Professional Documents
Culture Documents
PO NO.: PU310-H1316
SUBJECT: Operation & maintenance manual
For Information
CLIENT
PROJECT
CONSULTANT
CONTRACTOR
SUB. CONTRACTOR
H.Kang
5
4
3
2
1 09. 11. 17. 2nd Issue. S. J. Lee BSW KH
0 09. 9. 29. 1st Issue. S. J. Lee BSW KH
Rev. Date Description Prepared Reviewed Approved
1500-11, Songjung-dong, Gangseo-gu, Busan, Korea, 618-270 Tel. 82 - 51 - 832 - 1715 ~ 1718
Homepage www.hanilhi.com Fax. 82 - 51 - 832 - 1719
E-mail lsj@hanilhi.com
Table of Contents
Sheet No.
1. General
1.1 Introduction 1
1.2 References 1
1.3 General Cautions 1
2. Operation
3. Recommended Maintenance
4. Trouble Shooting
5. Water Treatment
6. Attachments
1. General
1.1 Introduction
This manual is intended to provide informations for safe and proper operation and maintenance of
the following equipment(s).
- Packaged Boiler
For auxiliary equipments and components, their own manuals or instructions shall also be referred to.
For specific data or information, please refer to the relative data sheet, document or drawing.
1.2 References
Vendor's prints and the manuals for the auxiliary equipments and components shall also be read carefully
and understood together with this manual.
This manual shall be readily available in the boiler room/space and any operator shall be familiar
with this manual.
Prepare and follow a preventive maintenance schedule and a check list based on recommendations
in this manual. A log book shall be maintained to record inspection and maintenance.
The boiler room/space shall be always clean and clear of all unnecessary materials. Proper air
circualtion, naturally or forcedly, shall be ensured so that sufficient air is supplied to the burner
to prevent incomplete combustion.
Never operate the boiler under the following conditions, which can result in serious damage or
explosion.
- Dry Fire, i.e., the boiler not being filled with water
- A function, "Low Water Level Shut-down" being in disorder
- A function, "High Pressure Shut-down" being in disorder
For furthers, please refer to "Precaution for Operation and Maintenance", which is attached.
2. Operation
1) Visual Inspection
Check that all foreign materials and tools have been removed.
2) Valve postion
Open the boiler vent, manual vent valve or start-up vent valve if provided.
4) All utilities such as electricity, instrument / service air and cooling water shall be available.
8) Fill water into the boiler upto the normal water level.
CAUTION : High quality water shall be used to minimize water side corrosion.
Water temperature shall match the temperature of the boiler metal to prevent
thermal stresses. Excessive temperature difference shall be avoided.
The following procedure shall be reviewed and carefully followed for start-up after completing the
preparation steps for start-up.
1) Check that all indications on the boiler control panel are normal.
2) Set the selector switch for fuel to "Fuel GAS" or "FUEL OIL" position, if a dual fuel burner is equipped.
5) Hold on minimum fire until steam pressure reaches around 1~2 bar.g
C
CAUTION
O : Observe
O firing
f state and never go to high fire
f to avoid excessive thermal stresses.
6) Set the master controller to "AUTO" position when steam pressure reaches around the normal
operating pressure.
CATION : Never open a valve under pressure quickly. The sudden change in pressure or
resulting water hammering may cause piping failure.
2 3 Hot
2.3 H t St
Start-up
t
The procedure is as same as above 2.2 except that 5), 6) and 9) of 2.2 are not required.
Effective operation of a boiler is critical to maintaining system efficiency, reliability and availability.
General
If the rate of steam flow from a boiler increases, the pressure drops because heat is carried
away faster than it is being supplied. If steam flow decreases, the pressure increases.
Visible water level is not always a true indication of the amount of water in a boiler because
steam bubbles, as well as water, are contained in the water space and cause the water to
swell.
If the steaming rate decreases, the amount of steam bubbles decreases, the water shrinks, and
the water level drops.
The tendency of water level to vary with steaming rate is known as "Swell" and "Shrink".
Swell and shrink shall be taken into consideration in controlling water flow so that the flow varies
properly with steam output.
Blowdown
The concentration of undesirable solids in boiler water can be reduced through blowdown, by which
a portion of boiler water is blown down and replaced by feedwater with a lower concentration.
The main purpose of blowdown is to maintain the solid concentration in boiler water within
acceptable limits.
Continuous Blowdown
Continuous blowdown rate is set to control boiler water within acceptable limits.
Intermittent Blowdown
Intermittent blowdown shall be performed at routine intervals to discharge sludge in the bottom.
Excessive blowdown results in energy loss and operating cost increase. Blowdown rate shall be
adjusted and minimized by sampling and testing boiler water routinely.
Although a boiler's efficiency is primarily a result of its design, the operator can maintain or
significantly improve efficiency.
The total heat loss to flue gas is determined by quantity and temperature of the flue gas.
The quantity of the flue gas is dependent on the fuel being burnt, but is also influenced by
the amount of excess air supplied to the burner.
While sufficient air must be provided to complete the combustion process, excessive amount
of air simply carry extra heat to the flue gas.
The temperature of the flue gas is affected by the cleanliness of the boiler heat transfer
surfaces.
While high flue gas temperature waste energy, excessively low temperature may also be
unacceptable. Corrosion can occur at the water or acid dew point of the flue gas.
Burner Adjustment
Fuel and combustion air combine and release heat at the burner.
To maintain even heat distribution across the width of the furnace, air and fuel flows must
be evenly supplied.
Adjustment can typically vary the turbulence and flow rates in the burner.
It also increases the combustion intensity, provides faster heat release, reduces unburnt
carbon, permits operation with less excess air and inceases boiler efficiency.
Water Treatment
The main function of a boiler is to transfer heat from combustion gas through tube walls
to heat water and produce steam.
2.5 Shut-down
Two shut-down situations may occur, a controlled shut-down or one required in an emergency.
