Professional Documents
Culture Documents
The grounding and bonding of direct current (DC) systems are primarily handled
by the Code the same manner as for alternating current (AC) systems, with only a
few differences. This makes sense, because DC systems are simply AC systems
that are at 0 Hz instead of the typical 50 or 60 Hz.
Many people think that DC systems cannot hurt you. This is not true. A rule of
thumb is that if a person is exposed to electrical energy for 1 s, 70 mA of 60-Hz
power is lethal, whereas 300 mA of DC power is lethal. There are many industrial
processes that utilize low-voltage (less than 60 V) DC electrical sources with very
high amperages (over 10,000 A) that can easily kill, such as electroplating,
chemical electrolysis systems, and electrolytic smelting. Unfortunately, many of
these types of systems are exempt from the National Electrical Code (NEC)
due to human safety studies that were conducted just after World War II. It is
important to understand that there is absolutely no basis for assuming that DC
electrical energy under 60 V is safe.
This section of the Code simply states that DC systems must comply with Part VIII
of Art. 250 and any other part of Art. 250 that is intended for DC systems. See
Arts. 250.6 (E) and 250.142(B), Exception No. 3 for more information.
All DC systems must be grounded as stated in Art. 250.162(A) and (B), which
states that all three-wire DC systems must be grounded, and all two-wire DC
systems operating between 60- to 300-V DC must be grounded. See Art. 250.162
(A) and (B) for more information.
Given the recent understanding of DC arc flash, you should expect to see a
change in the rules regarding DC systems over 300 V in the future. Properly
grounding the exposed non-current-carrying metal components of these systems
will only help to protect personnel and equipment. See more information in the
last paragraph of this section.
If your DC system is less than 60-V DC, you do not have to ground it. However,
there is no provision saying that you cannot ground the system, and you probably
should. The exposed metal parts and metal chassis of systems using DC at less
than 60 V will only benefit from having a properly sized and routed equipment-
grounding conductor.
Additionally, many DC systems are located near AC systems and are subject to
induced currents, harmonics, electrical noise, stray voltages, and other
objectionable currents inherent in AC systems. Ungrounded DC systems will have
no effective means of removing these stray voltages other than through the
neutral conductor of the electrical system, especially in isolated DC systems.
Proper grounding and bonding will only improve your electrical system.
The 2014 edition of the Code increased the DC voltage from 50 V to 60 V, and
required in Exception no. 1 that the source of power be adjacent to or integral to
the system.
Three-wire DC systems are not much different than any standard 208-V, single-
phase AC system, with the exception of the frequency (0 Hz). The neutral
terminal on the rectifier on a DC system will be grounded just as a neutral wire
would in an AC system.
Grounding of a DC system is in general to be conducted in the same manner as
grounding of an AC system.
Although the Code does not make it clear, this section is discussing both two-wire
and three-wire DC systems, which must be grounded in accordance with Art.
250.162(A) and (B).
Three-wire DC systems are not much different than any standard 208-V, single-
phase AC system, with the exception of the frequency (0 Hz). The center point of
the winding on an AC transformer (the XO) is 0 V, so we ground it at this point.
The same is true for a DC system, where the center point is 0 V, and we will
therefore ground it at this point. The wire attached to the zero point is the neutral
conductor (grounded conductor), just as in an AC system.
As with AC systems, you are to have one and only one neutral-to-ground
connection at the first service disconnect for the system. See NEC Art. 250 Parts
II and III for more information.
Two-wire DC systems are not much different than any standard 120-V, single-
phase AC system, with the exception of the frequency (0 Hz). The return
conductor of the two-wire DC system is the neutral, and it must be bonded to
ground in the first service disconnect, just as in an AC system.
Direct current systems must also have grounding electrodes installed into the
earth/soil and grounding electrode conductors, just as in AC systems. These
electrodes and conductors must comply with NEC Art. 250 parts II, III, and V.
