SITE TESTING OF

CABLES TERMINATION

JMPS J.M.PANG & SEAH (PTE) LTD SITE TESTING OF CABLE TERMINATION
Site High Voltage Testing of Cables

• DC or AC 50 hertz or AC VLF test.


test It is a
pass/fail test.

• Quantitative test includes measurement


of dissipation factor or tangent delta

JMPS J.M.PANG & SEAH (PTE) LTD SITE TESTING OF CABLE TERMINATION - 1
DC Hi-pot Test On Cables
Micro
Ampere

It = I1+I2+I3
I1 - leakage current across the cable insulator
I2 - depends on the capacitance of the cable
I3 - p
polarization current

I2
It
I1

I3
time/minutes
5 10 15

JMPS J.M.PANG & SEAH (PTE) LTD SITE TESTING OF CABLE TERMINATION - 2
Advantages of DC test
• The test set is small and portable.

Disadvantages of DC test
• DC breakdown voltage very much higher than
equivalent AC breakdown voltage for same fault.

• DC voltage distribution very different from AC voltage


in the insulation.

JMPS J.M.PANG & SEAH (PTE) LTD SITE TESTING OF CABLE TERMINATION - 3
AC at 50 Hz versus AC at 0
0.1
1 Hz

The voltage stress distribution for


frequencies as low as 0.1 0 1 hertz is not
significantly different from that at 50 hertz.

JMPS J.M.PANG & SEAH (PTE) LTD SITE TESTING OF CABLE TERMINATION - 4
Series resonant test set

R
L

Vout C
AC
Mains
VE C - capacitance of the test object
L - variable inductance

regulator excitation
transformer

Block Diagram of AC 50Hz Test Set


JMPS J.M.PANG & SEAH (PTE) LTD SITE TESTING OF CABLE TERMINATION - 5
Series Resonant Testing
• Th
The excitation
i i transformer
f supplies
li the
h power to the
h high
hi h voltage
l
circuit consisting of the variable inductance and the test object.

• Operation starts by first adjusting the variable inductance to match


the capacitance of the test object. This tunes the system to
resonance and is normally done at low voltage.
voltage

g can be increased to the required


• The test voltage q value byy the
voltage regulator and testing proceeds as in a conventional test
transformer system.

• Able to provide very high test voltage to a test object having very
high capacitance from a low voltage, low kVA source.

JMPS J.M.PANG & SEAH (PTE) LTD SITE TESTING OF CABLE TERMINATION - 6
Equation
VE
Vout =
(ωRC ) 2 + (1 − ω 2 LC ) 2

at resonance, ω 2 LC = 1

VE
h Vout =
then
ωRC

Vout ωL
= = Q, where Q is the quality factor of the circuit
VE R

JMPS J.M.PANG & SEAH (PTE) LTD SITE TESTING OF CABLE TERMIN8TION - 7
IEEE P400.2-2004 for AC VLF
Site Testing of Cables

• guideline for field testing of shielded power cable


systems using very low frequency.
• Sine wave, 0.1 hertz

• 15 minutes
i t att 2 to
t 3 times
ti phase
h t neutral
to t l voltage
lt

• p
pass/fail test

JMPS J.M.PANG & SEAH (PTE) LTD SITE TESTING OF CABLE TERMIN8TION - 8
Variable HV Polarity
Voltage Transformer Switch

50 Hz
HV
230 V
VLF

Sinusoidal
Rate-of-Rise Rectifier and
Discharge Network

Functional Schematic of the VLF System

JMPS J.M.PANG & SEAH (PTE) LTD SITE TESTING OF CABLE TERMIN8TION - 9
Dissipation Factor
- Equivalent Circuit for Cable Insulation
I
IR IC IR
V
tan δ =
R C IC
⎛ 1 ⎞
=V
R ⎜⎝ VωC ⎟⎠
IC I
1
=
RωC
δ

IR
JMPS J.M.PANG & SEAH (PTE) LTD SITE TESTING OF CABLE TERMIN8TION - 10
Dissipation Factor or
Tangent Delta Measurement

• It is the measure of the quality of the insulation.

• It is measured in the normal AC operating mode


of the cable.

• It is a more sensitive indicator of abnormal cable


insulation.

JMPS J.M.PANG & SEAH (PTE) LTD SITE TESTING OF CABLE TERMIN8TION - 11
CRE CBE
CRB
Red
phase
Bl
Blue
phase
CRE , CYE , CBE - capacitance
it b t
between
conductor to earth.

