Grid Automation Products

Integrated Engineering Tool


User manual
IET600 Ver. 5.4 Feature Pack 1
Document ID: 1MRK500114-UEN
Issued: May 2022
Revision: X
Product version: IET600 v.5.4 FP1

© 2013 - 2022 Hitachi Energy. All rights reserved


Copyright
This document and parts thereof must not be reproduced or copied without written permission from
Hitachi Energy, and the contents thereof must not be imparted to a third party, nor used for any
unauthorized purpose.

The software or hardware described in this document is furnished under a license and may be used,
copied, or disclosed only in accordance with the terms of such license.

Trademarks
Hitachi Energy is a registered trademark of Hitachi Energy Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their respective holders.

Warranty
Please inquire about the terms of guarantee from your nearest Hitachi Energy representative.
Disclaimer
We reserve the right to make technical changes or modify the contents of this document without prior
notice.

The data, examples and diagrams in this manual are included solely for the concept or product
description and are not to be deemed as a statement of guarantee properties. All persons
responsible for applying the equipment addressed in this manual must satisfy themselves that each
intended application is suitable and acceptable, including that any applicable safety or other
operational requirements are complied with. In particular, any risks in applications where a system
failure and/or product failure would create a risk for harm to property or persons (including but not
limited to personal injuries or death) shall be the sole responsibility of the person or entity, applying
the equipment, and those so responsible are hereby requested to ensure that all measures are taken
to exclude or mitigate such risks.

This document has been carefully checked by Hitachi Energy but deviations cannot be completely
ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer.
Other than under explicit contractual commitments in no event shall Hitachi Energy be responsible or
liable for any loss or damage resulting from the use of this manual or the application of the
equipment.

Important notice
Experience has shown that reliable operation of our products is assured, providing the information
and recommendations contained in these Operating Instructions are adhered to.

It is scarcely possible for the instructions to cover every eventuality that can occur when using
technical devices and systems. We would therefore request the user to notify us directly or our agent
of any unusual observations or instances, in which these instructions provide no or insufficient
information.

In addition to these instructions, any applicable local regulations and safety procedures must always
be strictly observed both when connecting up and commissioning this equipment.

We expressly accept no responsibility or liability for any damage, which may result from operation of
this equipment, even if no reference is made to the particular situation in the Operating Instructions.
1MRK500114-UEN Rev. X Table of contents

Table of contents

Section 1 Preface..........................................................................................................15
1.1 IET600, a System Engineering Tool.................................................................................... 15
1.2 Organization of the Manual................................................................................................. 15
1.3 Use of This Manual for Lookups..........................................................................................16

Section 2 Important concepts in IET600.....................................................................17


2.1 Parallelization of Tasks........................................................................................................17
2.2 Naming of Objects...............................................................................................................17
2.2.1 Internal Names..................................................................................................................17
2.2.2 Customer Names.............................................................................................................. 17

Section 3 IET600 User Interface.................................................................................. 19


3.1 GUI Overview...................................................................................................................... 19
3.1.1 Main Menu.........................................................................................................................19
3.1.2 Navigation Trees............................................................................................................... 20
3.1.3 Editors............................................................................................................................... 21
3.1.4 Properties..........................................................................................................................23
3.1.5 Logging..............................................................................................................................24
3.1.6 Status Bar..........................................................................................................................24
3.2 ‘Table’-based Editors........................................................................................................... 25
3.2.1 Editor Elements.................................................................................................................25
3.2.2 Context Menus.................................................................................................................. 26
3.2.3 Show/Hide Columns..........................................................................................................27
3.2.4 Sort on Columns................................................................................................................28
3.2.5 Three State Checkboxes...................................................................................................29
3.2.6 Set and Clear Filters..........................................................................................................29
3.3 GUI and Engineering Workflow........................................................................................... 30
3.3.1 Execute a Task via Main Menu..........................................................................................31
3.3.2 Execute a Task via Navigation Tree and Editor.................................................................31
3.4 Options................................................................................................................................ 31
3.4.1 Options -> Appearance..................................................................................................... 32
3.4.2 Options -> User Settings................................................................................................... 32
3.4.3 Options -> Updates........................................................................................................... 33
3.4.4 Options -> About............................................................................................................... 34

Section 4 IET600 Data Organization........................................................................... 37


4.1 Overview............................................................................................................................. 37
4.1.1 Project Data.......................................................................................................................37
4.1.2 Project Backup.................................................................................................................. 38
4.1.3 Project Archives................................................................................................................ 38
4.1.4 Program and User Configuration Data.............................................................................. 39
4.2 Managing IET Projects........................................................................................................ 39
4.2.1 The ‘Projects’ Dialog......................................................................................................... 39

Integrated Engineering Tool 1


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Table of contents 1MRK500114-UEN Rev. X

4.2.2 Create a New Project........................................................................................................ 41


4.2.3 Open an Existing Project...................................................................................................42
4.2.4 Save Project Data............................................................................................................. 43
4.2.5 Import and Export Projects................................................................................................44
4.2.6 Archive a Project............................................................................................................... 44
4.2.7 Unarchive a Project........................................................................................................... 46
4.2.8 Change the Version of a Project........................................................................................46
4.2.9 Record Comments on Project Changes............................................................................47
4.3 Upgrade Projects.................................................................................................................48
4.3.1 Introduction........................................................................................................................48
4.3.2 Preliminary Remarks......................................................................................................... 48
4.3.3 Upgrade Preparation.........................................................................................................49
4.3.4 Upgrade Projects...............................................................................................................49
4.3.5 Upgrade by Importing IETPRJ Files..................................................................................50

Section 5 Engineering Workflow.................................................................................51


5.1 Overview............................................................................................................................. 51
5.2 Engineering of a New Project..............................................................................................51
5.2.1 Overview........................................................................................................................... 51
5.2.2 Basic Substation Configuration......................................................................................... 52
5.2.3 Basic Signal configuration.................................................................................................53
5.2.4 Full Signal configuration....................................................................................................53
5.2.5 Communication configuration............................................................................................53
5.2.6 Dataflow Configuration......................................................................................................53
5.3 Engineering of a Retrofit Project......................................................................................... 54
5.3.1 Overview........................................................................................................................... 54
5.3.2 Import of Existing Configuration........................................................................................ 55
5.3.3 Add New Elements............................................................................................................55
5.3.4 Signal Configuration of New Elements..............................................................................55
5.3.5 Communication Configuration of New Elements...............................................................55
5.3.6 Dataflow Configuration......................................................................................................55
5.4 Engineering of Dataflow Only..............................................................................................56
5.4.1 Overview........................................................................................................................... 56
5.4.2 Import of Existing Configuration........................................................................................ 56
5.4.3 Update of SLD Configuration and LN Mapping................................................................. 57
5.4.4 Dataflow Configuration......................................................................................................57

Section 6 Substation Specification.............................................................................59


6.1 IEC 61850 Modelling of a Substation.................................................................................. 59
6.1.1 Substation ‘Containers’..................................................................................................... 59
6.1.2 Substation Equipment....................................................................................................... 59
6.2 Creating Substation ‘Containers’.........................................................................................60
6.2.1 Overview........................................................................................................................... 60
6.2.2 Create a Substation...........................................................................................................60
6.2.3 Create a Voltage Level......................................................................................................61
6.2.4 Create a Bay..................................................................................................................... 61
6.2.5 Create a ‘Function’............................................................................................................ 62

2 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Table of contents

6.2.6 Create a ‘Subfunction’.......................................................................................................63


6.2.7 Create a ‘Subequipment’...................................................................................................64
6.2.8 Create an ‘Equipment Function’........................................................................................ 64
6.2.9 Create an ‘Equipment Subfunction’...................................................................................65
6.3 Creating Equipment: The ‘SLD’ Editor................................................................................ 66
6.3.1 Overview........................................................................................................................... 66
6.3.2 Create a Single Line Diagram........................................................................................... 66
6.4 Creating a Substation by Importing SCD/SSD File............................................................. 67

Section 7 IED Engineering........................................................................................... 69


7.1 Introduction..........................................................................................................................69
7.1.1 IED Roles.......................................................................................................................... 69
7.1.2 IED Status Editor...............................................................................................................69
7.1.3 IED Settings Editor............................................................................................................ 70
7.1.4 LN Data Editor...................................................................................................................72
7.1.5 IED Services Editor........................................................................................................... 72
7.1.6 IED Capabilities Editor...................................................................................................... 74
7.2 Creating and Configuring IEDs............................................................................................75
7.2.1 Overview........................................................................................................................... 75
7.2.2 Create New IED................................................................................................................ 75
7.2.3 Create New Protection/Control IED...................................................................................78
7.2.4 Create New Switch............................................................................................................78
7.2.5 Create New HMI................................................................................................................80
7.2.6 Configure IEDs..................................................................................................................82
7.3 Updating IEDs..................................................................................................................... 86
7.3.1 Overview........................................................................................................................... 86
7.3.2 Compare IEDs...................................................................................................................86
7.3.3 Update one IED.................................................................................................................87
7.3.4 Update Several IEDs Together..........................................................................................89
7.4 Deleting IEDs...................................................................................................................... 91
7.4.1 Overview........................................................................................................................... 91
7.4.2 Delete an IED....................................................................................................................91
7.4.3 Delete the Contents of an IED...........................................................................................92
7.5 Mapping LNs to Substation Elements (“LN Mapping”)........................................................ 93
7.5.1 Overview........................................................................................................................... 93
7.5.2 LN Mapping Restrictions................................................................................................... 94
7.5.3 Map LNs in Bays............................................................................................................... 95
7.6 Disturbance Recording Configuration................................................................................. 96
7.6.1 Introduction........................................................................................................................96
7.6.2 Configuration.....................................................................................................................96
7.6.3 Disturbance Recording Directory Recommendations....................................................... 98
7.6.4 Export................................................................................................................................98
7.7 Dynamic Datasets............................................................................................................... 98
7.8 SNMP Configuration Usage................................................................................................ 99
7.8.1 SNMP Properties Configuration...................................................................................... 100
7.8.2 SNMP Configuration of Signals.......................................................................................100

Integrated Engineering Tool 3


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Table of contents 1MRK500114-UEN Rev. X

7.9 PCM Template Usage....................................................................................................... 101


7.9.1 PCM Template Configuration.......................................................................................... 101

Section 8 IEC 61850 Subnetwork Engineering........................................................ 103


8.1 Introduction........................................................................................................................103
8.2 Subnetwork Conditions and Limitations............................................................................ 103
8.2.1 IEC 61850 Subnetworks..................................................................................................103
8.2.2 Modelling of Other Protocols........................................................................................... 103
8.2.3 Modelling of HMI............................................................................................................. 103
8.3 Subnetwork Configuration................................................................................................. 103
8.3.1 Create a Subnetwork.......................................................................................................103
8.3.2 Connect IEDs to a Subnetwork in the Subnetwork Editor............................................... 105
8.3.3 Connect IEDs to a Subnetwork in the Communication Tree........................................... 106
8.3.4 Edit IP addresses............................................................................................................ 107

Section 9 Communication Configuration Engineering........................................... 109


9.1 Introduction........................................................................................................................109
9.2 The ‘CCD’ Editor............................................................................................................... 109
9.2.1 Diagram View.................................................................................................................. 109
9.2.2 Table View....................................................................................................................... 110
9.2.3 Navigate Within Views..................................................................................................... 111
9.2.4 Toolbar............................................................................................................................. 111
9.2.5 IED Shapes......................................................................................................................111
9.2.6 Detail View for Selected IED........................................................................................... 113
9.2.7 Fade Unselected Items....................................................................................................113
9.2.8 Zoom Diagram.................................................................................................................115
9.2.9 Magnify a Section............................................................................................................ 116
9.2.10 Show Bird’s Eye View......................................................................................................117
9.2.11 Draw Rectangle Shape....................................................................................................118
9.2.12 Draw Annotation Shape...................................................................................................119
9.2.13 Print Out Diagram............................................................................................................120
9.2.14 Export Image of Diagram................................................................................................ 121
9.2.15 Shortcut Keys..................................................................................................................121
9.3 Engineering Workflow....................................................................................................... 122
9.4 Creating and Configuring IEDs..........................................................................................122
9.4.1 Configure Communication Properties............................................................................. 122
9.5 Placing IEDs......................................................................................................................123
9.5.1 Move an IED Manually.................................................................................................... 124
9.5.2 Auto-Arranging IEDs....................................................................................................... 124
9.6 Connecting IEDs............................................................................................................... 125
9.6.1 Add Connection...............................................................................................................125
9.6.2 Remove Connection........................................................................................................125
9.6.3 Reconnect Connection....................................................................................................125
9.6.4 Reroute Connection Manually......................................................................................... 125
9.6.5 Add / Remove Connection Via-Point...............................................................................126

Section 10 Dataflow Engineering................................................................................ 127

4 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Table of contents

10.1 Introduction........................................................................................................................127
10.1.1 Overview......................................................................................................................... 127
10.1.2 Engineering Approach.....................................................................................................127
10.1.3 Common Problems in Dataflow Engineering...................................................................128
10.2 Dataset Configuration........................................................................................................128
10.2.1 Datasets Editor................................................................................................................128
10.2.2 Create Datasets.............................................................................................................. 129
10.2.3 Edit Datasets...................................................................................................................130
10.2.4 Add Dataset Entries........................................................................................................ 130
10.2.5 Delete Dataset Entries.................................................................................................... 132
10.2.6 Dataset Edition Compatibility.......................................................................................... 133
10.3 RCB Data Configuration....................................................................................................135
10.3.1 RCB Data Editor..............................................................................................................135
10.3.2 Create RCBs................................................................................................................... 136
10.3.3 Delete RCBs....................................................................................................................137
10.3.4 Edit RCBs........................................................................................................................138
10.3.5 Reuse “Deleted” RCBs....................................................................................................138
10.4 RCB Client Configuration.................................................................................................. 138
10.4.1 Prerequisites................................................................................................................... 138
10.4.2 RCB Client Editor............................................................................................................ 138
10.4.3 Basic Workflow for RCB Client Engineering....................................................................139
10.4.4 Configure Default Clients................................................................................................ 139
10.4.5 Configure RCB Clients.................................................................................................... 140
10.5 LCB Data Configuration.................................................................................................... 141
10.5.1 LCB Data Editor.............................................................................................................. 141
10.5.2 Create LCBs....................................................................................................................142
10.5.3 Delete LCBs.................................................................................................................... 143
10.5.4 Edit LCBs........................................................................................................................ 143
10.6 GCB Data Configuration....................................................................................................144
10.6.1 GCB Data Editor..............................................................................................................144
10.6.2 Create GCBs................................................................................................................... 145
10.6.3 Delete GCBs................................................................................................................... 146
10.6.4 Edit GCBs........................................................................................................................147
10.6.5 Reuse “Deleted” GCBs....................................................................................................147
10.7 GCB Client Configuration.................................................................................................. 147
10.7.1 Prerequisites................................................................................................................... 147
10.7.2 GCB Client Editor............................................................................................................ 147
10.7.3 Configure direct GCB Clients.......................................................................................... 148
10.7.4 Configure routable GCB Clients...................................................................................... 149
10.7.5 Configure filter for GCB Clients....................................................................................... 149
10.7.6 GCB monitoring configuration......................................................................................... 150
10.7.7 MAC-Layer Security configuration for GCBs...................................................................152
10.8 SVCB Data Configuration..................................................................................................153
10.8.1 SVCB Data Editor............................................................................................................153
10.8.2 Create SVCBs................................................................................................................. 155
10.8.3 Delete SVCBs................................................................................................................. 155

Integrated Engineering Tool 5


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Table of contents 1MRK500114-UEN Rev. X

10.8.4 Edit SVCBs......................................................................................................................156


10.8.5 Reuse “Deleted” SVCBs..................................................................................................156
10.9 SVCB Client Configuration................................................................................................ 156
10.9.1 Prerequisites................................................................................................................... 156
10.9.2 SVCB Client Editor..........................................................................................................156
10.9.3 Configure direct SVCB Clients........................................................................................ 157
10.9.4 Configure routable SVCB Clients.................................................................................... 158
10.9.5 Configure filter for SVCB Clients..................................................................................... 158
10.9.6 SVCB monitoring configuration....................................................................................... 159
10.9.7 MAC-Layer Security configuration for SVCBs.................................................................161
10.10 ‘Inputs’ Configuration.........................................................................................................162
10.10.1 Overview......................................................................................................................... 162
10.10.2 Inputs Editor.................................................................................................................... 162
10.10.3 Create Inputs...................................................................................................................163
10.10.4 Delete Inputs................................................................................................................... 163
10.10.5 Remapping Inputs to Different Parent LNs......................................................................165
10.10.6 Connections Resolving....................................................................................................166
10.10.7 Configure Predefined Inputs (Late Binding).................................................................... 167
10.10.7.1 Configure Mapping to Predefined DATA Attributes (DAs).......................................... 168
10.10.7.2 Configure Mapping to Predefined DATA Objects (DOs).............................................169
10.11 Dataflow Consistency Check.............................................................................................172
10.12 Dataflow Communication - IEC61850 Signal List..............................................................174
10.13 Dataflow Communication - IEC61850 Dataflow................................................................ 174

Section 11 Customer Name Engineering................................................................... 177


11.1 Overview........................................................................................................................... 177
11.2 The 'Naming' Editor........................................................................................................... 177
11.2.1 Rename IED, Internal Name........................................................................................... 177
11.2.2 Rename Bay, Internal Name........................................................................................... 178
11.2.3 Rename Substation or Voltage Level, Internal Name..................................................... 178
11.2.4 Hierarchical Customer Names........................................................................................ 179
11.2.5 Non-hierarchical Customer Names................................................................................. 179
11.2.6 Customer Path/Name Display......................................................................................... 179
11.3 LD Naming........................................................................................................................ 179
11.3.1 Customization of Logical Device Names.........................................................................180
11.3.2 Configuring Control Block Clients....................................................................................180
11.3.3 Displaying LDs Hierarchically..........................................................................................180

Section 12 HMI Engineering........................................................................................ 183


12.1 Introduction........................................................................................................................183
12.1.1 User Interface..................................................................................................................183
12.1.2 Engineering Workflow..................................................................................................... 183
12.2 HMI Creation and Configuration........................................................................................184
12.2.1 Overview......................................................................................................................... 184
12.2.2 Preliminary: Configure Project OI....................................................................................185
12.2.3 Create an HMI................................................................................................................. 185
12.2.4 Create a Hot-Standby (HSB) HMI System...................................................................... 186

6 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Table of contents

12.3 Signal Creation..................................................................................................................188


12.3.1 Overview......................................................................................................................... 188
12.3.2 Copy HMI Signals from another IED............................................................................... 188
12.3.3 Insert HMI Signals from Signal Templates...................................................................... 189
12.3.4 Import a MicroSCADA Database File..............................................................................189
12.3.5 Create HMI Signals manually..........................................................................................190
12.4 Signal Configuration.......................................................................................................... 190
12.4.1 Overview......................................................................................................................... 190
12.4.2 HMI Data Editor...............................................................................................................191
12.4.3 Generic HMI Signals....................................................................................................... 191
12.4.4 HMI Text Rules................................................................................................................ 192
12.4.5 Mapping Signals to IEC 61850 Attributes........................................................................196
12.4.6 Mapping Signals to SNMP OIDs..................................................................................... 196
12.4.7 HMI Data Consistency Check......................................................................................... 197
12.5 Signal Client Configuration................................................................................................199
12.5.1 Overview......................................................................................................................... 199
12.5.2 The Signal Clients Editor.................................................................................................199
12.5.3 Select Signals to be Sent to HMI Manually..................................................................... 200
12.5.4 Copy Full Signal Client HMI Configuration from Existing HMI.........................................200
12.6 Configuration of Signals of Non-IEC-61850 IEDs............................................................. 202
12.6.1 Introduction......................................................................................................................202
12.6.2 Supported Protocols........................................................................................................202
12.6.3 Engineering Workflow..................................................................................................... 202
12.6.4 Configure 'Mapped To' Attribute of Signals..................................................................... 203
12.6.4.1 Pseudo Mapping to Resolve References...................................................................203
12.6.5 Configure Signal Addresses............................................................................................203
12.7 HMI Status Text Configuration...........................................................................................204
12.7.1 Overview......................................................................................................................... 204
12.7.2 View/Edit Status Texts.....................................................................................................204
12.7.3 Add Status Texts............................................................................................................. 205
12.8 Merge HMI Data in MicroSCADA...................................................................................... 206
12.8.1 Introduction......................................................................................................................206
12.8.2 Engineering Procedure and Restrictions.........................................................................206
12.8.3 Preparation of Projects....................................................................................................207
12.9 Working With User Defined Signal Templates...................................................................207
12.9.1 Overview......................................................................................................................... 207
12.9.2 Create new Signal Template........................................................................................... 208
12.9.3 Insert Signal Template.....................................................................................................208
12.9.4 Maintaining Templates.....................................................................................................209

Section 13 HMI Mirroring..............................................................................................211


13.1 Overview............................................................................................................................211
13.1.1 User Interface.................................................................................................................. 211
13.2 Configure Clients and Servers...........................................................................................211
13.2.1 Configure an HMI to be a Mirroring Client....................................................................... 211
13.2.2 Configure an HMI to be a Mirroring Server for one Specific Client..................................211

Integrated Engineering Tool 7


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Table of contents 1MRK500114-UEN Rev. X

13.3 Configure Signals to be Mirrored.......................................................................................212


13.3.1 Mirrored vs. Copied Signals............................................................................................ 216
13.3.2 Configuring Copied Signals.............................................................................................216
13.3.3 Signals Which Cannot be Mirrored..................................................................................217
13.4 Edit Mirrored signals..........................................................................................................217
13.4.1 Inheritance.......................................................................................................................217
13.4.2 Blocked Attributes........................................................................................................... 217
13.5 Common Mirroring Configurations.................................................................................... 218
13.5.1 Mutual Mirroring in the Same Project.............................................................................. 218
13.5.2 Mirroring with one NCC Connection................................................................................218
13.5.3 Mirroring with two NCC Connections.............................................................................. 219
13.5.4 Mirroring to a Control Center...........................................................................................220
13.5.5 Mirroring Across Two Projects With one Common NCC Gateway..................................220
13.5.6 Mirroring Across Two Projects With Restricted Data Exchange......................................221

Section 14 NCC Gateway Engineering....................................................................... 223


14.1 Introduction........................................................................................................................223
14.1.1 Supported Gateway Products......................................................................................... 223
14.1.2 Supported Gateway Protocols.........................................................................................223
14.1.3 User Interface..................................................................................................................223
14.1.4 Prerequisites................................................................................................................... 223
14.2 Engineering Workflow....................................................................................................... 223
14.3 Creating and Configuring Gateways................................................................................. 224
14.3.1 Overview......................................................................................................................... 224
14.3.2 Create a Stand-Alone Gateway.......................................................................................225
14.3.3 Create a Gateway combined with HMI............................................................................226
14.3.4 Create a Hot-Standby (HSB) Gateway System...............................................................227
14.4 Creating NCCs.................................................................................................................. 229
14.4.1 Overview......................................................................................................................... 229
14.4.2 Create a Stand-Alone NCC............................................................................................. 229
14.4.3 Create a Hot-Standby (HSB) NCC System..................................................................... 230
14.4.4 Hot-Standby(HSB) HMI synchronization......................................................................... 232
14.5 Connecting Gateways to NCCs.........................................................................................234
14.5.1 Overview......................................................................................................................... 234
14.5.2 Connect Gateway to NCC............................................................................................... 234
14.5.3 IEC 101/104 Special Parameters.................................................................................... 238
14.6 Selecting Signals for NCCs............................................................................................... 239
14.6.1 Overview......................................................................................................................... 239
14.6.2 The Signal Clients Editor.................................................................................................239
14.6.3 Select Signals to Be Sent to NCC................................................................................... 240
14.7 Grouping Signals...............................................................................................................240
14.7.1 Overview......................................................................................................................... 241
14.7.2 Create an Indication Group............................................................................................. 241
14.7.3 Create a Command Group.............................................................................................. 242
14.8 Copying a Configuration from an Existing NCC................................................................ 243
14.8.1 Copy Full Signal Client NCC Configuration from Existing NCC...................................... 243