1) Controlled Shut-down
Push the push button, "BURNER STOP" after the firng rate has been gradually reduced to a minimum.
Then, the fuel is shut off and the furnace is post-purged.
The F. D. fan may be shut down or remain running for faster cool-down of the boiler.
The boiler pressure gradually lowers as heat is lost from the boiler surfaces.
2) Emergency Shut-down
The boiler may be held at a reduced pressure or may be completely cooled down.
The boiler water level shall not be decreased to allow tubes to be exposed to steam.
If the level drops below the minimum required, shut down the boiler and feed water slowly
until normal level is restored.
If there is any possibility that tubes have been damaged, cool down and inspect the boiler.
2) Tube Failure
By loss of water or steam, a tube failure can alter water circulation flow and result on other
tubes being overheated and failed.
The selector swith for operation mode shall be set to "MANUAL" position.
The pilot burner, the main burner, etc. can be manually operated.
For further details, please refer to the instruction manual for burner.
3. Recommended Maintenance
1) Daily
- Water Level
- Steam Pressure
- Flue Gas Temperature
- Water or Steam Leakage
- Flue Gas or Combustion Air Leakage
- Fuel Level or Pressure
2) Monthly
3) Quarterly
- Boiler Mountings
- Valve and fittings on pipe lines
4) Semi-annually
- Safety Valves
- Pressure Instruments
- Level Instruments
- Controllers
5) Annually
- Internal Surfaces
- Fireside Surfaces
When the boiler is removed from service, it shall be carefully prepared for the idle period.
During this period, excessive rusting and corrosion may occur on the water side and fire side surfaces.
Well planned procedures shall be followed for the boiler to be prepared for service.
There are two basic methods, " Wet Storage " and " Dry Storage " for the water side surfaces.
Wet storage is recommended for short term ( one month or shorter ) outage and has the advantage of allowing
the boiler to be returned to service on short notice.
Dry storage is recommended for long term ( one month or longer ) outage.
1) Wet Storage
Make periodic inspections to check water leakage. Replace all water loss from the boiler.
2) Dry Storage
When the boiler is to be idle for a considerably long period, it shall be emptied, thoroughly
cleaned, dried and then closed to exclude both moisture and air.
D i
Desiccant
t Method
M th d
Silica gel or other moisture absorbent may be placed on trays inside the boiler.
Check periodically and replace it when necessary.
CAUTION : Moisture absorbent such as silica gel shall not contact metal surfaces of
the boiler. Absorbed moisture can cause corrosion.
The boiler shall be filled and pressurized with nitrogen to about 0.5 bar.g.
The pressure shall be maintained throughout the storage.
For further details, please refer to "Boiler Lay-up Procedure", which is attached.
The boiler shall be cleaned at least once a year to maintain the high thermal efficiency and a long
life of the boiler.
If the boiler is to be shut down and taken out of service for a long period, the boiler shall be cleaned
immediately upon shut-down while flue gas passages are still warm. When the boiler gets cold,
deposits harden and make cleaning difficult. Further, hardened deposits would absorb moisture
and cause corrosion.
1) Internal Cleaning
The cleanliness of internal surfaces, water and steam side, is of prime importance because
internal deposits can lead to chemical attack, corrosion and overheating.
Hard scales shall be removed by performing "Boil-out Procedure", which is separately provided.
2) Fireside Cleaning
Remove soots from flue gas passages including tube inside using tools such as brush.
If soot deposits are difficult to remove manually, water cleaning shall be performed.
Drain water during water cleaning may be acidic. So, extreme care shall be taken to protect
personnel and to dispose of the effluent to avoid environmental pollution.
Performance monitoring and inspections establish the nature and extent of repair.
The equipment manufacturers can recommend, guide or carry our the work, but final decision
shall depend the operating company and inspectors.
Pressure part repairs must meet the requirements by the applicable code.
Repairs of pressure parts may be also made under the guidance of the local authority.
Welds joining pressure parts and Welds joining pressure parts to non-pressure parts
Welds joining pressure parts and welds joining pressure parts to non-pressure parts must
conform to the requirements of the applicable code.
The applicable code establishes the minimum requirements for base material selection,
qualification of welding procedures and welders, non-destructive examination, etc.
Welds that are made between non-pressure parts such as flue gas ducts, casings, etc. shall
conform to the detailed engineering documents and drawings provided.
A new boiler or boiler with major parts repaired shall be subject to pre-operational boil-out.
Boil-out shall be performed to remove debris, oil, grease and paint which may lower heat
transfer and lead to overheating.
Dry-out shall be performed to dry newly installed refractory inside the furnace.
Dry-out can be accomplished shortly during boil-out.
For details and procedure, please refer to "Boil-out Procedure", which is separately
provided.
4. Trouble Shooting
For further details, if required, refer to operation & maintenance manuals or instructions for
auxiliary equipments and components.
When the boiler has a severe over-pressure condition causing steam to blow out the safety,
assume that safety controls do not work.
The response to a severely over-pressurized condition shall be to shut down the boiler and
to allow the boiler to cool slowly. Never introduce cold water into the over-pressurized boiler.
The boiler shall be thoroughly inspected for damage. Before the boiler is returned to normal
service, the problems shall be fully corrected.
When boiler tubes are exposed to steam, the tubes become overheated and lead to tube
failure.
If a serious condition exists, take the boiler immediately out of service until the cause of the
problem is identified and corrected.
No Fire
- Other Shut-downConditions
Fuel Explosion
Check air flow and adjust to the correct air - fuel ratio.
No Fuel
5. Water Treatment
Water conditioning can increase the efficiency of the boiler as well as extend the boiler's life.
Without proper treatment, the boiler can suffer from serious damages, and thus can be destroyed.
This happens when calcium, magnesium and silica, common in most water, react with metal
in boilers to form a hard scale on the surfaces of the metal.