This section of the Code tells us that you must size the grounding electrode
conductor for DC systems in accordance with Art. 250.166(A) and (B), except as
allowed in Art. 250.166(C) through (E). Additionally, the grounding electrode
conductor is not required to be larger than a 3/0 copper or 250 kcmil aluminum.
In general, Table 250.66 (see Appendix B) can be used for proper sizing of
grounding electrode conductors for DC systems.
The 2014 edition of the Code placed a maximum size of 3/0 copper or 250 kcmil
aluminum for the grounding electrode conductor on DC systems.
250.166(A). Not Smaller Than the Neutral Conductor. Two-wire DC
generators used in conjunction with balancer sets in order to obtain a neutral
point for three-wire systems must be equipped with OCPDs that electrically
disconnects the three-wire system, in accordance with NEC Art. 445.12(D).
When this is the case, the grounding electrode conductor must be the same size
as the neutral conductor or an 8 AMG copper (or 6 AWG aluminum) conductor,
whichever is larger.
If this sounds like it refers to a very small set of DC systems, you are correct. This
rule only applies to DC systems with three-wire balancer sets or balancer
windings and with OCPDs. Please see Art. 250.166(B) for all grounding electrode
conductor requirements for all other DC systems.
250.166(B). Not Smaller Than the Largest Conductor. This section deals
with grounding electrode conductor requirements of all DC systems other than
those in Art. 250.166(A). The grounding electrode conductor for DC systems must
be equal in size to that of the largest phase conductor or an 8 AWG copper (or 6
AWG aluminum) conductor, whichever is larger.
Remember that aluminum is not allowed to come within 18 in. of the earth or to
be encased in concrete or to be used as an electrode, under Arts. 250.52(B)(1)
and 250.64(A).
250.166(E). Connected to a Ground Ring. The grounding electrode
conductor does not need to be larger than the size of the copper ground ring
conductor when it is the sole connection to the ground ring, as in Art. 250.52(A)
(4). This matches the requirements of AC systems that are connected to ground
rings, as found in Art. 250.66(C).
What this section tells you is that for DC systems, you must reference Table
250.66 (see Appendix B) and size the grounding electrode conductor accordingly
or match the size of the ground ring. The minimum size for a ground ring is 2
AWG copper per Art. 250.52(A)(4).
Remember that aluminum is not allowed to come within 18 in. of the earth or to
be encased in concrete or to be used as an electrode, under Arts. 250.52(B)(1)
and 250.64(A).
This new section of the Code requires ground-fault monitoring and detection on
ungrounded DC systems and makes it optional to install them on grounded DC
systems. Proper marking is also required.
This section tells us that the grounding electrode conductor must be connected
to the neutral conductor (grounded conductor) at the first service disconnect. The
system bonding jumper must be the same size as the grounding electrode
conductor, as in Art. 250.166 above. You must also comply with all the main
bonding jumper and system bonding jumper rules found in Art. 250.28(A), (B),
and (C). Please see Art. 250.28 for more information.
System bonding jumper A conductor, screw, or strap that bonds
the equipment-grounding conductor to the neutral (grounded)
conductor; sometimes called the main bonding jumper. The term
system bonding jumper is used to distinguish the bond at the load side
of the service (at the first service disconnect) from the supply-side
bonding jumper, which is the bonding used on the utility or supply side
of the service. For more details, see Arts. 250.24(A)(4), 250.24(B),
250.28, and 408.3(C).
An exception for vehicle-mounted and portable generators is made for this rule
and matches the rules found in Art. 250.34. Please see Art. 250.34 for more
information.
Citation
EXPORT
David R. Stockin: McGraw-Hill's National Electrical Code® 2014 Grounding and
Earthing Handbook. NEC 250 PART VIII: DIRECT CURRENT SYSTEMS, Chapter
(McGraw-Hill Professional, 2014), AccessEngineering
Copyright © McGraw-Hill Global Education Holdings, LLC. All rights reserved.
Any use is subject to the Terms of Use. Privacy Notice and copyright information.
This product incorporates part of the open source Protégé system. Protégé is
available at http://protege.stanford.edu//