CRY, CYB , CRB – capacitance between


CRY CYB conductors.
Yellow
phase

CYE

Dissipation Factor Equivalent Circuit of the Electrical


Insulation of Multi Core Cables
JMPS J.M.PANG & SEAH (PTE) LTD SITE TESTING OF CABLE TERMIN8TION - 12
Dissipation Factor in %

85°C

25°C

Voltage / kV

Dissipation Factor -Temperature Behavior

JMPS J.M.PANG & SEAH (PTE) LTD SITE TESTING OF CABLE TERMIN8TION - 13
Dissipation Factor in %

5 10 15 20 25 30 Time
Applied Voltage/kV
Dissipation Factor -Voltage Behavior

JMPS J.M.PANG & SEAH (PTE) LTD SITE TESTING OF CABLE TERMIN8TION - 14
Dissipation Factor Typical Values

Insulation Tangent delta (%)


LDPE (low density polyethylene) 0.1
HDPE (high density polyethylene) 0.1
XLPE (cross linked polyethylene) 0.1
Oil-paper 0.3
EPR (ethylene propylene rubber) 0.5
Neoprene 3.0

JMPS J.M.PANG & SEAH (PTE) LTD SITE TESTING OF CABLE TERMIN8TION - 15
PARTIAL DISCHARGE
MEASUREMENT IN
CABLE TERMINATION

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION
Partial Discharge - Equivalent circuit
Cable insulation

Cavity
CV
CP
CS

where CP - capacitance of cable


CV - capacitance of cavity
CS - capacitance of the insulation in series with the cavity

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION - 1
Partial Discharge in Cables

• Due to cavity in the insulation due to improper extrusion


process or impurity of the insulation material.

• If a voltage is applied across an insulation containing a cavity,


then the cavity will start to discharge when the voltage exceeds
the breakdown voltage, Vb.

• Vb is a function of pd where,
p = ggas ppressure
d = gas gap separation

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION - 2
Partial Discharge in Cables
Vb

pd

Cavity that does not discharge at the operating voltage of the cable are
quite harmless.
harmless
But cavity that discharges at operating voltage cannot be tolerated, since
the ensuing degradation of the insulation due to partial discharge will
l d to
lead t breakdown
b kd off the
th insulation.
i l ti

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION - 3
Partial Discharge

On Line Type Off Line Type

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION - 4
Partial Discharge – Off Line Measurement
step-up cable under test
transformer Blocking inductor

coupling
capacitor
p
Standard
capacitor,CS

Pico-Coulomb
PD measurement Pulse
set Generator

Calibration circuit

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION - 5
Partial discharge
sensors

HFCT type
TEV type
(High frequency Capacitor coupler
(Transient earth Ultrasonic type Embedded RTD
current type
voltage)
transformers)

Partial Discharge – Types of Sensors

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION - 6
Partial Discharge – What Is TEV?

• TEV stands for Transient Earth Voltage.

• Transient - a temporary phenomenon.

• Earth Voltage - refers to voltage of exposed


conductive parts which are
connected to earth
earth.

• TEV - temporary increase in earth voltage


which disappear after a very short time.

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION - 7
Partial Discharge – Transient Earth Voltage

• Amplitude varies from mill volts to volts

• nanoseconds rise time

• electromagnetic wave of 3 to 60 MHz

• TEV amplitude - a function of discharge


amplitude and attenuation
of propagation path.

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION - 8
Partial Discharge – Transient Earth Voltage

• Capacitive couplers placed at external metal


surface
f off electrical
l t i l equipment
i t using
i a magnett

• Pulse width - a few tens of nanoseconds


1
• Bandwidth =
10 nanosecondds
= 100 MHz

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION - 9
JOINT

HIGH VOLTAGE CONDUCTOR


Discharge

Probes

DETECTOR
EM WAVE

Partial Discharge – Transient Earth Voltage


JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION - 10
Partial Discharge
Discharge-TEV
TEV Sensor from EA Technology of UK

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION - 11
Partial Discharge- TEV Sensor from IPEC of UK

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION - 12
Partial Discharge-
Discharge- Good TEV readings for 24kV rated Toshiba AIS, VCB
Front Reading (DB)
PANEL
Jan-03 Mar-03 Apr-03 May-03 Jun-03 Jul-03 Aug-03 Sep-03 Oct-03 Nov-03 Dec-03
1 3 3 2 3 2 1 1 1 1 1 1
2 3 3 2 0 2 1 1 1 1 1 1
3 3 2 2 0 1 1 1 1 1 1 1
4 3 3 2 3 2 2 1 1 1 1 1
5 3 3 3 0 2 1 2 1 1 1 1
6 3 4 2 0 2 1 1 1 1 1 1
7 3 0 1 3 2 1 1 1 1 1 1
8 3 0 1 2 1 1 1 1 1 1 1
9 3 2 2 2 1 1 1 1 1 1 1
10 3 2 2 2 1 1 1 1 1 1 1

11 4 2 1 0 2 1 1 1 1 1 1
12 4 2 1 0 2 1 1 1 1 1 1
13 3 3 2 1 2 1 2 1 1 1 1
14 3 4 2 1 2 1 0 1 1 1 1
15 4 2 1 2 2 1 0 1 1 1 1
16 4 0 0 2 2 1 1 1 1 1 1
17 4 0 0 1 1 1 1 1 1 1 1
18 4 0 0 0 1 1 1 1 1 1 1
19 4 3 0 0 2 1 1 1 1 1 1
20 4 3 3 1 2 1 1 1 1 1 1
BACKGROUND 2 2 3 2 2 1 2 1 4 1 1