The hard scale formed reduces heat transfer and lower the boiler's efficiency.
If allowed to accumulate, boiler scale can eventually cause tubes to overheat and rupture.
Removing calcium and magnesium or other deposit-formimg materials from feedwater before
entering boilers is the best way to prevent scaling.
Dissolved oxygen interacts with boiler surfaces, forming "pits" on the metal surface.
These pits may eventually grow large enough to penetrate the metal, forcing a boiler shut-down.
Controlling the oxygen content in feedwater can be done through deaeration and chemical
treatment.
Another of the most common causes of corrosion is the presence of carbon dioxide in the
condensate.
Carbon dioxide forms carbonic acid and reduces the pH of the condensate and causes acid
attack.
A third corrosion related problem is caused when boiler water pH drops below about 8.5.
Known as acid attack, the effect exhibits rough pitted surfaces.
Boiler water pH shall be periodically monitored and maintained within the recommended
limits.
The boiler operators shall consult a water treatment specialist for actual operation conditions and
take proper steps for water quality control.
pH at 25 deg.C - 8.3 ~ 10 -
Dissolved Oxygen ppm max. 0.007 -
Total Iron ppm max. 0.1 -
Total Copper ppm max. 0.05 -
Total Hardness ppm max. 0.3 -
Nonvolatile TOC
OC ppm max. 1 -
Oily Matter ppm max. 1 -
Remarks
Water analysis must be routinely carried out mainly for the following.
Steam analysis must also be routinely carried out together with water analysis.
Water / steam analysis records shall be kept available to maintain proper operation.
Symptom
Possible Scale Corrosion Weakening Carry Over Possible
Cause Feed Feed Condens Solution
Boiler Boiler Boiler Steam Line
System System System
Feedwater
pH △ △ to be adjusted.
Hardness ○ ● X to be reduced.
Dissolved ○ ● ○ deoxidization
Oxygen
Oil ○ ● filteration
Contamination blow-down
Boiler Water
Chlorine ○ distillation
chemical
Silica ○ ● distillation
to add chemical.
Condensed
Water
CO2 ○ anti-corrosive
Notes :
△ and ▲ indicate that the farther pH gets away from the suitable range, the severer corrosion
becomes.
Especially in case of ▲ mark, the degree is larger.
○ and ● indicate that the higher the concentration becomes, the severer the trouble becomes.
Especially in case of ● mark, the degree is larger.
X mark indicates the secondary trouble which is often caused by the primary trouble.
5
4
3
2
1
0 09. 10. 07. 1st Issue. S. J. Lee BSW KH
Rev. Date Description Prepared Reviewed Approved
1500-11, Songjung-dong, Gangseo-gu, Busan, Korea, 618-270 Tel. 82 - 51 - 832 - 1715 ~ 1718
Homepage www.hanilhi.com Fax. 82 - 51 - 832 - 1719
E-mail lsj@hanilhi.com
The boiler shall be operated and maintained as designed for the specific service as possible.
Precautions for operation & maintenance are recommended to be followed.
2. Precautions
Safety Valves
The primary purpose of the safety valves is to prevent over-pressure in a pressure vessel such as the steam drum,
the superheater, the economizer and the deaerator.
The safety valves relieve over-pressure by discharigng steam or water in the vessel. Thus, there should be no obstructions
at the safety valves inlet and outlet.
The moisture and solid contents in steam can cause troubles to equipments and piping downstream of the boiler.
The level shall be maintained within allowable limits with performing proper water treatment and control.
Carry-over
The moisture and solid contents in steam can be increased to a large extent due to priming.
A sudden load change and/or a high water level can cause priming, and thus shall be avoided.
Loss of Water
Water loss may be due to tube leakage, excessive blowdown or other causes.
The boiler shall be shut down, if the cause has not been remidied, to avoid a successive occurrence such as tube failure.
Furnace Explosion
In any case, the furnace shall be prevented from the explosion inside of the furnace.
Pre-purging shall be done before firing, and also post-purging shall be done after shut-down.
BOILER LOGGING
5
4
3
2
1
0 09. 10. 07. 1st Issue. S. J. Lee BSW KH
Rev. Date Description Prepared Reviewed Approved
1500-11, Songjung-dong, Gangseo-gu, Busan, Korea, 618-270 Tel. 82 - 51 - 832 - 1715 ~ 1718
Homepage www.hanilhi.com Fax. 82 - 51 - 832 - 1719
E-mail lsj@hanilhi.com
Table of Contents
1. Introduction
2. Scope
3. References
4. Attachment
- Operating Log
- Maintenance Log
- Daily
- Weekly
- Monthly
- Quarterly
- Semi-annual
- Annual
1. Introduction
Boiler logs are check lists for the boiler operators and provide a means of recording data for operation
and maintenance.
The logs can be used to evaluate the boiler conditions and correct troubles before they become accidents.
For safe operation and good maintenance, it is most important to keep the logs complete and accurate.
2. Scope
Frequency and extent of recording will depend on operating and maintenance conditions and practices.
Items may be added to or deleted from the log sheets. Periods may also be adjusted.
It is not practical to cover all details which comes from the equipments' instructions
It is advisable for the operators to get familiar with the instructions ans add items to the log sheets.
There may be some requirements from the local Authority and the insurance company.
Those items shall be included in the log sheets.
