Professional Documents
Culture Documents
AC1 315-99
Details and Detailingof Concrete Reinforcement
(AC1 315-99)
Reported by AC1 Committee 315
This document provides Standards of practice for both the architect/engi- Part B-Responsibilites of the detailer
neer (ME) and reinforcing steel detailer in showing reinforcing steel Chapter 3-Placing drawings, p. 31 5-1 O
details. It is divided into three parts: one addressed to the N E , one for the
3.1-Definition
detailec and a third providing a reference table and figures. It defines the
responsibilities of both the NE and detailer It then establishes certain 3.2-Scope
standards of practice for both the structural and placing drawings. 3.3-Procedure
3.4-Drawing standards
Keywords: beams (supports); bending (reinforcing steels); bridges (struc-
tures); buildings;columns(supports);concreteslabs;detailing;drafting 3.5-Building drawings
(drawing);fabrication; floor systems;foundations;hookedreinforcing 3.4-Highway drawings
steels; microcomputers; placing drawings; reinforced concrete; reinforcing
steels; splicing; stirrups; structural design; structural drawings; ties; toler-
3.7-Detailing to fabricating standards
ances (mechanics); walls; welded-wire fabric.
Chapter 4-Fabricating practice standards, p. 315-15
CONTENTS 4.1-Fabrication
4.2-Extras
Part A-Responsibilities of the architedengineer 4.3-Tolerances
Chapter 1-Structural drawings, p. 315-2
1.1-General
Chapter f)-Supports for reinforcing steel, p.31516
1.2-Drawing standards 5.1 “General
1.3-Structural drawings-Buildings and other structures
5.2-Types of bar supports
1.4-Structuraldrawings-Highwayand transportation
5.3-Side form spacers and beam bolsters
structures
5.4-Placing reinforcing steel supports
Chapter 2-Standards of practice, p. 315-3
2.1-General Chapter 6-Computer-assisted detailing, p. 315-16
2.2-Tolerances 6.1-Use of computers indetailing
2.3-Bar lengths 6.2-Placing drawings
2.4-Hooks and bends 6.3-Ordering procedures
2.5-Beams and girders
2.6-columns Chapter 7-Recommended practices for location
sizekpacing, p. 315-17
of bars designated only by
2.7-Development and splices of reinforcing steel
2.8-Joint details
AC1 315-99 supersedes AC1 315-92 and became effective August 31, 1999.
2.9-Reinforcing steel supports Copyright O 1999, American Concrete Institute.
All rights reserved including rights of reproduction and use in any form or by any
2.lOSpecial details for seismic designof frames, joints, means, including the making of copies by any photo process, or by electronic or
walls, diaphragms, and two-wayslabs mechanical device, printed, written, or oral, or recordingfor sound or visual reproduc-
tion or for use in any knowledge or retrieval system or device, unless permission in
2.1 l-Corrosion-resistant coatings for reinforcing steel writing is obtained from the copyright proprietors.
315-1
must be correspondingly larger and meet microfilming stan- bars and welded-wirefabric in the structure.The list of bars
dards in accordance with the Association for Information and must show the number of pieces,size, length, mark of bars,
Image Management (formerlythe National Microfilm Asso- and bending details of all bent bars.The list of welded wire
ciation) publication “ModemDrafting Techniques for Qual- fabric must show the mark,style, width, length, and number
ity Microreproductions.” of pieces.
Reinforcing steel for larger structures is sometimes de-
1.3-Structural drawings-Buildings and other tailed, fabricated, and delivered by units, for example, foot-
structures ings, abutments, piers, and girders.The reinforcing steel list
1.3.1 General-Structural drawings and projectspecifica- may be subdivided similarly. If the structure is sufficiently
tions for elements such as beams, girders, columns, walls, large, a separate drawing and reinforcingsteel list is usually
and foundations shall show the type and gradeof reinforcing made for each unit.
steel, any special coatings, service live load, partition, ceil- Reinforcing steel for foundations, piers, abutments, wing
ing and hanging loads, or any special dead loads other than walls, andslabs are usually shown ona plan, section, or ele-
the self-weight(mass)and concrete strength.Structural vation viewon the drawings. Cross sections must be provid-
drawings and project specifications shall also show concrete ed for clarification where necessary. The reinforcing steel
dimensions, anchorage length of reinforcing steeland location list is a complete summary of materials required. All bars
and length of lap splices, type and location of mechanical should appear at least once in a plan or elevation view and in
and welded splices of reinforcing steel, concrete cover for a sectional view,or both.
For reference data on reinforcing bars and welded wire
the reinforcing steel, required joints, and anyother informa-
fabric from industry sources, refer to the Supporting Refer-
tionneeded for thepreparation of theplacing drawings.
ence Data section.This section includes specific information
Sleeve locations and any special reinforcing steel around
on applicable ASTM specifications,coated reinforcingbars,
sleeves or openings shall beindicated by the A/E. See Fig. 1,
common styles and design data for welded wire fabric, and
2, 3, 4, 5, 6, and 7 (in Part C-Figures and Tables), for ex- reinforcing bar supports.
amples. In addition to these requirements, structural draw-
ings of beams, girders, and columns must also show the CHAPTER 2-STANDARDS OF PRACTICE
information presented below. 2.1-General
1.3.2 Beams and girders-Schedules for beams and gird- This chapter provides the A/E with minimumstandards for
ers must contain the beam mark, size of member, number application during the development of the design. Informa-
and size of straight and bent bars, special noteson bending, tion presented hereis a collection of notes derivedfrom AC1
number, size, and spacing of stirrups or stirrup-ties, location 3 18 (3 18M); AC1 343R; AREMA Manualfor Railway Engì-
neering, Chapter 8, “Concrete Structures and Foundations;”
of top bars, and any special information, such as the require-
and AASHTO “Standard Specifications for Highway Bridges,”
ment of two layers of reinforcing steel. Show sections for industry practice, practical considerations, and research re-
beam-column joints, where necessary. sults current at the time of this report. Reinforcing steel for
In continuous beams, the number and spacingof top bars structures designed under the provisions of AC1 349, AC1
to be placedin T-beam flanges (slabs) for crack control shall 359, and other similar documents can generally incorporate
be shown, if so required by the design. the direction given inthis standard unless otherwise prohib-
1.3.3 CoEums4olumn designs shall show the size of col- ited by the provisionsof the respective related documents.
umns, number, locations, grade, and size of reinforcing steel,
and all necessarydetails where column sectionor reinforce- 2.2-Tolerances
AC1 117 provides standard tolerances for concrete construc-
ment changes. Method of splicing shall always be defined
tion. Practical limitations
of equipment and production efficien-
clearly, showing arrangementof splices, type (lap, mechani-
cy have led to the establishment of certain fabrication tolerance
cal or welded), length (iflap splice), and stagger. Orientation
of reinforcing steelin two-way symmetrical columns shall be
that can be met with standard shop equipment. These standard
tolerances are shown in Fig.8 and 9 (in Part C) for
both straight
shown when reinforcingsteel is not two-way symmetrical.
and bent bars. Where more restrictive tolerances are required
than those shown in the referenced figures, they shallbe indi-
1 .&Structural drawings-Highway and
transportation structures* cated in the contract documents. The effects of tolerances on
1.4.1 Dimensions-Becausethestructural drawings for cover, strength, constructability, and serviceability
of the struc-
highway structures usually are a combination of structural ture should be considered by the A/E.
and placing drawings from which the structure will be built,
all dimensions must be shown clearly. Drawings must show 2.3-Bar lengths
Placing drawings and bar lists must show all bar dimen-
the dimensions of concrete protection for allreinforcing
sions as out-to-out with barlengths as the sum of all detailed
steel.+Where separate placing drawings are prepared, struc-
dimensions, including hooksA and G (Table 1 in Part C).
tural dimensions may be omitted, following the same prac-
tice as for buildings (see Section 3.5). *The tcnn “highwayandtransportationstructureb”usedhereinincludesbridgcs,
1.4.2 Reinforcingsteel-Combination structural-placing drainage. and related structures.
‘Subject to requirements of AC1 318 (318M), Section 7.7. or the AASHTO bridge
drawings shall show the size, spacing, and location of the specifications. Articles8.22 and 9.26.
2.4-Hooks and bends equivalent to the area of the bundle. For bridge design, the
Hooks and bends are specified to standardize the fab- AREMA design manual andthe AASHTO bridge specifica-
rication procedure and to limit the concrete stresses in the tions require a minimum spacingequal to 1.5 times diameter
area of the hooks. See Table 1 andFig. 10 in Part C. of a single, equivalent area bar.
Spirals are used primarily for columns, piers, and drilled 2.7-Development and splices of reinforcing steel
caissons, but are also used in piles. Continuously wound,re- 2.7.1 General-In AC1 318 (318M), development and lap
inforcing steel in the form of a circular helix not meeting splice lengthsfor deformed reinforcing bars can be calculated
AC1 318 (318M) definition of a spiral may be used in these using one of two optional approaches. A previous calcula-
structures as tie reinforcement. Such reinforcing steel, some- tion approach, fromAC1 3 18-89 (3 18M-89)also remains ac-
times referred to as continuousties, is usually specified with ceptable. With multiplecode-compliant approaches to
a large pitch. calculation existing, choice, interpretation, and application
2.6.5 Column ties-The vertical bars in tied columns shall are the M ’ s responsibilities.Sufficient information shall be
be tied together laterally. Standard arrangements of ties for presented on thestructural drawings andin the project spec-
various numbers of vertical bars are shown in Fig. 13 and 14 ifications to allowdetailing of bars atsplices and embedment
in Part C. The A/E may also specify welded-wirefabric with locations without referencing back to thecode.
an equivalent area of reinforcing steel for column ties. The Tables in the supporting reference data section give values
arrangements of one-piece ties showninFig.13provide of tension development lengths and tension lap splice lengths
maximum rigidity for column cages preassembled on the site of straightbars.Valuesoftensionandtensionlapsplice
before erection. Preassembly is preferred only for the com- lengths in the tables are based on the provisions in 12.2.2.AC1
mon designs employingone-story-lengthvertical bars all lap All tabulated data are for Grade 60 (420) reinforcing bars in
spliced at or near one point abovethe floor line. See Section normalweight concrete
with
the
concrete
compressive
2.7.3 for lap splice restrictions. strength,f:, ranging from 3000 to 8000 psi(21 to 56 MPa).
With staggered butt splices on large vertical bars in two- The tables use the terminology Cases I and 2. Cases I and
story lengths, practical erection limitations usually require 2, which depend on the type of structural element, concrete
that column ties be assembled on free-standing vertical bars. cover, and the center-to-center spacing of the bars, are also
Standard arrangements for two-piece column ties shown in defined in thetables.
Fig. 13 and 14are recommended to facilitate field assembly. Separate tables are included for uncoated and epoxy-coat-
They are universally applicableto any splice arrangement re- ed bars. There are no special development requirements in
quired by the A/E. If access to the interior of a column or a AC1 3 18 (3 18M) for zinc-coated (galvanized) bars and they
should be treated as uncoated bars. For lightweight aggre-
pier is necessary,or if the A/E prefers, some other pattern of
gate concrete, the valuesin the tables would have to be mod-
ties maybe substituted, provided that the tie arrangement
ified by the applicable factor (AC1 12.2.4).
meets AC1 3 18 (318M) requirements.