8 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Table of contents

14.9 Configure NCC Data......................................................................................................... 244


14.9.1 Overview......................................................................................................................... 244
14.9.2 NCC Data Editor..............................................................................................................244
14.9.3 Configure NCC Signal Properties....................................................................................245
14.9.4 Configure NCC Addresses.............................................................................................. 245
14.9.5 Data Model Generation for IEC 61850 Server................................................................ 247
14.10 Merge NCC Data in MicroSCADA.....................................................................................249
14.10.1 Introduction......................................................................................................................249
14.10.2 Engineering Procedure and Restrictions.........................................................................250
14.10.3 Preparation of Projects....................................................................................................250
14.10.4 Calculate the NCC Gateway Group Offset......................................................................251
14.10.5 Configure the NCC Gateway Group Offset..................................................................... 251

Section 15 Bay-level Gateway Engineering............................................................... 255


15.1 Overview........................................................................................................................... 255
15.2 SPA-ZC40x........................................................................................................................255

Section 16 VLAN Engineering..................................................................................... 257


16.1 Introduction........................................................................................................................257
16.1.1 VLAN Properties..............................................................................................................257
16.2 VLAN Editor.......................................................................................................................257
16.3 VLAN Calculation.............................................................................................................. 259

Section 17 Data Import/Export.................................................................................... 261


17.1 ICD/IID File Exchange within a Project............................................................................. 261
17.1.1 Import an ICD/IID File to Update IEDs............................................................................ 261
17.1.2 Export an ICD/IID File..................................................................................................... 261
17.2 SCD File Exchange Within a Project.................................................................................261
17.2.1 Import an SCD File to Create a Project...........................................................................261
17.2.2 Import an SCD File to Update IEDs................................................................................ 263
17.2.3 Export an SCD File..........................................................................................................263
17.2.4 Export an SCD File, Mixed Systems............................................................................... 265
17.3 SSD File Import................................................................................................................. 267
17.3.1 Overview......................................................................................................................... 267
17.3.2 Substation Specification..................................................................................................268
17.3.3 LN Mapping Specification................................................................................................268
17.3.4 Data Type Templates Specification................................................................................. 268
17.3.5 IED Specification.............................................................................................................268
17.3.6 Subnetwork Specification................................................................................................268
17.3.7 Import an SSD File.......................................................................................................... 269
17.4 SED File Exchange Between Projects.............................................................................. 270
17.4.1 Introduction......................................................................................................................270
17.4.2 Basic Mechanism............................................................................................................ 271
17.4.3 Pre-Conditions for SED Data Exchange......................................................................... 271
17.4.4 IET600 behavior in SED Data Exchange........................................................................ 272
17.4.5 Good Engineering Practices in SED Data Exchange......................................................272
17.4.6 Example Transformer Interlocking via GOOSE...............................................................273

Integrated Engineering Tool 9


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Table of contents 1MRK500114-UEN Rev. X

17.4.7 Step 1: Export of an SED File in Project A...................................................................... 274


17.4.8 Step 2: Import of SED File into Project B........................................................................ 278
17.4.9 Step 3: Add Dataflow to Foreign IEDs in Project B......................................................... 280
17.4.10 Step 4: Re-Export Foreign IEDs and own IEDs from Project B.......................................281
17.4.11 Step 5: Import of SED File into Project A........................................................................ 282
17.4.12 Step 6: Add Dataflow to Foreign IEDs in Project A......................................................... 283
17.4.13 Step 7: Re-export Foreign IEDs from Project A.............................................................. 283
17.4.14 Step 8: Re-Import of SED File into Project B.................................................................. 284
17.4.15 IET600 SED File Content................................................................................................ 285
17.5 HMI Status Texts Exchange.............................................................................................. 286
17.5.1 Format of Status Text Files..............................................................................................286
17.5.2 Import Status Texts..........................................................................................................286
17.5.3 Export Status Texts......................................................................................................... 287
17.6 HMI Signal Information Exchange.....................................................................................287
17.6.1 Overview......................................................................................................................... 287
17.6.2 Exchange File Formats................................................................................................... 287
17.6.3 Import Behavior of IET600.............................................................................................. 288
17.6.4 Import Considerations..................................................................................................... 289
17.6.5 Import a MicroSCADA ‘lof’ File........................................................................................289
17.6.6 Import a MicroSCADA ‘sfx’ File....................................................................................... 292
17.6.7 Import a MicroSCADA ‘csv’ File with Process Object Data.............................................295
17.6.8 Import a MicroSCADA ‘sasmsc’ File............................................................................... 298
17.6.9 Import Signal Overview................................................................................................... 301
17.6.10 MicroSCADA Comparison Preferences dialog................................................................303
17.6.11 Export a MicroSCADA ‘lof’ File....................................................................................... 303
17.6.12 Export a MicroSCADA ‘sfx’ File.......................................................................................305
17.6.13 Export a MicroSCADA ‘csv’ file with Process Object Data..............................................307
17.6.14 Export a MicroSCADA ‘sasmsc’ file................................................................................ 307
17.7 NCC Gateway Signal Information Exchange.................................................................... 308
17.7.1 Overview......................................................................................................................... 308
17.7.2 Import COM500 Configuration File (XRF)....................................................................... 309
17.7.3 Export COM500 Configuration File (XRF).......................................................................310
17.7.4 Export Configuration Data for Other NCC Gateways...................................................... 310

Section 18 Customer Signal Lists............................................................................... 311


18.1 Introduction........................................................................................................................311
18.2 Customizing a Template.................................................................................................... 311
18.2.1 Copy the Default Template into Your Project Folder........................................................311
18.2.2 Customize the Template..................................................................................................312
18.3 Customizing Filtering, Grouping, Sorting and Formatting................................................. 312
18.3.1 Open the ‘Export Customer Signal List’ Dialog............................................................... 312
18.3.2 Configure Filtering........................................................................................................... 314
18.3.3 Configure Grouping.........................................................................................................315
18.3.4 Configure Sorting............................................................................................................ 317
18.3.5 Configure Formatting.......................................................................................................319
18.4 Export a Customer Signal List...........................................................................................322

10 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Table of contents

18.4.1 First Export......................................................................................................................322


18.4.2 Update an Existing Customer Signal List........................................................................ 326
18.4.3 Editing exported Customer Signal List............................................................................ 327
18.5 Import a Customer Signal List........................................................................................... 329

Section 19 Protecting IEDs Against Changes............................................................333


19.1 Introduction........................................................................................................................333
19.2 Applying Protection........................................................................................................... 333
19.2.1 General Principles...........................................................................................................333
19.2.2 Configuring and Editing Protection..................................................................................334
19.2.3 Displaying Protection.......................................................................................................334
19.2.4 RCB Dataflow Protection.................................................................................................335
19.2.5 GCB Dataflow Protection................................................................................................ 336
19.2.6 SVCB Dataflow Protection.............................................................................................. 336
19.2.7 HMI Engineering Protection............................................................................................ 336
19.3 Engineering Workflow and Protection............................................................................... 337
19.3.1 GCB Dataflow Protection After FAT................................................................................ 337
19.3.2 GCB Dataflow Protection of Third-Party Engineered IEDs............................................. 337
19.3.3 Commissioning Bays.......................................................................................................337
19.3.4 Protecting HMIs While Engineering a Gateway.............................................................. 338

Section 20 Migration of Engineering Data from Older Projects............................... 339


20.1 Overview........................................................................................................................... 339
20.2 Migration Effort Considerations......................................................................................... 339
20.2.1 Scenarios That Will Profit from Migration to IET600....................................................... 339
20.2.2 Scenarios to be Evaluated for Migration to IET600.........................................................339
20.2.3 Scenarios not Very Suitable for Migration to IET600.......................................................339
20.3 Migration of Systems of Different Types............................................................................340
20.3.1 Existing IEC 61850-based System with MicroSCADA Station Level.............................. 340
20.3.2 Existing Non-IEC 61850 System with MicroSCADA Station Level..................................340
20.3.3 Integration of Non-61850 IEDs into a 61850 Substation................................................. 340
20.4 Migration Step Details....................................................................................................... 341
20.4.1 Prerequisites................................................................................................................... 341
20.4.2 Import SCD file................................................................................................................ 341
20.4.3 Create HMIs and Gateways............................................................................................ 341
20.4.4 Create NCCs................................................................................................................... 341
20.4.5 Import HMI and COM500 Configuration..........................................................................341

Section 21 Diagnostics................................................................................................ 343

Section 22 Annex: Naming Conventions....................................................................347


22.1 Introduction........................................................................................................................347
22.1.1 Introduction......................................................................................................................347
22.1.2 General Conventions in IEC 81346.................................................................................347
22.1.3 Hierarchies in IEC 81346 and IEC 61850....................................................................... 347
22.2 Default Substation Naming................................................................................................347
22.2.1 Typical Bay, Line............................................................................................................. 347

Integrated Engineering Tool 11


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Table of contents 1MRK500114-UEN Rev. X

22.2.2 Typical Bay, Transformer.................................................................................................349


22.2.3 Typical Bay, Bus Coupler................................................................................................ 350
22.2.4 Typical Diameter, Line/Transformer................................................................................ 350

Section 23 Annex: Switch Configuration................................................................... 353


23.1 The Switch Data Model..................................................................................................... 353
23.2 MAUs.................................................................................................................................353
23.2.1 Short description............................................................................................................. 353
23.2.2 References......................................................................................................................354

Section 24 Annex: MicroSCADA OI Settings............................................................. 355


24.1 Setting the OI Attribute...................................................................................................... 355
24.2 OI Settings on Project....................................................................................................... 355
24.2.1 Default Settings...............................................................................................................355
24.2.2 Configuration...................................................................................................................356
24.3 OI Settings for MicroSCADA............................................................................................. 356
24.3.1 Configuration...................................................................................................................356
24.4 Known Limitations............................................................................................................. 357

Section 25 Annex: Mirroring Command Group Logic...............................................359


25.1 Introduction........................................................................................................................359
25.2 Predefined Mirroring Group...............................................................................................359

Section 26 Annex: NCC Command Group Logic.......................................................361


26.1 Introduction........................................................................................................................361
26.2 Predefined Command Groups...........................................................................................361
26.2.1 Group of 5 Fixed Commands with 1 Fixed Feedback Indication.....................................361
26.2.2 Group of 1 Fixed Command with 1 Fixed Feedback Indication.......................................362
26.2.3 Group of 2 Fixed Commands with no Feedback Indication.............................................363
26.2.4 Group of 4 Fixed Commands with 1 Fixed Feedback Indication.....................................363
26.3 Flexible Command Groups................................................................................................363

Section 27 Annex: IED Capabilities............................................................................ 365


27.1 Introduction........................................................................................................................365
27.2 Capabilities Description.....................................................................................................365
27.3 Common Corrections with IED Capabilities...................................................................... 370
27.3.1 Service ConfReportControl, Max attribute.......................................................................370
27.3.2 Service ConfDataset, maxAttributes attribute................................................................. 371
27.3.3 Service ConfDataset, Modify attribute.............................................................................372
27.3.4 Client Services................................................................................................................ 372
27.3.5 Dataflow Cannot be Created or Edited at All...................................................................373

Section 28 Annex: IET600 and IEC 61850 Edition Handling..................................... 375


28.1 IEC 61850 Classification................................................................................................... 375
28.1.1 IEC 61850 Edition, Version and Revision........................................................................375
28.1.2 IEC 61850 Namespaces................................................................................................. 375
28.1.3 SCL Elements Conflicting With SCL Namespace Version 2003..................................... 375
28.1.4 IED DATA Conflicting With Namespace Version 2003.................................................... 376

12 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Table of contents

28.2 IEC 61850 Compatibility Issues........................................................................................ 376


28.2.1 SCL Namespace compatibility Problems........................................................................ 376
28.2.2 Name Length Problems...................................................................................................377
28.2.3 Dataflow Compatibility Problems.....................................................................................377
28.2.4 CDC compatibility problems............................................................................................ 377

Section 29 Annex: IET600 Mixed System Engineering............................................. 379


29.1 Mixed Systems, Engineering Scenarios............................................................................379
29.1.1 Extension of an Existing Substation with Edition 1 IEDs.................................................379
29.1.2 Mixed Substation Specified by Customer........................................................................380
29.2 IET600 Mixed System Engineering................................................................................... 380
29.2.1 Put IEDs of Different Versions Into Different Subnetworks............................................. 382
29.2.2 SCD Export..................................................................................................................... 383
29.2.3 SCD files Version 2007A.................................................................................................385
29.3 IET600 Versioning of IEC 61850 Items............................................................................. 385
29.3.1 Versioning Based on IED DATA Namespaces................................................................ 385
29.3.2 Versioning Based on XML Namespace...........................................................................386
29.3.3 Versioning of Switch IEDs............................................................................................... 386

Section 30 Annex: Client Driven Engineering............................................................387


30.1 Introduction........................................................................................................................387
30.2 Client Driven Engineering Workflow..................................................................................387
30.2.1 Requirements..................................................................................................................387
30.2.1.1 IED Capabilities..........................................................................................................387
30.2.1.2 IED Settings............................................................................................................... 387
30.2.1.3 SCL File and Server IED............................................................................................388
30.2.2 Workflow..........................................................................................................................388
30.3 Elements affected by Client Driven Engineering............................................................... 390
30.3.1 Server IEDs..................................................................................................................... 390
30.3.2 Client IEDs...................................................................................................................... 390

Section 31 Annex: Inputs Predefined from IED (Late Binding)................................ 391


31.1 Introduction........................................................................................................................391
31.2 Late Binding SCL Attributes.............................................................................................. 391
31.3 Late Binding Workflow.......................................................................................................391
31.3.1 IEC 61850 Intended Workflow.........................................................................................391
31.3.2 IEC 61850 Late Binding Mapping Rules......................................................................... 392
31.4 Configuration of Late Binding in the System Configuration Tool....................................... 393
31.4.1 Implementation in IET600............................................................................................... 393

Section 32 Annex: OPC server to ISS client conversion.......................................... 395

Section 33 Annex: SCL document security............................................................... 397

Section 34 Annex: IEC 61850 Mapping.......................................................................399

Section 35 Annex: IEC 61850 Reference creation..................................................... 401

Section 36 References................................................................................................. 405

Integrated Engineering Tool 13


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Table of contents 1MRK500114-UEN Rev. X

Section 37 Glossary of Terms..................................................................................... 407

14 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 1
Preface

Section 1 Preface GUID-C749075D-31DA-47CB-BD33-8378D0B00DA8 v1

1.1 IET600, a System Engineering Tool GUID-9CE211A8-A317-4F73-9820-0144DACF2F4E v1

ABB’s Integrated Engineering Toolbox (IET600) is a system engineering tool, designed to engineer
Substation Automation systems (with emphasis on but not exclusively for IEC‑61850‑based
Systems).

IET600 provides:

• Engineering of IEC-61850-Systems (IET600 is a System Configuration tool as defined by IEC


61850):
• Simple integration of IEC‑61850‑based ABB and third-party devices that follow the IEC
61850 standard.
• High scalability from small substations to large switchyards.
• Use of the standardized IEC 61850 Substation Configuration Language (SCL) to
exchange data with other engineering tools.
• Creation of Single Line Diagrams and Communication Configuration Diagrams.
• IEC-61850‑compatible extensions to allow an enhanced modelling of complex
communication configurations.

• Engineering of ABB MicroSCADA systems (SYS600/C, COM500).


• Database engineering for multiple systems (including hot-standby systems and database
mirroring).
• COM500 Gateway engineering.

1.2 Organization of the Manual GUID-C172699E-5DEE-4614-9164-F988B1099BF5 v1

This manual is organized as follows:

• Chapter Important concepts in IET600 introduces some new concepts which make engineering
considerably more efficient. Read this to understand and take full advantage of the efficiency-
enhancing features of IET600.
• Chapter IET600 User Interface introduces the IET600 user interface. Read this to understand
how to access and edit you data in IET600 and to learn about GUI features available in most of
the editors.
• Chapter IET600 Data Organization gives a short overview of how IET600 organizes and stores
data. Read this to get an overview how to backup and restore your data and how to exchange
IET600 project data.
• Chapter Engineering Workflow describes different engineering workflows, read this to
understand which tasks can be executed in parallel to gain time during engineering and to
decide which workflow is suitable for your project.
• Chapters Substation Specification to Dataflow Engineering describe the engineering steps
related to IEC 61850 engineering. Read any of these chapters to get detailed information about
using IET600 as an IEC 61850 System configuration tool.
• Chapter Customer Name Engineering describes the engineering of customer names, relevant
for both IEC 61850 engineering and MicroSCADA database engineering.
• Chapters HMI Engineering to NCC Gateway Engineering describe the engineering steps related
to MicroSCADA database engineering. Read any of these chapters to get detailed information
about using IET600 as a MicroSCADA database configuration tool.
• Chapter Bay-level Gateway Engineering deals with a few special situations regarding Bay-level
Gateways.
• Chapter Data Import/Export describes the Data Exchange between IET600 and other tools with
different data formats.
• Chapter Customer Signal Lists describes how to customize and export Customer Signal Lists.

Integrated Engineering Tool 15


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 1 1MRK500114-UEN Rev. X
Preface

• Chapter Protecting IEDs Against Changes describes how IEDs may be protected against further
changes; a feature useful in Commissioning.
• Chapter Migration of Engineering Data from Older Projects describes how to proceed when
migrating a project from another environment to IET600. Read this chapter to understand how
old projects can be migrated and to decide which workflow is suited best to your specific
migration.
• Chapter Diagnostics describes how to analyze and detect inconsistencies inside the project.

1.3 Use of This Manual for Lookups GUID-C0D55A97-11D0-4B16-8A33-AEB17D4B4D2A v1

This manual has grown thick enough that it becomes laborious to read it completely. Many users will
consult the manual once they face a problem. In such a case there are some ways to efficiently find
the information you are looking for.

1. Search for the word of what you actually have problems with (e.g. a menu item, an IED Service
etc.), e.g. “ConfReportControl.Max”.
2. Search for a more generic word, but still related to what you actually have problems with, e.g.
“ConfReportControl”.
3. Search for a word related to the engineering step you want to perform, e.g. “RCB Client”.
4. Look at the index to find a title related to the engineering step you want to perform.

16 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 2
Important concepts in IET600

Section 2 Important concepts in IET600 GUID-AF340F1D-3406-4796-8F8C-C5297C0CBCE2 v1

2.1 Parallelization of Tasks GUID-23A1A4B0-4CBF-474F-89D6-DB9998585405 v1

System engineering is often considered as a linear process starting at base design and ending with
commissioning of the system. In practice, however, situations frequently occur where engineering
tasks need to be done in parallel and merged later. Common examples of such situations include:

• Station-level engineering is required early in the project, before the bay-level engineering has
begun (e.g., a preliminary SAS database is needed for SCADA engineering or a signal list for
discussions with the customer).
• Different project parts are engineered by different people (e.g. bay-level engineering and station-
level engineering are often assigned to two different engineering groups working in parallel to
reduce project execution time).
• When changes and corrections are needed, resulting in re-engineering of some parts of the
project (for example, a commissioning engineer needs to implement corrections after an
acceptance test).

IET600 supports parallel workflows by decoupling engineering tasks within the tool itself, allowing the
system engineer to work flexibly and merge these various parts at a later stage. Engineering of the
station level is decoupled from the IEC 61850 communication engineering, reducing the impact of
changes considerably.

2.2 Naming of Objects GUID-E5D781DA-A132-498D-A6EE-E8E5E5587A76 v1

Technical projects very often have the difficulty that the manufacturer has one naming convention
and the customer has another one. The customer needs his naming scheme for efficient operation;
the manufacturer needs his own scheme for efficient commissioning and also to be able to provide
efficient support and in case of expansion projects later.

Additionally, the IEC 61850 standard imposes certain restrictions for some objects (e.g. for IED
names), while allowing a lot of freedom in other respects (e.g. objects in the Substation section).

To provide a solution to both parties, IET600 provides a dual naming scheme. For all objects and for
signal texts, IET600 provides an “Internal Name” or “Internal Text” (which belongs to ABB) and a
“Customer Name” or “Customer Text” (which belongs to the customer). User Interface elements can
be configured to display either one or the other, or sometimes both, if required.

2.2.1 Internal Names GUID-EFEF0A16-F30A-4B12-AE78-28C3B218F5C2 v1

Internal names of any object may contain only characters A-Z and a-z and digits 0-9. Furthermore,
adheres to the naming standard as defined in IEC 81346 which imposes further restrictions (for
detailed description, see chapter Annex: Naming Conventions). This convention is applied for the
naming of all Substation objects as well as for IEDs and IEC 61850 Subnetworks.

These internal object names are used as Name attributes in the IEC 61850 data model. Therefore,
they typically need to be unique (e.g. IED names in a project need to be unique, Bay names within a
Voltage Level need to be unique etc.).

2.2.2 Customer Names GUID-9096DF12-6F77-4B3C-AAFC-352F663FD1DD v1

Customer names of any object, on the other hand, may contain any Unicode characters and have no
restrictions whatsoever. They need not be hierarchical (however, a hierarchical naming scheme is
recommended whenever possible as it allows many advantages e.g. in renaming.)

Integrated Engineering Tool 17


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 2 1MRK500114-UEN Rev. X
Important concepts in IET600

These Customer object names are exported as desc (Description) attributes in the IEC 61850 data
model.

Substation automation is sometimes just a part of a bigger plant (e.g. a power generation station or a
refinery) which imposes other naming conventions. If those naming conventions are not compatible
with IEC 81346, the Customer name needs to be used to implement those names.

18 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 3
IET600 User Interface

Section 3 IET600 User Interface GUID-433B84C9-8D7C-422C-8D10-67E9F33972FE v1

This chapter gives an overview of the IET600 graphical user interface (GUI), describes its different
parts and describes general functionality that is provided throughout IET600. For a specific
description of a functionality or editor, please see chapters Managing IET Projects to Protecting IEDs
Against Changes.

3.1 GUI Overview GUID-53687544-85FE-4970-9C22-64325153BC77 v1

The IET600 user interface has the following distinct sections:

1. Main menu
2. Editors
3. Navigation Trees
4. Properties
5. Logging
6. Status bar

3.1.1 Main Menu GUID-3656F1C1-D41E-44A5-AF20-6B6767C05DAF v1

The Main menu gives the user an overview of engineering tasks. The Main menu is organized in a
series of tabs, each related to a particular task:

Integrated Engineering Tool 19


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 3 1MRK500114-UEN Rev. X
IET600 User Interface

Home Display-related menu items (adjust windows), often used functions (SCD Export/
import)
Substation Menu items related to Substation configuration (create SS, Voltage Levels etc.)
IEDs Menu items related to IED configuration (import, create, and configure IEDs)
Communication Menu items related to Dataflow configuration (create Subnetworks, create Datasets,
and Control Blocks, configure Control Block Clients
HMI Menu items related to HMI, Gateway and NCC configuration (creation, import/export
of lists related to their configuration).