3. References
Documents by National Board of Boiler and Pressure Vessel Inspectors Inc. ( NBBI )
NFPA 70
Year :
Load Fuel Steam Flow Pressure, bar.g Temp., deg.C Flue Gas Water / Oil Level Water
Date Time Operator Remarks
%MCR Gas / Oil Flow,kg/h kg/h Boiler Deaerator Deaerator Flue Gas O2 Nox BoilerDeaerator Oil Tk Test
Date reviewed :
Date :
Equipment / System Check / Action / Test Item Method Result Correction / Action if any Remarks
Blowdown Bottom Manual
Water Column Manual
Level Gauges Manual
Boiler Proper
Check steam / water leakage. Visual
Check flue gas leakage. Visual
Check noise and vibration. Auditory
Observe combustion state. Visual
Check fuel gas leakage. Visual
Burner Unit Check fuel oil leakage. Visual
Check combustion air leakage. Visual
Check noise and vibration. Auditory
Blowdown Storage Tank Manual
Water Column Manual
Deaerator Level Gauges Manual
Check steam / water leakage. Visual
Check noise and vibration. Auditory
Demi. Water System Inspect exterior. Visual
Feedwater System Check leakage. Visual
Steam System Check noise and vibration. Auditory
Blowdown System
Fuel Gas System
Fuel Oil System
Combustion Air System
Notes :
Reviewed by :
Date reviewed :
Reviewed by :
Date reviewed :
Notes :
Safety Valves
Boiler Proper
Reviewed by :
Date reviewed :
Notes :
Burner Unit
Feedwater System
Valves
Reviewed by :
Date reviewed :
Notes :
Safety Valves
Pressure Instruments
Level Instruments
Temperature Instruments
Controllers
Burner Unit
Inspect components.
Adjust combustion.
Reviewed by :
Date reviewed :
Notes :
Check / Action / Test Items Year -> 2010 2011 2012 2013 2014 2015 Remarks
Boiler Proper
Pumps
Electricals
Reviewed by :
Date reviewed :
Notes :
5
4
3
2
1
0 09. 10. 07. 1st Issue. S. J. Lee BSW KH
Rev. Date Description Prepared Reviewed Approved
1500-11, Songjung-dong, Gangseo-gu, Busan, Korea, 618-270 Tel. 82 - 51 - 832 - 1715 ~ 1718
Homepage www.hanilhi.com Fax. 82 - 51 - 832 - 1719
E-mail lsj@hanilhi.com
Table of Contents
1. Introduction
2. References
3. Principle
4. Procedure
6. Auxiliary Equipments
1. Introduction
- Packaged Boiler
The purpose of Lay-up is to protect the boiler from corrosion and rusting during an idle period when the boiler
is taken out of service.
2. References
3. Principle
There are two basic methods, " Wet Storage " and " Dry Storage " for the water side surfaces.
Wet storage is recommended for short term ( one month or shorter ) outage and has the advantage of allowing
the boiler to be returned to service on short notice.
Dry storage is recommended for long term ( one month or longer ) outage.
1) Wet Storage
The boiler shall be filled full with feedwater or condensate which is conditioned chemically.
2) Dry Storage
Desiccant Method
Silica gel or other moisture absorbent may be placed on trays inside the boiler.
4. Procedure
The boiler shall be completely filled with chemically treated water and closed to prevent air from entering.
1) Add chemicals into the boiler just before the boiler has been shut down.
2) If the boiler is empty, fill the boiler with water and the chemical solution. And then, operate the boiler
on a low fire for a short time for water circulation and mixing of the chemicals.
3) Fill the boiler completely using air vents.
4) Close the boiler tightly.
5) Sample and test the water weekly to ensure that the chemical concentration is within the proper level.
If the concentration has been decreased below the level, add additional chemical into the boiler
by lowering the water level, and then take a step for circulation and mixing.
Desiccant Method
4) Put moisture absorbent such as silica gel on trays, and place them inside the boiler.
5) Close
Cl the
th boiler
b il tightly.
ti htl
6) Check the moisture absorbent monthly, and replace if required.
CAUTION : Moisture absorbent such as silica gel shall not contact metal surfaces of
the boiler. Absorbed moisture can cause corrosion.
Warning signs shall be posted so that the boiler should not be operated
until the moisture absorbent inside have been removed.
CAUTION : Warning signs shall be posted so that nitrogen only is, oxygen to breathe is not inside
the boiler, and thus anyone never enter inside the boiler.
Flue Gas and humid air can cause corrosion to steel surfaces during long term out-of-service.
The following steps are recommended for longer than three (3) month lay-up.
2) Put moisture absorbent such as silica gel on trays, and place them inside the furnace.
3) Close air duct inlet and gas duct outlet with installing plates to prevent air in-flow.
6. Auxiliary Equipments
Equipments and/or their parts are subject to corrosion during long term lay-up.
Shafts and bearings shall be routinely attended to check and keep them in good conditions.
5
4
3
2
1
0 09. 10. 07. 1st Issue. S. J. Lee BSW KH
Rev. Date Description Prepared Reviewed Approved
1500-11, Songjung-dong, Gangseo-gu, Busan, Korea, 618-270 Tel. 82 - 51 - 832 - 1715 ~ 1718
Homepage www.hanilhi.com Fax. 82 - 51 - 832 - 1719
E-mail lsj@hanilhi.com
This technical sheet provides information for trouble shooting in boiler operation.
No Fire
Fuel Explosion
No Fuel
Water Level Too High Larger Feedwater Flow Adjust the control valve.
Water Level Too Low Less Feedwater Flow Adjust the control valve.
Flue Gas Temp., Too High Severe Fouling of Heating Surface Clean the heating surface.
Flue Gas Fume or Odor Leakage in Flue Gas Ducting Locate and repair.
