles 1

5 Design Ambient Temperature 50°C

6 Service Outdoor

7 Type of Tank Live Tank

8 Type of Current Transformer Oil Cooled, Hermetically Sealed

9 Rated Primary Current 250-500 A

10 Rated extended primary current 120%

11 Code and Standard IS 2705 / IEC 61869


Specification BVSI/RJ/SANGRAH/EE/TS/CT/01

12 Rated short time thermal withstand 31.5kA for 1s


current

13 Rated Dynamic Current 80 kAp

14 Temperature rise over ambient As per IEC (Manufacturer to specify)


temperature

Page 2 Rev. 0
Vendor Data Vendor Data
Sr.No. Description Requirement
101-CT 102-CT

15 Rated Insulation Level

16 Full wave impulse withstand voltage ±650kVp


(1.2/50µs)

17 One minute power frequency dry 275kVrms


withstand voltage (dry and wet)

18 One minute power frequency withstand 5kVrms


voltage between secondary termminals &
earth

19 Maximum radio interference voltage for 500 microvolts at 92kVrms


frequency between 0.5MHz and 2MHz

20 Seismic acceleration 0.3g

21 Partial Discharge As per IEC (Manufacturer to specify)

22 Number of terminal All terminals of control circuit shall be


wired up to marshalling box plus 20%
spare terminals evenly distributed on all
TBs

23 Minimum creepage distance 31mm/kV (Manufacturer to specify)

24 System neutral earthing Effectively earthed

25 Core Details:

a) Material CRGO Silicon Steel

Page 3 Rev. 0
Vendor Data Vendor Data
Sr.No. Description Requirement
101-CT 102-CT

b) Size (mm) Manufacturer to specify

c) Weight (Kg) Manufacturer to specify)

26 Flux Density at Knee point Voltage <1.4 T

27 Type of Primary Winding Bar type

28 Details of Windings:

a) Primary:

i) Material Copper

ii) No of Turns. Manufacturer to specify

iii) Cross Sectional area of each turn in Manufacturer to specify


Sq.mm

b) Secondary :

i) Material Copper

ii) No. of Turns Manufacturer to specify

iii) Cross Sectional area of each turn in Manufacturer to specify


Sq.mm

30 Winding Connections for obtaining CT


Ratios:

Page 4 Rev. 0
Vendor Data Vendor Data
Sr.No. Description Requirement
101-CT 102-CT

i) At Lowest Ratio Manufacturer to specify

ii) At Middle Ratio Manufacturer to specify

iii) At Highest Ratio Manufacturer to specify

31 Permisible Limits :

a) Guaranteed Ratio Error (Max.) Within permisible limits as per IS-2705


(Manufacturer to specify)

b) Guranteed Phase Angle Error (Max.) Within permisible limits as per IS-2705
(Manufacturer to specify)

c) Guaranteed Composite Error ( Max.) Within permisible limits as per IS-2705


(Manufacturer to specify)

32 Max. Temp. rise Within permisible limits as per IS-2705


(Manufacturer to specify)

33 Insulation Class Class "A"

34 Magnetisation Curve To be furnished by vendor

35 Insulators :

a) Type Porcelain

b) Make To be furnished by vendor

c) Total Creepage Distance (mm) 3625 mm

Page 5 Rev. 0
Vendor Data Vendor Data
Sr.No. Description Requirement
101-CT 102-CT

d) Protected Creepage Distance (mm) As per IS-5621

e) IS confirmity to Insulator IS : 5621 & IS : 2099

f) Arcing Distance 1200 mm

g) Max. Creepage Factor 4

36 Current Density in Primary Winding


corresponding to:

a) Short time thermal rating of 1 sec. 51.7 A/Sq.mm

b) Normal Continuous Current 1.65 A/Sq.mm

37 Total Weight of CT with Oil Manufacturer to specify

38 Insulating Oil:

a) Weight (Kg) Manufacturer to specify

b) Volume Manufacturer to specify

c) Type EHV Grade Transformer Oil, confirming


to IS :335

39 Overall Dimensions of CT Manufacturer to specify

40 Thickness of Tank Sheet (mm) 3 mm (minimum)

41 Mounting Details Manufacturer to specify

Page 6 Rev. 0
Vendor Data Vendor Data
Sr.No. Description Requirement
101-CT 102-CT

42 Type of Treatment:

a) External Surfaces of all ferrous parts. Manufacturer to specify

b) Internal Surfaces of all ferrous parts in Manufacturer to specify


contact with oil.

43 IS to which CT Conforms To IS - 2705 (1992) and IS 16227

44 Type Test Report of CT Yes

45 Terminal Connector Bimettalic

46 Tan Delta 0.004 (Max.) without any Temp.


correction

47 Other Features of CT:

a) Pressure Relief Device Required

b) Oil filling/drain valve Required

c) Nitrogen or any other inert gas above Required


oil level

d) Weather Proof Secondary terminal box Required


fitted with hinged door.

e) Terminal Blocks Suitable for 4 Sq.mm Cu. Wires

f) Gland Plate Removable Gland Plate to be provided

Page 7 Rev. 0
Vendor Data Vendor Data
Sr.No. Description Requirement
101-CT 102-CT

g) Lifting Lugs/Holes Required

h) Rating & Connection Diagram Plate Required

i) Two Earthing Terminals Required

48 Bushing Porcelain

49 Sealing Nitrogen gas cushion

50 Type of Mounting Pedestal

51 Primary terminal Material

Terminal type and dimension Manufacturer to specify

Whether shorting links provided with Manufacturer to specify


terminal

Test provision for terminals possible Manufacturer to specify


during operation

Number of holes and diameter Manufacturer to specify

Max. pull on primary terminal 2000 N (minimum, maximum proposed


value manufacturer to specify)

Page 8 Rev. 0