Using the Main menu is intuitive: select the tab related to the task you want to perform, and then click
on the menu item:

Some tabs are “context-dependent”, i.e. they are shown only, if a certain Editor is selected:

Single Line Diagram Tasks specific for the SLD Editor


CCD Tasks specific for the CCD Editor

When selecting any function in the Main menu, IET600 will automatically select a Navigation Tree
and an Editor best suited to this task. This is intended to support a user who is not too familiar with
the engineering procedure. Experienced engineers will usually prefer to select their own Navigation
Tree and editor and perform tasks from the context menus of elements.

Some functionality, mainly import, and export of different files, are only available from the Main menu.

3.1.2 Navigation Trees GUID-1A305F94-87D7-433C-ADC9-53D817D51A9D v1

Navigation Trees display objects in different hierarchies. Selecting a particular object in a Navigation
Tree shows data of this element and lower elements in the currently selected editor.

The following Navigation Trees are available:

Substation Displays the substation topology, primary equipment and


IEDs; roughly based on the Substation section as
defined by IEC 61850-6.
IEDs Displays all IEDs in a flat structure.
Communication Displays the Subnetworks and their attached IEDs;
based on the Communication section as defined by IEC
61850-6.
HMIs Displays HMIs, Gateways, NCCs and their relations;
displays also mirroring configurations.

The following Navigation Tree is also available, but hidden by default, as it is rarely needed:

20 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 3
IET600 User Interface

Data Type Templates Displays the Data Type Templates of all IEDs.
The Data Type Templates contain the definition of the
exact structure of specific Logical Nodes (LNs) of
specific IEDs. They may be needed in rare cases to find
errors, but their analysis requires in-depth knowledge of
IEC 61850 LN classification.

The following possibilities are available:

3.1.3 Editors GUID-80AC6936-8BFA-43F3-ABE6-884C5B6DC9C7 v1

The editors are the place where the user actually configures the data of a project.

An editor will display the data related to the element selected in the Navigation Tree and all its lower
elements. As not all elements are suitable for all editors, an editor will display an appropriate
message, if it cannot display the element selected in the Navigation Tree.

To use a specific editor, select its tab:

Integrated Engineering Tool 21


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 3 1MRK500114-UEN Rev. X
IET600 User Interface

IEC202100290 V1 EN-US

To change to another editor, click on its tab.

Alternatively, right-click on any Tab -> a popup menu with available editors will show:

IEC202100291 V1 EN-US

Select the editor tab which you want to use -> this editor will open. This is a useful way to navigate
rapidly between editors at the beginning and at the end of the tabs.

Each editor provides detailed views related to various engineering tasks:

Editor Function
IED Status Display IED status information (Import, Export, Versions, Engineering protection),
configure engineering protection.
IED Settings Configure IED-related information (Disturbance Recording, PCM600 Templates,
SNMP Access Parameters).
SLD Edit Single Line Diagram, configure LN Mapping.
Table continues on next page

22 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 3
IET600 User Interface

Editor Function
CCD Edit Communication Configuration Diagram, configure physical communication
information.
Naming Configure Internal and Customer Names for Substation objects, IEDs, Subnetworks
etc.
Subnetworks Configure IED-to-Subnetwork relations and communication address information.
Signal Clients Map HMI signals from IEDs to HMI and GW clients, configure mirrored signals.
HMI Data Configure HMI signals.
NCC Data Configure NCC signals.
Datasets Configure Datasets and their content.
RCB Data Configure RCBs.
RCB Clients Map client IEDs to RCBs.
LCB Data Configure LCBs (hidden by default).
GCB Data Configure GCBs.
GCB Clients Map client IEDs to GCBs.
SVCB Data Configure SVCBs.
SVCB Clients Map client IEDs to SVCBs.
Inputs View and edit IED inputs.
VLAN Data View and modify switch configurations related to VLANs - same as "Ports VLANs"
CCD subeditor.
LN Data View IEC 61850 Data one IED at a time, edit selected attributes.
IED Services View IEC 61850 Services related to Dataflow and their relation to IED Capabilities
(hidden by default).
IED Capabilities View IED Capabilities (hidden by default).

IET600 can be used as a pure System Configuration Tool for IEC 61850 Dataflow; or it can be used
to configure HMI- and NCC-related functionality. To optimally adapt to the intended use, it is possible
to show/hide the following editors:

• Signal Client
• HMI Data
• NCC Data

This can be done from the Main menu/HMI/Show/Hide HMI Editors :

IEC202100292 V1 EN-US

3.1.4 Properties GUID-D49F509E-1F66-45D5-B7E7-D99827A2F6EA v1

This pane shows detailed properties for the element selected in the Navigation Tree. Most of the
properties can be edited more easily in the editor designed for this task. Few properties need to be
edited in the Properties pane.

Integrated Engineering Tool 23


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 3 1MRK500114-UEN Rev. X
IET600 User Interface

IEC202100293 V1 EN-US

3.1.5 Logging GUID-F00C42F7-02EA-4258-B307-340D32336BB0 v1

The Logging section displays a log of events to support analysis and trouble-shooting of the project
during engineering. It contains two tabs to display logged events:

• Output
• Error list

The Output list has the following features:

• It serves as a permanent log, contains all log messages time-tagged and in chronological order.
• All messages that are logged into the Output tab are also written into a user-specific log file
(which is located in C:\Users\<username>\AppData\Roaming\HITACHI\IET600\<version
number>\Logfiles and can be accessed directly from the context menu, see below).
• It has a context menu with the following menu items:
• Clear Output clears the output list.
• Copy selected text / Copy all text copies selection or whole output content to the copy
buffer.
• Word wrap wraps lines that do not fit in the editor.
• View logfile opens the log file mentioned above.

The Error List tab has the following features:

• It contains errors, warnings and info related to an action performed.


• It is cleared automatically before every bigger action so that the user should see only the logs
related to the most recent action.
• It should therefore be consulted immediately after every action performed.
• It allows filtering of errors, warnings or info or any combination (default is to show all of them).

3.1.6 Status Bar GUID-1321663A-0D52-4876-AFDC-796A517EF7AF v1

As in most applications the Status bar provides some additional information. Relevant in IET600 are:

• A Progress bar shows the action description and progression of actions that take a longer time,
e.g. opening or saving a project, or updating an IED from an SCL file.

24 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 3
IET600 User Interface

• A ‘Selection’ indicator shows (in table-based editors only) the visible and the total rows
(thereby providing an indicator about filters).
It also shows the current selection: rows, cells or columns, and how many.

• An ‘Update’ indicator shows that an update for your IET600 is available.

A click on the indicator will open a dialog from which you can install the update directly (this
dialog also pops up if you start IET600 and an available Update is discovered):

IEC202100298 V1 EN-US

To prevent this dialog from popping up again, you may select Don’t notify me again for this
version; this may be useful if you are in a critical phase of a project and do not want to update
right now. The update indicator will still be available.
Alternatively, you can update IET600 from Options/Updates (as described in chapter
"Options").

3.2 ‘Table’-based Editors GUID-D26D779A-2569-487E-A6E4-9EBF57C29761 v1

Most editors in IET600 show data in the form of tables. Each editor provides:

• a row context menu


• a column context menu
• a cell context menu
• optionally: column tool tips

IET600 provides the following general functionality for table-based editors:

• Show/hide columns
• Sorting on (multiple) columns
• Selecting whole columns
• Filtering the data based on filter criteria in multiple columns

3.2.1 Editor Elements GUID-7BE72B37-9B1E-4108-9DD6-35B823D70851 v1

In the remainder of the document, we will use some terms to designate specific elements of an
editor. The following overview shows these elements and their respective names:

Integrated Engineering Tool 25


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 3 1MRK500114-UEN Rev. X
IET600 User Interface

IEC202100300 V1 EN-US

3.2.2 Context Menus GUID-155C3E97-BC0B-4363-BA81-0A300325B736 v1

As with context menus in general, you can open them by right-clicking into the appropriate area of
the table:

IEC202100301 V1 EN-US

• Right-clicking on the column header shows the column context menu.


• Right-clicking into any row header shows the row context menu (if no rows are shown, right-
clicking anywhere into the empty space below the column headers will also bring up the row
context menu).
• Right-clicking into any cell shows the row context menu.

26 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 3
IET600 User Interface

The column context menu will usually contain the following menu items (individual editors may
contain additional menu items or modify them):

• Set to “Sort” mode/Set to “Select” mode determines whether clicking on the column header will
sort this column or select the column. Default behavior is Sort.
• Show only Rows with Warnings will set a filter so that only rows with warnings (i.e. rows that
contain a red error mark) are shown. This is helpful in some editors to systematically go through
all rows that contain any error. It is different from the column filter that shows rows with errors in
one specific column.
If this menu item is disabled, it means that there are no rows with warnings in the current editor
for the element currently selected in the Navigation Tree.
• Reset all filters clears all existing filters, including the Show only Rows with Warnings and
the Filter by these warnings (the same functionality as clicking on the button in the Filter row
header). The menu item is disabled, if there are no filters currently set in an editor.
• Scroll to column allows rapidly finding a column by scrolling to it, and by making it visible if it
was hidden. This is particularly useful in editors with many columns (e.g. ‘HMI Data’) or rarely
used hidden columns (e.g. RCB editor).
This function is not available for dynamic columns, e.g. client columns in the miscellaneous
‘XXX Clients’ editors.
• Reset Table layout sets back column sequence, visibility, width and sorting to a default, clear
any grouping and clears all filters.

The row context menu will usually contain the menu items Insert New Row (i.e. create a new
element) and ‘Delete Rows’ (remove one or several elements). These menu items are not available
in editors that do not allow creation or deletion of objects, e.g. the IED Status editor.

The cell context menu will usually contain the menu items Copy, Cut and Paste which are probably
familiar to anybody. Additionally it contains the following menu items:

• Fill Down is designed to rapidly fill a number of cells in one single column with the same values.
Mark the cells you want to fill first, then right-click to get the context menu and select Fill Down.
The value used to fill the cells is the one of the first cell selected. Columns with numerical values
have the additional feature that IET600 will take the difference of the first two cells and
propagate this difference to all other cells. To fill a numerical column with identical values,
ensure that the first two cell values are the same.
To rapidly fill down a big number of cells (several thousands), mark the first cell and then use
Ctrl+Shift+PgDn (or Ctrl+Shift+PgUp), this is considerably faster than using mouse dragging to
mark cells.
• Find and replace calls a dialog that allows finding all cells in a column containing a specific
value and optionally replacing it with another user-defined value. Find and replace works only
on the rows in the editor, not on the whole project.
• Export to Excel allows exporting the contents visible in a table-based editor into an Excel
sheet. A re-import is not possible.

3.2.3 Show/Hide Columns GUID-99088791-3191-40F1-A97E-0507C89968F3 v1

To show or hide columns:

1. Click on the top left icon of the editor:

Integrated Engineering Tool 27


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 3 1MRK500114-UEN Rev. X
IET600 User Interface

IEC202100302 V1 EN-US

2. The Field Chooser dialog will appear, select the columns to be shown or hidden by checking/
unchecking their respective selection boxes:

IEC202100303 V1 EN-US

3.2.4 Sort on Columns GUID-90EADE26-B090-451A-93FE-3EF8F95EAFAD v1

IET600 allows to sort on single or multiple columns. The current sorting is indicated by small arrows
in the header, the example shows an editor which is sorted by ascending Station Text and then
ascending Signal Text.

IEC202100304 V1 EN-US

28 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 3
IET600 User Interface

• To sort on a single column, left-click on its header -> any existing sorting will be cleared and the
data in the editor will be sorted ascending by that column.
• To reverse the sort order of a single-sorted column, left-click on a sorted column -> its sort order
will reverse.
• To sort on multiple columns, left-click on the header of the first column on which you want to sort
(this will clear any existing sorting).

Then press SHIFT and left-click on additional columns in the sequence that the sorting shall be
applied (once to add a column with ascending sort, twice for descending) -> the data in the
editor will be sorted ascending by that column.

You can add columns any time by pressing SHIFT and left-clicking. However, the editor does not
provide any feedback about the sort order of the already selected columns (e.g. in the above
example, you do not know whether it is sorted by ascending Station Text and then ascending
Signal Text or vice versa).

• To reverse the sort order of a multiple-sorted column, you cannot simply left-click on a sorted
column. To do so will not only reverse the sort order of this column, but also put it at the end of
the sorting sequence. E.g. the above example is sorted by ascending Station Text and then
ascending Signal Text. If you press SHIFT and left-click Station Text, the new sort order will be
ascending Signal Text and then descending Station Text.
• You cannot clear a sorting; you can only sort on another column.

3.2.5 Three State Checkboxes GUID-5EE51D93-58AF-41CC-B355-79D0E790965F v1

In various places, IET600 is using 3-state checkboxes, which can have the values:

GUID-30BDBBCD-6470-4687-85C5-5E1F353F2267 V1 EN-US

When clicking on a checkbox, it toggles its state from checked to unchecked and vice versa.

To bring it into the undefined state, select the checkbox and press the Delete key.

3.2.6 Set and Clear Filters GUID-A368CD74-90A5-4A01-B80B-21F2D1553146 v1

There are two different, mutually exclusive ways in IET600 how to access filters. You can toggle
between these two ways of accessing filters in Options/ Appearance (for a detailed description, see
chapter "Options -> Appearance" ).

1. Via Filter Symbol in the column header:

IEC202100306 V1 EN-US

The Filter Symbol allows you to select a Filter from a combo box that appears when you click on
it. To create a complex filter, select Custom and specify your Filter conditions.
2. Via Filter Row:

IEC202100307 V1 EN-US

Integrated Engineering Tool 29


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 3 1MRK500114-UEN Rev. X
IET600 User Interface

The Filter Row allows a more selective and rapid approach:


• The Filter logic button on the left determines how the following condition is evaluated.
The default is Starts with, click on the button to change this value.
• The adjoining text/combo box allows you to type the filter condition directly. Alternatively,
you can also select any of the options available from the combo box.
• The Clear filter button on the right allows you to clear an existing filter for one column.
• The Clear all filters button in the row header of the filter row allows you to clear all
existing filters for all columns (the same can be done with the Reset all filters menu item
from the column context menu).

The Combo box offers the following choices.

(All) shows all rows (reset filter)


(Custom) opens a dialog to configure customized filters
(Blanks): shows all rows with no content in this column
(NonBlanks): shows all rows with content in this column
(Errors) shows all rows with an error in this column
(NonErrors) shows all rows with no errors in this column
< value> shows all rows with matching value (the list includes all different values found in that
column)

As a special filter, Show only Rows with Warnings is available from the column context menu. It
will cause all rows with warnings (i.e. rows that contain a red error mark) to be shown (which is
different from the column filter that shows rows with errors in one specific column).

A quick way of checking for set filters is the Reset all filters menu item from the column context
menu: if it is not disabled than a filter of some sort is active.

If you hide a column that has a filter set, this filter still applies after you have hidden
the column.

Filters are saved when you close a project or close IET600. So if you set a filter in
one project, then close it and open another project, the filter will apply to the data of
the new project (which may be desirable or not).

3.3 GUI and Engineering Workflow GUID-C31F93B4-01E2-4008-B713-EE8999A0670A v1

For an individual engineering step, you have two ways to execute a task:

• Via Main menu, a method suited to users less familiar with IET600
• By choosing Navigation Tree, edited element and editor yourself, a method suited to users
familiar with IET600 and the engineering process

As a rough rule for users yet unfamiliar with IET600, tasks in a basic engineering process are
arranged in the Main menu tabs from left (steps early in the engineering process) to right (steps late
in the engineering process).

After a while you will want to take advantage of the parallelization of tasks. See chapter Engineering
Workflow for a more sophisticated overview of possible engineering workflows.

30 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 3
IET600 User Interface

3.3.1 Execute a Task via Main Menu GUID-B0AB06E9-C73E-4C51-B67D-508B4FC9D5E8 v1

As a rough rule, tasks in a basic engineering process are arranged in the Main menu tabs from left
(steps early in the engineering process) to right (steps late in the engineering process).

1. Select the Main menu tab that fits your engineering step best.
2. Select the task you want to perform in this tab. IET600 will then automatically select a
Navigation Tree and an Editor that is suited to your task.

After a while, you will get the feeling which Navigation Trees and editors are best used for what task
and you can proceed as described below.

After a while you will also want to take advantage of the parallelization of tasks. See chapter
Engineering Workflow for a more sophisticated overview of possible engineering workflows.

3.3.2 Execute a Task via Navigation Tree and Editor GUID-1C2943E0-7B23-44D9-AF1B-EAE5058DCEE7 v1

Select the Navigation Tree that suits your task:


• Substation for most editing
• IEDs for task related specifically to one IED
• Communication for some communication-related tasks
• HMIs to create/reconfigure HMIs, Gateways and NCCs

Select the element in the Navigation Tree you want to edit; consider the following:

• A higher element allows you to compare data from different sub-elements in the Editor (e.g.
selecting the project will display the data of all IEDs, allowing you to compare already configured
IEDs with not yet configured ones).
• A lower element shows more specific data; the editors will show the data faster and there is less
danger that you accidentally edit a wrong element.

Select the editor appropriate to your task.

3.4 Options GUID-F3544E51-633C-4617-9A0F-A996EB2A5F77 v1

To access the user options, click the round button on the top-left corner of IET600, then click the
Options button:

IEC202100308 V1 EN-US

The Options dialog will appear, offering you several Sub-Dialogs where you can configure settings.

Integrated Engineering Tool 31


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 3 1MRK500114-UEN Rev. X
IET600 User Interface

3.4.1 Options -> Appearance GUID-45FC57F8-7CF2-4CE2-9835-F1DF24E004D0 v1

This section contains options that affect the appearance of IET600. They are more or less self-
explanatory.

IEC202100309 V1 EN-US

As application language, only “English” is currently available.

3.4.2 Options -> User Settings GUID-C93A05FF-FAAE-44C5-8EA7-0F5BCBBFB39E v1

This section allows to set user-specific file paths and activate a history, if required. For a more
detailed explanation of these paths, please see chapter IET600 Data Organization.

32 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 3
IET600 User Interface

IEC202100310 V1 EN-US

3.4.3 Options -> Updates GUID-F0ADAECC-A091-4116-AF06-F31D064D459A v1

This section allows to check for IET600 Updates. Click on the Check for Updates. If an update is
available, you can download it and install it at your convenience.

For a more detailed explanation about IET600 updates, see document “IET600 Installation Manual”,
chapter “Updating IET600”.

Integrated Engineering Tool 33


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 3 1MRK500114-UEN Rev. X
IET600 User Interface

IEC202100313 V1 EN-US

3.4.4 Options -> About GUID-71E76BD9-A3B0-4EE6-BD6C-C2E948EAECBC v1

Click About to get additional information about the IET600 version and the version of its
components:

34 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 3
IET600 User Interface

IEC202100314 V1 EN-US

Integrated Engineering Tool 35


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
36
1MRK500114-UEN Rev. X Section 4
IET600 Data Organization

Section 4 IET600 Data Organization GUID-9FA981AA-A206-48F3-AC8A-E8F49A10DED0 v1

4.1 Overview GUID-A7332CFB-D645-4C57-87DF-5B93092E8675 v1

In IET600, you have several different kinds of data:

• Project Data which include the actual project (an MSSQL database), files imported into IET600
and files exported from IET600.
• Project Backups, each file containing the MSSQL database of one project.
• Project Archives, each archive containing a database Backup and configuration files of a project.
• Configuration data.

4.1.1 Project Data GUID-7BC8BCA3-3CC8-43B6-BF8A-0AF01DF5CCD9 v1

IET600 uses Microsoft SQL Server (MSSQL) to store its data.

MSSQL has some system databases which handle access rights and register the databases of the
individual projects. The location of those system databases is determined during installation and
cannot be changed. The default path is C:\Data\IETDatabases. As a user, you should not need to
have anything to do with this System Database.

The project data are stored below a user-definable path, the default is C:\Data\IETProjects. If you
change this path, new projects will be created in the new place; however the existing projects cannot
simply be copied or moved to the new path, because their path is registered in the System Database.

Both paths must be on a local drive and must not be compressed or encrypted (this is required by
MSSQL).

The data of an individual project are stored below this path, in a folder C:\Data\IETProjects\[project
name__SQL2014]. This folder has again 3 subfolders:

• Data (containing the MSSQL project database, it should not be used for anything else).
• Export (containing a copy of all exported files in a number of pre-defined subfolders).
• Import (containing a copy of all imported files, again in a number of pre-defined subfolders
identical to those in the export folder).

Integrated Engineering Tool 37


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 4 1MRK500114-UEN Rev. X
IET600 Data Organization

4.1.2 Project Backup GUID-73B3E446-48AB-4A94-8F17-9360E29CFF16 v1

IET600 allows to import and export the MSSQL project database, to either create a backup of a
project in a defined state, or to exchange it with another IET600 installation. The detailed procedure
is described in chapter "Import and Export Projects".

A project export is a zipped MSSQL database backup. To distinguish it from the multitude of other zip
files, IET600 gives it an “.ietprj” file extension.

The default folder for such files is C:\Data\IETBackup. However, it is strongly recommended to set
this path to a location/hard disk different from the drive where you actual project data are located
(typically C:\Data\IETProjects), in order not to lose both project data and backup if the local hard
disk fails. A good choice is a USB or network drive. Be sure, however, to select a location with
sufficient space (a medium-sized project backup has a size of about 12-15 MB; big projects may
have 30-40 or sometimes even 100 MB).

If you import or export a database, you can select any path. However, IET600 always keeps a copy
in the project backup folder, thereby eliminating the need for you to make such a copy manually.

4.1.3 Project Archives GUID-19CCFF32-283A-45E5-94AB-11AB3AC13C03 v1

At certain stages of a project, you may want to create a backup not only of the database, but of all
project-related files. A typical example would be, if you hand over your project to another engineering
crew, or to create a backup for a project milestone for legal reasons. The detailed procedure is
described in chapter "Archive a Project".

A project archive is a zipped file that contains the most recent backup of a project and the import and
export folders in exactly the same structure as in the project.

38 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 4
IET600 Data Organization

The default folder for such files is C:\Data\IETArchives. It is recommended to set this path to a
location/hard disk different from the drive where you actual project data are located (typically C:\Data
\IETProjects). A good choice during the engineering phase is a Network path with the “official”
project folder; during testing and commissioning, a USB drive may be needed. Be sure, however, to
select a location with sufficient space (a medium-sized project archive has a size of about 20 MB; big
projects may have 40-50 or sometimes even more than 100 MB).

The default archive path is configurable; however, you can select any path.

4.1.4 Program and User Configuration Data GUID-A8D4157C-4BB1-4B3F-8D81-AB6E8233AF84 v1

These are stored in the default paths that Microsoft has defined for such Data.

User-specific data are stored under the pre-defined user application data path:

C:\Users\<username>\AppData\Roaming\HITACHI\IET600\<version number>

Data saved here are e.g. IET600 layout, editor configurations etc. Each user can have his/her
separate configuration. However, when you install a new version, the configuration will currently not
be automatically taken over from the older versions.

