Bohn Refrigeration Analysis


Client Data:
Name: cam. higo Quotation:
Date: 05/05/2021
, Job Name:
Phone: Fax: Location: Guadalajara, Jalisco Mexico
Room Data:
Room Temp: 35.0ºF @ 0.89 % RH Ambient Temp.: 91.0ºF DB
Dimensions: 14.4 ft long X 12.5 ft wide X 8.20 ft high
K Factor in.
Temp Insulation: BTU/ft²/°F/in Thick Square Feet
Ceiling: 111.0ºF POLYURETHANE 0.160 3.0 180.00
Floor: 51.0ºF CONCRETE 1.250 6.0 180.00
Wall #1 (L): 91.0ºF POLYURETHANE 0.160 3.0 118.00
Wall #2 (W): 91.0ºF POLYURETHANE 0.160 3.0 102.00
Wall #3 (L): 91.0ºF POLYURETHANE 0.160 3.0 118.00
Wall #4 (W): 91.0ºF POLYURETHANE 0.160 3.0 102.00
Infiltration Data:
Qty Size (ft) Entering Air Opening Time Air Curtain Number of
Doors: 1 7 X 5 91.0 ºF DB 68.0 WB 2 /hr. 0.40 min. .00 % Auxiliary Doors

0 Glass

0 Dock

Product Data:
Type: GRAPES, AMERICAN Packaging: Freeze Point: 29.7ºF
Max. Load: 9,921 lbs SpHt Above Freeze: 0.86
Load Time: 24.0 hrs.
Final Temp: 35.0 ºF SpHt Below Freeze: 0.44
Ent. Temp: 53.6 ºF Pulldown Time: 24.0 hrs. † Lat. Ht. Fusion: 116
Max. Inventory: 9,921 lbs Ht of Respiration: 0.60

Miscellaneous Data:
Occupancy: 0.06 People Motors: 0.09 Equiv HP
Lighting: 1.00 w/ft² Forklift: 0.00 Other: 0 BTU/day

Calculation Results:
Wall Heat Gains: 3,430 BTUH 21 % Total Load: 15,981 BTUH ‡
Infiltration Load: 2,257 BTUH 14 % Runtime: 20.00 hrs/day
Product Load: 9,056 BTUH 57 %
Misc Loads: 1,238 BTUH 8%

Equipment Selection:
Model: ( 1) BHB025X6 - 1- LO165_E Power:
(condensing unit = 230/1/60) & (evaps = 115/1/60)
System Capacity: 16,723 BTUH @ 10.1 TD Runtime 19 Hrs. Hertz: 60

Total Price: $0 List Including selected options ©

†) Calculated load is based on pulldown data as provided by user, it is the responsibility of the user to ensure
appropriate product packaging and air flow conditions prevail which will allow pulldown within this time period.
‡) The TOTAL LOAD includes a contingency safety factor of 10% to cover the possibility of unforeseen high load
conditions, excessive ambient temperatures, unexpected increases of business, or product packaging changes.
©) All pricing is firm for a period of 30 days from the date of this quotation and is subject to all of our standard
terms and conditions of sale. Prices herein do NOT include any applicable federal, state or local taxes.

Copyright © 1998-2003 by Heatcraft Refrigeration Products LLC All rights reserved.

You might also like