AC1 1.2.1 requires that anchorage lengthof reinforcement
The spacing of ties depends on the sizes of vertical bars, and location and length of lap splices be shown onthe struc-
columns, and of ties. The maximum spacings permitted are tural drawings. This information can be shown by dimen-
shown in a table in the supporting reference data section. sioning cut-off locations and including tables of applicable
In addition to showingsize and regular spacing of column lap splice lengths.
ties, the A/E shall also show any additional ties required for 2.7.2 Splices, general-In beams or girders that require
other special conditions such as at splices, and offset bends bars longer than can be carried in stock, splices shall be spec-
(see also Section 2.1 O for seismic details). ified. The A/E shall show or specify by notes how the splic-
If the design requires lateral reinforcement in the column ing is to be realized; namely, lap splices, mechanical splices,
between the topof the main spiral and the floor level above, or welded splices.
it may be providedby a stub spiral (short section of spiral) or The A E shall also show, by details on structural drawings,
circular column ties to permitplacing of the reinforcing steel the location and length of all splices. In beams or girders,
in the floor system, and the arrangement shall be shown. splices should preferably be made where thestress in the bar
is minimum, that is, at the point of inflection. Splices where resist tension, but the hook may not be considered in deter-
the critical design stress is tensile should be avoided by the mining theembedment provided for compression.
AIE wherever possible. Lapped bars may be either in contact Separate splice bars (dowels) are necessary for splicing
or separated. The A/E shall show or note on the structural column bars where the column section changes 3 in.(80mm)
drawings whether splices are to be staggered or made at the or more, where the placing of parts of the structure is de-
same location. Bars to be spliced by noncontact lap splices in layed, or between various units ofstructures. Except for spe-
flexural members shall notbe spaced transversely more than cial cases, separate splice bars (dowels) should be the same
the smallerof one-fifth the lengthof lap and 6 in. (150mm). number, size, and grade as the bars joined and should be of
2.7.3 rclp splices-It is necessary for the A/Eto show the proper length to splice with the main bars, and shall be spec-
location and length of lap splices because the strength of a ified by the AfE.
lap splice varies withthe bar diameter, concrete strength, bar Lap splices for deformed welded-wire fabric shall be
spacing, concrete cover, position of the bar, distance from shown by the m.* AC1 318 (318M) requires that, for de-
other bars, and the type of stress (compressive or tensile). formed welded-wire fabric, the splice shall be at least 1.3
Where bars of two sizes are lap spliced, the A/E must indi- times the development length (8 in. [200 mm] minimum).
cate the appropriatelap splice length. Lap splices are not per- The A/E shall indicate the required splice dimension(s).
mitted for No. 14 and 18 (No. 43 and 57) bars, except for Lap splices for plainwelded-wire fabric shall also be
transferring compression to smaller size dowels that are an- shown by the A B . * AC1 3 18 (318M) requires that the splice
chored into footings for buildings. Lap splices for bars larger length, as measured between outermost cross wires of each
than No. 11 (No. 36) are not permitted by the AREMA de- fabric sheet, shall be notless than one spacing of cross wires
sign manual or the AASHTO bridge specifications. plus 2 in. (50 mm) nor less than 1.5 ld(6 in. [ 150 mm] min-
At column bar splice locations, sufficient bars (or dowels) imum) when A, providedA, required < 2. When A, provided
from the lower columns must extend into the upper column A, required r 2, only the requirement of 1.5 ld(2 in. [50 mm]
minimum) will apply.Therefore, the A/E can either show the
to provide not less than the cross-sectional area of the re-
required splice dimension or indicate a typical detail show-
quired bars in the upper column.These bars must extendthe ing the lap splice length equal to one spacing of cross wires
minimum distance required for lap splices. The A/E should plus 2 in. (50 mm), if that controls.
note that unless otherwise specified or shown on structural 2.7.4 Butt splices-Mechanical splices or welded splices
drawings, the detailer will detail the remaining bars in the can be specified or, for compression only, end-bearing splices
lower column extending to within 3in. (75 mm) of the top of can be specified as butt splices for vertical column bars.For
the floor or other member transmitting the additional load to No. 14 and 18 (No. 43 and 57) bars, butt splices shall be
the column.Where the top ends of column barsare less than used. Special preparation of the ends of the vertical bars is
6 ft (1800 mm) above the top of footings or pedestals, the usually required for butt splices. Where a mechanical splice
bars should extend into the footings or pedestals. Normally,
is used, both ends of the bar can be either square cut, flame
dowels will be used only if specifically noted on structural cut, or standard shear cut, depending on the type of splice
drawings.
used. Because mechanical splices are usually staggered be-
Dowels for lap splices at column offsets should have a tween alternate vertical bars and their location depends on
cross-sectional area at least equal to that of the bars above the design requirements, the A/E must indicate the types of
and they shall extend both above and below the splice loca- mechanical splices permissible, their location, and end prep-
tions, as specified by the A/E. aration required. Where bars are welded, the most common
The N E should also be aware that it is a standard practice practice is to provide a square-cut end at the top of the lower
bar
in the industry when detailing column verticals to use the ap- and a double-beveled end on the bottom of the upper bar. Field
propriate lap splice length for the bars in the column above. All welding
preparation of ends by flame cutting is satisfactory.
This applies regardless of differences in bar sizes. of reinforcing bars shall conformAWS to Dl .4.
For columns, the arrangement of bars at a lap splice is
shown in Fig.4. It should be noted that the amount of offset 2.8-Joint details
of the bars is greater for rectangular columns than for round 2.8.1 Rigidframe corners -The AIE shall exercise care in de-
columns. Column verticals to be lap spliced in square or rect- signing the comer joint of a rigid frame. AU main reinforcing
angular columns, where column size does not change, are usu-
steel that passes through the joint shall be free of any kinks
ally shop offset bentinto the column above, unless otherwise or discontinuous bending. The center of radius of the bend
shown by the M.The A/E shall indicate which vertical bars must be kept within the joint. This point is important in splic-
are to be offset bent for round columnsin those cases where ing the topbars from the girder to the outside bars in the col-
the column size doesn’t change. umn. The A/E must provide complete information, showing
Where the depth of the footing, or footing and pedestal the radius of any nonstandard bends andlocation and dimen-
combined, is less than theminimum length of embedmentre- sions of lap splices. If a mechanicalor welded splice is to be
quired for dowels of a certain size, the size of dowel should used, a physicaldescription must beprovided. Tension in the
be decreased andthe number of dowels increased to give an
equivalent area. This should also be shown on the structural *Supplementarydata on welded wire fabric appears in Chapter 2 (“WeldedWire
drawings. Hooks at the ends of the bars can be desirable to Fabric”) of the supporting reference datasection.
concrete surrounding the reinforcing steel where the steel 2.10-Special details for seismic design of frames,
changes direction must be considered. joints, walls, diaphragms, and two-way slabs
2.8.2 Wall intersections altd corners-All horizontal wall 2.10.1 Introduction-In designs for high seismic risk (such
reinforcing steel in one, or sometimes both, faces of a wall as NEHRP Seismic Performance CategoriesD and E)+rein-
shall be sufficiently extended pasta corner or intersection to forced-concrete members shall satisfy AC1 318(318M),
be fully developed (Fig. 15 in Part C). The A/E shall indicate Chapters 1 through17and Sections 21.2through21.7of
which, if any, horizontal reinforcing steel must be extended, Chapter 2 1 to provide a structural system with adequatede-
how far it must be extended, and how it must be anchored at tailstopermit nonlinear response without critical loss of
intersections andcomers of walls and footings. Inareas strength.
where the applicable building code requires earthquake-resistant Indesigns for moderateseismicrisk(such as NEHRP
design, standard practice requires adequate anchorageof all SeismicPerformanceCategory C),t reinforced-concrete
horizontal bars. framesandtwo-way slabs shall satisfy AC1 318(318M),
Walls withloads that open comer intersectionsmust bere- Chapters 1 through 18 and Section 21.8of Chapter 21.
inforced differently than walls withloads that close such in- The provisions of Chapters 1 through18ofAC1318
tersections. Typical details are shown in Fig. 15 for (318M) apply to the design anddetailing of reinforced con-
resistance against loads fromoutside or inside, with the rein- crete structures in regions of low or no seismicrisk (such as
forcing steel from the appropriate face or faces anchored. NEHRP Seismic Performance Categories A and B).?
Precautions to restrain radial tension are similar to those for For seismic design, member sizes should be selected and
rigid frame corners. reinforcing steel arranged to avoid congestion of the rein-
2.8.3 Closedstirrups-Where the structural drawings forcement. Carefulselection of member size and reinforcing
show closed stirrups, these stirrups may be closed by two- steel arrangement will helpto avoid difficulties in the place-
piece stirrups usingoverlapping standard 90 degreeend ment of the reinforcement andconcrete.
hooks enclosing a longitudinal bar, or by properly spliced The requirements of Chapter 2 1 of AC1 3 18 (3 18M) are
pairs of U-stirrups or a standard one-piece Type T l or T2 used to illustrate what the A/Eshall convey to the detailer
stirrup tie. At least one longitudinal bar must be located at (and to familiarize the detailer with the seismic reinforcing
each corner of the section, the size of this bar to be at least steel details). Much information can be shown by schematic
equal to the diameter of the stirrup but not less than a No. 4 diagrams as shown in Fig. 5, 6, 7, 17 and 18 ( in Part C).
(No. 13). These details shall be shown by the A E . (see Fig. These special seismic details are, in principle, applicable to
12). It should be noted that the use of 90 degree hooks and flexural frame members and frame members subjected to
lap splices in closedstirrups is not consideredeffective in sit- both bending andaxial load in regions of high seismic risk.
uations where the member is subjected to high torsional It is importantfor the A/E to examine the reinforcing steel
stress. Tests (Reference 1) haveshownpremature failure layouts carefully in three dimensions and give the detailer the
caused by spalling of the concrete covering and consequent proper information. This examination will show congestion at
loss of anchorage in the 90 degree hooks and lap splices in beam-column joints of beam, column, and hoop reinforce-
these situations (see Fig. 16 in Part C). ment. Large scale drawings, models, or mock-ups of the joint
2.8.4 Structural integrity-Specific details for continuity details, such as those shown in Fig. 7, may be worthwhile to
of reinforcing steel to meet structural integrity requirements ensure that a design can be assembled and concrete can be
shall be incorporated inthe design details by the AIE. Conti- placed.
nuity is required in cast-in-place construction for joists, When subjected to reversals of lateral overloads, joints in
beams, and two-way slabs. Continuity of selected flexural frames and boundary members of walls must be capable of
reinforcement is achieved by making bars continuousor pro- developing plastic hinging and continuing to resist loads af-
viding Class A tensionlap splices and terminating bars with ter yielding of the reinforcing steel without crushingor brit-
standard hooks at noncontinuous supports. Certain propor- tle failure of the concrete. To develop this ductility, concrete
tions of top and bottom flexural reinforcement in perimeter in these members, includingthe joints, shall be confined by
beams shall be made continuous around the structure and transverse reinforcement consisting of rectangular or circu-
confined with closedstirrups. See AC1 7.13 andFig. 2 and 3, lar hoops (see Fig. 5,6,7, 17, and 18).
for example details for structural integrity.