Common configuration data of IET600 are saved under the pre-defined common application data
path:

C:\ProgramData\ABB\IET600\[version number]

Normally, these data files are installed by IET600 and there should not be any need to change them.
Normal users have only read rights to this path; only administrators can change these files.

4.2 Managing IET Projects GUID-122F6ED3-9582-4D6C-9608-6E7FDB0A5D33 v1

4.2.1 The ‘Projects’ Dialog GUID-40AD014E-855D-4F29-81FB-0291E893F017 v1

To get an overview and perform all kinds of project-related functions, IET600 provides the Projects
Dialog:

Integrated Engineering Tool 39


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 4 1MRK500114-UEN Rev. X
IET600 Data Organization

IEC202100319 V1 EN-US

The Dialog provides the following information:

• An overview of all the IET600 projects


• The status of each project
• The IET600 version needed to open the project
• The time the project was last modified

Additionally it provides access to the following functions:

• Create a new project


• Open an existing project
• Rename a project
• Delete a project
• Import/export (or backup/restore) a project database
• Archive a project

To open the Projects Dialog, click the round button on the top-left corner of IET600, then select
Manage Projects:

IEC202100320 V1 EN-US

40 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 4
IET600 Data Organization

4.2.2 Create a New Project GUID-9571F75B-4FBA-4EA4-81C1-C85AF0051821 v1

1. Click the round button on the top-left corner of IET600, then select Manage Projects -> the
Projects dialog opens.

IEC202100321 V1 EN-US

2. To create a new project, click on the New button. The following dialog will open:

IEC202100322 V1 EN-US

Enter the desired project name and click OK -> a new project will be created:

Integrated Engineering Tool 41


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 4 1MRK500114-UEN Rev. X
IET600 Data Organization

IEC202100323 V1 EN-US

The small indicator to the right of the project icon indicates the IEC 61850 version of the project,
it can be “Ed.1” (per default) or “Ed.2”. The “Ed.1” or “Ed.2” refers to the IEC 61850 edition to
which the project is compatible.
How the version of a project affects the engineering possibilities and compatibility with other
engineering tools is a rather complex issue, unfortunately. To learn how to change the version of
a project, see chapter "Change the Version of a Project".
To learn more about the relatively complex way of how IET600 handles this versioning, see
chapter Annex: IET600 and IEC 61850 Edition Handling.

4.2.3 Open an Existing Project GUID-B1B82A38-2CAD-4908-9163-46DFAD5AF8DA v1

1. Click the round button on the top-left corner of IET600, then select Manage Projects -> the
Projects dialog opens.

42 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 4
IET600 Data Organization

IEC202100324 V1 EN-US

2. Select the row with the project you want to open, and then click Open. The project will open in
IET600.

Consider the following points into account:

• If the project is already opened, you cannot open it again.


• If a project has a status ‘Migration required’, it will be migrated to a newer tool version. Before
doing so, a backup will automatically be created below the Backup Folder C:\Data\IETBackup
\AutomaticBackup. After migration, it cannot be opened with older IET600 versions; however,
you may import the older version again from the AutomaticBackup folder mentioned above.
• You can open only two projects at the same time. The second project will be opened in read-
only mode which means that data in this project cannot be modified during this session.
However, you may copy data from the second project (e.g. entire Bays, IEDs, signals, etc.) into
the first project.

4.2.4 Save Project Data GUID-C96D5C31-C3DD-43CB-9B0A-70F2664B056E v1

Note that IET600 does not save automatically. You must press the save button to save current state
of the project.

Save your work regularly to shorten saving times.

IEC202100325 V1 EN-US

Integrated Engineering Tool 43


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 4 1MRK500114-UEN Rev. X
IET600 Data Organization

4.2.5 Import and Export Projects GUID-46C98D06-4AC4-406F-9DC4-353D54384E55 v1

A project can be easily exported and imported in order to either transfer the project to other users or
to create a backup. The import/export functions can be accessed from the Projects dialog using the
Import and Export buttons. The exported project will be stored in an “.ietprj2” file, which can be
imported by other users.

When importing a project, you may need to be aware of the project Identifier:

• If you import a project in a different version (e.g. for comparison), you should keep the identifier,
as it still represents the same project.
• If you import one project to create a second project from it (e.g. if you create a second project for
a customer and want to use an old project of the same customer as a template), you should set
the checkbox Create new identifiers.

Same project Different project

IEC202100326 V1 EN-US IEC202100327 V1 EN-US

IET600 has the above as the default behavior: if you keep the same project name, just with (01), (02)
etc. added, it will by default keep the identifier. If you use another name, it will automatically set the
checkbox Create new identifiers. However, you can override this, if you are in a special situation.

The identifier serves as a means to determine which IEDs are owned by which projects. This is
important when configuring Dataflow between projects or Substations, e.g. as described in chapter
"SED File Exchange Between Projects".

4.2.6 Archive a Project GUID-D2F2CB02-D36F-436B-99FD-ECA8D2C3C479 v1

You can only archive an open project.

1. You can only archive an open project. Open the project first, as described in chapter "Open an
Existing Project" above.
2. Open the Projects dialog again by clicking the round button on the top-left corner of IET600 and
selecting Manage Projects:

44 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 4
IET600 Data Organization

IEC202100328 V1 EN-US

3. Select the row with the opened project -> the Archive button will become enabled.
4. Click on the Archive button -> the following dialog will open:

IEC202100329 V1 EN-US

You have now several options which differ essentially in the number and type of files which are
included in the archive.
• Create an archive with standard files:
This option is intended to create an Archive that can be passed to another person who will
take over engineering.In this option, IET600 will search the ‘Backup’ ‘Import’ and Export’
folders of your project for the following:
• The most recent project Backup.
• An SCD file of the project and all files imported into IEDs.
• Configuration files for all Gateways and HMIs.

Integrated Engineering Tool 45


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 4 1MRK500114-UEN Rev. X
IET600 Data Organization

If some of these files are not found, IET600 will indicate this in the ‘Status’ column. It is up
to the user to decide whether to create an Archive without these files or to stop and create
these files first.
Per default, all files found are selected for archiving; you can decide to exclude files by
unchecking them.
• Create an Archive with all files:
This is intended for projects with an unusual configuration, where the standard file option
above does not cover all essential files.
In this option, IET600 will search the ‘Backup’ ‘Import’ and Export’ folders of your project
for the following:
• The most recent project Backup.
• All files contained in the ‘Import’ and Export’ folders.
• Configuration files for all Gateways and HMIs.

If some of the standard files are not found, IET600 will indicate this in the ‘Status’ column.
It is up to the user to decide whether to create an Archive without these files or to stop and
create these files first.
Per default, all files found are selected for archiving; you can decide to exclude files by
unchecking them.
• Create a Milestone-Archive:
This is intended to document the project state at certain defined project milestones. As
described above, you can include either only standard files or all files in the Milestone
archive.
If you try to create a Milestone Archive and some standard files are missing, IET600 will
warn you and ask you for confirmation, before creating an incomplete Milestone Archive.
5. You may adapt the destination folder for the Archive and the Archive file name, if required.
6. To finally create the Archive, click Export. To close the dialog at any time, click Close.

4.2.7 Unarchive a Project GUID-27801345-35AF-4D94-BF6A-2768F27C875F v1

This is currently not provided by IET600.

If you want to restore an archived project, proceed as follows:

1. Extract the archive to a temporary folder.


2. Import the *.ietprj file contained in the root of the archive. This will create a folder for the project.
3. Copy the complete ‘Export’ and ‘Import’ folders contained in the archive into the project folder.

4.2.8 Change the Version of a Project GUID-1B7E10A8-33C2-4B0F-8516-EEBEEF9C3DAF v1

If you create a new project, it will have “Ed.1” as version, indicated by a small text to the right of the
project icon in any of the Navigation Trees. This “Ed.1” refers to the IEC 61850 edition to which the
project is compatible.

• A higher project version may be required, if an IED DATA model requires it (this, it will be
handled on ICD/IID file import).
• Few functionalities in the domain of IET600 (e.g. in the ‘Substation’ Tree, the usage of a
Function below a Bay) also require a higher project version.
• For compatibility reasons with an older IED configuration tool, you may want to downgrade your
version to a lower version number. This however, will often not be possible.

Before changing a version of a project, always consult chapter Annex: IET600 and IEC 61850 Edition
Handling. It describes in more detail the IET600 project versioning, its relation to the IEC 61850
standard versions and its implications and restrictions.

To change the project version, click on the project element in any Navigation Tree. The Properties
window will show the following:

46 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 4
IET600 Data Organization

IEC202100330 V1 EN-US

Use the combo box to select another version.

If you try to downgrade the version, this may not be possible. The following dialog will inform you
about the reasons:

IEC202100331 V1 EN-US

4.2.9 Record Comments on Project Changes GUID-71B6193D-74FD-493C-B157-471DAF1969D3 v1

IET600 allows the user to add and modify comments for modifications in the project, which will be
stored in a text file inside the project directory. The timestamp and the user name will be used for
identification.

IEC202100332 V1 EN-US

Integrated Engineering Tool 47


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 4 1MRK500114-UEN Rev. X
IET600 Data Organization

4.3 Upgrade Projects GUID-7850A369-332E-433D-A5BC-0289BE4B9C7C v1

4.3.1 Introduction GUID-3DA51545-29A9-4F45-BB83-70A7676B70B0 v1

IET600 uses MSSQL as a database to store its projects; MSSQL is installed in the ABB IET600
Prerequisites setup.

Until IET600 5.3.2xx MSSQL Server® 2008 Express was used. Any earlier IET600 version used the
same MSSQL version, therefore there was no need for any upgrade.

To support Windows 10 (which IET600 5.3 FP3 supports), MSSQL Server® 2014 Express is
required. It will be installed in parallel to the older MSSQL Server® 2008 Express.

New projects created with IET600 5.3 FP3 will therefore be residing on a different database than the
old ones. Unlike in earlier updates, you will not see any projects from older IET600 versions, but
must take an additional step to transfer them to the new database, from where they can then be
migrated and opened like in earlier IET600 Updates.

The Installation procedure is described in the Installation Manual (chapter “Upgrading from IET600
5.3 FP2 and earlier”), the upgrading of older projects from within IET600 will be described in detail in
the following chapters.

4.3.2 Preliminary Remarks GUID-8DA83388-0B15-4A00-AC19-E0B5BB2A3680 v1

You may use both MSSQL Server® versions in parallel, if you need to work with both IET600 5.3
FP2 (or older), and IET600 5.3 FP3 (or newer) on the same PC. Also for the upgrade described here,
you need both versions.

To prevent conflicts between the two MSSQL server products, several names and folders have been
changed in IET600 5.3 FP3. The following table gives an overview of the differences:

IET600 5.3 FP2 or older IET600 5.3 FP3 – FP5 IET600 5.3 FP6
IET600 Prerequisites Version 5.1.x or older Version 5.2.x – 5.2.3 Version 5.2.4
MSSQL Server MSSQL Server® MSSQL Server® MSSQL Server®
Product 2008 Express 2014 SP2 Express 2014 SP3 Express
MSSQL Server In-stance IETSERVER IETSERVER2 IETSERVER2
Name
Project Subfolder \IETProjects\ \IETProjects\ \IETProjects\
project project__SQL2014 project__SQL2014
Project Backup File .ietprj .ietprj2 .ietprj2
Extension

Table continuation:

IET600 5.3 FP7 or newer


IET600 Prerequisites Version 5.2.5 or newer
MSSQL Server MSSQL Server®
Product 2014 SP3 Express
MSSQL Server In-stance Name IETSERVER2
Project Subfolder \IETProjects\
project__SQL2014
Project Backup File Extension .ietprj2

48 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 4
IET600 Data Organization

4.3.3 Upgrade Preparation GUID-03B16114-4C84-4A22-8056-B88CC5C774C3 v1

1. Close all older IET600 programs (they access the old IETSERVER instance which prevents an
upgrade).
2. Close any program which might access any files of projects you want to migrate. E.g. make sure
you do not have any Customer Lists open in Excel; and also make sure, you do not have any
project folders or files open in Windows Explorer.
3. Both MSSQL Instances, IETSERVER and IETSERVER2 must be running. If you could install
IET600 5.3 FP3, this can be assumed to be the case (consult the Installation Guide, chapter
“Upgrade IET600 Installation “ how to check this).
4. Before any action, the old database will be exported into the <Backup>\AutomaticBackup folder;
therefore you do not specifically need to do an ‘Export’ or ‘Archive’ in an older IET600 version.

4.3.4 Upgrade Projects GUID-E9978CAE-858B-434C-88A4-29FE0DED9D91 v1

To upgrade projects from IET600 5.3 FP2 or older to IET600 5.3 FP3 requires first that the respective
project databases will be shifted from the MSSQL Server® 2008/ IETSERVER instance to the
MSSQL Server® 2014/IETSERVER2. This can be done from within IET600.

1. Open the Manage Projects dialog:


If you have projects to migrate, an additional Upgrade button is visible on this dialog. This
button is only visible if the following conditions are fulfilled:
• IET600 Prerequisites 5.1.x or older are installed
• The ‘SQL Server (IETSERVER)’ service is running
• Its MSSQL server instance contains at least one IET600 project database.

If you open the Manage Projects dialog and you have no migrated projects yet, a dialog will
provide some guidance (if the above upgrade conditions are fulfilled).

IEC202100333 V1 EN-US

This dialog will appear only as long as you did not upgrade any projects; after migrating at least
one, it is assumed that you know the way to do it for additional projects.

Be aware than on an older Hard Disk, it may take a while to scan the SQL Server for
projects and display them. You can recognize this by the fact that all buttons except
Exit Dialog will be greyed out while scanning is not complete.
2. Click on Upgrade, the actual Upgrade Dialog opens:

Integrated Engineering Tool 49


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 4 1MRK500114-UEN Rev. X
IET600 Data Organization

IEC202100334 V1 EN-US

3. Select one or several projects you want to upgrade and then click Upgrade. The upgrade
progress will be indicated by a progress bar in the bottom of the dialog. After the upgrade has
successfully finished, those projects will disappear from the list.
(What happens during this upgrade is that the project folder is renamed and the project
database is transferred to the new IETSERVER2 instance).
You may upgrade some more projects by repeating the above steps
4. If you have finished, click on Exit Dialog (you can still upgrade additional projects at a later
time, if so required).

All upgraded projects should now be visible in the Manage Projects dialog. You can now continue as
usual by opening the upgraded projects from the Manage Projects Dialog.

4.3.5 Upgrade by Importing IETPRJ Files GUID-F310D883-89D8-447B-A0B7-970CC30980A7 v1

In IET600 5.3 FP3, you can import any *.ietprj or *.ietprj2 files, irrespective whether it was created
with a version IET600 5.3 FP3 and newer or IET600 5.3 FP2 and older.

Simply go to the Manage Projects dialog, click Import and select the file you want to import, as you
are probably used to already. The project will be imported as usual, any necessary upgrade happens
in the background and needs no action by the user.

50 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 5
Engineering Workflow

Section 5 Engineering Workflow GUID-9E2EE3CD-7826-4904-AC7E-4CCACF218CFA v1

5.1 Overview GUID-76DBAA3A-1262-4D47-AB98-0AC60351F016 v1

The engineering process for an IEC 61850-based substation automation system usually involves the
following steps:

1. Substation Specification (Single Line Diagram)


2. Signal engineering
3. IED Data engineering
4. Communication configuration (CCD)
5. Dataflow configuration

Decoupling of the system specification tasks is a central concept in IET600 which provides flexibility
to decide when and how to complete the various engineering tasks. In other words, the tool does not
impose a strict engineering workflow, but allows work on the various steps to be done in parallel and
provides the support to unite the configuration at a later stage of the project.

5.2 Engineering of a New Project GUID-7FB6A84D-292B-4FCC-92F4-63EF7AAC9B3C v1

5.2.1 Overview GUID-96A36840-0E01-44DD-B855-D89356B366BD v1

In IET600, it is possible to start engineering at several places in parallel. The following overview
shows how different engineering steps are linked.

Integrated Engineering Tool 51


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 5 1MRK500114-UEN Rev. X
Engineering Workflow

The recommended engineering process can be divided into the following steps:

1. Basic Substation configuration (SLD and IEDs, the latter without any content at the moment).
2. Basic Signal configuration
3. Full Signal Configuration.
4. Communication Configuration (CCD)
5. Dataflow configuration.

Engineering steps 2 to 5 above can partially be executed in parallel, the diagram shows the
dependencies.

5.2.2 Basic Substation Configuration GUID-4417CA39-D9D1-40C0-9EE4-F72E85DE80E7 v1

1. Create the whole substation structure (Substation, Voltage Level and Bays), create Equipment
in Bays.
2. Draw the Single Line Diagram.
3. Configure customer names for all the above elements.
4. Create the IEDs in Bays.
At this stage, you have a Single Line Diagram available.
To actually draw the Single Line Diagram is optional. However, the equipment and its internal
and customer names are needed for a correct signal configuration.
Experience shows that drawing the Single Line Diagram requires little additional effort and
considerably enhances the ability to orient oneself in the substation. It is therefore highly
recommended.

52 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 5
Engineering Workflow

5.2.3 Basic Signal configuration GUID-3F77C8B5-7F22-46B1-9D6A-D08DA9B05E09 v1

1. Configure customer names for the IEDs.


2. Add signals to the IEDs and configure them.
3. Do the LN mapping.
At this stage, you are ready to export Signals Lists for approval by the customer.

5.2.4 Full Signal configuration GUID-D78322B1-BC2D-414D-BE22-BA7FAA5D2EC2 v1

1. Create all IEDs that were still missing (HMIs, Gateways, NCCs, Switches and other
communication equipment).
2. Add monitoring signals to those IEDs and configure them.
3. Do the LN mapping for those signals, if required.
4. Map the signals to HMIs and Gateways, as required.
At this stage, you are ready to export complete Signal Lists and configuration files for HMIs and
Gateways.
Depending on your HMI/Gateway configuration tool, you may also need the SCD file (see
chapter Dataflow Configuration ).

5.2.5 Communication configuration GUID-963FF1C0-857B-412F-A166-DA2BF8FB5E82 v1

This configuration is not mandatory, i.e. you can fully engineer a substation, even if you skip this
section. However, a Communication Configuration Diagram (CCD) does not take a lot of time to
configure and can be of great use in the following situations:

• discussion with the customer, particularly for redundancy configuration


• problem tracing in the commissioning phase

It is therefore recommended to do it; the time is usually well spent. As a precondition, you should
have most of your IEDs created, and any redundancy configuration should be clear.

1. Configure the physical communication ports for all IEDs.


2. Arrange the IEDs in the CCD.
3. Connect the IEDs in the CCD.
4. In complex communication configurations (e.g. redundancy), you may want to add Access
Points to IEDs and map them to physical ports, if you do not have the IEC 61850 Data model of
these IEDs available.

At this stage, you have a fully configured physical communication and can print a CCD.

5.2.6 Dataflow Configuration GUID-AF801641-6AFB-469C-81A5-F8A544243231 v1

1. Create Subnetworks and configure them for the appropriate protocols.


2. Connect the IEDs to the appropriate Subnetworks
3. If you have not done so till now, import the IEC 61850 Data model to the IEDs
4. Configure the Dataflow:
• RCBs with their Datasets
• LCBs with their Datasets, if configurable
• GCBs with their Datasets
• SVCBs with their Datasets, if configurable
5. Configure the Dataflow clients.

After this step is performed, you can export an SCD file.

Integrated Engineering Tool 53


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 5 1MRK500114-UEN Rev. X
Engineering Workflow

5.3 Engineering of a Retrofit Project GUID-425C1A43-63CD-4ABB-A07C-3AD777B34AEE v1

5.3.1 Overview GUID-0FDAA505-73E0-4D6B-AE73-9E0D0674C693 v1

In a retrofit project, the engineer will start with an SCD file and some HMI/Gateway configuration
files. After these are imported to provide the existing configuration, he may add new items as
requested (the example below assumes that a Bay is added to an existing Substation).

The recommended engineering process can be divided into the following steps:

1. Import of the existing configuration


2. Add new elements (Bays, IEDs)
3. Signal configuration of new elements
4. Communication configuration of new elements
5. Dataflow configuration

Steps 3 to 5 above can partially be executed in parallel, the diagram shows the dependencies.

54 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 5
Engineering Workflow

5.3.2 Import of Existing Configuration GUID-CBA9BBB4-1490-443A-BE18-25C09F693956 v1

1. Import SCD file. The SCD file will provide IED data models and Dataflow configuration. It may
additionally provide SLD and CCD information and LN mapping; however, this information tends
to be incomplete and needs to be carefully checked.
2. Import HMI/Gateway configuration files. IET600 will try to associate signals to individual IEDs
based on Signal information; signals that cannot be reliably associated will remain on the HMI to
which the configuration file belongs. IET600 will also recreate an existing NCC configuration, if
the proper configuration files are provided.

5.3.3 Add New Elements GUID-BBF1D5C3-C47D-4270-9EF8-29A936953D94 v1

1. Add new structures as needed (usually Bays), add equipment as needed.


2. Complete the Single Line Diagram.
3. Configure customer names for all the above elements.
4. Add IEDs as required.

At this stage, you have the revised Single Line Diagram available.

5.3.4 Signal Configuration of New Elements GUID-AE1643ED-7A91-45E9-880D-44200F6A3F60 v1

1. Configure customer names for the added IEDs.


2. Add signals to the added IEDs and configure them.
3. Do the LN mapping for the added signals.
4. Map the signals to HMIs and Gateways, as required.
At this stage, you are ready to export complete Signal Lists and configuration files for HMIs and
Gateways.
Depending on your HMI/Gateway configuration tool, you may also need the SCD file (see
chapter Dataflow Configuration).

5.3.5 Communication Configuration of New Elements GUID-276F25B3-FBDF-402A-8378-FAF39F959C1F v1

This configuration is not mandatory. If the existing Substation already provided a CCD, you will
probably also want to configure the added elements.

1. Configure the physical communication ports for the added IEDs.


2. Arrange the added IEDs in the CCD.
3. Connect the added IEDs in the CCD.
4. In complex communication configurations (e.g. redundancy), you may want to add Access
Points to IEDs and map them to physical ports, if you do not have the IEC 61850 Data model of
these IEDs available.

5.3.6 Dataflow Configuration GUID-249ECEA6-E3B7-4552-BF16-D70091FDF443 v1

1. (Create additional Subnetworks, if required; most likely you will re-use existing Subnetworks).
2. Connect the added IEDs to the appropriate Subnetworks
3. If you have not done so till now, import the IEC 61850 Data model to the added IEDs
4. Configure the Dataflow of the added IEDs:
• RCBs with their Datasets
• LCBs with their Datasets, if configurable
• GCBs with their Datasets
• SVCBs with their Datasets, if configurable
5. Configure the Dataflow clients.

After this step is performed, you can export an SCD file.

Integrated Engineering Tool 55


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 5 1MRK500114-UEN Rev. X
Engineering Workflow

5.4 Engineering of Dataflow Only GUID-1D7FF676-1129-44EC-8C68-2085FCB328CB v1

5.4.1 Overview GUID-C3F7F6EC-FBD9-48C3-A55C-CCD863125F55 v1

In some Substation Automation projects, it happens that one party delivers protection and control
IEDs, another party delivers the HMI/Gateway. In this case, the first party is expected to configure not
only the IED data model, but also the Dataflow; the second party is responsible for the configuration
of Signals, HMI and/or Gateway.