Back Reading (DB)


PANEL
Jan-03 Mar-03 Apr-03 May-03 Jun-03 Jul-03 Aug-03 Sep-03 Oct-03 Nov-03 Dec-03
1 3 3 4 3 2 1 1 2 1 0 2
2 3 4 4 3 2 1 2 2 1 0 2
3 3 2 5 3 2 2 2 2 1 2 1
4 4 3 3 0 3 1 2 3 1 1 1
5 4 3 3 0 3 1 2 3 1 0 2
6 5 4 2 1 2 1 1 2 1 0 1
7 5 1 1 3 1 1 1 2 1 2 2
8 6 1 1 0 1 1 2 2 1 3 1
9 6 0 1 0 2 1 2 2 1 0 1
10 7 0 1 1 2 1 1 2 1 0 1

11 3 0 0 0 2 1 1 1 1 0 2
12 3 0 0 0 2 1 1 2 1 1 1
13 3 0 1 0 2 1 2 2 1 1 1
14 3 3 3 3 2 2 2 2 1 2 2
15 4 4 2 3 2 1 3 2 1 2 2
16 3 4 2 2 2 1 2 2 1 0 2
17 3 3 3 2 2 1 2 1 1 1 1
18 3 3 4 1 1 1 2 1 1 1 1
19 3 4 4 1 1 1 2 2 1 2 1
20 3 3 3 0 1 1 2 2 1 2 2

Side Reading (DB)


PANEL
Jan-03 Mar-03 Apr-03 May-03 Jun-03 Jul-03 Aug-03 Sep-03 Oct-03 Nov-03 Dec-03
1 2 3 2 0 2 2 1 1 2 2 1
10 4 3 2 0 2 1 2 1 2 2 1
11 3 4 2 1 2 1 2 2 1 1 1
20 4 4 3 2 2 1 1 2 1 1 1

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION -13
Partial Discharge – What is HFCT?
• HFCT = high frequency current transformer

• Does not respond to 50Hz current

• Frequency range of 300kHz to 20MHz

• Soft ferrite range

• Split core construction

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION - 14
Partial Discharge - Split core HFCT sensor (300kHz to 20MHz)

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION - 15
10
1.0

0.8

0.6

0.4

0.2

0
0MHz 10MHz 100MHz
Partial Discharge Frequency Spectrum

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION - 16
0 1.3 6.7 104 180 222 222 224 218 200

Partial Discharge
Discharge- Frequency response of HFCT

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION - 17
Partial Discharge – Transfer Impedance

Ratio of the output voltage to a constant input current,


as a function of frequency.
frequency

Output Voltage
Transfer Impedance =
Input
p Current

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION -18
50

45
e (mV/mA))

40

35
mpedance

30

25
Transfer im

20

15

10
T

0
0.010 0.100 1.000 10.00 100.0
Frequency (MHz)

Partial Discharge – Transfer Impedance Curve

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION -19
What is Ultrasound?

• Sound waves beyond the hearing range of


the human ear

• Audio range of human ear (20Hz to 5000Hz)

• Sound waves in the 20kHz to 120kHz range.

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION -20
Ultrasound- Airborne ultrasonic sensor with output in the ultrasonic
frequency
q y range
g ((40kHz ± 1kHz))

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION -21
Ultrasound-Contact ultrasonic sensor with output in the ultrasonic
frequency range (100kHz ± 20kHz)

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION -22
Ultrasound-Contact ultrasonic sensor with output in the audio
frequency range (20Hz to 5000Hz)

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION -23
Ultrasound-Airborne ultrasonic sensors with output in the audio
frequency range (20Hz to 5000Hz)

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION -24
Ultrasound – Frequency Range

1) Frequency range of human ear (20Hz - 5000Hz)

2) The sound of arcing, tracking, corona. (around 40Hz)

3) The
Th sound
d off iinternal
t l partial
ti l di
discharge.
h (20kH
(20kHz - 30kHz)
30kH )

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION -25
Ultrasound – Block Diagram for Ultrasonic Measurement
ULTRASONIC DETECTOR

OSCILLATOR 20 Hz TO 5000 Hz
EAR PHONE
20 kHz TO AMPILFIER
100 kHz PIEZO-ELECTRIC
PIEZO ELECTRIC
SENSOR SOUND RECORDER
MIXER
A/D MINI DISC D/A

EAR PHONE
SOUND CARD FFT SOFTWARE

FREQUENCY DOMAIN TIME DOMAIN


DISPLAY DISPLAY

COMPUTER

JMPS J.M.PANG & SEAH (PTE) LTD PARTIAL DISCHARGE MEASUREMENT IN CABLE TERMINATION -26