2.10.2 Concrete- AC1 3 18 (3 18M) requires that the specified
concrete strengthfi shall notbe less than 3000 psi (20 “a).For
2.9-Reinforcing steel supports lightweight aggregate concrete,f,‘ shall not exceed 4000 psi
The A/E is responsible for specifying acceptable materi- (30 MPa).
als, and corrosion protection required for reinforcing steel
supports, or both, and if required, for side form spacers, as ‘Established industiy practices recommended for general use of bar supports issued
well as the particular structural elements or areas in which by the Concrete Reinforcing Steel Institute are reprinted in the supporting reference
data section.
each is to be used. Specifications for the use of reinforcing ‘“NEHRP Recommended Provisions for the Development of Seismic Regulation
steel supports usually are based onestablished industry prac- for New Buildings” prepared by the Building Seismic Safety Councilfor the Federal
Emergency Management Agency, issued in 1994, referred to as NEHRP. Seismic per-
tice.* For moredetails on barsupports and side form spacers, formance categories in ASCE 7 are similar to NEHRP. Regions of high earthquake
risk correspond to Zones 3 and 4, regions of moderate earthquake risk to Zone2, and
see Chapter 5. low or no risk in Zone 1 in the Uniform Building Code.
2.10.3 Reinforcing steel-Longitudinal reinforcement, re- positive and negative momentstrengths shall be equal to or
sisting earthquake-inducedflexural and axialforces in frame greater than one-fifth the negative moment strength at the
members and in wall boundary members,shall comply with face of either joint. The A/E shall indicate quantities of rein-
ASTM A 7061A 706M. ASTMA 6 151A 6 15M Grade60 and forcing steel required to satisfy AC1 3 18 (318M), cut-off
Grade 40 (420 and 300) can be used, provided that actual points, and length and location of splices.
yield strength does not exceed the specified yield strength by Stirrups shall be provided for a minimum length of twice
more than 18,000 psi (120 MPa), and tensile strength is at the memberdepth from the support at an initial spacing of 2
least 25% greater than the actual yield strength. in. (50 mm) and a remaining spacing not more thand14, 8db
In regions of moderate seismic risk,standardASTM of the smallestenclosed longitudinal bar, 24 diameters of the
A615lA615M Grade60 and 40 (420 and 300) can be used. stirrup bar, or 12 in. (300 mm). Forthe remaining beam
Test results indicate thatwelded-wire fabric hoops de- length, stirrups shall be spacedat not more thand12.
signed according to AC13 18 ( 3 18M)requirements are effec- 2.10.6 Columns-High seismicriskt-Transverserein-
tive in confining the concrete in thejoints (Reference 2). forcement consisting of single or overlapping rectangular
2.10.4 Beams-High seismic risk*-At least two bars, top hoops for rectangular columns, and single, circular hoops or
and bottom,shall be providedas continuous longitudinal re- spirals for round columns are required (seeFig. 6). A rectan-
inforcement for beams. For beams framing into two opposite gular hoop is closed by overlapping 135 degree hooks hav-
sides of a column, these bars shall extend through the column ing tail extensions of six bar diameters (3 in. [75 mm]
core at least twice thebeam depth without splices(see Fig. 5) minimum) inside the core of the hoop.
and shall develop the bars beyond their theoretical cut-off Crossties of the same bar size and spacing of hoops may
points. be used, but each end ofthe crosstie shall engage a peripheral
At joint faces, the positive moment strength of the beam vertical bar. See Fig. 6 and 17.
shall be equal to or greater than one-half the negative mo- Hoops at a maximum spacing not exceeding one-quarter
ment strength. At other locations in the beam, the positive of the minimum column dimension and 4 in. (100 mm) shall
and negative moment strengths shall be equal to or greater be provided within the joint and above and below the joint
than one-fourth the negative momentstrength at the face of for a distance not less than the column depth, one-sixth the
either joint. The A/E shall indicate quantities of reinforcing column clear height, and 18 in. (450 mm). AC1 3 18 (318M)
steel, cut-off points, and length and locationof splices to sat- provisions regulate the size and spacing of the hoops. Out-
isfy these multiple code requirements. side this region, hoops shall be as required for nonseismic
Continuous top bars must be spliced near the center of a columns, including requirements for shear, and spacingshall
span in frames where moments are usually minimum and not exceed six times the diameterof the longitudinal column
gravity load moments do not usually produce tensile stress- bars or 6 in (150 mm).
es. Bottom bars shall not be spliced at the columns because Column verticals can be spliced lap by splices, mechanical
of possible reversal of beam stresses. splices, or welded splices. Lap splices are permitted only
At beam-column joints, the A/E shall indicate where and within the center half of the column length and shall be de-
how the bars, straight or hooked, are to be terminated. signed as tension splices. ACT 3 18 (3 l SM) requires that me-
Where beams frame into only one side of a column, as at chanical splices or welded splices shall be staggered at least
exterior columns, top andbottombeam reinforcing steel 24 in. (600 mm) and applied to alternate verticals. Offsets of
must havea 90 degree hook thatextends to the far face of the longitudinal reinforcement is not recommended within the
confined region (core) and bends intothe joint.? The devel- joint.
opment length of the hook for tension shall not beless than 2.10.7 Columns-Moderate seismic risk?-Tie spacing so
8db,6 in. (150 mm), or fydbl(65 df;) [fydbl(5.4 df;)]. over a length Io from the face of the member shall notexceed
Hoops shall be provided in frame members over twice the the smaller of eight diameters of the smallest enclosed bar,
member depth from the faces of the supports and toward 24 diameters of the tie bar, one-half the smallest cross-sec-
midspan. If inelastic yielding can occur elsewhere, the A/E tional column dimension, and 12 in. (300 mm). Length 1,
shall indicate location and hoop spacing requirements on shall not be less than one-sixth of the clear span (height) of
both sides of the sections where the inelastic yielding can oc- the member, maximum cross-sectional dimension of the
cur. Hoop spacing requirements are shown in Fig. 5. member, and 18 in. (450 mm). The first tie shall be spaced
Where hoops are not required bythe A/E, stirrups shall be not more than s,12 from the joint face and theremaining ties
provided, spaced at not more than dl2 throughout the remain- shall be spaced not more than so.
ing length of the member anddetailed as shownby the A/E. 2.10.8 Walls und diuphrugms-High and moderate seismic
risk-Walls and diaphragms, if designed as parts of the force-
2.10.5 Beams-Moderate seismic risk*-AC1 3 18 (318M)
resisting system, are relatively stiff members compared with
requires that, at joint faces, the positive moment strength of
ductile beam-column frames. Because wdls may or may not
the beam shall be equal to or greater than one-thirdthe neg-
be designed as part of the primary lateral-load resisting sys-
ative moment strength. At other locations in the beam, the
tem, it is mostimportant that theA/E provide a complete de-
'A frame memberis defined as abeam if the factored compressive axial load is not
scription of the requirementsfor wall reinforcement.Usually
greaterthan(A&)/ 10.
+Core.This term is indirectly defined inAC1 10.0 by the term "A," (area of core) = *A frame member is defined as a beam if the factored compressive axial load is
area within outside dimension of the confining reinforcement. greater than (A&) / 10.
this task can be accomplishedby identifying structural walls uncoated reinforcement. The coating process adds time to
and diaphragms andreference to typicaldetails (see Fig. 18). the normal delivery cycle. Replacement reinforcing steel or
The vertical and horizontal reinforcement shall be placed additional reinforcement to correct oversights may not be
in at least two curtains if the in-plane factored shear force ex- readily available.Therefore, it is important thatthe A E con-
ceeds 2A,,,.\ifL [( 1/6)A,,.\if i]. Thereinforcement ratio in vey specific complete instructions in the project specifica-
each direction shall be equal to orgreater than 0.0025 with a tions or onthe structural drawings for the use of coated
maximum bar spacing of 18in. (450 mm). reinforcing steel.
When the compressive force in a boundary member ex- 2.11.1.2 Provisions to be included in project specijìca-
ceeds 0.2f i A , , the member shall be reinforcedas a column tions-Provisions to be includedare:
in a high seismic risk area withclosely spaced hoops extend- 1. Mechanical splices-Specify requirements for repair of
ing until the compressive force is less than 0.15f ;A,. Trans- damaged coatingafter installation of mechanical splices.
verse reinforcement from wall and diaphragm members shall 2 . Welded splices-Specify any desired or more stringent
be fully developed within the confined cores of boundary requirements for preparation or welding, such as removal of
members. coating, beyond those contained in AWS D1.4; specify re-
2.10.9 Joints-High seismic risk frames-Forces in longi- quirements for repair of damagedcoating after completion of
tudinal beam reinforcing steel atjoint faces shall be based on welding.
a flexural tension stress of 1.25fY and a corresponding in- 3. Field bending of coated bars partially embedded in con-
crease in balancing compressive stresses and shear. Trans- crete-If permitted by the A E , specify requirements for re-
verse hoop reinforcement, as for high-risk seismic columns, pairofdamaged coating after completion of bending
shall be provided in the joints. If the joint is confined by operations.
structural membersmeeting special requirements, lesser 4. Cutting of coated bars in thefield-This practice is not
amounts of transverse reinforcement can be used. The A/E recommended,but ifrequiredandpermittedbythe A E ,
shall evaluate requirements for confinement and end anchor- specify requirements for coating the ends of the bars.
age of longitudinal beam reinforcement. These requirements 5. Limits on coating damage-Specify limits on permissi-
can often be shown by typicaldetails (see Fig. 5,6,7, and 17). ble coating damage causedby handling, shipment, andplac-
2.10.10 Two-way slabs without beams-Moderate seismic ing operations, and when required, the repair of damaged
risk -Reinforcing steel for the fraction of M, to be trans- coating.
ferred by moment (Eq. (13- l), AC1 3 18 [3 1SM]), but notless 2.11.1.3 Usage-Foroveralleconomy,maximize the
thanhalf the total reinforcement required for the column use of straight bars and use the fewest possible different bar
strip, shall be placed in the width of slab between lines 1.5 sizes for a project. On projects where uncoated and coated
times slab or drop panel thickness on opposite faces of the bars are used, to avoid confusion, be precise in identifying
column. (This width equals 3h+ c2 for edge andinterior col- those bars that are to be coated. It is seldomsufficient to call
umns or 1S h + c2 for comer columns.) The A/E shall show for coated reinforcing bars in an element with a general note.
the reinforcing steel to be concentratedin this critical width. Reinforcing bars projecting into the element must beidenti-
See Fig. 19(d) in Part C for typical detail used for locating fied if they are to be coated.
other bars in nonseismicareas.* 2.11.2 Epoxy-coated reinforcingbars
A minimum of one-fourth of the column strip top reinforc- 2.11.2.1 Material specification-See “Standard Speci-
ing steel shall be continuous throughoutthe span. fication for Epoxy-Coated Reinforcing Steel Bars”
Continuous column strip bottom reinforcing steel shall be (ASTM A 775/A 775M). To meet AC1 318 (3 18M), the re-
not less than one-third of the total columnstrip top reinforce- inforcing bars that are to be epoxy-coated shall conform to
ment at the support. A minimum of one-half of all bottom re- the requirements of AC1 3.5.3.1.