In this case, the engineer will start with an SCD file from a configuration tool like PCM600, which
contains all IEDs and may contain some Substation configuration, some LN mapping, some
Subnetwork and Dataflow configuration.

The engineer will use IET600 to calculate the complete Dataflow. If required, he may also provide LN
mapping.

The recommended engineering process can be divided into the following steps:

1. Import of the existing configuration (via SCD file).


2. Update of SLD configuration and LN mapping, if required.
3. Dataflow configuration.

5.4.2 Import of Existing Configuration GUID-04AE513D-CA8D-416C-8164-4AD42B826A71 v1

1. Import SCD file. The SCD file will provide IED data models and may provide a default Dataflow
configuration. It may or may not contain Subnetworks. It may additionally provide SLD and LN

56 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 5
Engineering Workflow

mapping; however, this information tends to be incomplete and needs to be carefully checked if
it is to be used.

5.4.3 Update of SLD Configuration and LN Mapping GUID-21252457-19D6-4687-BFA4-4760489C16CB v1

(optional)

1. Add Substation structures and equipment as needed.


2. Provide LN mapping as needed.
3. Draw/complete the Single Line Diagram.
At this stage, you can export a Single Line Diagram, if needed.

5.4.4 Dataflow Configuration GUID-3B07734F-DD32-467E-9E57-02735050C714 v1

1. Create Subnetworks as required; most likely you will re-use existing Subnetworks).
2. Add Client IEDs (HMIs/Gateways), if they are not provided by the SCD already.
3. Connect IEDs to the appropriate Subnetworks.
4. Configure the Dataflow of the IEDs:
• RCBs with their Datasets
• LCBs with their Datasets, if configurable
• GCBs with their Datasets
• SVCBs with their Datasets, if configurable
5. Configure the Dataflow clients.
After this step is performed, you can export an SCD file.

Integrated Engineering Tool 57


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
58
1MRK500114-UEN Rev. X Section 6
Substation Specification

Section 6 Substation Specification GUID-DF3BCC6D-7FB4-42B3-BF78-F203E2D040CC v1

6.1 IEC 61850 Modelling of a Substation GUID-9CB4C211-C0BA-468B-8A18-CBD009596ECE v1

IEC 61850 allows you to build a Substation tree so that you can model your Substation Hierarchy.

The main purpose of the Substation tree elements is that Logical Nodes (LNs) of an IED can be
mapped to such elements. This mapping can then be used e.g. for identification (CSWI1 belonging to
QA1, CSWI2 to QB1 etc.) or to automatically configure texts in signals.

IEC 61850 distinguishes between ‘containers’ and ‘equipment’. Containers are e.g. a Substation, a
Voltage Level or a Bay, Equipment is e.g. a Circuit Breaker, a Voltage Transformer or a Tap Changer.

6.1.1 Substation ‘Containers’ GUID-89785B45-DD35-47CC-89BC-C0CCC6EA7949 v1

Originally, IEC 61850 (Ed. 1) allowed you to have 3 levels of containers only:

• Substation -> Voltage Level -> Bay.


• Substation -> ‘Function’ -> ‘Subfunction’ (to model auxiliary functionality).

The three levels proved insufficient, so that IEC 61850 (Ed. 2) expanded this container model:

• ‘Functions’ could now be used below Voltage Levels and Bays also, and ‘Subfunctions’ could
contain other ‘Subfunctions’.

A Diameter e.g. can now be modeled as Bay and its Sections can be modelled as Functions
(fragment "Typical Diameter, Line/Transformer" provides an example how to model a Diameter). Be
aware that this modelling requires IEC 61850 (Ed. 2), as Functions below Bays were not allowed in
Ed. 1. See Annex: IET600 and IEC 61850 Edition Handling for more details about edition handling.

6.1.2 Substation Equipment GUID-578777FF-3927-4B88-92F2-92B54FDA3F4B v1

IEC 61850 (Ed. 1) split ‘Equipment’ into 3 types:

• Power Transformers (a separate category due to their complexity)


• Conducting Equipment (electrical equipment such as Circuit Breakers, Disconnectors etc.)
• General Equipment (non-electrical equipment such as Pumps, Valves etc.)

Additionally you could use a ‘Sub-Equipment’ to further divide Equipment (typically used to model
phases of an Equipment, e.g. a Circuit Breaker.

Again, IEC 61850 (Ed. 2) expanded this model:

• Equipment could now contain an ‘Equipment Function’ which in turn could contain an
‘Equipment Subfunction’ which could contain other ‘Equipment Subfunctions’.

This is mainly intended to allow the modeling of redundancy of some sort; e.g. rather than modeling
protection trips all to the same Circuit Breaker, an engineer could model two Equipment Functions
‘Main 1’ and ‘Main 2’ so that LNs of the respective IEDs ‘Protection Main 1’ and ‘Protection Main 2’
can be mapped to those Equipment functions rather than the equipment itself.

Integrated Engineering Tool 59


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 6 1MRK500114-UEN Rev. X
Substation Specification

6.2 Creating Substation ‘Containers’ GUID-70AC00A8-6EA8-42E4-979B-3BCB5D7BA308 v1

6.2.1 Overview GUID-2046CE90-4BAA-4D25-96B0-BE1AA792FC7B v1

IET600 provides 2 different methods to configure containers:

1. All container types can be created from the context menu of the respective items in the
‘Substation’ Navigation Tree. The choice is limited to those container types that can be created
for a specific parent (e.g. below a Substation, you can create only a ‘Voltage Level’ or a
‘Function’).
2. The most commonly used containers (Substation, Voltage Levels and Bays) can be created
from the Main menu:

IEC202100357 V1 EN-US

6.2.2 Create a Substation GUID-811A551E-A5A0-42F0-85FB-A0DC79F855DC v1

1. Select the Substation tab in the Main menu and click Create Substation:

IEC202100358 V1 EN-US

Alternatively, from the context menu of the project in the Substation Navigation Tree, select
Create new Substation.
2. Enter a name for the Substation. The name must be unique within the project.

IEC202100359 V1 EN-US

3. Click OK -> a new Substation is created below the project in the Substation Navigation Tree.

60 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 6
Substation Specification

6.2.3 Create a Voltage Level GUID-996AFBE7-819B-46FC-B581-6359068D3A20 v1

1. Select the Substation tab in the Main menu and click Create Voltage Level:

IEC202100360 V1 EN-US

Alternatively, from the context menu of a Substation in the ‘Substation’ Navigation Tree, select
‘Create new Voltage Level’.
2. Enter a name for the Voltage Level. The name must be unique within the substation.

IEC202100361 V1 EN-US

3. Click OK -> a new Voltage Level is created below the Substation in the Substation Navigation
Tree.

6.2.4 Create a Bay GUID-F73BE8DF-9BF0-4789-AB9B-0800F2802656 v1

1. Select a Voltage Level, right click and select Create New Bay or click on the Bay function in the
menu to open the Bay dialog.
2. Enter a name for the new Bay. The name must be unique within the Voltage Level.

Integrated Engineering Tool 61


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 6 1MRK500114-UEN Rev. X
Substation Specification

IEC202100362 V1 EN-US

3. Click OK -> a new Bay is created below the Voltage Level in the ‘Substation’ Navigation Tree.

To configure Bay Equipment and Topology:

1. Select the Bay you want to configure in the Substation Tree.


2. Add/configure Equipment as described in chapter Creating Equipment: The ‘SLD’ Editor.

To configure a whole Voltage Level:

1. Repeat the above step for all Bays in a Voltage Level.


2. Select the Voltage Level you want to configure in the Substation Tree.
3. Create Busbars as needed.
4. Use the Layout Bays or Align Bays from the Single Line Diagram tab in the Main menu to do
an automatic initial layout.
5. Adapt the layout manually, if needed.

6.2.5 Create a ‘Function’ GUID-FD7C1944-26D6-42DB-A9D0-85C14FCAAA60 v1

1. Select a Substation, Voltage Level or Bay, right click and select Create New Function -> this
will open a dialog.
2. Enter a name for the new Function. The name must be unique within the parent Substation,
Voltage Level or Bay.

62 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 6
Substation Specification

IEC202100363 V1 EN-US

3. Click OK -> a new Function is created below the parent Substation, Voltage Level or Bay in the
Substation Navigation Tree.

6.2.6 Create a ‘Subfunction’ GUID-48496C59-026D-43E7-9511-C350779FA6FF v1

1. Select a Function or Subfunction, right click and select Create New Subfunction -> this will
open a dialog.
2. Enter a name for the new ‘Subfunction’. The name must be unique within the parent Function or
Subfunction.

IEC202100364 V1 EN-US

3. Click OK -> a new Subfunction is created below the parent Function or Subfunction in the
Substation Navigation Tree.

Integrated Engineering Tool 63


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 6 1MRK500114-UEN Rev. X
Substation Specification

6.2.7 Create a ‘Subequipment’ GUID-AD741470-F20D-43CE-8879-70882C3C0CC2 v1

1. Select an Equipment, right click and select Create New Subequipment -> this will open a
dialog.
2. A Subequipment should normally be used for Phases. Select the Phase, if applicable -> a
default name will be inserted.
3. If necessary, modify the name for the new ‘Subequipment’. The name must be unique within the
Equipment.

IEC202100365 V1 EN-US

4. Click OK -> a new Subequipment is created below the Equipment in the ‘Substation’ Navigation
Tree.

6.2.8 Create an ‘Equipment Function’ GUID-B2703119-9472-4E94-9AC7-7AB3D23F256C v1

Please do not use ‘Equipment Function’ to model phases of an Equipment, use ‘Subequipment’ for
this purpose.

1. Select an Equipment, right click and select Create New Equipment Function -> this will open a
dialog.
2. Enter a name for the new ‘Equipment Function’. The name must be unique within the
Equipment.

64 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 6
Substation Specification

IEC202100366 V1 EN-US

3. Click OK -> a new Equipment Function is created below the Equipment in the Substation
Navigation Tree.

6.2.9 Create an ‘Equipment Subfunction’ GUID-7A041EED-B423-41BD-92CB-D1C277321CEA v1

1. Select an Equipment Function or Equipment Subfunction, right click and select Create New
Equipment Subfunction -> this will open a dialog.
2. Enter a name for the new ‘Equipment Subfunction’. The name must be unique within the parent
Equipment Function or Equipment Subfunction.

IEC202100367 V1 EN-US

3. Click OK -> a new Subfunction is created below the Equipment Function or Equipment
Subfunction in the Substation Navigation Tree.

Integrated Engineering Tool 65


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 6 1MRK500114-UEN Rev. X
Substation Specification

6.3 Creating Equipment: The ‘SLD’ Editor GUID-BC38EA22-4686-4A96-81E9-40C1E725B37D v1

6.3.1 Overview GUID-C563599F-CEDB-4DC4-A5A7-D3C7BA92166A v1

IET600 provides the ‘SLD’ Editor to create and connect equipment.

Some restrictions apply, however:

• Only equipment commonly used in Substation engineering can be created, not all equipment
types specified by IEC 61850 are available.
• In IET600, equipment can only be created within Bays, although IEC 61850 allows so-called
‘General Equipment’ and Transformers to be allocated to other containers as well.

Alternatively, equipment can be created by importing an SCD or SSD file to initially create a project.
IET600 will also import and display equipment from types which are not available from the ‘SLD’
editor and will also show equipment allocated to Voltage Levels and Substations in the tree according
to their allocation. However such equipment cannot be re-allocated.

6.3.2 Create a Single Line Diagram GUID-980353B6-D245-4627-85F5-176A936DAF19 v1

The editor provides shapes for primary equipment and shapes to connect equipment. Moreover, the
Bay equipment can be connected to the Busbar to define a complete Single Line Diagram for a
voltage level.

IEC202100368 V1 EN-US

To draw the single line diagram for a Bay:

1. Select the Bay in the ‘Substations’ Navigation Tree.


2. Click on the primary equipment you want to insert (e.g. a circuit breaker).
3. Move cursor to the Bay drawing area (orange box) and click where you want to insert your
equipment.
4. Repeat steps 1 to 3 to draw all primary equipment.
5. Connect the primary equipment with lines.

To view the shape names, move your cursor above the shape and the Tooltip box will appear.

66 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 6
Substation Specification

Alternatively, you can right click on the connectivity node and select ‘Attach Conducting Equipment’
to connect to available shapes.

Multiple selection is supported for equipment:

1. Select Arrow shape .


2. To select multiple equipment, press the Ctrl key on the keyboard and
• Either click sequentially on each equipment you want to include in the selection.
• Or select an area with mouse drag’n’drop -> all equipment fully or partially within this area
is selected.
3. Use keyboard shortcuts Ctrl+C to copy and Ctrl+V to paste.

To unselect, click on an equipment not included in the multiple selection or on a Bay. You cannot
selectively remove a single equipment out of a multiple selection.

When using the SLD editor, the Main menu shows a context-dependent menu ‘Single Line Diagram’
that provides some additional features:

• IEC/ANSI/Custom: changes the symbols according to the selected standard.


• Align Bays: aligns multiple Bays in the same drawing (e.g. voltage level) to avoid overlapping
Bays.
• Layout Bays: aligns multiple Bays in the same drawing (e.g. voltage level) and orders Bays in
alpha-numerical order from left to right.

IEC202100370 V1 EN-US

A diagram of the whole substation is not available.

6.4 Creating a Substation by Importing SCD/SSD File GUID-A920033B-18D2-4DFC-B174-6010982FBB3B v1

To create the substation structure by importing an SCD or SSD file, please see chapters "Import an
SCD File to Create a Project" or "SSD File Import". This can only be done in an empty project which
does not contain a Substation already.

To create IEDs in a Bay, Voltage Level or Substation, please see chapter "Creating and Configuring
IEDs".

Integrated Engineering Tool 67


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
68
1MRK500114-UEN Rev. X Section 7
IED Engineering

Section 7 IED Engineering GUID-1AE36871-5A0D-4D75-A581-1E354DB6A436 v1

7.1 Introduction GUID-FF91BAC4-2BBB-42EA-86F3-FA4170C06242 v1

In IET600, you have several ways to engineer IEDs:

• Create an IED manually, and then add/edit their data.


• Copy a configured IED from the same or another project.

7.1.1 IED Roles GUID-31126128-B6DE-4A31-9B63-851794C8D0BD v1

Each IED must have at least one role (primary role). In IET600, the following roles can be configured:

• Archive
• HMI / Gateway*
• IED (Protection / Control IEDs)
• Merging Unit
• NCC
• Printer
• Router
• Security Device
• Switch / Hub *
• Time Server
• Other

* Some few roles can be combined with other roles. For example it is allowed to create a Gateway
IED with an additional role HMI. A combination of roles is only possible for related roles. Related
roles are listed in the same line and in italic type.

An already created IED can be reconfigured with a related role only.

7.1.2 IED Status Editor GUID-C299DB97-5691-4E8E-9F57-CFE0239E3404 v1

The IED Status editor provides an overview of all IEDs in the project, including revision history
information. The following properties are available:

Property Description
Modified Indicates if changes to the IED have been made since
the last SCD export. The flag is reset with SCD export.
IED Name IED name
IED Type IED type (i.e. product family) from imported ICD/IID file
(read-only)
IED Version The SCL version as which this IED is treated (for details,
see IEC 61850 Classification)
Blocked due to SCL Version Conflict Dataflow Engineering is restricted due to IEC 61850
version conflicts (for details, see chapter 28.4 IET600
Mixed System Engineering)
Customer Name Customer specific name
Manufacturer Manufacturer name from imported ICD/IID file (read-
only)
Table continues on next page

Integrated Engineering Tool 69


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 7 1MRK500114-UEN Rev. X
IED Engineering

Property Description
Foreign IED Information related to SED file transfer (for details, see
"SED File Exchange Between Projects")
IEC 61850
Engineering Rights
Pending SED Transfer
Checked Out
Protected Summary protection flag, indicating that some protection
is active for an IED (s. below)
Protect RCB Dataflow Protect IED against specific configuration changes (for
details, see Protecting IEDs Against Changes).
Protect GCB Dataflow
Protect SVCB
Dataflow
HMI Engineering Right
SCL Import File Name Path and file name of imported ICD/IID file (read-only)
SCL Import Date Date and time of last ICD/IID file import (read-only)
SCL Export Date Date and time of last SCD file export (read-only)
Configuration Version IED Configuration Version from imported ICD/IID file
(read-only)
Software Revision IED Software revision from imported ICD/IID file (read-
only)
Configuration Revision Configuration Revision from imported ICD/IID file (read-
only)
Only the 1st LD is shown in the table, use Tool Tip to see
all, if IED contains several LDs.
Primary Role (read-only)
HMI Signal Count Number of HMI Signals per IED, as defined in HMI Data
editor (read-only)
Capability Definition Reference to Manufacturer and IED Type in the IED
Capabilities editor (read-only)

7.1.3 IED Settings Editor GUID-5CAC917D-65E1-4602-B26A-608DCD568605 v1

The IED Configuration editor provides a list of IED properties that can be configured. These are
mainly Disturbance Recording parameters which can currently only be used by ABB OPC Server
clients.

Property Description
IED Name IED name
IED Type IED product family (from imported CID/ICD/IID file)
IED Version The SCL version as which this IED is treated (for details,
see chapter "IEC 61850 Classification")
IED Version Override Overrides IED Version
There are three values avalible:
"Treat as Ed.1" equal to 2003 Rev. A
"Treat as Ed.2" equal to 2007 Rev. B
"Treat as Ed.2.1" equal to 2007 Rev. B Release 4 - This
option should be used only when IED contains elements
intorduced with Edition 2.1 of IEC 61850 standard
Customer Name Customer specific name
Manufacturer Manufacturer name from imported ICD/IID file
Table continues on next page

70 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 7
IED Engineering

Property Description
Disturbance true, if Disturbance Recording should be enabled.
Recording (see chapter "Disturbance Recording Configuration" for
enabled more details)
Disturbance true, if Disturbance Recordings on the IED will be
Recording deleted after a successful upload.
Delete Recordings After Upload (see chapter "Disturbance Recording Configuration" for
more details)
Disturbance true, if the directory, where the Disturbance Recordings
Recording are stored, is as defined in IEC 61850.
61850 Default Directory (see chapter "Disturbance Recording Configuration" for
more details)
Disturbance The directory, where the Disturbance Recordings are
Recording stored.
Directory (see chapter "Disturbance Recording Configuration" for
more details)
Disturbance On the Server IED, the minimum allowed polling period
Recording in seconds (to avoid performance problems due to a
Polling Period misconfigured client)
On the Client IED the actual polling period in seconds.
(see chapter "Disturbance Recording Configuration" for
more details)
Disturbance true, if Disturbance Recordings can be uploaded via
Recording MMS.
MMS Upload Capability (see chapter "Disturbance Recording Configuration" for
more details)
Disturbance true, if Disturbance Recordings can be uploaded via FTP.
Recording (see chapter "Disturbance Recording Configuration" for
FTP Upload Capability more details)
Disturbance true, if Disturbance Recordings can be uploaded via
Recording FTPS.
FTPS Upload Capability (see chapter "Disturbance Recording Configuration" for
more details)
Dynamic Datasets Allows to configure whether an 8-MMS Client IED shall
try to configure Dynamic Datasets on an 8-MMS Server
IED.
(see chapter "Dynamic Datasets" for more details)
PCM Template Reference to PCM600 IED Configuration Template.
(see chapter "SNMP Configuration Usage" for more
details)
PCM Object Type Reference to PCM600 Object/IED Type.
(see chapter "SNMP Configuration Usage" for more
details)
SNMP String specifying the SNMP Community allowed to write
Write Community via SNMP.
(see chapter "SNMP Properties Configuration" for more
details)
SNMP String specifying the SNMP Community allowed to read
Read Community via SNMP.
(see chapter "SNMP Properties Configuration" for more
details)
SNMP Poll Rate Seconds between polling IEDs via SNMP.
(see chapter "SNMP Properties Configuration" for more
details)
SNMP Timeout Seconds for Timeout if an SNMP Server does not
respond to a request from an SNMP Client.
(see chapter "SNMP Properties Configuration" for more
details)
Table continues on next page

Integrated Engineering Tool 71


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 7 1MRK500114-UEN Rev. X
IED Engineering

Property Description
SNMP Retry Limit Amount of retransmissions to the IED after the first poll
timeout. If no response is received, IED is marked as
suspended.
SNMP Suspended Poll Rate Controls how often the connection to IED is attempted
when it is in not responding state. Unit for the parameter
is seconds.
SNMP Version SNMP Protocol Version to communicate.
(see chapter "SNMP Properties Configuration" for more
details)
SNMP Authentication Protocol Algorithm for authentication of client to server.
(see chapter "SNMP Properties Configuration" for more
details)
SNMP Encryption Algorithm Algorithm for encryption of communication between
client and server.
(see chapter "SNMP Properties Configuration" for more
details)
SNMP User Name User name used for authentication.
(see chapter "SNMP Properties Configuration" for more
details)

7.1.4 LN Data Editor GUID-C15DC60A-1D14-430D-8C10-2BE0AD3615D2 v1

The LN Data editor provides a view on the IEC 61850 model of the IED, including the following
attributes.

• IED
• LD
• LN
• Path
• Value
• Short Address
• Description

Note that most of these attributes are “read-only”, as they must be defined by the
IED configuration tool in the ICD/IID file.

7.1.5 IED Services Editor GUID-DFC74299-70C1-42B8-86D5-B7F73DD609D8 v1

IEC 61850 specifies IED services, with which an IED can declare its own capabilities and limitations.
The understanding of IED services, however, is made somewhat complex by three facts:

• The default values, if a service is missing, are not consistent.


E.g. service FileHandling: a missing service indicates that IED File handling services are not
supported, an existing service FileHandling without sub-services means that file transfer via
MMS is supported while file transfer via FTP or FTPS is not supported.
• IEC 61850 allows to specify services on either IED or Access Point(s) to allow different services
to be available via different Access Points.
• Due to incomplete service specifications (at least in IEC 61850 Ed.1), IET600 introduced its ‘IED
Capabilities’ which sometimes just provide a default value, if the service is missing, sometimes
they override an existing service.

The ‘IED Services’ editor is intended for persons which are familiar with the IEC
61850 services as it does not explain the services, but only makes the above-
mentioned complexity transparent. If used by a non-expert, it may confuse more
than it clarifies.

72 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 7
IED Engineering

The IED Services editor is hidden by default. To make it visible, open the Main menu (top left circle),
select Options, Appearance and enable the checkbox Show IED Services Tab:

IEC202100371 V1 EN-US

The ‘IED Services’ Editor then shows:

• Default values in case a service is missing


• Which services are defined by the IED and whether those services are defined on IED or
Access Point level.
• Whether IET600 provides any overrides or default values (see chapter "IED Services Editor").
• The final result of all the above (and whether the result applies on IED or Access Point level).

Integrated Engineering Tool 73


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 7 1MRK500114-UEN Rev. X
IED Engineering

IEC202100372 V1 EN-US

By filtering on the Service Name column, you can compare a service across several IEDs.

7.1.6 IED Capabilities Editor GUID-F2970BDB-D5EF-4D0A-9930-6449476F2EB0 v1

In IEC 61850, so-called services, which are part of an part of an ICD/IID/SCD file, define certain
capabilities of an IED. These services – for historical reasons – may not always be correctly
configured by the IED configuration tool or correctly interpreted by IET600. Therefore, the IED
Capabilities editor allows the user to define default values or override behavior for the purpose of
correct engineering in IET600.