BU R N E R O & M M A N U A L
5
4
3
2
1
0 09. 11. 17. 1st Issue. S. J. Lee BSW KH
Rev. Date Description Prepared Reviewed Approved
1500-11, Songjung-dong, Gangseo-gu, Busan, Korea, 618-270 Tel. 82 - 51 - 832 - 1715 ~ 1718
Homepage www.hanilhi.com Fax. 82 - 51 - 832 - 1719
E-mail lsj@hanilhi.com
F. D. F A N O & M M A N U A L
5
4
3
2
1
0 09. 11. 17. 1st Issue. S. J. Lee BSW KH
Rev. Date Description Prepared Reviewed Approved
1500-11, Songjung-dong, Gangseo-gu, Busan, Korea, 618-270 Tel. 82 - 51 - 832 - 1715 ~ 1718
Homepage www.hanilhi.com Fax. 82 - 51 - 832 - 1719
E-mail lsj@hanilhi.com
============================
FAN INSTRUCTION MANUAL
============================
1. OPERATION MANUAL
2. MAINTENANCE MANUAL
MANUAL\M001E1
Yujin Engineering Y J N
& Mfg. Co., Ltd. M001E1
FAN INSTRUCTION MANUAL
1. OPERATION MANUAL
1) Make sure that every part is thoroughly equipped, clear around the machine, and make
sure that there is no foreign matter around the inlet opening or in the suction line piping.
3) Lubricating Oil
Inspect the bearing grease. Excessive filling of grease will cause excessive heat in
bearings. The kinds of oil, generally speaking, for 150℃ or below, SHELL Alvania
grease No. 2, GULF Crown EP No. 2 or turbine oil GULF Harmony #32 is recom-
mended, and for temperature exceeding 150℃ , MOLUB alloy 850-2 or turbine oil GULF
harmony #64 is recommended.
The amount of grease required for the lubrication of bearing is sufficient when filled
and approximately 1/3 for in the bearing case.
If the pillow type inlet is applied, with Alvania grease No. 2 is already filled,
there is no need for further feeding.
Look at the oil level gauge and fill the oil up to the specified amount (approximately
to the middle of the gauge). In the case where a cooling water piping is provided,
pass approximately 1-2 kg/cm 2 of cooling water .
4) Turning by Hand
Make sure there is no unreasonable or forced arrangement in the suction and discharge
of ducts or air leakage. Also make sure there are no remainders of material used
during installation work. After confirming no irregularity, turn the blower by hand to
check abnormal contact in the interior.
MANUAL\M001E1
Yujin Engineering Y J N
& Mfg. Co., Ltd. M001E1
FAN INSTRUCTION MANUAL
Even though belt tension and alignment are set before shipping, the alignment and tension
can be checked at site before starting as follows :
* Alignment between both grooved pulleys for V-belts is to be checked either by applying
a stretch to the side of both pulleys or by stretching a thread. Adjustment is to be made
accordingly by moving the motor body on the slide base.
* Belt tension can also be adjusted by moving motor slide base back or forward. Care is
to be taken to ensure against whirling of overtightness of the belts. As a reference for
normal belt tension, 15mm per 1m of span length of deflection is appropriate when 1.5kg
for A type, 3kg for B type, 5kg for C type or 10kg for D type is applying on the middle
of belt span.
6) Starting
Start the blower with the air control damper closed. Sudden increase of speed should
be prohibited. Check the bearing, noise in the casing inside, vibration and temperature,
then increase the speed gradually to the speed.
1-2 Start-Up
During the start-up of the trial operation, the bearing temperature, vibration and contact
with the rotating member require special attention.
2) Carefully observe the variation of the current during the start, and if any abnormality
is found, immediately stop the motor.
3) Pay attention the vibration and sound during the start. If any abnormality is noticed,
stop the fan to check for causes.
4) While carefully observing the variation of the current, gradually adjust the opening of
the suction and/or discharge valve to set the current predetermined value.
5) If the operation condition is smooth thus far, the bearing temperature becomes constant
after half an hour to an hour. Therefore, operate the fan at least for one hour to
check the operational condition such as the bearing temperature and vibration.
MANUAL\M001E1
Yujin Engineering Y J N
& Mfg. Co., Ltd. M001E1
FAN INSTRUCTION MANUAL
1-3 Operation
1) Damper Control
After the machine attains full speed, operating the air control damper closed for a long
time incurs danger, because the accumulation of compressed heat within the blower
casing may cause heat distortion. Therefore as soon as full speed is reached, when
using discharge damper, the air control damper needs to be opened with a minimum
amount of air quantity so that surging phenomenon may not occur. Then loading can
be successfully increased gradually.
When using the suction damper, there is no fear for surging. Control the damper by
watching the ammeter of the motor to make that the motor doesn't overload. Confirm
at this time that the motor ampere is below the rated value.
Confirm the circulation of oil after full speed has been attained and measure the tem-
perature increase in bearing. This should be under 40℃ and the bearing temperature
should be kept under 70 ℃ under any condition. The temperature will become constant
after one hour from starting. It is considered safe if you can keep your palm on the
bearing for more than 10 seconds. For the blower which is provided with a gland, pay
attention so as not to tighten the gland unbalancedly. Then, operate the motor for a
moment to ascertain the revolving direction and inner contact.
If the bearing temperature is 70℃ or below, it is normal, however, should the tempera-
ture exceed that value, carry out an inspection of oil, bearings and the shaft alignment.
(Refer to the paragraph under Inspection and Maintenance.) Damage in the bearing or
oil shortage causes a small metallic noise.
In the case where the gas has a smaller specific gravity than that of a normal tem-
perature air treated under normal temperature, it sometimes develops an overload.
Pay attention not to commit such an irregularity.
4) Surging
MANUAL\M001E1
Yujin Engineering Y J N
& Mfg. Co., Ltd. M001E1
FAN INSTRUCTION MANUAL
Measure the bearing vibration and its amplitude of the fan at the centermost position of
each bearing horizontally, vertically and in an axial direction. Use 1/1000 mm as the
unit, and express the vibration in total amplitude. Check the reading of the instrument
whether it is in half amplitude or in total amplitude.
For everyday inspection, touching by hand may be applied. However, when the vibration
becomes big, measure it with a vibration gauge. If it exceeds the permissible value of
the bearing vibration, stop operation without delay to inspect and adjust.
When vibration starts and keeps of going, it becomes impossible to operate continuously.
Therefore the imbalance should be rectified immediately.
For a reference for permissible vibration, Fig 2 can be used as a guide.
e.g. the limit of permissible vibration is 165 ㎛ with 1750 rpm.