inforcement at midspan shall be continuous and developed at 2.11.2.2 Identification-Epoxy-coatedbars are identi-
the faces of the supports. fied with a suffix (E), or with an asterisk (*) and a note stat-
All top and bottomreinforcing steel shall be developed at ing that all bars marked are to be epoxy-coated.
discontinuous edges. 2.11.2.3 Compatible tie wire and barsupports-Coated
tie wire or other acceptable materials must be specified for
2.1 1-Corrosion-resistant coatings for reinforcing fastening epoxy-coated reinforcing bars. Suitable coatings
steel
2.11.1 General are nylon, epoxy, or vinyl. Bar supports should be made of
dielectric material or wire bar supports should be coated with
2.11.1.1 Specification-Coated reinforcing steel pro-
vides a corrosion-protectionsystem for reinforced-concrete dielectric material, such as epoxy or vinyl compatible with
structures. Structural drawings for structures or elements of concrete, for a minimum distance of 2 in. (50 mm) from the
structures that contain coated reinforcing steel shall include point of contact with the epoxy-coatedreinforcing bars. Re-
all of the essential information noted previouslyfor uncoated inforcing bars used as support bars shouldbe epoxy-coated.
reinforcement. The AE must be cognizant that coatedrein- 2.11.3 Zinc-coated (galvanized) reinforcing bars
forcing steel undergoesfurther processing as compared with 2.11.3.1 Material specijìcation-See “Standard Specifï-
cation for Zinc-Coated (Galvanized)Steel Bars For Concrete
‘Even more necessaryfor moderate seismicrisk, wind, or other lateral load. Reinforcement” (ASTMA 767/A 767Mj. To meet AC1 318
(3 1 SM)requirements,the reinforcing bars that are to be zinc- mation necessaryfor complete fabrication and placingof all
coated (galvanized) shall conform to AC1 3.5.3.1. reinforcing steel.
2.11.3.2 Supplementary requirements-There are three
Supplementary Requirements inASTMA 767lA 767M: 3.3-Procedure
Supplementary Requirement S 1 requires sheared ends to be Placing drawings are prepared by a detailer in accordance
coated with a zinc-rich formulation; when bars are fabricated with the A/E’s instructions contained in the contract docu-
after galvanizing, S2 requires damaged coating to be re- ments. Any necessary, additional information must be sup-
paired with a zinc-rich formulation; and if ASTM A 615lA plied by the contractor concerning field conditions, field
615M billet-steel bars are being supplied, S3 requires that a measurements, construction joints, and sequence of placing
silicon analysis of each heat of steel be provided.S 1 and S2 concrete. After approvalby the A I E , including necessary revi-
should be specified when fabrication after galvanization in- sions, the drawings may be used by the fabricator and placer.
cludes cutting and bending.S 2 should bespecified when fab-
rication after galvanization includes only bending. 3.4-Drawing standards
2.11.3.3 Coating weights(massFTable 1 of ASTMA 767 Placing drawings are prepared according to the same gen-
has two classes of coating weights (mass). Class 1 (3.5 odft2 eral standards as structural drawings.
[lo70 g/m2]) is normally specified for general construction. 3.4.1 Layout-Drawings usually show a plan, elevations,
2.113.4 Other embedded metals-No uncoated reinforc- sections, and details of a structure, accompanied by sched-
ing steel, nor any other embedded metal dissimilar to zinc, ules for footings, columns, beams, and slabs. The plan nor-
should be permitted in close proximity to galvanized reinforc- mally is drawn in the upper left comer of the sheet, with the
ing bars except as part of a cathodic protection system. elevations and details below and to the right of the plan.
2.11.3.5 Zdentification-Bars are usually galvanized af- Schedules (and bending details) are normally placed in the
ter fabrication. Bars that require special finished benddiam- upper right comer of the drawing. A figure in the supporting
eters (usually smaller bar sizes for stirrups and ties) should reference data section presents a recommended layout.
be identified. Maintenance of identification to the point of An arrow indicating the direction ofNorth should be
shipment during the galvanizing process is the responsibility placed beside every plan view.
of the galvanizer. Regular tags plus metal tags shouldbe at- 3.4.2 Symbols and notation-Common symbols and ab-
tached to each bar bundle. (The regular tag is often con- breviations for placing drawings are shown in the supporting
sumed in the galvanizing process, leaving the metal tag for reference data section.
permanent identification.)Zinc-coated (galvanized) bars are Where unusual details or conditions require use of other
identified with a suffix (G) and a note stating that all bars (special) symbols or abbreviations, the drawings must pro-
marked as such are to be zinc-coated (galvanized). vide explanations of the notation applied.
2.11.3.6 Compatible tie wire and barsupports-No dis- 3.4.3 Schedules-The reinforcing steel of floors and many
similar metals nor uncoatedbars should be permitted in the other parts of structures can best be shown in tabular form
same reinforced-concreteelement with galvanized bars. Gal- commonly referred to as a schedule. A schedule is a compact
vanized bars must not be coupled to uncoated bars. Zinc- summary of all the bars complete with the number ofpieces,
coated tie wire or nonmetallic coatedtie wire should be used. shape and size, lengths, marks, grades, coating information,
Wire bar supports and support bars should be galvanized or and bendingdetails from which bar lists can be writteneasily
coated with dielectric material, or bar supports should be and readily. Although these schedules usually include the
made of dielectric material. bending details for bent bars, separate bending detail sched-
ules can be used.
PART B-RESPONSIBILITIES OF THE DETAILER 3.4.4 Coated reinforcing bars-When coated reinforcing
bars are detailed along with uncoated reinforcing bars, the
CHAPTER &PLACING DRAWINGS coated reinforcing bars must be identified in some manner,
3.1-Definition such as with a suffix (E) or (G) or with an asterisk (*), and a
Placing drawings are working drawings thatshow the note stating that allreinforcing bars marked as such areto be
number, size, length, and location of the reinforcing steel epoxy-coated or galvanized. Epoxy-coated reinforcing bars
necessary for the placement andfabrication of the material. listed with uncoated reinforcingbars in schedules or bills of
Placing drawings can comprise plans, details, elevations, materials must also be marked with (E) or (*). The designa-
schedules, material lists, and bending details. They can be tion (G)is appropriate for galvanized reinforcing bars.
prepared manuallyor by computer.
3.5-Building drawings
3.2-Scope Placing drawings, ordinarily prepared by the fabricator,
Placing drawings are intended to convey theA I E ’ S intent as show details for fabrication and for the placing of reinforcing
covered in the conb-act documents. The contract documents steel. They are not for use inconstructing formwork (except
plus any additions, such as addenda issued by the AIE (per joist forms when these are supplied by the same fabricator),
terms agreed onin the contract if issued after the contract is and consequently the only required dimensions are those
made), constitute the sole authority for information in plac- necessary for the proper location of the reinforcing steel.
ing drawings. The placing drawings must include all infor- Building dimensions are shown on the placing drawing only if
necessary to locate reinforcing steel properly, as the detailer be- Columns, and generally footings, are numbered consecu-
comes responsible for accuracy of dimensions, when given. tively or are designated by a system of coordinates on the
The placing drawings must be used with the structural draw- structural drawings. The same designations should be used
ings. on placing drawings.
Bending details can be shown on a separate drawing in- The described marking systems identify individual, rein-
stead ofon the placing drawings. forced-concrete members of a structure. Reinforcing bars
3.5.1 General requirements4n receipt of the structural must be individually identified on placing drawings. Only
drawings, the fabricator takes the following steps: bent barsare given a mark to assist theplacer in selectingthe
1. Prepares placing drawings (including bending details); proper bars for each member.The straight barsize and length
2. Submits placing drawings, if required by the project is its own identification.
specifications, to the specified authority for review and ap- 3.5.3 Schedules-Reinforcing steel in elements of a struc-
proval; ture can be drawnon placing drawings either on theplan, el-
3, Prepares bar lists (bills of materials); evation, or section, or canbe listed in aschedule. It is
4. Fabricates reinforcingsteel; acceptable practice to detail footings, columns, beams, and
5. Provides coated bars if specified; slabs in schedules.There is no standard format for schedules.
6. Provides bar supports percustomer requirements; and They take the place of adrawing, such as a beamelevation,
7. Tags, bundles, and delivers the fabricated reinforcing and must clearly indicate to the placer exactly where and
bars to the job site. how all the material listedis to be placed.
It should be noted that the general term fabricator, as used 3.5.4 Responsibility of the detailer-The responsibility of
in this document,refers to a companythat employs detailers, the detailer in preparing a placing drawing is to carry out all
estimators, and shop personnel. In this regard, it is actually instructions on the contract documents.
the detailer who performssteps 1,2, and 3, whereas the shop The A/E must furnish a clear statement of the require-
personnel do steps 4,5,6, and 7. ments. The detailer must carry out therequirements supplied
Placing drawings must show the size, shape, grade, and lo- by the A/E. The A.&, in either the project specifications or
cation of coated and uncoated bars in thestructure,including structural drawings, may not referthe detailer to an applica-
bar supports, if supplied bythe fabricator. They alsoserve as ble building code for information to use in preparing placing
the basis for preparing barlists. drawings. This information must be interpreted by the A/E
Where approval of placing drawings is required, the plac- and must be shownin the form of specific design details or
ing drawings should be submitted before reinforcing bar fab- notes for the detailer to follow.
rication is begun. 3.5.5 Beams and joists -For beams, joists, and girders, re-
For the convenience of both the contractor and fabricator, inforcing steel is usually shown in schedules. Bending details
reinforcing steel is detailed, fabricated, anddelivered by may be separate or incorporated in the schedule. The detailer
units, which generallyconsist of building components, such must show number, mark, and size of members; number, size,
as footings, walls, columns, each floor, and roof. A separate and length of straight bars; number, size, mark, and length of
placing drawing and barlist are usually madefor each com- bent bars and stirrups; spacing of stirrups; offsets of bars; lap
ponent. For small structures, all reinforcingsteel can be han- splices; bar supports; and anyother special information nec-
dled as one unit. For large projects, the contractor may desire essary for the proper fabrication and placement of the rein-
a unit, such as a single floor, to be dividedto correspond with forcing steel.
the construction schedule. Such arrangements, between the Among thespecial items that must be noted are:
contractor and fabricator, with theA/E's approval, are made 1. Overall length of bar;
before the detailing is begun. All sections should be keptas 2. Height of hook where suchdimensions are controlling;
large as practical becauseit is more economical to detail and 3. Lap splice lengths;
fabricate for large units, especially where thereis apt to be a 4. Offset dimensions, if any; and
duplication of bars. 5. Location of bar with respect to supporting members
3.5.2 Murks "slabs, joists, beams, girders, and sometimes where the bar is not dimensioned symmetrically on each side
footings that are alike on structural drawings are given the of the support.
same designation mark. Where possible, the same designa- 3.5.6 Slabs-Reinforcing steel for slabs can be shown in
tions should be used on the placing drawings as on thestruc- plan views, in a schedule, and sometimes even in section.
tural drawings.Whenmembers alike on the structural The schedule and bending details for slabs are similar to
drawings are slightly different on the placing drawings, a those for beams.