For more information and to address some known problems which can be solved with IED
capabilities, please see chapter Annex: IED Capabilities.

Be very careful when editing anything in the IED Capabilities editor. The default
options are set according to an ABB-tested engineering process for defined ABB
devices and reflect product-specific know-how and engineering experience. To
change these settings, expert knowledge is required; and extreme care must be
taken to test and verify results of changed setting, as such changes may otherwise
result in improper functioning of a system.

Note that the changes in the IED Capabilities tab will not be written into the SCL IED Services of the
exported SCD file; they are only used within IET600.

To enable the IED Capabilities editor, open the Main menu (top left circle) and select Options and
enable the checkbox Show IED Capabilities Tab:

74 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 7
IED Engineering

IEC202100373 V1 EN-US

7.2 Creating and Configuring IEDs GUID-94DBB999-7D9A-4ACF-923B-1EF2054CFD0D v1

7.2.1 Overview GUID-FF2DE64E-7504-42EB-AC3C-6C4B60D6A947 v1

You can create new IEDs in several locations:

• In the IED Tree below a project.


• In the Substation Tree, below a Substation, Voltage Level or Bay.
• In the HMI Tree (station-level IEDs only, like MicroSCADA SYS600 HMIs and COM500 NCC
Gateways).

The next chapter describes how to create a generic new IED. Subsequent chapters describe how to
create new IEDs with a predefined role. There are also some special properties which are available
dependent the role (e.g. OPC servers for HMIs).

7.2.2 Create New IED GUID-A9771333-089F-4FA2-B1CD-11756538B907 v1

An IED can be created using either the Substation menu or in the Substation or IEDs navigation tree
using the context menu.

1. In the Substation or IEDs menu, select the IED button:

Integrated Engineering Tool 75


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 7 1MRK500114-UEN Rev. X
IED Engineering

IEC202100374 V1 EN-US

2. Alternatively, you can create an IED from the context menu in:
• a ‘Substation’, ‘Voltage Level’ or ‘Bay’ element in the ‘Substation’ tab, or
• the ‘Project’ element in the IED tree

Right-click the element -> the context menu for that element appears. Select Create New IED ->
Other…

IEC202100375 V1 EN-US

3. This opens the dialog Create new IED.

76 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 7
IED Engineering

IEC202100376 V1 EN-US

The following steps describe the mandatory input fields:

• First, select the location for the new IED on the left hand side of the dialog. The location is the
element under which the IED will be created.
• Depending on the previously selected location, IET600 proposes a name, which you can adapt
according to your needs. Invalid names are indicated by an error mark (invalid names are
usually either duplicate names or contain characters that are not allowed for a particular
element).
• Select one of the available roles as primary role. If you started the dialog with a predefined role
you cannot change the role here anymore.

Additionally, the dialog allows you to configure some further settings:

• The IED Type is set to GENERIC by default. You can adapt it according your needs.
• You can select the number of ports and configure individual ports, select the first tab, ‘Ports’.
(Ports are required to design the communication configuration diagram. For more detailed
information about port configuration, see chapter "Configure Communication Properties").
• For some IEDs, (e.g. MicroSCADA, Switches), you can configure Access Points. To do so,
select the second tab. You can add, remove or rename access points. Note: At least one access
point is required.
• To reduce the engineering time, IET600 allows you to use templates which contain predefined
settings for the communication parameters. They are only available if the primary role is already
set. Also there aren’t templates for all roles. To apply a template perform following steps:
• In the section Available Templates, select a template.
• Click the arrow button to transfer the template settings to the IED. Note: Applying the
template will overwrite all current communication parameters. You can undo this action
only by exiting the dialog with Cancel.

Depending on the selected primary role, there are other settings available. For more information see
the following chapters which describe how to create IED with specific roles.

Click OK to create the new IED or Cancel to close the dialog without creating an IED.

If you created a new IED, the Navigation Tree will change to either the Substation or IEDs Tree.

Integrated Engineering Tool 77


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 7 1MRK500114-UEN Rev. X
IED Engineering

7.2.3 Create New Protection/Control IED GUID-5E006333-45BC-4F08-AE74-D84ABD3D759F v1

This section describes the specific part of configuring a Protection or Control IED and is based on the
general description for creating an IED (see chapter "Create New IED" ):

1. Select the Substation or IEDs Navigation Tree, and select an element below which you want to
create an IED. This could be:
• a ‘Substation’, ‘Voltage Level’ or ‘Bay’ element in the ‘Substation’ Tree
• the ‘Project’ element in the ‘IEDs’ tree

Right-click the element -> the context menu for that element appears. Select Create New IED ->
Protection/Control IED…:

IEC202100377 V1 EN-US

2. This opens the dialog Create new IED.


3. To configure the general part, see chapter "Create New IED".
4. In the section Role Parameters -> tab IED, you can define if the IED is for protection and/or
control.

7.2.4 Create New Switch GUID-52447B6E-DD10-4262-A395-A938F673D770 v1

If you create a switch, IET600 will currently automatically generate its model based on IEC 61850
and according to IEC/TR 61850-90-4.

78 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 7
IED Engineering

This section describes the specific part of configuring a switch and is based on the general
description for creating an IED (see chapter "Create New IED"):

1. Select the ‘Substation’ or ‘IEDs’ Navigation Tree, and select an element below which you want
to create an IED. This could be either:
• a ‘Substation’, ‘Voltage Level’ or ‘Bay’ element in the ‘Substation’ Tree
• the ‘Project’ element in the ‘IEDs’ tree
Right-click the element -> the context menu for that element appears. Select Create New
IED -> Switch…:

IEC202100378 V1 EN-US

The dialog Create new IED will open.


2. To configure the general part, see chapter "Create New IED"
3. In the section ‘Role Parameters -> Switch’ you can define the ‘RSTP priority’. Possible values
are root switch, backup switch or undefined.
4. When creating a switch, the ‘Ports’ table in the dialog contains the additional columns ‘MAU
Type’* and ’Auto negotiation’. If ‘Auto negotiation’ is disabled a ‘MAU Type’* should be selected.
Configure them as needed.
“MAU” is an abbreviation for “Medium Attachment Unit”; it defines certain capabilities of a port.
For a detailed explanation, consult chapter Annex: Switch Configuration.

Integrated Engineering Tool 79


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 7 1MRK500114-UEN Rev. X
IED Engineering

7.2.5 Create New HMI GUID-F4A80AB0-D21D-4959-8804-1672E331B79A v1

This section describes the specific part of configuring an HMI and is based on the general description
for creating an IED (see chapter "Create New IED"):

1. Select the ‘Substation’ or ‘IEDs’ Navigation Tree, and select an element below which you want
to create an IED. This could be either:
• a ‘Substation’, ‘Voltage Level’ or ‘Bay’ element in the ‘Substation’ Tree
• the ‘Project’ element in the ‘IEDs’ tree
Right-click the element -> the context menu for that element appears. Select Create New
IED -> HMI…:

IEC202100379 V1 EN-US

2. This opens the Create new IED dialog.


3. To configure the general part see chapter "Create New IED".
4. In the section ‘Role Parameters -> HMI’ you can specify one or several OPC servers which run
on the HMI you are creating. To create or remove an OPC server right-click in the OPC server
table and choose Insert new OPC server resp. Delete OPC server(s):

80 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 7
IED Engineering

GUID-299DB8E6-1589-471F-9931-4CD1208F2B49 V1 EN-US

For each created OPC server, a new access point on the HMI will be created automatically. Like
other access points this access points also appears in the Access Point tab.
The OPC servers have their own Edition. Edition of new OPC server is Edition 2. The only way
to change edition of OPC server is to go to the Configure IED dialog and then select OPC that
you want to configure. After submitting the changes all necessary changes to the model are
made.

This feature was added in IET600 5.3 FP8, all OPC servers that are migrated from
previous versions of IET600 have their Edition unchanged.
5. In the section ‘Role Parameters -> HMI’ you can specify one or several ISS Clients. To create or
remove an ISS client right-click in the ISS client table and choose Insert New ISS Client resp.
Delete ISS Client(s):

Integrated Engineering Tool 81


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 7 1MRK500114-UEN Rev. X
IED Engineering

For ISS Client 'Edition' propery is defined with two options: Ed.1 and Ed.2. But internally there is
only Ed.2 model. 'Edition' property has influence in Client editors where a client connection can
be created only with a compatible source dataset and a client.

To convert already exisitng OPC server to ISS clients see Annex: OPC server to ISS
client conversion

7.2.6 Configure IEDs GUID-183D03A2-84EE-429F-8F27-9BDB597E3685 v1

Already created IED can be configured:

1. Select the IED you want to configure in:


• 'Substation' Navigation tree
• 'IEDs' Navigation tree
• 'HMIs' Navigation tree
2. Right-click the IED -> the context appears. Select Configure IED…:

82 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 7
IED Engineering

IEC202100383 V1 EN-US

3. This opens the Configure IED dialog:

Integrated Engineering Tool 83


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 7 1MRK500114-UEN Rev. X
IED Engineering

IEC202100384 V1 EN-US

4. You can now reconfigure the IED. In contrast to the ‘Create IED’ procedure (see Chapter
"Create New IED"), some input fields are disabled or have more restricted selection range:
• The IED location is fixed.
• The primary role and also further roles of the IED cannot be changed (for more detailed
information see chapter "IED Roles").
• Additional Role parameters can be set, e.g. in the above example, you can check the
‘Protection’ flag to define an IED specifically as ‘Protection IED’.
• When setting an IED’s Primary Role to Router, the user should define at least two access
points as routers.

IEC202100385 V1 EN-US

• When setting an IED’s Primary Role to Time Server, the user should define at least one
access point as a clock.

84 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 7
IED Engineering

IEC202100386 V1 EN-US

• It’s possible to configure the Synchronization Protocols that a Time Server uses. At the
bottom of the dialog window, in the Role Parameters section, the user can select
Synchronization Protocols and add their own, custom ones as well. Multiple protocols can
be added to each Time Server IED.

IEC202100387 V1 EN-US

5. Click OK to adopt the changes or Cancel to reject all changes.

Integrated Engineering Tool 85


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 7 1MRK500114-UEN Rev. X
IED Engineering

7.3 Updating IEDs GUID-DE6BA47B-ED39-414A-9D16-0EF4A5CA9F56 v1

7.3.1 Overview GUID-12A8E3DE-C66A-4FAB-89A3-E382A59EB704 v1

Updating an IED involves importing the ICD or IID file for a given IED. IEDs can be updated:

• from the Main menu -> IEDs tab -> Update IEDs
• from the context menu of an IED (single IED only)
• from the context menu of an element that can have IEDs below it, e.g. Substation, Voltage Level
or Bay

7.3.2 Compare IEDs GUID-240EFA4E-8E10-4059-BA42-029A88513D01 v1

The 'Compare' dialog provides additional information when re-importing SCL data.

It is available when updating or re-importing SCL files into the project (e.g. Update IED). The dialog
provides:

• preview of the content in import file


• compare differences between data in project and in the import file

The dialog is opened by clicking on the Compare column during Update IED, as shown below:

IEC202100388 V1 EN-US

86 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 7
IED Engineering

On the left-hand side of the dialog is the IED model in the import file and on the right-hand side is the
existing IED model in the project. By selecting a node in either window, the details of the differences
are shown in the bottom window.

7.3.3 Update one IED GUID-D5ABC924-B966-4F04-ACD2-C1FBD02E250B v1

1. Right-click on the IED you want to update -> the IED context menu appears:

IEC202100389 V1 EN-US

2. Select Update IED -> the normal dialog for selecting a file appears.
3. Select any valid SCL file (SCD-, ICD- or IID-file) and click Open.
4. The following dialog appears:

Integrated Engineering Tool 87


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 7 1MRK500114-UEN Rev. X
IED Engineering

IEC202100390 V1 EN-US

If the file contains only one IED (ICD- or IID-file), the source IED (in the file) will automatically be
mapped to the destination IED (in IET600). If the file contains several IEDs, IET600 will try to
automatically match IEDs with the same name. For those IEDs in IET600 where no IED with
matching name is found, you need to select the source IED manually.
• You may select the same source IED to be imported into several destination IEDs; in
some situations, this may be helpful.
• You can also override any automatic mapping done by IET600.

The ‘Compare’ column indicates whether the IET600 IED and the IED in the file are equal (==)
or different (<>). You can click on the symbol, which will open the Compare dialog as described
in the previous section.
If IET600 detects something which might be due to an error (e.g. if the source IED has a
different manufacturer or IED Type, this might indicate that the wrong ICD/IID file has been
selected), it shows the ‘Error’ indicator in the ‘Update’ Column and unchecks this column.
Putting the mouse over the error indicator shows possible errors:

IEC202100391 V1 EN-US

You may now either Cancel, compare both IEDs for differences, or simply override the warning
by checking Update manually.
5. To check the differences between the Source and the Destination IED, click the button in the
Compare column. The following dialog will open:

88 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 7
IED Engineering

IEC202100392 V1 EN-US

Check the differences. ‘Close’ will return you to the 'Update IED(s)' dialog.
6. To import the IED from the file, ensure that Update is checked, then click OK. The IED will be
imported without further questions.
To close the dialog without importing anything (e.g. if you found unexpected differences when
comparing IEDs as described above), click Cancel.

7.3.4 Update Several IEDs Together GUID-9BAAF6C2-1590-4A95-A689-BAC702E126B6 v1

1. Right-click on a Project, Substation, Voltage Level or Bay-> the context menu appears:

Integrated Engineering Tool 89


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 7 1MRK500114-UEN Rev. X
IED Engineering

IEC202100394 V1 EN-US

2. Select Update IEDs… -> the normal dialog for selecting a file appears.
3. Select any valid SCL file (SCD-, ICD- or IID-file) and click Open.
The following dialog appears:

IEC202100395 V1 EN-US

90 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 7
IED Engineering

IET600 will try to automatically match IEDs with the same name in IET600 and in the file. For
those IEDs in IET600 where no IED with matching name is found, you need to select the source
IED manually.
• You may select the same source IED to be imported into several destination IEDs; in
some situations, this may be helpful.
• You can also override any automatic mapping done by IET600.
The ‘Compare’ column indicates whether the IET600 IED and the IED in the file are equal
(==) or different (<>). You can click on the symbol, which will open the Compare dialog as
described in the previous chapter.
The ‘Update’ column allows you to select/deselect individual IEDs for updating. Only IEDs
marked with  will be included in the update.
The ‘Error’ indicator in the ‘Update’ column indicates potential import problems which you
can evaluate as described in the previous chapter.

Be aware that any error will unselect the IED for an ‘Update’ to avoid
accidentally overwriting the current configuration with a faulty one.

4. Click OK in the Update IEDs dialog to update the selected IEDs. Click Cancel to close the
dialog without updating any IEDs.

7.4 Deleting IEDs GUID-28CF7704-797A-4585-A39F-C518B40213C3 v1

7.4.1 Overview GUID-9C03A225-2591-4575-A5A5-D9A463ADD557 v1

Basically, you can delete any IED from its context menu. You can either delete the IED totally or you
can remove its content, leaving the IED empty.

7.4.2 Delete an IED GUID-FDF2DFBE-FFB7-46D3-AABC-F16D47CEB3EE v1

1. Right-click on the IED you want to delete -> the context menu appears:

Integrated Engineering Tool 91


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 7 1MRK500114-UEN Rev. X
IED Engineering

IEC202100396 V1 EN-US

2. Select Delete -> a confirmation dialog appears:

IEC202100397 V1 EN-US

3. Confirm deletion with Yes or cancel it with No.

7.4.3 Delete the Contents of an IED GUID-3C4B838F-91AE-44F2-BF5A-76FF2242FF5A v1

1. Right-click on the IED whose contents you want to delete -> the context menu appears:

92 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 7
IED Engineering

IEC202100399 V1 EN-US

2. Select Delete Content -> a confirmation dialog appears:

IEC202100400 V1 EN-US

3. Confirm deletion with Yes or cancel it with No.

7.5 Mapping LNs to Substation Elements (“LN Mapping”) GUID-247E5086-5DCF-4EFE-A921-3D4D38F43A63 v1

7.5.1 Overview GUID-A60EDCE3-CBAA-4734-8364-C30F8DA06DE9 v1

According to part 6 of the IEC 61850 standard, the SCD file shall describe not only the system
specification in terms of the single line diagram and configured IEDs in terms of logical nodes (LNs),
but also the relation between these LNs to parts and equipment of the single line. The LN Mapping
table in IET600 serves as editor to configure this relation. The table is available in the Single Line
Diagram (SLD) editor.

Since the LN mapping information from the ICD/IID file is not available in IET600, it must be entered
manually. Note that this information must be synchronized with the functional/LN mapping used in the
IED configuration tool (e.g. PCM600).

Integrated Engineering Tool 93


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 7 1MRK500114-UEN Rev. X
IED Engineering

By default, the LN Mapping editor is displayed when displaying a Bay, but hidden when displaying a
Voltage Level. To override this behavior, use the ‘Show/Hide LN Mapping Editor’ menu item in the
‘Single Line Diagram’ menu:

IEC202100402 V1 EN-US

The LN mapping table is shown on the right hand side of the SLD editor, as shown below:

IEC202100403 V1 EN-US

For Substation Level the LN Mapping editor is always displayed (SLD editor is not displayed) and
context tab in Main menu is not visible.

Each row in the table refers to a LN and its properties. The following properties are shown:

• Mapping Target – reference to the Bay and primary equipment


• IED Name, LD Name, LN Name, LN Prefix, LN Class, Instance – LN properties
• Status – indicates the source of the LN:
• ‘resolved’ indicates a LN from an IED in the project.
• ‘virtual’ indicates that a LN has been defined from an HMI signal and is not yet mapped to
an IED.

The last point refers to a concept of decoupling between the IEC-61850-model of an IED and its HMI
signals, which is described in the chapter on HMI Engineering.

To map LNs from an IED which belongs to another Bay, select the field ‘Add LNs from IED’ and
select another IED in the project.

To rapidly map all LNs to the Bay and then map some few LNs individually to Equipment (typically
the CSWIs and some measurement LNs), use ‘Fill Down’ from the cell context menu.

7.5.2 LN Mapping Restrictions GUID-843F443F-7199-4934-AEE5-A5F41CB5319D v1

IET600 places some restrictions to the LN Mapping Editor. These restrictions were implemented to
improve the quality of the substation section in the SCD file. Some common restrictions are:

94 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 7
IED Engineering

• LN type CSWI can only be mapped to equipment of type Circuit Breaker (CBR) or Disconnector
(DIS); each Circuit Breaker (CBR) or Disconnector (DIS) can have only one CSWI allocated.
• LN type XSWI can only be mapped to equipment of type Disconnector (DIS); each Disconnector
(DIS) can have 1..4 XSWI allocated.
This is to allow the modelling of phases; however, it is better practice to model the phases and
attach 1 XSWI to each phase and 1 - the common XSWI calculated from the phases – to the
DIS itself.
• LN type XCBR can only be mapped to equipment of type Circuit Breaker (CBR); each Circuit
Breaker (CBR) can have 1..4 XCBR allocated.
This is to allow the modelling of phases; however, it is better practice to model the phases and
attach 1 XCBR to each phase and 1 - the common XCBR calculated from the phases – to the
CBR itself.
• RSYN can only be mapped to equipment of the type CBR; each CBR can have 1..5 RSYN
allocated (for max. 2 control and 3 protection IEDs).
• LN type CILO can only be mapped to equipment of the type Circuit Breaker (CBR) or
Disconnector (DIS); each Circuit Breaker (CBR) or Disconnector (DIS) can have several CILO
allocated.
This is to allow a distributed interlocking logic where different CILOs may be used to provide the
complete interlocking logic.
• LN type MMXU can only be mapped to equipment of the type Current Transformer (CT) or
Voltage Transformer (VT).
• LN type LLN0 and LPHD can only be mapped to the Bay.

7.5.3 Map LNs in Bays GUID-42AA0A97-8A11-41D3-A52C-F7D1116116C7 v1

1. Select the 'Substation' tab in the Navigation Tree.


In the Navigation Tree, select the element you want in the configuration Tree (Voltage Level or
Bay).
2. Select the 'SLD' editor.
By default, the LN Mapping editor is displayed when displaying a Bay, but hidden when
displaying a Voltage Level. If it is hidden, make it visible from the tab Single Line Diagram ->
Show/Hide LN Mapping Editor.

IEC202100404 V1 EN-US

On the right of the single line diagram is the LN Mapping Editor. The first column shows the
mapping target and the remaining columns to the right show the available LNs and their
properties. The first column allows you to select a Substation item (Bay or Equipment) to map to
that LN.

Integrated Engineering Tool 95


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 7 1MRK500114-UEN Rev. X
IED Engineering

IEC202100405 V1 EN-US

To select the LN Mapping target, one can either type in the target, select it from a
drop down menu, or use the ‘Fill Down’ function to fill multiple rows automatically.
IET600 will apply the LN mapping restrictions as described in the previous section.

7.6 Disturbance Recording Configuration GUID-B14BE459-F3CC-43EE-93A9-A09861CF155C v1

7.6.1 Introduction GUID-9FA3A246-AABF-48E0-BEA4-4EE8E67115EE v1

The configuration for Disturbance Recording can currently only be used by MicroSCADA via
‘.sasmsc’ file. If you need any other program to upload Disturbance Recording files from an IED for
further processing, a configuration in IET600 will currently not be helpful.

In the following description, the following terms will be used:

• Disturbance Recording Server for an IED that creates Disturbance Record files (typically a
Protection IED).
• Disturbance Recording Collector for an IED that uploads Disturbance Recording files from
individual Disturbance Recording Servers and collects them in a defined place in the file system.

7.6.2 Configuration GUID-C3282C26-B914-4FEE-A2C9-86E35021483E v1

The configuration for Disturbance Recording is done in the IED Settings Editor.

Disturbance Recording can only be configured for:

• IEDs (see chapter "Configure IEDs" for more details), these IEDs act as Disturbance Recording
Servers.
• OPC Servers, these IEDs act as Disturbance Recording Collectors.

If all values are greyed out, preventing you from configuring individual settings, please check whether
one of the above conditions is fulfilled.