After the complete closing of air control damper, stop the main electric motor. Make
sure that any abnormal sound is not heard, and that the drop of the number of revolution
is not abnormally fast until the rotor is completely stopped.
For a shut down of a long period, drain thoroughly the water such as the cooling water
in the bearing housing every part, and also the machine thoroughly. Coat the finished
faces of each section of the machine with appropriate corrosion inhibitor. Provide cover
over the necessary places to prevent dust, rain, etc., settling in the machine.
Pay special attention to the motor.
MANUAL\M001E1
Yujin Engineering Y J N
M001E1
& Mfg. Co., Ltd. FAN INSTRUCTION MANUAL
MANUAL\M001E1
Yujin Engineering Y J N
M001E1
& Mfg. Co., Ltd. FAN INSTRUCTION MANUAL
2. MAINTENANCE MANUAL
Pay attention to the following points everyday and carry out the inspection of the blower.
1) When the operation of the fan is to be suspended, pay much attention in cleaning,
rust prevention of the blower, and be cautious in preventing dust, dirt and water
getting into bearings.
2) Pay attention to prevent humidity against all electrical parts such as the motor and
other parts.
3) Remove water completely from the bearing cooling water piping and bearing cases.
Carry out periodical inspection at least once a year, and inspect the following items:
MANUAL\M001E1
Yujin Engineering Y J N
M001E1
& Mfg. Co., Ltd. FAN INSTRUCTION MANUAL
Inasmuch as the operation diary is the data for making a diagnosis of the fan, keep a
meticulous entry for present and future reference. If the operating record is kept, it is
possible to find abnormality in the early stage, and even if trouble occurs, it is easy to
find the cause of trouble.
Even under the strictest observation, there may be a discrepancy the operator may have
never expected, which may lead to trouble. We will find out its causes and take proper
countermeasure for you provided that you supply us with history of operation since the
beginning and current situation of the problem. See Table 1 where causes of troubles
and their countermeasure are listed.
Inspection
Troubles Causes Countermeasures
Point
MANUAL\M001E1
Yujin Engineering Y J N
M001E1
& Mfg. Co., Ltd. FAN INSTRUCTION MANUAL
Inspection
Troubles Causes Countermeasures
Point
MANUAL\M001E1
Yujin Engineering Y J N
M001E1
& Mfg. Co., Ltd. FAN INSTRUCTION MANUAL
Inspection
Troubles Causes Countermeasures
Point
MANUAL\M001E1
Yujin Engineering Y J N
M001E1
& Mfg. Co., Ltd. FAN INSTRUCTION MANUAL
Inspection
Troubles Causes Countermeasures
Point
MANUAL\M001E1
Doc. No. MP-V-AB-92-001-6.7
A C T U A T O R O & M M A N U A L
5
4
3
2
1
0 09. 11. 17. 1st Issue. S. J. Lee BSW KH
Rev. Date Description Prepared Reviewed Approved
1500-11, Songjung-dong, Gangseo-gu, Busan, Korea, 618-270 Tel. 82 - 51 - 832 - 1715 ~ 1718
Homepage www.hanilhi.com Fax. 82 - 51 - 832 - 1719
E-mail lsj@hanilhi.com
CONTENTS
1. GENERAL ··············································· 2
2. STANDARD SPECITICATION·························· 2
3. NOMENCLATURE········································· 3
4. STRUCTURES············································ 4
Pneumatic Actuator is an equipment for remote position controlling of devices such as Dampers, Fan
inlet vanes, Butterfly valves, Lever operated valves and other final control elements.
The Actuator is totally enclosed structure consists of an air cylinder with well combined linkage, positioner,
air control sets and electrical position transmitter etc.
2. STANDRAD SPECIFICATIONS
* Construction : Totally Enclosed Outdoor Type
* Ambient Temperature : -10℃ ~ 50℃
* Relative Humidity : Below 85 %
* Rating : Continuous
* Input Signal : Current : DC 4 ~ 20mA
Air Pressure : 0.2 ~ 1.0 Kg/cm2G
* Supply Air Pressure : 1.4 ~ 7.0 Kg/cm2G
* Operating Angle : 90°
* Air Consumption : 25Nℓ/min. ( Balancing Position )
* Painted Color : Munsell 7.5 BG 6/1.5
CYLINDER SIZE ( mm )
RATED TORQUE( Kgf-m ) APPROX. WEIGHT
MODEL
(S.A.P 5.5 Kg/cm2G) (Kg)
BORE STROKE ROD. DIA
-2-
3. EXPLANATION OF NOMENCLATURE
SE-05H □□□□□□
Basic Model
SE-01H 80H (Rated Torque 17 ~ 720 kgf-m)
Manual Operator
H
Type
O Standard
N Explosionproof
Limit Switches
O None
L Equipped (2 SPDT Switches)
Space Heater
O None
cy
T Equipped (CYSH-O)
-3-
4. STRUCTURES
When the checking and maintenance of the Pneumatic Actuator, refer to following constructions.
(SE-01H ~ 05H)
Power Arm
Positioner
Lever Arm
Limit Switch
Pressure Gauge
Auto-Manual
Change Valve
Air Cylinder
Manual
Handle
Filter Regulator
Lock up Valve
Terminal Block
(SE-08H ~ 18H)
Power Arm
Chain Sprocket
Current
Transmitter
Worm Wheel
Output
Shaft
Pressure Gauge
Clutch Lever
Manual Handle
Air
Cylinder
Positioner
Lock up Valve
Clutch Unit
Manual
Operator Unit
-4-
5. MOVEMENT AND INSTALLATION
5-1. MOVEMENT
5-3. INSTALLATION
1) Two anchor bolts should be get through at front side after removing of front cover, and the other two
anchor bolts should be get through installed at back side after removing of back cover.
The anchor bolts and nut should be tightened completely by use of offset wrench, etc. to avoid
shortage of tightening.