suffix letter is added to the designation to differentiate the Panels thatare exactly alike are given anidentifying letter
numbers. If some of the beams marked2B3 on the structural and reinforcing steel is shown for only one panel of each
drawing actually differ from the others, the placing drawing kind. In skewedpanels, such as for the quadrant of a circle,
would show some of the beams as 2B3 and the others as the bars are fanned out so that theyare placed at the required
2B3A. In reinforced-concrete joist floors, there can be so spacing at a specific location, usually at the midspan. Addi-
many variations from the basicjoists shown on the structural tional bars aroundopenings, if required, mustbe shown.
drawings that it is necessary to change the basicdesignations 3.5.7 Columns -Placing drawings for columns generally
(for example, from prefix J to prefix R, for rib). use aschedule form for detailing. The detailer must not only
interpret the structural drawing, but clearly convey thisinter- gardless of size or length. Standardizedmarks aresometimes
pretation to the placer. The detailer must show the quantity, used for bars occumng in the same relative position in cul-
size, and length or mark of all bars, including dowels, prin- verts.
cipal vertical bars, and ties. The detailer must also include Any system of letters and numerals is acceptable. SomeA/E's
plan sketches of typical bar arrangements for all but the sim- not only provide individual bar markings, but also indicate,
plest conditions. The detailer must clearly show length and by the mark, where the bar is placed in thestructure.
locationof lap splices, location of mechanical splices or 3.6.2 Schedules-Highway structural drawings most often
welded splices, and position of offset bars. show details of the various elements directly on the plan or
3.5.8 Dowels-Dowels shouldbe detailed, preferably, elevation. Schedules are sometimes used for piers, small
with the reinforcing steel in the element that is placed first. structures, andevenretainingwalls.Highway structural
They must be ordered with the element to be available for drawings usually include, when detailed completely, a type
placement at the propertime. of schedule that is really abill of material, sometimes segre-
3.5.9 Reinforcing steel supports-Reinforcing steel sup- gated by elements of a structure.These drawings are used by
ports specified in the contract documents, including quanti- the fabricator to prepare shop bar lists,
ties and description, can be shown on the placingdrawings. 3.6.3 Dimensions-When the drawings for highway struc-
Bar support placing layouts for typical panels are required fortures are a combination of structural and placing drawings
two-way reinforcing steel and wherever needed to clarify plac- from which the structure will be built, alldimensions must be
ing sequenceor quantities required. These layouts can be shown shown clearly. The contractor should not have to compute
on the placing drawing or given by reference to the CRS1 Man- anyneededdimensions.Drawingsmustshowthedimen-
ual of Standard Practice. Support bars, when required, must be sions of concrete protection for all reinforcing steel. For ex-
shown clearly and identified on the placing drawings. ample, they must plainly show whether the cover dimension
specified on agirder is the clear distance from the main rein-
3.6-Highway drawings forcing steel or the clear distance from the stirrups. Where
Unlike the customary practice in the field of reinforced- separate placing drawings are prepared, structural dimen-
concrete buildings, many state highway departments prepare sions may be omitted following the same practice as for
a combinationstructural and placing drawing. The combina- buildings.
tion drawing includes a list of reinforcing steel materials 3.6.4 Reinforcing steel -Drawings must show the grade,
from which the fabricator prepares bar lists. The placer uses size, spacing, splices, and location of the coated and uncoat-
the combination drawing toplace the reinforcing bars. High- ed bars in the structure. The bar schedule (combined draw-
way departments that do not use combinationdrawings fol- ing) must show the number of pieces, size, length, mark of
low the procedures of Section 3.5. bars, and bendingdetails of all bent bars.
3.6.1 Marks-Usually, each highway structure is identified Reinforcing steel for larger structures is usually detailed,
by a bridge number, street name, or a station number (each fabricated, and delivered by units for the convenience of
station being100 linear ft [30 ml) that designates itslocation both the contractor and fabricator; for example, footings,
on the project. This station identification or bridge number abutments, piers, and girders. The bar list is then similarly
must be shownon all bundle tags andshipping papers to fa- subdivided. If the structure is sufficiently large, a separate
cilitate proper distribution of reinforcing bars on delivery. drawing and barlist is made for each unit.
For small, simple structures such as culverts, slab bridges, Reinforcing bars for foundations, piers, abutments, wing
manholes, and catch basins, a station number inaddition to walls, and slabs are usually shown on plan, section, or eleva-
the title description of the structure is sufficient identifica- tion views. Reinforcing steel can be shown in the simplest
tion without dividing the structure into smaller units by fur- and clearest manner, however, the bar list must be a com-
ther marking. plete summary.
Larger structures, such as reinforced-concrete deck gird- To be certain that all of the reinforcing steel is properly
ers, I-beam bridges, continuous-type bridges,and arches, placed or positioned in a unit, a cross section is frequently re-
consist of small units thattogether make up complete
a struc- quired in additionto the plan and elevation of the unit where
ture. These units are referred to as end bents, intermediate the bars are shown.
bents, abutments, piers, retaining walls, end spans, intenne- 3.6.5 Reinforcing steel supports-Plain metal supports are
diate spans, etc., and must be designated by markings. The used widelyas a meansof securely holding reinforcing steel
construction unitsof unusually long culverts with more than in proper position whilethe concrete is being placed. Plastic
one design of barrel, for varying load conditions or, where coated or stainless legs can be specified to avoid possible
constructionjoints are required across the barrel, can be iden- rusting at points of exposure. Precast concrete blocks are
tified by section numbers. Schedules of reinforcing bars are used insome states, particularly inthe western UnitedStates.
used to divide a structure into parts enabling the fabricator to Other types of proprietary supports are available and may be
make it more convenient for the placer by delivering the bars suitable. Support bars, when furnished, should be shown
in lots as required. clearly and identified.
For highway structures, both straight and bent bars are given Where an exposed concrete surface is to receive special
an individual mark. In highway structures, such as culverts finishing treatments, such as sandblasting,bush-hammering,
and bridge spans, the arrangement of bars is the same, re- or any other removal of surface mortar, special consideration
must be given to such things as selecting bottom bar supports The minimum benddiameter of hooksshall meet the fore-
and side form spacers that will not rust or otherwise impair going provisions. The standard hooks (Table 1) were devel-
the finished surface appearance. oped such that the minimumrequirements were met, but at
Class of wire barsupport, precast concrete blocks, or other the same time the needto allow for springback infabrication
proprietary supports, and locations where each is to be em- and maintaining a policy of productionfabrication pin size
ployed, should be specified or shown in the contract docu- no smaller than the ASTM A615/A615M bend test pinsize
ments. The detailer should identify the specified types and was recognized as well. In the Table, the extra lengthof bar
show locations where each isto be used. allowed for the hook is designated A orasG and shown to the
nearest 1 in.(25 mm) for end hooks and to the nearest 114 in.
3.7-Detailing to fabricating standards (5 mm) for stirrupand tie hooks.
It is standard practice in the industry to show all bar di- Where the physicalconditions of the job are such that ei-
mensions as out-to-out and consider the bar lengths as the ther J, A, G , or H of the hook is acontrolling dimension, it
sum of all detailed dimensions, including Hooks A and G must be so noted on the drawings,schedules, and bar lists.
(see Table 1). 3.7.3 Stirrup anchorage
3.7.1 Bending-To avoid creating excessive stresses dur- 3.7.3.1 There are several permissible methodsfor stirrup
ing bending, bars must notbe bent too sharply. Controls are
anchorage. The most common is to use one of the hooks
established by specifying the minimum inside radius or in-
shown inTable 1. Types S1 to S6 in Fig. 10 illustrate not only
side diameter of bend that canbe made for each size of bar.
the usesof the two types of hooks, but also the directions in
The radius or diameter of the bend is usually expressed as a
which the hooks can be turned. In detailing the anchorage,
multiple of the nominal diameter of the bar db The ratio of
diameter of bend to diameter of bar is not constant
a because care must be taken that the ends of stirrup hooks that are
it has been foundby experience that thisratio must belarger turned outward into shallow slabs have adequate cover. If
as the bar sizeincreases. not,the hooks should be turnedinwardand this change
The minimum diameters of bend specified by AC1 3 18 brought to the A I E ’ S attention.
(318M) for reinforcing bars, measured on the inside of the 3.7.3.2 Where the free ends of stirrups cannot be tied to
bar, are: longitudinal bars, or where there are no longitudinal bars,
stirrup support bars should be specified by the AIE.*
Other than 3.7.4 Standard bar bends
Bar sizes, No. tiedstirrups Ties or stirrups
3.7.4.1 To list the various types of bent bars in a sched-
3,4,5
(10, 13, 16) 6db 4db ule, it is necessary to have diagrams of the bars with the
6,7,8 lengths of the portions of the bars designated by letters. A
6db 6db
(19,22,25) chart of such standard bar bends is shown in Fig. 10.
9, 10, 11 - 3.7.4.2 Dimensions given for Hooks A and G are the ad-
(29, 32,36) 8db
ditional lengthof bar allowed for the hook as shown inTable
1. For straight portions of the bar, the distance is measured to
the theoreticalintersection of the outside edge line extended
to the outside edge line of the adjacent straight portion, or to
The inside diameter of bendsof welded-wire fabric (plain
the pointof tangency to a curve, from which point the length
or deformed) for stirrups and ties, as specified by AC1 3 18
(318M), shall not be less than 4db for deformed wire larger of the latter is tabulated, as in Types 10 and 11 in Fig. 10.
than D4 (MD38.7) and 2db for all other wires. Bends with in- Truss bar dimensioningis special andis shown in large-scale
side diameter ofless than 8db shall not beless than 4db from detail in Fig. 10.
the nearest welded intersection. 3.7.5 Radius bending-When reinforcing bars are used
3.7.2 Hooks-AC1 318 (318M), Section 7.2 specifies min- around curvedsurfaces, such as domes or tanks, and no spe-
imum bend diameters for reinforcing bars. It also defines cial requirement is established in the contract documents,
standard hook (Section7.1) to mean the following: bars prefabricated to aradius equal or less than those inthe
a) A 180 degree bend plusan extension of at least 4db, but following table are prefabricated by the reinforcing bar fab-
not less than 2-1/2in. (60 mm), at the free end of the bar; or ricator. In the smaller sizes, the bars are sprung to fit varying
b) A 90 degree bend plus an extension of at least 12db at job conditions, such as location of splices, vertical bars, jack
the free end of the bar; or rods, window openings, and other blocked out areas in the
c) For stirrup and tie hooks only, either a 90 degree bend forms. The larger size bars, which are more difficult to spring
plus 4db extension for No. 3 , 4 , 5 (No. 10, 13, 16), and 12db
into desired position,are ordinarily employed in massive struc-
extension for No. 6, 7, and 8 (No. 19, 22, and 25), or a 135
tures where placing tolerances are correspondingly larger.
degree bend plus an extension of at least 6db at the free end
of the bar. For closed ties, defined as hoops in Chapter 21 of
AC1 3 18(318M), a 135 degree bend plus an extension of at mese decisions should be shown on the structural drawings. If not, the detailer
may suggest solutions, but only when subject to review and approvalby the A/E.”be
least 4db but notless than 3 in. (75mm). final decisionon these design problemsis the . W E ’ S responsibility.