96 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 7
IED Engineering

Column Function
Disturbance Recording Enabled Checking this flag on a Disturbance Recording Server (a
Protection IED) will indicate to a client that it should try to
upload Disturbance Records from this IED. The flag is
enabled only
Checking this flag on a Disturbance Recording Collector
(OPC Server) will indicate that it is an active client.
Disturbance Recording Delete Recording After Upload Checking this flag will cause a Disturbance Recording
Collector to try and remove Disturbance Records from an
IED after a successful upload.
When having several Disturbance Recording Collectors
doing uploads from an IED, it is important to set this flag
correctly (normally only one Collector should have this
flag set).
Disturbance Recording Use IEC 61850 Default Directory IEC 61850 specifies a fixed directory on a protection
IED, from where Disturbance Records can be retrieved
by a Disturbance Recording Collector: the IED must
have a Logical Device containing an LN of class RDRE;
the path is then [LDName]\COMTRADE.
Checking this flag on a Disturbance Recording Server
will cause the Disturbance Recording Directory to be set
to this fixed value.
Disturbance Recording Directory The directory where the Disturbance Recording files are
stored.
On a Disturbance Recording Server, it is the directory
from where the Disturbance Recording Collector will try
to upload files. This value is read-only, if the ‘Disturbance
Recording Use IEC 61850 Default Directory’ flag is
checked. See chapter "Disturbance Recording Directory
Recommendations" for detailed recommendations how
to set this path.
On a Disturbance Recording Collector (currently only
supported for ABB OPC Servers), it is the root directory
where uploaded Disturbance Record files will be saved,
(the substructure may vary between different
Disturbance Recording Collectors).
Disturbance Recording Polling Period On a Disturbance Recording Server, the minimum
sensible polling period. Used for Legacy purposes;
mostly an event-triggered upload is used.
On a Disturbance Recording Collector, the actual polling
period, should not be smaller than the largest minimum
polling period of any Disturbance Recording Server.
Used for legacy purposes; today, mostly an event-
triggered upload is used.
Table continues on next page

Integrated Engineering Tool 97


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 7 1MRK500114-UEN Rev. X
IED Engineering

Column Function
Disturbance Recording MMS Upload Capability A flag indicating whether Disturbance Records can be
uploaded via 8-MMS protocol (IEC 61850).
For IEC 61850 Ed.2 IEDs, this is read-only, as it is
defined in the Services of the IED.
For IEC 61850 Ed.1 IEDs, the default value is taken from
the IED Capabilities. If several Capabilities are selected,
8-MMS will be preferred over FTP over FTPS.
Disturbance Recording FTP Upload Capability A flag indicating whether Disturbance Records can be
uploaded via FTP protocol (IEC 61850).
For IEC 61850 Ed.2 IEDs, this is read-only, as it is
defined in the Services of the IED.
For IEC 61850 Ed.1 IEDs, the default value is taken from
the IED Capabilities. If several Capabilities are selected,
8-MMS will be preferred over FTP over FTPS.
Disturbance Recording FTPS Upload Capability A flag indicating whether Disturbance Records can be
uploaded via FTPS protocol (IEC 61850).
For IEC 61850 Ed.2 IEDs, this is read-only, as it is
defined in the Services of the IED.
For IEC 61850 Ed.1 IEDs, the default value is taken from
the IED Capabilities. If several Capabilities are selected,
8-MMS will be preferred over FTP over FTPS; to enforce
FTPS, you need to uncheck the other two flags.

7.6.3 Disturbance Recording Directory Recommendations GUID-2260FF2D-411B-4F66-9D25-01579C22EF42 v1

Be aware that the handling of the Disturbance Recording Directory on a Disturbance Recording
Server is currently not yet consistent. As a guidance we suggest to use the following paths (without
the “”):

• For IED611 series, use “COMTRADE\” as path (an empty path will upload unexpected files).
• For IED615 series, use “COMTRADE\” as path (an empty path will upload unexpected files).
• For IED620 series, use “COMTRADE\” as path (an empty path will upload unexpected files).
• For most other ABB IEDs, use “*” (the IED will automatically use its internally known path).
• For many 3rd party IEDs, try “*” (the IED will automatically use its internally known path). If this
does not work, consult the manual.
• For Ed.2-compliant IEDs, you may try “Use IEC 61850 Default Directory”; however, the current
experience is that this fails fairly often; also this is not useful when using protocols other than 8-
MMS for upload. Always test this setting, and use “*”, if it does not work.

7.6.4 Export GUID-29C4D9E4-C6DA-4740-9AB5-099CF2AF14D5 v1

The engineer does not need to export this information separately, as it will automatically be included
in an ‘.sasmsc’ file, provided that the following condition is met:

• At least one OPC Server belonging to the MicroSCADA must be configured as a Disturbance
Recording Collector by setting its ‘Disturbance Recording Enabled’ flag to true.

7.7 Dynamic Datasets GUID-1111D1DA-4368-442C-8721-68BB8866510C v1

This flag is currently just used for the OPC Server as an RCB Client, to specify whether it should
initialize dynamic Datasets from an 8-MMS Server IED (the information is included in the *.sasmsc
file only, see chapter "Import a MicroSCADA ‘sasmsc’ File").

Dynamic Datasets A flag indicating whether Dynamic Datasets should be


queried for by the MicroSCADA OPC Server

98 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 7
IED Engineering

If the IED not have a server, only a Client Access Point, the flag is in intermediate state. It should be
left as such.

In any other situation, the flag is set to false. In this case, the MicroSCADA OPC Server will not query
for Dynamic Datasets (as this is the most common situation). You may set the flag to true which will
the cause the MicroSCADA OPC Server to query the Server IED. This behavior can be enforced
even though the Server IED may not provide Dynamic Datasets, it is the responsibility of the
engineer to configure this correctly).

7.8 SNMP Configuration Usage GUID-36A0C7F8-FC46-4453-8E46-6C3FCC1BEEC6 v1

The SNMP Configuration can currently only be used by MicroSCADA and its new SNMP-OPC-
Gateway via ‘.sasmsc’ file.

If you need any other program to supervise IEDs via SNMP (including the Obermeier OPC-SNMP
Gateway), a configuration in IET600 will currently not be helpful.

The parameters described below are used to tell the SNMP-OPC-Gateway how to communicate with
the corresponding Server IEDs.

If You want to modyfie SNMP properties IED must an ABB SNMP OPC or SNMP IED.

ABB SNMP OPC - OPC server with manufacturer "ABB" in SNMP subnetwork

SNMP IED - an IED wit at least on ABB SNMP signal

Integrated Engineering Tool 99


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 7 1MRK500114-UEN Rev. X
IED Engineering

7.8.1 SNMP Properties Configuration GUID-40E76499-C495-46BD-A5B0-3BC34B8F05F7 v1

Property Description
SNMP String specifying the password to allow writing via SNMP.
Write Community In SNMPv3, proper authentication is used. In older
SNMP versions, this string is equivalent to a cleartext(!)
password: the client must send this string along with any
request, the server will only respond if the string/
password is known to it.
In IET600, the string is defined as the one that the client
will send to the Server IED. The Server IED cannot
currently be configured with IET600, the engineer must
therefore find out what string the Server IED expects and
configure it appropriately.
The string “private” is a default setting of most SNMP
Servers which allow to write; it does not mean that
writing is disabled (!). It is good practice for each network
not to use such default strings; however, be aware that
the string is readable in plain text in the IET600
configuration database, the SNMP-OPC-Gateway
configuration file and on the network.
SNMP String specifying the password to allow reading via
Read Community SNMP.
In SNMPv3, proper authentication is used. In older
SNMP versions, this string is equivalent to a cleartext(!)
password: the client must send this string along with any
request, the server will only respond if the string is
known to it.
In IET600, the string is defined as the one that the client
will send to the Server IED. The Server IED cannot
currently be configured with IET600, the engineer must
therefore find out what string the Server IED expects and
configure it appropriately.
The string “public” is a default setting of most SNMP
Servers which allow to write; it does not mean that
writing is disabled (!). It is good practice for each network
not to use such default strings; however, be aware that
the string is readable in plain text in the IET600
configuration database, the SNMP-OPC-Gateway
configuration file and on the network.
SNMP Poll Rate Minimum seconds between two polls from the SNMP
Client to the SNMP Server.
SNMP Timeout Seconds for Timeout if an SNMP Server does not
respond to a request from an SNMP Client.
SNMP Version SNMP Protocol Version to communicate.
Can be SNMPv1, SNMPv2c or SNMPv3
SNMP Authentication Protocol Algorithm for authentication of client to server.
SNMP Encryption Algorithm Algorithm for encryption of communication between
client and server.
SNMP User Name User name used for authentication
(As IET600 does not provide suitable protection – such
as encryption of data – and as it is not compatible with
current security practice to have plaintext passwords, it is
not possible to enter the password for the user here).

7.8.2 SNMP Configuration of Signals GUID-535DD9B0-69DC-453A-BE24-ABA7ED561344 v1

The above-mentioned attributes apply to the SNMP Client. Additionally, the individual Signals need to
be configured with OIDs, see chapter "Mapping Signals to SNMP OIDs".

100 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 7
IED Engineering

7.9 PCM Template Usage GUID-0643327C-CD20-4181-8D08-BA38FCC3BF33 v1

IET600 provides two attributes which can be used to refer to templates to be used in PCM when
exchanging SCL Data with PCM600. The usage of such Templates and object types is entirely
determined in PCM600; IET600 only provides a way to specify these templates as names for each
IED.

7.9.1 PCM Template Configuration GUID-6BFA33B0-2170-4A08-81CA-2B4DC4E48E94 v1

The configuration for PCM Templates is done in the ‘IED Settings’ Editor. The following two columns
are provided:

PCM Template Can be used to refer to a matching template in PCM. Set


or change only in collaboration with the person doing
PCM600 engineering.
PCM Object Type Can be used to refer to a matching object type in PCM.
Set or change only in collaboration with the person doing
PCM600 engineering.

Integrated Engineering Tool 101


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
102
1MRK500114-UEN Rev. X Section 8
IEC 61850 Subnetwork Engineering

Section 8 IEC 61850 Subnetwork Engineering GUID-31310723-9B81-4834-AB45-64B5799E6B55 v1

8.1 Introduction GUID-7CFBF400-0929-492A-B7AB-2E7E6A803854 v1

A ‘Subnetwork’ is an artificial item defined by the IEC 61850 standard. It serves basically to define a
collection of IEDs which all talk the same protocol. The protocol is defined on the Subnetwork level,
IEDs attached to the Subnetwork are assumed to talk the corresponding protocol.

Therefore a Subnetwork is a logical grouping of IEDs talking the same protocol. It must not be
confused with the TCP/IP Subnet or with the physical network.

8.2 Subnetwork Conditions and Limitations GUID-FBFBD848-2421-4114-BEA7-EB89B161361D v1

8.2.1 IEC 61850 Subnetworks GUID-1166249E-131F-47FC-AF53-FB7D102E4416 v1

IEC 61850 requires that all IEDs using any protocol defined in IEC 61850 (8-MMS, GOOSE or
Sampled Values) are attached to the same Subnetwork.

IEC 61850 historically did not distinguish between those protocols. One needs to look at the IED
services to find out whether an IED is capable of talking 8-MMS, GOOSE and/or Sampled Values.

8.2.2 Modelling of Other Protocols GUID-97FBA962-CC49-4E31-98A4-6D2094ED2353 v1

An IED may be capable of different protocols (e.g. 8-MMS/GOOSE for IEC 61850, FTP for
Disturbance Recording upload and SNMP for Network supervision).

However, the number of protocols which can be modeled via Subnetworks is limited by its Access
Points. It is quite common that an IED, although capable of several protocols, has only 1 Access
Point. Its protocol capabilities (e.g. as described in the example above) cannot be modelled fully, as
the System Configuration Tool is not allowed to add, modify or remove Access Points.

8.2.3 Modelling of HMI GUID-F82CF0D7-52A8-4216-900B-BCF795D80510 v1

While adding HMI`s access points there is a limitation

8.3 Subnetwork Configuration GUID-6958ADE0-FC19-46FA-A5DF-AA924E8F7C52 v1

The 'Communication' Navigation Tree displays the Subnetworks and IEDs (or – more precisely - IED
access points) assigned to the Subnetwork. The 'Subnetworks' editor shows engineering information
related to the IED Access points, including:

• Subnetwork name
• IP address
• IP subnet mask

The following section will describe how to build this communication structure and define the
communication properties in IET600.

8.3.1 Create a Subnetwork GUID-96DA53DD-42D0-49F3-AEBC-573EB50DEA6E v1

1. Open the Communication menu tab and select the Subnetworks button:

Integrated Engineering Tool 103


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 8 1MRK500114-UEN Rev. X
IEC 61850 Subnetwork Engineering

IEC202100406 V1 EN-US

2. Alternatively, select the Communication tab in the Navigation Tree, right-click on the project
and select Create New Subnetwork:

IEC202100407 V1 EN-US

The following dialog appears:

104 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 8
IEC 61850 Subnetwork Engineering

IEC202100408 V1 EN-US

(A Subnetwork can only be created in the project which is pre-selected).


The tool proposes a name, which you can adapt according to your wishes. Invalid names are
indicated by an error mark (Invalid names typically are either duplicate names or contain
characters that are not allowed for a particular element).
3. Configure the protocol type for this Subnetwork from the available selection.
4. Click OK to create the new Subnetwork or Cancel to close the dialog without creating a
Subnetwork.
5. If you created a new Subnetwork, the Navigation Tree will change to ‘Communication’ and the
Subnetwork will appear there. The editor will not change.

8.3.2 Connect IEDs to a Subnetwork in the Subnetwork Editor GUID-BDC7252B-CBE2-494A-B1D0-C40BB0E08E83 v1

Select a Navigation Tree where the Subnetwork Editor is visible (‘Substation’, ‘IEDs’ or
‘Communication’ tab); select an appropriate element (usually the ‘Communications’ tab and the
Project or a Subnetwork is a good choice).

1. Select the ‘Subnetwork’ editor:

Integrated Engineering Tool 105


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 8 1MRK500114-UEN Rev. X
IEC 61850 Subnetwork Engineering

IEC202100409 V1 EN-US

2. From the combo box with available Subnetworks, select the Subnetwork to which you want to
add the IED/Access Point. To disconnect it, select the empty row.

After exiting the Combo Box, the Communication Tree will be updated, the IED (or, more precisely, its
‘Connected Access Point’ can be seen under the new Subnetwork).

An IED can have several Access Points which can be connected to different Subnetworks. It is not
allowed, however, to have a Server IED with a Server with two Access Points and connect them both
to the same Subnetwork.

Use the ‘Fill Down’ mechanism to rapidly connect multiple IEDs/Access Points to a Subnetwork. Use
an appropriate sorting mechanism to avoid mapping two Access Points of the same IED to the same
Subnetwork, e.g. by sorting first on the Access Point and the on the IED.

IEDs of different IEC 61850 versions should not be put to the same subnetwork as this causes
compatibility problems. For more details, read chapter (IET600 Mixed System Engineering).

8.3.3 Connect IEDs to a Subnetwork in the Communication Tree GUID-23321A04-CBF8-42DD-9FFC-4F7228B2D547 v1

1. Select the ‘Communication’ Navigation Panel.


2. Drag'n'drop an IED (or, more precisely, its “Connected Access Point”) to the Subnetwork you
want to connect it to. Drag'n'drop it to the Project node to disconnect it from any Subnetwork.

106 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 8
IEC 61850 Subnetwork Engineering

IEC202100410 V1 EN-US

IEDs of different IEC 61850 versions should not be put to the same subnetwork as this causes
compatibility problems. The indicator next to the subnetwork icon gives a hint:

E1: Contains Editions 1 IEDs only.


E2: Contains Editions 2 IEDs only.
M: ‘mixed’, contains both Editions 1 and Editions 2 IEDs;
this should be avoided.
(empty): Non-61850 subnetwork (e.g. NCC, SNMP)

For more details, please consult chapter "IET600 Mixed System Engineering".

8.3.4 Edit IP addresses GUID-6410F4AA-E6CB-4F78-B77E-771FC0375351 v1

1. Select the 'Subnetwork' Editor:

Integrated Engineering Tool 107


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 8 1MRK500114-UEN Rev. X
IEC 61850 Subnetwork Engineering

IEC202100411 V1 EN-US

Enter the IP Addresses directly in the column ‘IP Address’. Duplicate addresses will be marked with a
red circle (Exception: OPC servers can have the same addresses as their related HMI).

If you need to edit additional address information (e.g. OSI addresses), click on the button in the ‘Edit
Addresses’ column. A dialog will pop up which will allow editing additional address attributes. This
should not normally be needed, though.

108 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 9
Communication Configuration Engineering

Section 9 Communication Configuration


Engineering GUID-665685E2-EB95-4CE6-99BC-74FFE9C3061F v1

9.1 Introduction GUID-A41A937A-CD75-4D1A-95A5-5A67D9602ED4 v1

The Communication Configuration Diagram (CCD) allows you to configure the physical
communication topology of a project, i.e. to:

• arrange all IEDs of a whole project in one diagram


• define physical ports of IEDs and their properties (e.g. redundancy type, plug type or position).
• create connections between ports of IEDs, thereby designing the communication topology.

9.2 The ‘CCD’ Editor GUID-D691F697-F51B-420D-ACCC-E2F64965FB68 v1

The CCD is divided into two views and additionally contains a toolbar.

IEC202100412 V1 EN-US

The ratio between the diagram view and the table view is adjustable by dragging the divider placed
between the two views to the left respectively to the right. Optionally the table view can be collapsed
by clicking the button centered the divider element (see illustration above).

9.2.1 Diagram View GUID-80194AF5-BC17-4573-9C5C-7DEA309227D1 v1

The diagram view is intended to design the topology by creating connections between IEDs.

The diagram view itself also is divided into 2 areas:

• The main area (colored in white) at the right side.


• The area for unplaced IEDs (colored in blue) at the left side. This area is only visible if one or
more unplaced IEDs are available.

Integrated Engineering Tool 109


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 9 1MRK500114-UEN Rev. X
Communication Configuration Engineering

Additionally, the diagram has sections. These sections are intended to support the design of a clearly
arranged topology; and they are also used for the auto-arrange mechanism (see chapter "Auto-
Arranging IEDs").

The height of the diagram sections can be adjusted by dragging the section dividers upwards or
downwards:

IEC202100413 V1 EN-US

To hide the sections, unselect Show diagram sections in the diagram context menu:

IEC202100414 V1 EN-US

9.2.2 Table View GUID-4B07AEA0-827E-45B9-BB51-B1618657C39A v1

This view contains two tables. The table in the first tab lists all IEDs from the whole project and their
main communication properties. The table in the second tab lists the ports of all IEDs.

110 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 9
Communication Configuration Engineering

In contrast to the IED configuration dialog (see chapter "Configure IEDs") which is intended to
configure a single IED, the table view allows editing properties from several IEDs together (e.g.
changing the Plug type of several ports with help of the Fill-down mechanism).

9.2.3 Navigate Within Views GUID-A727A331-E43F-42DC-8847-38DC1787E769 v1

In general, the selection in the diagram view and in the two table views are always synchronized.
Selecting one or several items in the diagram view automatically selects the same items in both table
views:

Action in Diagram View IED Table View Port hardware View Port VLANs View
Select an IED IED row will be selected. All ports of IED will be All ports of IED will be
selected. selected.
Select a Connection IEDs on which the Ports on which the Ports on which the
connection is attached will connection is attached will connection is attached will
be marked. be marked. be marked.

Action in IED Table View Diagram View Port hardware Table View Port VLANs Table View
Select an IED Selected IED will be All ports of selected IED All ports of selected IED
marked. will be marked. will be marked.

Action in Port Table View Diagram View IED Table View


Select a Port IED to which the port belongs and IED to which the port belongs will be
connection which is attached to the selected.
port will be selected.

All actions described above can be performed on one or several elements. Also the two actions in
the Diagram View can be combined.

9.2.4 Toolbar GUID-229A4F47-7F89-474F-9BBF-CCD9BC1F84F0 v1

The toolbar contains several auxiliary tools for dealing with the communication configuration diagram,
such as:

• Zooming / panning
• Printing (including print configuration)
• Exporting an image of the diagram
• Creating rectangle shapes and annotation in the diagram
• Editing diagram properties (diagram size, format)

By default, the toolbar only displays the last used ‘print out’ and ‘create diagram shape’ option. To
open the full menu of this tools move the mouse over the button without clicking it and then select the
desired option.

9.2.5 IED Shapes GUID-33987D4A-0A97-4F19-AD16-3BB201DF4113 v1

In the Communication Configuration Diagram, the IEDs are displayed with different shapes
depending on their primary role:

Integrated Engineering Tool 111


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 9 1MRK500114-UEN Rev. X
Communication Configuration Engineering

IED Shape Associated Roles


IED (protection / control), Security Device, Archive

IEC202100415 V1 EN-US

Switch, Hub, Router (shape resizes according to port


count)

HMI (including OPC servers)

Gateway, NCC

Printer

Time Server

Merging Unit

Some IED roles support redundant ports. To distinguish redundant ports from single ports they are
shown in different colors:

112 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 9
Communication Configuration Engineering

• Port B in a redundant pair of ports is red.


• Port A in a redundant pair of ports is green.
• Single ports (and ports of switches) are black.

9.2.6 Detail View for Selected IED GUID-DF9AAA76-2D88-4F79-B2ED-4B674D96FB21 v1

If the user zooms out fully to show the whole substation in an overview, the IEDs are usually too
small to display detailed information; therefore such information is hidden and only becomes visible
at higher zoom levels.

To access detail information, select a single IED -> a ‘Details’ view appears in the lower right corner
of the diagram:

IEC202100421 V1 EN-US

The ‘Details’ view is independent of the actual zoom level. It disappears if either the single IED in the
diagram is deselected, or if more than one IED is selected.

You can suppress this automatic popping up with a click on the ‘Hide detail view’ button.

9.2.7 Fade Unselected Items GUID-2CBA4831-C076-4FFA-9001-9C3C77A353E3 v1

If there are a lot of IEDs and connections between them, it is difficult to determine a single
connection or a port on which this connection is attached.

To better be able to see one item and its connections, it is possible to dim unselected items (IEDs,
Connections and other diagram elements). To do this, use one of the following possibilities:

• Select the Communication Configuration Diagram tab in the Main menu and enable the
checkbox Fade unselected items.
• Right-click in the diagram area and select Fade unselected items.

Integrated Engineering Tool 113


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 9 1MRK500114-UEN Rev. X
Communication Configuration Engineering

If one or more elements are selected, only the selected items and all items connected to it will be
displayed normally, all other elements will appear dimmed:

114 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 9
Communication Configuration Engineering

In the example above, one IED is selected. Two other IEDs connected to it are displayed normally, all
other IEDs appear dimmed.

If no element is selected, all elements get visualized normally again.

9.2.8 Zoom Diagram GUID-939FF2EE-9AFE-42D8-8613-AC63C1806B64 v1

The diagram view provides a zoom in / zoom out functionality. This can be done via:

• The context menu in the diagram view:

IEC202100424 V1 EN-US

• Keyboard shortcuts

Integrated Engineering Tool 115


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 9 1MRK500114-UEN Rev. X
Communication Configuration Engineering

• Ctrl + Mouse wheel up to zoom in, Ctrl + Mouse wheel down to zoom out
• Ctrl + '+' to zoom in; Ctrl + '-' to zoom out
• The toolbox menu (zoom in / zoom out button or slider):

IEC202100425 V1 EN-US

• The Main menu:

IEC202100426 V1 EN-US

To quickly zoom out as much as to see the complete diagram, use the option Zoom to fit (Ctrl + 0) in
the context menu or in in the toolbox.

9.2.9 Magnify a Section GUID-E6444E5F-0464-47D4-B89E-05E87480394F v1

As an alternative way to zoom the whole diagram, it is also possible use a magnifying glass to zoom
in the area around the mouse cursor. To activate the magnifying glass press and hold the function
key ‘F2’. To deactivate the glass just release ‘F2’. Alternatively the magnifying glass button in the
toolbar can be used:

116 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 9
Communication Configuration Engineering

IEC202100427 V1 EN-US

To lock the magnifier glass press Ctrl + F2. The glass remains now until the function key F2 is clicked
again or the ‘Esc’ key is pressed.

As in normal mode you can also move IEDs, create and modify connections etc.
while the magnifier glass is active.

9.2.10 Show Bird’s Eye View GUID-3847DA40-651C-4980-8114-B170FB6E5717 v1

The CCD toolbox offers a ’bird’s eye view‘, a small overview of the whole diagram independent the
actual zoom level. The currently visible area of the main diagram is highlighted. With the Bird’s eye
view you can rapidly navigate to another area of the diagram without having to zoom out and back in
again.