2) At the installation of connecting link, the following points should be observed carefully.
* In order to maintain the rated output of pneumatic actuator, adjust so that the angle create by
lever arm and connecting link ( turnbuckle ), should be 90°at 50% opening of pneumatic actuator.
( Fig. 2 )
Note : The installation angle of lever arm can be changed at any positions of 360°by 10 ~ 12°
pitch against torque shaft.
* The connecting link should be installed precisely so that the center line of connecting link is
matched with the center line of lever arm. ( Fig. 2 )
Note : As the lever arm is clutched to torque shaft by spline, it can be shifted to the axial
direction of torque shaft.
When the lever arm is shifted to shaft direction for the resetting between lever arm
and connecting link, the spline joint must be maintained with sufficient engaged
length.
-5-
Precisely measure
the center of connecting link
for installation.
90° at
the 50%
opening
Fig. 2
Fig. 3
-6-
6. PIPING AND WIRING
Conduit conn.
Terminal bolck
Supply air conn.
Fig. 1 Fig. 2
※ The case of explosion proof type connect the wire to positioner and limit switch
directly because terminal block is cannot used.
-7-
6-3. BASIC PIPING DIAGRAM
The switching from "AUTO" to "MANUAL" operation is made by operation of " AUTO / MANUAL "
changeover valve. When the changeover valve is switched to MANUAL position, the air pressure
supplied to positioner is cut, and simultaneously the air chambers of both upper and lower of power
cylinder are connected each other by by-passing, so that the manual operation can be admitted.
( Refer to 7-2 Auto/Manual Switching Procedure. )
3 3 10
8
9
1 1
5
11 6
2 2
4 4 5
7
7
AIR SUPPLY AIR SUPPLY INPUT SIGNAL
Fig. 3
-8-
7-2. AUTO / MANUAL SWITCHING PROCEDURE
As the manual operation lever is made solid with the output lever, manual operation can be
performed made simply. For switching over to a manual operation, turn the knob of transfer valve
mounted at front face of pneumatic actuator to " MANUAL " position. In this time, as the pneumatic
actuator will lose its output power, if unit is being loaded, tighten the lock lever located on the
manual operation lever by clockwise direction, then the lever can be locked. For the turning back to "
AUTO " operation, after matching the input signal to its opening of pneumatic actuator, the transfer
valve can be turned over to " AUTO " position.
For the Auto/Manual switching, the procedure should be conduced in accordance with the description
plate installed at front face to Pneumatic actuator.
* Turn over the lever to manual position(manual clutch on position) in which is located on
left-upper side of hand wheel.
Note : This procedure is to be engaged the clutch unit in manual drive reduction mechanism.
However, as there is the case that the clutch engagement is not fitted with the relation
of clutch position, in that case, find the engaged point with rotating of hand wheel by
any directions, then turn over the lever.
* Next, turn over the changeover valve's knob located under the input signal pressure gauge
mounted on front face of Pneumatic actuator to manual position.
* After the input signal corresponding to its opening of Pneumatic actuator has been, the knob of
changeover valve located at under side of pressure gauge mounted on front face of Pneumatic
actuator can be turned over to auto position.
* In order to make a complete matching the Pneumatic actuator opening and input signal, adjust to
-9-
the input signal corresponding to its opening until the manual handle can be operated lightly.
Then, the lever located on left-upper side of hand wheel can be turned over to auto
position( Manual clutch off position).
Note 1 : The switching operations for "Auto to Manual" and "Manual to Auto" should be
performed securely. If this operation is not perfect, the troubles such as spline teeth
damage of clutch unit may occur. So please operate this carefully.
Note 2 : In order to prevent the damage of clutch unit of manual mechanism, "Auto to Manual"
operation must be performed at the time when the drive unit is at standstill.
8. ADJUSTMENT OF ACCESSORIES
8-1. POSITIONER
At 0% or 100% opening position of drive unit, the contact point of cam roller installed on the feedback
lever should be matched at start point of cam.
Provide the input signal of 0.2Kg/cm2G ( zero point ) to the positioner, and adjust the spring load by the
zero adjustment knob so that the opening of drive unit will be 0%( Full close or open ).
Next, for the input signal range from 0.2 to 1.0 Kg/cm2G, span adjuster so that the drive until will move its
full stroke.
Before the span adjustment, loosening the lock screw of span adjuster.
A repeat zero adjustment should be made because the zero point may be changed by touching of span
adjuster.
A repeat adjustment by the zero and span adjusting knobs should be continued until the 50%
opening( Linear Cam, when the using of Square Cam ; 22.4% ) at 0.6Kg/cm2G of input signal and full
stroke operation in input signal change from 0.2 to 1.0 Kg/cm2G can be obtained.
After the span adjustment, don't forget the locking of lock screw.
In the linearity has been deviated from specified value ( ±2°), it can be compensated by adjusting the
length of turnbuckle jointed with feedback lever of positioner and power arm installed on power shaft of
Pneumatic actuator.
- 10 -
Lock screw of Span adjustment Zero adjustment
Span adjuster Knob Knob
Feedback spring
Feedback Lever
Diaphragm
Cam
As the assembly position of limit switches has been adjusted at factory, so major adjustment may not be
necessary. If the adjustment of contact point is required, loosen the screw on cam attached to power
shaft, then change the cam position.
Set Screw
Limit Switch
- 11 -
9.CHANGING THE ACTING DIRECTION OF POWER SHAFT ROTATION
9-1. DIRECT-ACTION
A Pneumatic actuator called direct-acting(DA) when an increase in the input signal causes the piston of
power cylinder moving upward. The power shaft moves counterclockwise in view from right side.
9-2. REVERSE-ACTION
The Pneumatic actuator is called reverse-acting(RA) when an increase in the input signal causes the
piston of power cylinder moving downward. The direction of shaft rotation for reverse-acting is reverse
motion of direct-acting.