I Obb2949 U S Y 8 4 1 5 357 W
COPYRIGHT American Concrete Institute
Licensed by Information Handling Services
~~ ~~
-~ ~
315-14 MANUAL OF CONCRETE PRACTICE
Spacers are sometimes used for maintaining the proper Spirals may be subdivided andlisted in groups by the size
pitch and alignment of the spiral and, when used, must con- of bar, diameter of spiral, pitch of spiral, and length. See the
form to the minimum requirements of a table inthe support- bar listexample in the supporting reference data section.
ing reference data section. Maximum length of spacers is
that of the spiral plus one pitch. One alternative method to CHAPTER 4-FABRICATING PRACTICE
using spacers is to ship the spiral as a compressedcoil and tie STANDARDS
it in place in the field. The project specifications or subcon- 4.1-Fabrication
A fabricated reinforcing baris any deformedor plain steel
tract agreements should be writtenclearly to cover the sup-
bar for concrete reinforcing steel, conforming to ASTM
ply of spacers or field tying of the spiral reinforcement.
specifications A 615lA 615M, A 616lA 616M, A 617lA
The height of one-piece assembledspirals for fabrication 617M, or A 706lA706M, which is cut to a specified length
and shipping is limited to 25 ft (7500 mm) unless special or cut and bent to a specified length and configuration.
handling arrangements are made.For greater heights, spirals Welded-plain- and deformed-wire fabric meeting ASTM A
must be field spliced by lapping or welding. Spacers can be 185 or A 497, respectively, and spirals formed from cold
provided. Spirals are also used in piles, but these do not fall drawn wire conforming to ASTM A 82 or A 496, are also
within AC1 3 18 (3 18M) definitionof a spiral and are usually considered concrete reinforcement withinthis definition.
made of light wire andrelatively large pitch. Other materials used as concrete remforcement and processes
3.7.8.2 Spiral derails-Unless otherwise specifically other than cutting and bending are not includedthisindefinition.
provided, spirals should be detailed as extending from the
floor level or top of footing or pedestal to the level of the 4.2-Extras
lowest horizontal reinforcement in the slab, drop panel, or Reinforcing bars are sold on the basis of their theoretical
i beam above. In column
a with
a capital, the
spiral shall ex- weights(mass)computed from thevaluesgiven in the
tend to the plane at which thediameter or width ofthe capital ASTM specifications,as calculated from the detailed placing
is twice that of the column. See Detail 2, Fig. 4. If the struc- drawings, lists, or purchase orders. Indeterminingthe
tural drawings require lateral reinforcement in the column weight (mass) of a bent bar,it is standardpractice in the in-
between the top ofthe main spiral and thefloor level above, dustry to showall bar dimensions as out-to-out and consider
it should be providedby a stub spiral (short sectionof spiral) the bar lengths requiredfor fabrication as the sum of all de-
tailed dimensions, including Hooks A and G (seeFig. 10).
or by circular column ties. Where stub spirals are used, they
Charges for extras can be addedto the baseprice per hun-
must be attached to the main spiral for shipment or fully
dredweight. In this event, the principal extra charges are:
identified by mark numbers.
a) Size extras-vary as bar size changes;
3.7.9 Dowels-Dowels will be provided by the detailer as
b) Gradeextras-are added tosome grades ofbars; and
specified in the contractdocuments for the following:
c) Bending extras-are added for all shop bending.
1. Columnfootings to columns;
Bending extra charges are separated into three classes as
2. Wall footings to walls;
follows:
3. Wall intersections;
1.Light bending-All No. 3 (No. 10)bars, stirrups,
4.Stairs to walls;
hoops, supplementary ties, and ties, and all bars No. 4
5. Constructionjoints in footings, walls, and slabs;
through 18 (No. 13 through 57) that are bent at more
6. Columns at floor levels where the vertical reinforce- than six points onein plane, or bars that are
bent in more
ment cannot beoffset bent and extended; and than one plane (unless special bending, see below), all
7. Other places where itis not possible or desirable to ex- one-plane radius bending with more thanone radius in
tend the reinforcingsteel continuously through ajoint. any bar (three maximum), or a combination of radius
Dowels, preferably, should be detailed with that portion of and other type bending inone plane (radius bending be-
the structure where concrete is placed first. They should al- ing defined as all bends having a radius of 12 in. [300
ways be ordered with that portion. mm] or more to inside of bar);
3.7.10 Bar lisrs-Bar lists used in cutting, bending, tag- 2. Heavy bending-Bar sizes No. 4 through 18 (No. 13
ging, shipping, and invoicing are prepared from placing through 57) that are bent at not more than six pointsin
drawings. Bars are grouped separately on the bar listas fol- one plane (unless classified as light bending or special
lows: bending) and single radius bending; and
1. Straight; 3. Special bending-All bending to special tolerances
2. Bent, including stirrups and ties; and (tolerances closer than those shown inFig. 8 and 9), all
3. Spirals. radius bending in morethan one plane,all multiple
The grade of reinforcing steelfor all items must be shown. plane bending containing one or more radius bends, and
Straight bars are usually grouped according to size, with all bending for precast units.
the largest size first and those of the same size listed in the d) Services and special fabrication-Extra charges for ser-
order of their length with thelongest bar first. vices and specialfabrication may be computed individually
Bent bars, stirrups, and ties are usually listed in a similar to suit conditions for each product on items such as:
manner. 1. Detailing, listing, or both;
STD A C 1 315-ENGL
COPYRIGHT American Concrete Institute
Licensed by Information Handling Services
315-16 PRACTICE
CONCRETE
OFMANUAL
mats more than 4 ft (1200 mm) thick that suppliers furnish commonly is designated by size and spacing combinationsto
supports for such purposes only by special arrangement. the nearest 1/2 in. (10 mm) for spacing. If the structural
drawing specifically shows the positions of the first bar per
CHAPTER 6“COMPUTER-ASSISTED DETAILING panel, or for a given lengthshows the total number of bars,
6.1-Use of computers in detailing no problem is created-the detailer simply follows the spe-
The computer system for detailing reinforcing bars has cific requirements.Therefore, design notes, suchas 20-No. 4
been devisedto use digital computers and other data process-
(20-No. 13) in a designatedlength, or No. 4 at 12 (No. 13 at
ing equipment to speed up the preparation of placing draw-
ings, to facilitate neater and morecompact drawings, and to 300 mm) with location ofthe starting bar shown, requires no
relieve the detailer of tedious and time-consumingcomputa- further interpretation to complete a placing drawing or to
tions that can be performedefficiently by a computer. calculate total number ofbars required. When the structural
Computer-aided drafting, commonly called CAD, is also drawing shows No. 4 at 12 (No. 13 at 300 mm) with no fur-
being used in thedrawing and detailing of placing drawings. ther instructions in the general notes or in the project speci-
This system gives the detailer speed, accuracy, andan expe- fications, the procedures shown in Fig. 19 (in Part C ) are
ditious way of making changes when necessary. recommended.
-
SIZWSPACING ing steel.
Especially in slabs and walls designedfor a given areaof Project drawings-The drawings which, along with project
reinforcing steel per running foot, required reinforcement specifications, complete the descriptive informationfor con-
structing the work required or referred to in the contract docu- American Railway Engineering and Maintenance-of-Way
ments. Association
Project specifications-The written documents that spec- Manual for Railway Engineering,Chapter 8, Concrete Struc-
ify requirements for a project in accordance with the service tures and Foundations, 1996
parametersandother specific criteria established by the American Society for Testing andMaterials
owner. A 82-97a Standard Specification for Steel Wire, Plain,
Schedule"Tab1e on placing drawings to give the size, for Concrete Reinforcement
shape, and arrangement of similar items. A 185-97 Standard Specification for Steel Welded
Sleeve--A tube that encloses such items as a bar, dowel, Wire Fabric, Plain, for Concrete
or anchor bolt. Reinforcement
S p l i c d o n n e c t i o n of one reinforcing bar to another by A 496-97a Standard Specification for Steel Wire,
lapping, mechanical coupling or welding; the lap between Deformed, for Concrete Reinforcement
sheets or rolls of welded-wirefabric. A 497-97 Standard Specification for Steel Welded
Wire Fabric, Deformed, for Concrete
Structural drawings-Drawings that show all framing
plans, sections, details, and elevations required to construct Reinforcement
A 6151 Standard Specification for Deformed and
the work. For reinforced-concrete structures, they include
the sizes and general arrangement of all the reinforcement A 6 15M-96a Plain Billet-Steel Barsfor Concrete
from which the fabricator prepares the placing drawings. Reinforcement
A 6161 Standard Specification for Rail-Steel
Welded splice-A means of joining two reinforcing bars
A 616M-96a Deformed and Plain Bars for Concrete
by electric arc welding.Reinforcingbar may belapped, butt-
Reinforcement
ed, or joined with splice plates or angles.
A 6171 Standard Specification for Axle-Steel
Work-The entire construction, or separately indentifi- A 617M-96a Deformed andPlain Bars for Concrete
able parts thereof, which are required to be furnished under Reinforcement
the contract documents.Work isthe result of performing ser- A 7061 Standard Specification for Low-Alloy
vices, furnishng labor, and furnishing and incorporatingma- A 706M-96b Steel Deformed and Plain Barsfor Concrete
terials and equipment into the construction, as required by Reinforcement
the contract documents. A 7671 Standard Specification for Zinc-Coated
A 767M-97 (Galvanized) Steel Bars for Concrete
CHAPTER 9"REFERENCES Reinforcement
9.1-Referenced standards A 7751 Standard Specification for Epoxy-Coated
The documents of the various organizations referred to in
A 775M-97 Reinforcing Steel Bars
this standard are listed below with their serial designation,
including year of adoption or revision. The documents listed American Society of Civil Engineers
were the latest edition at the time this standard was revised. ASCE 7-95 Minimum Design Loads for Buildings and
Because some of these documents are revised frequently, Other Structures
generallyinminor detail only, the user of thisstandard American Welding Society
should check directly with the sponsoring group if it is de- D1.4-98 Structural Welding Code-Reinforcing
sired to refer to the latest revision. Steel
Association for Information and Image Management
American Association of State Highway and Transporta-
Modem Drafting Techniques for Quality Microreproductions
fion OfJicìals
AASHTO Standard Specifications for Highway Bridges, Building Seismic Safety Council
16th Edition 1996 NEHRP-97NEHRPRecommended Provisions for
Seismic Regulations for New Buildings
American Concrete Institute Concrete Reinforcing Steel Institute
117-90 Standard Tolerances for Concrete Construction Manual of Standard Practice, 26th Edition, 2nd Printing, 1998
and Materials Reinforcement Anchorages and Splices, 4th Edition 1997
3 18-95 Building Code Requirements for Structural
International Conference of Building Oflcials
Concrete
Uniform Building Code, 1997
3 1 SM-95 Building Code Requirements for Structural
Concrete (Metric) These publications can be obtained from the following
343R-95 Analysis and Designof Reinforced Concrete organizations:
Bridge Structures American Associationof State Highway andTransportation
349-97 Code Requirements for Nuclear Safety Related Officials
Concrete Structures 444 North Capitol Street, N.W., Suite 249
359-92 Washington, D.C. 20001
Code for Concrete Reactor Vessels and Containments
AC1STANDARD HOOK
( T I L T FROM VERTICAL IF NECESSARY
TO MAINTAIN 3.{[20mn]CLEARANCE)
SEC. A-A
1 [ 40ml COVER
X=SPAC ING
TABULATED
SFC. 8 -8
END SPAN, SIMPLYSUPPORTED
~ 0.3L OR 0 . 3 L 1-- O. 3 1 OR 0 . 3 L l
GREATER GREATER
X=SPAC ING
4 L =CLEA'RSPAN
INTERIORSPAN, CONTINUOUS
TABUL ATE0
SLAB TH I CKNESS
SEC. c -c
3(c MIN. 6"[15Omn]. UNLESS OTyERWISE SPECIFIED 6 Y THE ARCHITECT/ENGINEER
Note: Unless noted otherwise, tables and figures are based on AC1 318 (318M). Concrete cover shown is minimum and should be increased for more severe
conditions. Except forsingle span slabs where top steel is unlikely to receive constructiontraffic, top bars lighter than No. 4 at 12 in. (No. 13 at 300 mm)are not rec-
ommended. For a discussion of bar support spacing, see Section 5.4 of this standard. See also Chapter 12 of AC1 318 (318M). Barcutoff details must be verified
to provide required development of reinforcement.
