Subject : Supply of labor, tools, materials, equipment and technical supervision necessary for the Preventive Maintenance of Main
Substation (Power Transformer, Medium Voltage Switchgear, ATS, FEEDER PANEL, Auxiliary Transformer, Metering and Cables )
Dear Sir,
This is to submit our offer for the supply of labor, tools & equipment, and technical supervision and necessary materials to execute the above
requirements with the following scope of works, price quoted and terms.
A. Scope of Works:
1. Provide JGentech specialized technician, tools, and equipment.
2. Coordinate with end user for safety orientation and work permit.
3. Mobilization of Man Power and Equipment on site
4. Conduct thermal scanning before PMS to know hot spot and loose termination points
5. Set up of Mobile generator for lighting and instrument supply 220V, 3Phase, 60Hz
6. Isolation of Main Power Supply 34.5Kv ( By Meralco through CGT coordination )
7. Lock out/tag out/test out ( LOTOTO) procedure for the safety of working personnel
8. Draw out incoming Vacuum Circuit Breaker (1250A VCB) to secure that no incoming voltage of 34.5Kv
9. Check incoming power cables if there is still medium voltage is present using no contact medium voltage tester
III. PMS OF AIR CIRCUIT BREAKER (ACB) RATED 2,500A, AEG BRAND ATS -AN1
III.1 Draw out ACB and check all mechanical linkage
III.2 Conduct instrumentation test :
a. Insulation Resistance Test
Address: Block 4 Lot 13 Cherry Street, Sapphire Hills, Victoria Homes, Tunasan, Muntinlupa City
Telefax: +63 (2) 5569034 | +63 (2) 4780941
Email: sales@jgentech.com.ph | Website: www.jgentech.com Page1|3
JGENTECH ENTERPRISES
Power Generation Services
VIII. CHECKING OF ALL HIGH VOLTAGE CABLES AND LOW VOLTAGE CABLES
VIII. 1 Visual and physical inspection of each cables for any damage or cracked insulation
VIII.2 Check high voltage termination kit for possible damage or cracked insulation
VIII.3 Conduct insulation resistance test and high pot test if necessary
VIII.4 Check tightness of terminal lugs and check overheating or discoloration
VIII.5 Take pictures for documentation before and after PMS
Address: Block 4 Lot 13 Cherry Street, Sapphire Hills, Victoria Homes, Tunasan, Muntinlupa City
Telefax: +63 (2) 5569034 | +63 (2) 4780941
Email: sales@jgentech.com.ph | Website: www.jgentech.com Page2|3
JGENTECH ENTERPRISES
Power Generation Services
Address: Block 4 Lot 13 Cherry Street, Sapphire Hills, Victoria Homes, Tunasan, Muntinlupa City
Telefax: +63 (2) 5569034 | +63 (2) 4780941
Email: sales@jgentech.com.ph | Website: www.jgentech.com Page3|3