For instance, in order to change made from direct-acting to reverse-acting, the pipe line from positioner
output-1 should be changed the connection to up from bottom of cylinder, and also output-2 should be
changed the connection to bottom from top of power cylinder.
Next, remove the positioner cover, then the characterized cam consisting in positioner mechanism
should be attached inside out. ( Confirm to the stamp on front face of cam. )
The changing method to direct-acting from reverse-acting should be made by reverse procedure to the
above.
10. MAINTENANCE
1) Check about every 3 months whether the pin and key part have no abnormality and also the manual
handle mechanism can be operated normally.
2) The packing of power cylinder should be inspected once a year and the packing replaced as required.
3) Lubrication Cycle
Knuckle
Point A B C D Joint PIn A
Clutch Unit D
Capacity 5 cc 20 cc 100cc 5 cc
Cycle 1 Year Manual
C Operator Unit
Model EP 2
Manufac
turers Alvania No. 2
- 12 -
Doc. No. MP-V-AB-92-001-6.8
M. O. V. D R A W I N G
5
4
3
2
1
0 09. 11. 17. 1st Issue. S. J. Lee BSW KH
Rev. Date Description Prepared Reviewed Approved
1500-11, Songjung-dong, Gangseo-gu, Busan, Korea, 618-270 Tel. 82 - 51 - 832 - 1715 ~ 1718
Homepage www.hanilhi.com Fax. 82 - 51 - 832 - 1719
E-mail lsj@hanilhi.com
PROJECT MISURATA 20T/H AUX.BOILER A 09.03.11 FOR APPROVAL L.Y.K L.Y.K I.Y.LEE
LOCATION LIBYA REV NO. DATE DESCRIPTION PREP CHK APP'D
1 KKS NO 90QLB20AA101 □ ON-OFF
GENERAL 2 SERVICE MAIN STEAM VENT MOV SERVICE 39 CONDITION ■ INCHING
3 QUANTITY 1 set(s) □ REGULATING
4 TYPE & SIZE GLOBE / 4" 40 SPACE HEATER ■ YES □ NO
5 RATING & ENDS 300# / BW POSITION ■ YES
41
6 BODY MATERIAL A216-WCB ATTACH- TRANSMITTER □ NO 4~20mA
7 TRIM MATERIAL 13Cr + STELLITE MENT ■ YES
42 POTENTIOMETER
8 FLUID STEAM □ NO
VALVE 9 TEMP.DESIGN 374 ℃ 43 POSITION INDICATOR ■ YES □ NO
10 PRESS.DESIGN 224.3 Kg/㎠g 44 STEM PROTECTION TUBE □ YES ■ NO
11 TURNS FOR O/C 7.2 REV 45 TYPE N/A
12 STEM ACTION RISING GEAR BOX 46 MODEL N/A
13 OPERATING TIME 20 SEC 47 FACTOR/RATIO N/A
14 REQUIRED TORQUE 76 Nm 48 OUTPUT TORQUE MAX -
15 TYPE 49 MATIC MODEL, MATIC AM01.1
16 MODEL 50 SA10.1 TYPE/MODE OF OPERATION INTEGRAL
17 ENCLOSURE IP67 51 REVERSING CONTACTOR ■ YES □ NO
CLOCKWISE ■ CLOSE OPEN-STOP-CLOSE ■ YES
18 ROTATION 52
□ OPEN PUSH BUTTONS □ NO
ACTUATOR 19 OUTPUT RPM 22 RPM REMOTE-OFF-LOCAL ■ YES
53
DECLUTCHABLE CLOCKWISE ■ CLOSE SELECTOR SWITCHES □ NO
20
SIDE HANDWHEEL □ OPEN CONTROLS 54 INDICATING LAMP OPEN.CLOSE.FAULT
SET TO 55 TRANSFORMER ■ YES □ NO
21 7.2 TURNS / STROKE
LIMIT SWITCHING 56 POSITIONER □ YES ■ NO
LIMIT SWITCH 2 NC 2 NO (OPEN,CLOSE) 57 PHASE DISCRIMINATOR ■ YES □ NO
22
INTERMEDIATE NC NO (OPEN,CLOSE) 58 M0NITOR RELAY ■ YES □ NO
23 TORQUE SWITCH 2 NC 2 NO (OPEN,CLOSE) 59 COLLECTIVE FAULT ■ YES □ NO
RATED TORQUE(Nm) OPEN 120 CLOSE 120
24 OPEN LIMIT
SETTING TORQUE(Nm) OPEN 90 CLOSE 90 60 SEATING METHOD
CLOSE LIMIT
25 AMB. TEMP. -25 ℃ ∼ + 70 ℃
26 MANUFACTURER AUMA 61 PAINTING PROTECTION KN / STANDARD
27 POWER SOURCE AC 400 V, 50 Hz, 3 Ph 62 LUBRICATION GREASE
28 CONTROL SOURCE DC 24V OTHERS 63 NAME PLATE ENGLISH / STAINLESS.S
29 MOTOR POWER 0.37 KW 64 WEIGHT ACTUATOR 33 Kg
30 RPM 2800 1/min 65 CABLE CONNECTION G1",G3/4",G1/2"
31 NOMINAL CURRENT 1.4 A 66 COLOR SILVERGREY(A0001)
MOTOR 32 MAX. CURRENT 1.9 A FINAL INSPECTION ■ YES
67
33 STARTING CURRENT 4.5 A RECORD □ NO
34 INSULATION F CLASS 68 QUALITY CERTIFICATE ■ YES □ NO
35 TEMP. RISE B CLASS DOCUMENT 69 OUT DIMENSION DWG. ■ YES □ NO
36 DUTY S2-15MIN MSP1810AC3--F18E1
70 WIRING DIAGRAM
37 MOTOR PROTECTION ■ YES 3 THERMO-S / W KMS TP150/301