11," 40mnjC~R-J
UNbdR ST I RRUPS
. A-
V
NOWPERIMETER BEAM WITH OPEN
STIRRUPS
\ ,-t%mlb
O. 3~ Q O. 3L1
GRtATtR k
0.3L W 0.3L1-
GREATER 4
I4 0 m )
2 "' [ 5 0 m 1
I
A
L-
Li ~
CLEA v
NON-PERIMETER BEAM WITH CLOSED STIRRUPS
I ,I,{
7 [ 4 mn
t . 3 L or 0.3Lq
GREATER
AT LEAST
1
I
OF POSITIVE MOMENT REINFORCEMENT
CONTINUOUS OR CLASSATENSION
p . 3 L or 0 . 3 L T
GREATER
SPLICED
C?
i
I 4 1 I
L, IR f k L s J
L=CLEARSPAN 'J
C
P E R " BEAM
AC1
STANDARD HOOK (BAR SIZE SAME AS SMALLER
BOTTOM
BAR I F HOOK WILL F I T : OTHERWISE
USE TWO
SMALLER BARS TO PROVIDE SAME AREA OF S T E E L )
ON
AT LEAST ONE
BOTTOM JOIST WIDTH
SINGLE SPAN JOIST CONSTRUCTlON SEC. A-A
AT LEAST ONE
BOTTOM
BAR
CONTINUOUS
OR CLASS A TENSION SPLICE
D I S T . R I B AS NOTED G SYMMETRICAL
\ 4"[100mnlMIN. /;BOUT E
TEMPERATURE
O. 3L OR 0.3L1 0.3L OR 0.3L1. REINFORCEMENT
" GREATER
OP SLAB
r
I
1
t
1iST '
DEPTH
BEVEL USED F 0
COMPUTATIONS
_J j
J- jl7~7'52~7-n
20" OR 30"
A S NOTED
L1
B J J O I S T WIDT
INTERIOR SPAN JOIST CONSTRUCTION SFC. ß -R
AT LEAST ONE
BOTTOM BAR
CONT ' I NUOUS
OR CLASS A TENS ION SPL ICE
TEMPERATURE DIST.RIB AS
AC1
STANOARD HOOK ON
AT LEAST ONE BOTTOMBAR
END SPAN JOIST CONSTRUCTION S C . c -c
Note:: See also Chapter 12 and Section 7.13 of AC1 318 (318M). Bar cutoff details must be veriiied to provide required development of reinforcement.
@kiS{RS D
@ M Il ANKIBAR
1.S T EYR S
W
DISTANCE
DIISTANCE LOWER BAR 1 'ja" [ 4Omnl
1 *2" 14Omn)
BAR PPER LOWER BAR
LOYER BAR BAR UPPER
s E C T I ON A'-A' UPPER BAR
SECT ION &B'
SECT I O N BLB1 PREFERRED ARRANGEUENT
ACCEPTABLE ARRANGEMENT FOR
MAXIWU NUMBER OF BARS
L A PS P L I C E
IF THIS OFFSET
T I E SIZE AS
AEOUIRED BY
STRUCTURAL OWCS
-
SECTION A-A
li il
S E C T I O N B-B
o3 D E T A I LT Y P I C A L
EDGE
COLUMN
WITH SPANDREL BEAM
QOETAIL
FULLYDWNTLAP
SPLICES WITH NO OFFSET
FULL WENT CAPACITY SPLICE
Note: Where column size e v e is unchanged from below, "upside down" offset bars are effective in maintainingfull moment capacity
at end of column. In US. practlce, this unusual detailis rare, and should be fully illustrated on structural drawins to avoid misunder-
standings, wheneverits use is deemednecessary. For maximum tie spacing, see table in Supporting Referencetata section.
r
LQNGtTUDINAL RFINF0FU;EMENTe TOP ANDBOTTOM
;;":"F9 +
THE F M F A E OF M E COLUMN CORE. PAOVIOING MIN.
FOR TENSION PER SECTION
C%OR RE55 ON PER SECTION 1 2 . 3 AC1 316[318M]
MINIMUM ASWJObW d / f y . 3Jfb
MAX I MUM p50.025
bW d / f y
[ 1 . 4 b w W f y . 6 bw d / ( 4 f y ) ]
EXTEND ta,
INTO CORE
ENGINEER
MUST PROVIDE
DIMENSIONS h24d MAXIMUM HOOP/TIE SPACINGS
f l r P * S l . S 2 HOOP
AND STIRRUP OEPTH " AND I N LENGTH S 1 SPACING HOOPS
I FOR
SPACING. ANCHORAGE LENGTH.
CUT-OFF %/41 Bdb OF SMALLEST BARI 24db
POINTS OF DISCONTINUOUS BARS. M. OR OF HOOP. OR 121N.[300mn]
Rdh IF LESS THEN ACROSS
COLUMN CORE *AT LAP SPC[CES. SPACING OF
HOOPS
SU/4 BUTNOTGREATERTHAN 4 " [ lOOmnj
I N LENGTH S 2 . SPACING STRIRRUPS
eY/2
ALTERNATE S I D E OF CROSSTIE
PLACE 90"
CROSSTIE 90' HOOKS HOOKS
ON SLAB-CONFINE
SPANDREL
EXCEPT
AT SIDE (ANCHORED SLAB
EARS
NOTSHOWN)
OINT HOOPS
MAY BE SPACED AT "2Sh"
ONLY WITHIN OR THE
DEPTH OF THE SHALLOWEST
CENTER HALF OF EAM WHEN BEAMS WITHWIDTH >'r4
CLEAR COLUMN IMES THE WIDTH OF THE COLUMN
FRAME
NT0 HEIGHT FOUR THE S l D E S OF A COLUMN.
db. 3 " [ 7 5 m n ] M I N .
6db 3"[75m]M1N.
Sh = HOOP
AND SUPPLEMENTARY CROSSTIESPACING.
NOTTO EXCEED BS/4 OR 4 " [ 1 0 0 ~ 1 ~ 1 l
SO =COLUMN T I E SPACING. NOT TO EXCEED 8db
DF VERTICALS. 24db OF TIES. Bs/2 DR 12"[300mn]
St = S E E AC1 2 1 . 4 . 4 . 6
Bs =SMALLER DIMENSION OF COLUMN CROSS SECTION
10 LARGEST COLUMN DIMENS ION, BUT NOT LESS
THAN ONE-SIXTH CLEAR HEIGHT. OR 1 8 u [ 5 0 0 m n ]
COLUMN HOOPS
2'9" [ 6 0 m ] CL
TOEND OF -
HOOKS ON J O I N T HOOP
BEAM BARS
J
FX
-4
X
BEAM HOOPS
COLUMN HOOPS”
Z1/2/1 [ 6 0 m ] CL
T O END OF-
HOOKS ON
B E A MB A R S
F
X
7 X
*JOINT HOOPS
SPANDREL
BEAM HOOPS 4
J O I N T HOOPSk
2!+” [ 60mmj CL
T O - E N D OF-“c
HOOKS ON
B E A MB A R S
Y Y
t 3
COLUMN HOOPS
BEAM BARS
7 X
*J O I NT HOOPS
BEAM HOOPS
*JOINT HOOPS MAY BE USED ONLY W I T H I N
BEAM WIDTH WHERE BEAM IS NARROWER
THAN COL., USE TO REPLACE I N T E R I O R
T I E S ONLY.
V E R T I C A L S E C T I O N Y-Y
PLAN S E C T I O N X-X
Fig. 7(c}-Typical seismic-resistant joint details-Case 3: For regions of moderate seismic risk. Interior beam wider than
column: spandrel beam is same width as column.
STRAIGHT
I- -,
I
2
@ L U ,
1 = *1/2 in. (15 mm) for bar sizeNo. 3,4, and 5(No. 10, 13, and 16)
(gross length c 12 ft. O in. (3650 mm))
o 2
DEVIATION+
1 = ilin. (25 mm) for bar size No. 3, 4, and 5 (No. 10, 13, and 16)
(gross length L 12 ft. O in. (3650 mm))
1 = i 1 in. (25 mm) for bar sizeNo. 6, 7, and 8 (No. 19,22, and 25)
2 = i 1 in. (25 mm)
Note: All tolerances single plane and as shown.
3 = +O, -1/2 in. (15 mm) Dimensions onthis line are to be within tolerance shown but are not to dif-
4 = i1/2 in. (15 mm) feffrom the opposite parallel dimension morethan 112 in. (15mm).
5 = i 1 / 2 in. (15 mm) for diameterI 3 0 in. (760 mm) Angular deviation-maximum * 2-1/2degrees or + 112 in.m (40 mdm),
by!;ot less than 1/2 in. (15mm) on all90 degree hooks and bends.
5 = i 1 in. (25 mm) for diameter> 30 in. (760mm)
6 = f 1. W O x "O"dimension, 2 i 2 in. (50mm) minimum arc or bar length, the bar may be shipped;;trai ht
~ -~
If amlication of Dositive toleranceto TvDe 9 results in a chord lenoth 2 the
~ ~~
~ ~
Tolerances for Types Sl-S6,S l l , Tl-T3, ?&T9 apply to bar size No. 3
through 8 (No. 10 through 25)inclusive only.
Fig. 8-Standard fabricating tolerances for bar sizes No. 3 through 11 (No. 10 through 36).
i*
(ISOMETRIC
VIEW)
@ y-”
TOLERANCE SYMBOLS
1 = *1/2 in. (I5 mm) for bar sizeNo. 3,4,and 5 (No. 1O, 13, and 16:
(gross length c 12 ft. O in. (3650mm))
1 = *1 in. (25mm) for bar size No. 3, 4, and 5 (No. 10, 13,and 16)
(gross length2 12 ft. O in. (3650mm))
1 = 21 in. (25 mm) for bar size No. 6,7 , and 8 (No. 19, 22, and 25)
Note: All tolerances single plane and as shown.
2 = 1 in. (25mm) ‘Dimensions on this line are to be within tolerance shown but are not to
3 = +O, -112 in.(15mm) differ from the opposite parallel dimension more than 1/2 in. (15 mm).
4 = *V2 in. (15mm) Angular deviation-maximum * 2-1/2 degrees or * 1/2 in./ft (40 mrdm),
by!?ot less than 112 in. (15 mm) on all 90 degree hooks and bends.
5 = +1/2 in. (15 mm) for diameter S 30 in. (760mm) If application of positive tolerance to Type 9 results in a chord length 2
5 = *1 in. (25 mm) for diameter > 30 in. (760 mm) the arc or bar len th, the bar may be shipped strai ht.
Tolerances forlypes S1-SB, S l l , T l - T 3 ,Te-79 apply to bar size No.
6 = 1.5% x “ O dimension, 2 2 2 in. (50mm) minimum 3 through 8 (No.10 through25)inclusive only.
Fig. 8 (cont.)-Standard fabricating tolerancesfor bar sizesNo. 3 through I l (No. 10 through 36).
STRAIQKT , LL
c 8
1 I- I
SEE NOTE
ANGULAR
o DEVIATION* *
.-
TOLERANCE SYMBOLS
tn
Symbol No. 14 (No. 43) No. 18 (No. 57)
dimension, 2
Fig. 9-Standard fabricating tolerances for barsizes No. 14 and 18 (No. 43 and 57).
@ 'W'A D
I' O
B 10 O
1
Notes:
1. All dimensions are out-to-out of bar except "A" and "G" on standard 180
o U C D
B LTC
C [~~ A
[c]
D D W
o t B
G
Where slope differs from
45" dimensions,H' " and
'K"must be shown.
STANDARD STANOARD
HOOK ( T Y P . 1 r H O O K (TYP. 1
LONGITUDINAL
LONGITUOINAL BAR REOUIRED
HOOKS AT BAR REOUIRED
AT HOOKS AND
""_ 10.1 7dbfy/Jf7 1
AT EACH BEND
( S E C T I O N1 2 . 1 3 . 3 1 AT EACH BEND
MID-HEIGHT 12.13.3) [SECTION OF
MEMBER. h/.?
m
SAME 2 OPTIONS
AS FOR SINGLE
USTIRRUPS
? ( S E C T I O N1 2 . 1 3 . 3 )
SAME 2OPTIONS
S A M 2 OPTIONS A S FOR SINGLE
AS FOR S INGLE U STIRRUPS
h U STIRRUPS BARS LONGITUDINAL
REOUIREO WITH
~ .. _. - ~
ALLOPTIONS
hJ
T I
J m .o c,
( S E C T I O N1 2 . 1 3 . 3 )
MORE D I F F I C U L T FOR P L A C I N G MOST D I F F I C U L T FOR PLACING AND F A B R I C A T I N G
RECOMMENDED E F F E C T I V ES I N G L E
CLOSED STIRRUPS-TORSION AND SHEAR
ALTERNATE FOR
nF DEEP
CLASS B
I N T E R I O R BEAMS
<
,
-
4
m- 7
e * ' .,
I
6 BAR ~~
OTE 1 ( T Y P I C A L )
SPACING < 6 " [ 1 5 0 m ] SPACING > 6 " [ 1 5 O m ]
TE 4 (TYPICAL 1
1 2 EAR
6"MAX [ 1 5 0 m n j
NOTE 2
1 4 BAR [TYPICAL 1
16 BAR S I M I L A R
(4-AR BUNDLES EA CMINERI
Notes: employing special large vertical bars, bundled vertical bars, staggered splices,
1. Alternate osition of hooks in placing successive sets of ties. or specially grouped vertical bars as shown.
2. Minimum k p shall be 12 in. (300 mm). 7. Bars must be securely supported to prevent displacement suring concreting.
3. B indicates bundled bars. Bundlesshall not exceed four bars. 8. Tie patterns shown may accomodate additional single bars between tied
4. Eliminationof tie for center bar in groupsof three limits clear spacing to be groups provided clear spaces between bars do not exceed 6 in. (150 mm).
6 in. (150 mm)maximum. Unless otherwise specified, bars should be so 9. Minimum cover to ties, 11/2 in. (40 mm) for nonprestressedcast-in-place
grouped. concrete.
5. Note to ArchitecVEngineer: Accepted practice requires that design draw- 10. Spaces between corner bars and interior groups of three and between
ings show all requirements for splicing column verticals. that is. type of splice, interior groups may vary to accomodate average spacing > 6 in. (150 mm).
lap length if lapped, location in elevation, and layout incross section. 11. For average spacing c 6 in. (150 mm), one untied bar may be located
6. Noteto Detailer: Dowelerectiondetails are required foranydesign between eachtied group of three and between a tied group and a corner bar.
Fig. 13-Standard column ties upplicable for either preassembled cages or field erection.
- (NOTE 7 1
10 OR 1 4 B A 6
(NOTE 7 1 SPACING>6v [150mn]
9
SEE NOTE 1
(NOTE 7)
2 4 BARS
Fig, l u t a n d a r d column ties applicable for either preassembled cages or jìeld erection, special-shaped cohmns, and
columns with barsin two faces only.
LOADS
OUTSIDE LOADEDONLY
W I N S I D E OR O U T S I D EL O A D E D
T Y P I C A L CORNER D E T A I L S
I LIWlD LlMJlD
ETC. ) ETC. I
NO CONF I NEMENT
'.I
I N E F F E C T I V E CLOSED S T I R R U PS T Y L E S WHICH S H O W E D
PREMATURE
FAILURE
~
Notes: These styles are NOT RECOMMENDED for those members to be subjected to high torsional stress. Note lack of confine-
ment when compared with similar members with confinement shown in Fig.
12.
Fig. 16-Not recommended; closed stirrup styles considered ineffectivefor members subjected to high
torsion stress (based on tests by Collins and Mitchell).
CONSECUTIVECROSSTIES
MUST
HAVE THEIR 90-DEGREE
HOOKS ON OPPOSITE SIDES OF
COLUMN
I I
I l I ' \
"
X X
1- I
X MUST
NOT
EXCEED 14 l N C H E S [ 3 5 0 ~ ]
6db. 3"[75mn]MIN.
z
Fig. 17-Typical seismic resistant details: transverse reinforcement in columns.
I d . OR WHERE
HOOKED. ldh i d . OR WHERE H O O K E D * l d h
OVERLAiPING
HOOPS I
.NF.
b825
'SINGLE HOOPS WITH
TYPICAL COLUMN
AND STRUCTURAL WALL CROSST[ES*
CONTINUOUS SPACINGS
FULL L, I FULL SPACE
I 1
o ........ ........
FULL
SPACINGS
CONTINUOUS
SPACE
FULL 1 , I F U L L SPACE
I -
o I I I
@ EDGE B A R % & ] 1. . . . . . . . . . . . . . . . . . .
MASONRY WALL
F U L L SPACE- 1 I - CONTINUOUS
SPACINGS
FULL L
I
............................ I
F U L L SPACE-
I I]
I CONTINUOUS
SPACINGS
FULL
1
M
2 ”I N
[ 5.0 m n ] C L E A R
II
-’
“-CORF~ATED METALDECK
AS IN-PLACE FORM”
FULL SPACE ( M A X I - CONTINUOUS
SPACINGS
FULL
Fig. 19(a)--Location ofjrst bar designatedonly by size and spacing, one-way slabmain flexural reinforcing bars,
o
F U L L SPACE O N T I N OUS FULL SPACINGS
I-
l l I
FULLSPACE
h I
. . . . . { (. . . . . . . . . . .
I L
MASONRY
WALL
4
t
- SPACINGS
CONTINUOUS
FULL
II I "CORRUGATED
AS "IN-PLACE
METAL DECK
FORM" I
Fig. 19(b)-hcation of first bar designated only by size and spacing, one-way slab shrinkage and temperature reinforcing
bars.
SPECIFIED
-
_ L-
,
i~I...i.
7
. FULL
SPACE
(MAX. f
VE
-
A&&A& UNcER
OPEN I NG
-
. .
e
e
-OVER OR
e
e
VERTICAL BAR
e . .
e
e . .
FULL
TYPICAL SPACINGS b m
I
@ ml
VERTICAL
SECTIONS-WALLS A T FLOORS N
I
o
:I :I- J
m
VERTICALSECTIONS-WALLS AT FOOTINGS
Fig. 19(c)--location of$rst bar designated only by size and spacing, reinforcing bars in walls.
I
1
I-
l
i-
l
I
MANUAL OF CONCRETE PRACTICE
I I
1
i
I
I
l
-
."
*
50mn L.
l I
I l
I I
I I
1 I
t
I I
1 I
I l
I- t "
l l
STANDARD SPACINGUNLESSOTHERWISEDESIGNATED
EXCEPT
FOR
BARS PARALLEL TO SLAB EDGES. SPACf ALL REOUIREOBARS
UNIFORMLY
ACROSS
COLUMN OR MIDDLE STRIPS STARTIMCAT ONE-HALF
SPACING FROM
EDGES DF COLUMN STRIPS. MIDDLE STRIPS, OR
SPANDREL
BEAMS.
SPACE
THE FIRST BARS PARALLEL TO SLAB EDGES WITH MINIMUM
2 IN. [SOmn] CLEAR COVER;.WIENSTRUCTURALDRAWING DES IGNATES SEPARATEL.Y 'A
NUMBER OF BARSTO BE UNIFORMLYSPACEDAND A NUMBER
TO BE
CONCENTRATED A ~ D U TTHE COLUMN CENTERLINE. START THE UNIFORMLY
SPACEDBARSATONE-HALÇ SPACING FROM
THE
EDGES
OFTHE
COLUMN STRIP
Fig. 19(d)--location ofjìrst bar designatedonly by size and spacing, two-way slabreinforcing bars.
Detailing Hook
Dimension A orG
' +
dI
4d or L
T
A
4
d a
L U
a
O
-
CJ
9O0 v I
RECOMMENDED ENDHOOKS
All grades
D = Finished bend diameters
'Finished bend diameters include "spring back" effect when bars straighten out slightly after being bent and are
slightly larger than minimum bend diameters in3.7.2.
i
A or G
d--c
U
D -
Q lo
I
Beam goo 135" I d'
I-
135'
STlRRl IP
(TIES SIMI LAR)
STIRRUP AND TIEHO 3K DIMENSIONS
ALL GRA >ES
Bar size,No. D,' in. (mm) 90 degree hook 135 degree hook
Hook A or G, ft-in. (mm) Hook A or G , ft-in. (mm) H approx., ft-in. (mm)
3 (10) 1 1/2 (40) 4 (105) 4 (105) 2 1/2 (65)
4 (13) 2 (50) 4 1/2 (115) 4 1/2 (115) 3 (80)
5 (16) 2 1/2(65) 6 (155) 5 1/2 (140) 3 3/4 (95)
6 (19) 4 1/2 (115) 8 (205) 1-0 (305)
4 1/2 (115)
7 (22) 5 1/4 (135) 9 (230) 1-2 (355)
5 1/4 (135)
8 (25) 6 (155) O) 6 (155) 10 1/2 (270) 1-4 (41
'Finished bend diameters include 'spring back" effect when bars straightenout slightly after being bent and are slightly larger than minimum bend diameters in
3.7.2.