The bird’s eye view can be displayed by clicking the corresponding Toolbar button:

Integrated Engineering Tool 117


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 9 1MRK500114-UEN Rev. X
Communication Configuration Engineering

IEC202100428 V1 EN-US

9.2.11 Draw Rectangle Shape GUID-7C193424-8935-4E0D-B2E9-04FADEAAE854 v1

To create a new rectangle (only possible inside the main diagram area):

1. Click the Create new rectangle shape button (the cursor change its appearance to a crosshair
cursor):

IEC202100429 V1 EN-US

2. Press and hold the left mouse key in the desired left top corner from the rectangle.
3. Move the cursor to the right bottom of the rectangle and release the button.

To modify the size, select the rectangle and use the border marks to resize. To modify the position,
select the rectangle at the center mark and move it to the target location.

To delete a rectangle shape select it and press the keyboard key Delete.

To configure rectangle properties, like fill color, border color, etc., open the rectangle editor:

118 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 9
Communication Configuration Engineering

• via the rectangle context menu item Configure rectangle…


• via shortcut Ctrl + E (exactly one rectangle must be selected)

IEC202100430 V1 EN-US

9.2.12 Draw Annotation Shape GUID-10D47597-4057-4F0A-9ECA-C4B53AAD7C85 v1

To create a new annotation (only possible inside the main diagram area):

1. Click the Create new annotation shape button -> the cursor change its appearance to a text
cursor:

IEC202100431 V1 EN-US

2. Left click at the position in the main diagram you want to create the annotation.
3. Write the text with help of following special keys:
• Press Alt + Enter for a line break.
• Press Enter to finish the action.
• Press Esc to cancel the action (the annotation will be removed again).

To edit an annotation, double-click it again to switch to the edit mode again.

Integrated Engineering Tool 119


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 9 1MRK500114-UEN Rev. X
Communication Configuration Engineering

To modify the position of an annotation, select it and drag & drop it to the target location.

To delete an annotation shape, select it and press the keyboard key Delete (also if the annotation is
empty it will be deleted automatically).

To configure the properties like size, color, font type, etc., open the annotation editor:

• via the annotation context menu item Configure annotation….


• via shortcut Ctrl + E (exactly one annotation must be selected).

IEC202100432 V1 EN-US

9.2.13 Print Out Diagram GUID-396344AE-E95F-48D7-BB88-E03BCD66C42C v1

IET600 offers two alternative print options which can be triggered via toolbar menu or with keyboard
shortcuts:

1. Print out the entire diagram (Ctrl + P).


2. Print out the currently visible diagram area (Ctrl + Shift + P).

IEC202100433 V1 EN-US

The following diagram settings will also be used for the print out (set these properties before printing
out the diagram):

• IED details (visibility depends on zoom level)


• IED, connection, rectangle and annotation visibility (normal, faded, or highlighted)
• Diagram grid
• Diagram section lines

120 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 9
Communication Configuration Engineering

9.2.14 Export Image of Diagram GUID-DD732611-FDE7-4B6D-9543-DED80FD86F33 v1

The diagram view can also be exported as an image. The image can either be saved to a path or be
copied to the clipboard. Additionally it can be chosen if just the visible area of the diagram or the
complete diagram is exported:

1. Save an image of the diagram to a specific path (complete diagram, or visible area only)
2. Copy an image of the diagram to the Clipboard (complete diagram, or visible area only)

IEC202100434 V1 EN-US

The following diagram settings will be used for the image export (set these properties before
exporting):

• IED details (visibility depends on zoom level)


• IED, connection, rectangle and annotation visibility (normal, faded or highlighted)
• Diagram grid
• Diagram section lines

9.2.15 Shortcut Keys GUID-A71D12FC-DAC1-4D26-9AF1-D447394D6B98 v1

In the Communication Configuration Diagram are several shortcuts available:

F2 Press to show magnifier glass, release to hide it


Ctrl + F2 Shows magnifier glass permanently (to hide it, press F2).
Ctrl + E Configure selected diagram item (IED, Annotation or
Rectangle)
Ctrl + 0 Adjust the zoom level to fit the whole diagram into the
visible area.
Ctrl + Mouse Wheel Zoom in / out
Ctrl + ‘+‘ Zoom in
Ctrl + ‘-‘ Zoom out
Alt + Left Mouse Drag Pan
Ctrl + A Select all diagram items (IEDs, Connections, Rectangle,
Annotation)
Ctrl + P Print out entire diagram
Ctrl + Shift + P Print out actual visible diagram area
Esc Cancel current action (e.g. dragging diagram item,
creating connection, etc.)
Del Delete selected Items (Connections, Annotations and
Rectangles but not IEDs)

Integrated Engineering Tool 121


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 9 1MRK500114-UEN Rev. X
Communication Configuration Engineering

9.3 Engineering Workflow GUID-E6D6E84B-62DD-4534-A23D-0CF8E4D8CB19 v1

The following steps suggest a possible way to create the physical communication diagram:

1. Create IEDs.
Typically, the IEDs are initially created without IEC 61850 data model.
2. Configure IEDs
To connect IEDs it is required to configure the communication model first. At least, the physical
communication ports and their properties (redundancy, plug type, etc.) must be defined.
3. Place IEDs
Created IEDs are not positioned initially. For a quick positioning, IET600 offers several different
ways for automatic placement. After this, you can rearrange them manually according your
preferences.
4. Connect IEDs
Finally the IEDs can be connected physically via their Ports.

You can do the above-mentioned configuration steps at different times for different IEDs. For
example, in a first cycle, you may want to design network and station level topology. (Substation-level
Switches, HMIs, Gateways, Printers, Clocks etc.). In a second cycle you may then design bay-level
IEDs (Protection and Control IEDs, Merging Units).

9.4 Creating and Configuring IEDs GUID-D063CCF2-C9C6-4DC4-A0A1-6214D9EEC089 v1

To read about how to create and configure an IED in detail, see chapter "Creating and Configuring
IEDs".

You can open the Configure IED dialog described in the chapter from the CCD directly:

• via the IED context menu item Configure IED…


• via shortcut Ctrl + E (exactly one IED must be selected)

9.4.1 Configure Communication Properties GUID-0E1B09FF-8E84-4D70-8E81-979C3525A0F0 v1

Open the ’Create new IED’ or ‘Configure IED’ dialog. In the ‘Communication Parameters section’ all
kind of communication properties can be defined:

122 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 9
Communication Configuration Engineering

1. Define the number of (physical) ports.


2. If two ports are redundant, define the second port as redundant to the first port by selecting the
number of the first port in the ’Redundant to‘ column of the second port:
• If no port is selected, the port is not redundant.
• Be aware that in many redundancy protocols, first and second port have defined
meanings (e.g. in HSR the first port of one IED needs to be connected to the second port
of the next): define redundant ports with this in mind.
• A port can be redundant to exactly one other port. In the drop down menu, only those
ports, which do not already belong to such a redundant pair, are available for selection.
• Not all roles support redundant ports (the column is disabled in this case).
3. If one or several port pairs are defined as redundant, select the redundancy protocol of the
second port for each pair. The selected protocol will automatically be applied to the first port also
(cell is read only).
4. Define one or several access points for each port:
• A physical port or a redundant port pair can have several Access Points connected to
them.
• One Access Point can belong only to one port or one redundant port pair.
• For a redundant port pair, configure the Access Points on the second port; The selected
Access Point(s) will automatically be applied to the first port also (cell is read only).
5. Choose the plug type for each port.
6. Define where the ports are positioned. They can be basically be positioned left, right, top or
bottom; some primary roles restrict this choice (e.g. in an HMI, ports can only be configured at
the bottom due to the way its interior is displayed).
7. The order in which the ports appear in the diagram can also be changed for each side. This can
be used to avoid crossing connections.

9.5 Placing IEDs GUID-79BA0D7E-ABA3-49E8-B065-1601946989E5 v1

By default, IEDs are not placed in the Communication Configuration Diagram but in an extra section
on the left side of the main diagram (blue colored).

Depending on their primary role, IEDs will be placed in different sections:

Section IED Roles


NCC NCC
Station HMI, Gateways, Hub, Printer, Router, Security Device,
Time Server, Archive
Network Switch (except bay-level switch*)
Bay IED (protection / control), Bay level Switch*
Merging Unit Merging Unit

* A switch is handled as bay-level switch if it is placed beneath a Bay in the substations tree.

Integrated Engineering Tool 123


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 9 1MRK500114-UEN Rev. X
Communication Configuration Engineering

IEDs can be placed and moved manually by drag & drop or also automatically. The ‘auto arrange’
functions (see detail description below) are mainly intended for a first positioning of one or several
IEDs. After this, you can manually move the IEDs according your preferences.

9.5.1 Move an IED Manually GUID-1958BC93-7645-4112-8091-E493896862D6 v1

To place an IED manually:

1. Left-click the IED you want to move.


2. Press and hold the left mouse button and move the IED to new location.
3. Release the mouse button to move the IED definitely; or press the ‘Esc’ Key before releasing
the mouse button to abort the move procedure (this sets IED back to the original position).
The move procedure will be automatically aborted if any of the following conditions is fulfilled
while releasing the mouse:
• Moved IED overlaps any other IED.
• Moved IED overlaps any connection which isn’t attached to this IED.
• Moved IED is not fully inside the diagram sheet.

All connections attached to the moved IED will be rerouted automatically.

9.5.2 Auto-Arranging IEDs GUID-C357A463-C970-4B58-B226-3A7FF3597091 v1

The ‘Auto Arrange’ functionality allows a rapid initial placement of a considerable number of IEDs.

There are three variations of auto-arrange that can be called via the context menu of the
communication configuration diagram:

• Arrange all IEDs


• Arrange selected IEDs (only enabled if at least one IED is selected)
• Arrange all unplaced IEDs (only enabled if at least one IED is still not placed in the diagram)

‘Auto Arrange’ uses the following rules for the placement of IEDs:

• IEDs allocated within one Bay are placed as a group close together.
• These groups are then placed in an alphabetical order according to the Bay name.
• IEDs are placed in sections depending on their roles.

124 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 9
Communication Configuration Engineering

9.6 Connecting IEDs GUID-E4CB9B26-7B47-4A77-A9A0-4BAD29468204 v1

IET600 allows creating physical connections between two IED ports. There are some restrictions:

• A connection must be attached always to exactly two ports. It is not possible to create “dangling”
connections (i.e. connections attached to only one or no port).
(Deleting an IED will also automatically delete all links attached to a port of this IED; thereby
preventing “dangling” connections).
• A connection must always be between two different IEDs, connections within an IED are not
allowed.
• Connection segments are always horizontal or vertical, creating a diagonal connection or a
diagonal connection segment is not possible.

Moving an IED provokes an automatic rerouting of all connections which are


attached to this IED. All modifications that have been made manually will be lost.

9.6.1 Add Connection GUID-9926EE2C-CA4B-4F0B-83FB-6F33EAC3D51D v1

1. Move the mouse cursor over the first port you want to connect -> the cursor changes its
appearance to a ‘pointing hand’.
2. Press and hold the left mouse button and move the mouse cursor to the second port. A ‘pointing
hand’ cursor symbolizes a port which can be connected, otherwise a ‘prohibited’ cursor appears.
3. Release the left mouse button while mouse cursor is over the second port.

9.6.2 Remove Connection GUID-AA85CFF3-D618-44DC-BDAA-FB08BFD0E07A v1

1. Select one or several connections.


2. Click Delete Button.
3. A confirmation dialog will appear. Select yes to delete the connection(s) or no to cancel the
action.

9.6.3 Reconnect Connection GUID-A3F83D52-CB13-4447-A8E1-016BC911F42C v1

1. Select a single connection.


2. Move the mouse cursor over the port from which you want to detach the connection -> cursor
changes to a four-way arrow symbol.
3. Press and hold the left mouse button and drag the connection to another free port.
4. Release the left mouse button.

9.6.4 Reroute Connection Manually GUID-00922BB5-B4E6-4F06-AC2F-56CC3C0966F7 v1

Connections can be rerouted manually:

1. Select a single connection.


2. Move the mouse cursor over a via-point of the selected connection (cursor change to four way
arrow symbol).
3. Press and hold the left mouse button and shift the via-point to desired position.

As start point or end point of a connection cannot be rerouted, moving a via-point next to a start point
or end point is also restricted:

Integrated Engineering Tool 125


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 9 1MRK500114-UEN Rev. X
Communication Configuration Engineering

IEC202100438 V1 EN-US

• Via-point cannot be moved horizontally or vertically


• No via-point available, connection cannot be rerouted
• Via-points can be moved only in horizontal direction

For rerouting a connection, add first one or several via points (see chapter "Add / Remove
Connection Via-Point".

9.6.5 Add / Remove Connection Via-Point GUID-7074CF9E-E1F8-445C-874E-1AFFE6B54C30 v1

To add a via-point:

1. Select a connection.
2. Double click the connection where you want to add a via-point.
To remove a via-point (Note: only via points which are in line with previous and next via point
can be removed):
3. Select a connection.
4. Double click the via-point you want delete to.

126 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

Section 10 Dataflow Engineering GUID-647C460F-D34E-48CC-8489-E7E4B2B535BD v1

10.1 Introduction GUID-4A86D1B8-2DAD-418C-90B0-BFCA636A010E v1

10.1.1 Overview GUID-409430AB-7CB8-4D90-A8F9-529FE4A03D64 v1

Dataflow is a general term for the functionality and configuration that is needed to exchange data
between different IEDs. To configure the dataflow, the data model of the participating IEDs and the
communication (the connection between the IEDs) must be more or less defined.

In IET600, there are several ways to engineer Datasets, RCBs and GCBs:

• Create Datasets, RCBs and GCBs manually, and then add/edit their data.
• Copy an IED with configured Datasets, RCBs or GCBs from the same or another project.
• Import a configured Dataset, RCB or GCB from an IED SCL (CID/IID) file.

10.1.2 Engineering Approach GUID-C80CE2A2-A9F5-405E-BB87-91112313D337 v1

The IEC 61850 standard distinguishes:

A Dataset that specifies what data are sent. It can basically be understood as a defined sequence of
data items that can be sent as a whole packet only.

A Control Block that specifies how the data are sent. IEC 61850 defines:

• Report Control Blocks (RCBs)


• GOOSE Control Blocks (GCBs)
• Sampled Value Control Blocks (SVCBs)
• GSSE Control Blocks (obsolete, should not be used)
• Log Control Blocks
• Setting Group Control Blocks

IET600 stresses a slightly different approach. From an engineering point of view, it is helpful to
distinguish:

Vertical communication from bay-level IEDs to HMIs or NCC Gateways. The vertical communication
includes:

• configuring Datasets
• configuring Report Control Blocks (RCB)
• configuring Clients for the RCB in a matrix

Horizontal communication, essentially to exchange information between IEDs. The horizontal


communication includes:

• configuring Datasets
• configuring Goose Control Blocks (GCB)
• configuring receivers for GCB in a matrix

Analogue data communication (Sampled Values), essentially between IEDs transforming analogue
measurement values into data streams, and IEDs. The analogue data communication includes:

• configuring Datasets.
• configuring Sample Value Control Blocks (SVCB).
• configuring receivers for SVCB in a matrix.

Integrated Engineering Tool 127


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

10.1.3 Common Problems in Dataflow Engineering GUID-BC1B747D-B3C1-4383-95D1-0635181AA4C2 v1

In IEC 61850, so-called services define how Dataflow can be edited in an IED. These services – for
historical reasons – may not always be correctly configured by the IED configuration tool or correctly
interpreted by IET600. IET600 behaves very conservatively and often blocks creating or editing
Dataflow elements in such cases.

To learn how to get information about such services, see chapter "IED Services Editor".

To learn how you may adapt IET600 in such cases to get the desired result, see chapter "IED
Capabilities Editor".

10.2 Dataset Configuration GUID-D78E45B1-3F96-4145-B571-BF5D850BEDD0 v1

10.2.1 Datasets Editor GUID-BEF05600-FD0E-4E43-89F4-B155984B007E v1

The Datasets editor provides the following views:

• All available Datasets and their properties


• Dataset entries of selected Dataset
• A selection editor to allow adding/removing Dataset entries

The following Dataset properties are shown:

Property Description
Type IED Type
IED IED Name
AP Access Point name
Table continues on next page

128 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

Property Description
Srv Server name
LD Logical Device where RCB is defined
LN Logical Node where RCB is defined
Dataset Name of Dataset
Related Control Blocks Reference to related RCB/GCB data
Status Describes the method by which the Dataset was created:
“IED-defined, read-only” or “IED-defined, configurable”
are Datasets which have been imported with an SCL file.
“Manually configured” are Datasets which were defined
by the user in IET600.
“Generated by Client Driven Engineering” are Datasets
that were generated in process of Client Driven
Engineering.
Edition Compatibility Defines which IEC editions are compatible with the
dataset. Value is determined by Dataset Entries
belonging to The dataset. Value might be either ed.1,
ed.2 or both. Each Data Object or Data Attribute has its
own Edition Compatibility defined by the Standard.

Allow All Connections If checked it allows that dataset to be subscribed to by


incompatible IEDs. Usage must be limited to already
existing projects with such clients’ connections.

Description Text field which can be used to define purpose of


Dataset

10.2.2 Create Datasets GUID-3BC58A17-614A-4162-A78A-3D38379AA1E3 v1

1. Select an appropriate IED in the Substation, IEDs or Communication Navigation Tree where
the Dataset shall be created. To have the full choice of IEDs, select the project.
Alternatively, this dialog can also be opened from the Communication tab in the Main menu,
using the Create Dataset(s) menu item:

IEC202100442 V1 EN-US

2. Select the Datasets Editor.


3. Select a row and right-click to select Insert New Row from the context menu.
4. A dialog Create New Datasets is opened. The Tree in the dialog will show all IEDs below the
element you selected. Navigate to the IED and then to the LN where you want to create the new
Dataset. For ABB IEDs, Datasets are normally allocated to LD0/LLN0.

Integrated Engineering Tool 129


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

IEC202100443 V1 EN-US

5. Once you select an LN, the tool proposes a name, which you can adapt according to your
wishes. Invalid names are indicated by an error mark (Invalid names typically are either
duplicate names or contain characters that are not allowed for a particular element).
6. Click OK to create the new Dataset or Cancel to close the dialog without creating a Dataset.

10.2.3 Edit Datasets GUID-45CDBDAE-EC22-40DB-9675-054B96D038AE v1

In the Dataset Editor, you can edit the name and the description of a Dataset. If you change the
name, attached RCBs or GCBs will automatically be updated.

To attach a Dataset to a Control Block is currently not possible in the Dataset Editor; you have to use
the RCB Editor or GCB Editor, respectively.

10.2.4 Add Dataset Entries GUID-BB86D72A-9D37-45AC-93D2-82A910F639D1 v1

To add Dataset Entries, you need to use the lower part of the editor.

1. Select the Dataset to which you want to add entries. The first list below shows the available LDs:

130 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

GUID-835FF6EA-08FF-4F34-B8F9-3E52DCDEFD4D V1 EN-US

2. Select LD -> a choice of LNs appears. Continue selecting LN, Data Objects (DOIs) and Data
attributes (DAIs) as appropriate (it is recommended to use Data Objects for RCB-Datasets and
Data Attributes for GCB-Datasets).
3. If the functional constraint is not unique yet by your selection, select it now. You can only select
FCs that make sense for spontaneously sent data (e.g. ST or MX).
In the 'Result List', you see all the attributes that will be added to the Dataset. If it is empty, your
selection is not valid yet (typically when the Data Object has attributes with several Functional
Constraints - e.g. CF and ST - and you have not selected the FC yet).
4. After verifying the attributes in the result box, click ‘Append’ or ‘Insert’ to add your selection to
the Dataset entries.
As long as the error indicator appears, something is not (yet) correct in the selection. The tool tip
of the error indicator provides additional information.

It is not possible to add the same data twice to the same attribute, e.g. you cannot
add CMMXU1.A[MX] twice.

You can still add CMMXU1.A.phsA[MX] after having added CMMXU1.A[MX],


although they partially contain the same data. Such a configuration usually does not
make sense (some few clients even refuse to work correctly when receiving such
Datasets); it is the responsibility of the engineer to avoid such configurations.

Ed.1 compatible Data Objects or Data Attributes are indicated with blue color, for
Ed.2 it’s red. Black ones are compatible with both editions. You can hide not Ed.1/
Ed.2 compatible objects/attributes by selecting ‘Hide not Ed.1 compatible’ or ‘Hide
not Ed.2 compatible’ checkboxes in the middle section of editor. It is not possible to
Append Ed.1 dataset entry to Ed.2 dataset and vice versa. In such case whole
dataset would become incompatible with any edition. This action is forbidden by the
tool and will trigger error to appear. To learn more about compatibility see "Dataset
Edition Compatibility".

The maximum number of Dataset Entries in a Dataset is limited. The current and the allowed number
of entries are indicated in the Editor. Also the total number of Dataset entries for the IED is displayed
(for statistics only).

Integrated Engineering Tool 131


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

IEC202100445 V1 EN-US

The maximum number of Dataset Entries is specified by a service in the SCL file,
ConfDataset.maxAttributes. Historically, some IEDs were counting entries, others were counting
attributes. To visually indicate which way a particular IED is counting, IET600 displays the value used
by the IED in black and the other way greyed out. E.g. in the above example, the IED is counting
entries.

For a more detailed explanation, see chapter "Service ConfDataset, maxAttributes attribute".

10.2.5 Delete Dataset Entries GUID-2504686D-6FFC-4C09-9C8F-EC069B730B3C v1

To delete a Dataset Entry, you have two possibilities:

1. Select the entries you want to delete in the Dataset Entry part of the editor. Right-click and
select Delete Row(s) or press the Delete key. A confirmation dialog appears, confirm the
Deletion or cancel it.
This is the only way to delete multiple Dataset entries in one action.
2. Select a single entry you want to delete in the Dataset Entry part of the editor.
As long as the error indicator appears, something is not (yet) correct. The tool tip of the error
indicator provides additional information.

132 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

GUID-688B357D-DC26-4911-8CA8-A112E04C700D V1 EN-US

3. Click the Remove button in the lower part of the editor. The entry is removed from the Dataset
entries without further warning, but it is still preserved in the bottom part of the editor. You can
append it again or insert it into some other place in the Dataset entry list.

10.2.6 Dataset Edition Compatibility GUID-B0FAE040-13A0-4687-9F4C-30C508210474 v1

Each dataset can be compatible with Edition 1, Edition 2, both or none. A dataset's Edition
Compatibility depends on its entries. You can see an entry's Edition Compatibility when adding it to a
dataset (blue means Ed. 1, red means Ed. 2 and black is compatible with both).

GUID-01D926DA-30B4-4E6F-ABC9-3D7FEC3E00E5 V1 EN-US

For the existing datasets you can also check how each entry influences their Edition Compatibility in
Entries View.

Integrated Engineering Tool 133


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

GUID-8CFFA95E-42AA-415A-A2E2-1231114185CE V1 EN-US

Additionally, you can get even more information by right-clicking a dataset and selecting Check
Dataset Edition Compatibility (or Check All Datasets Edition Compatibility to check all
datasets). This option returns information about each attribute's Edition Compatibility and puts it in
the Output window and in a log file.

GUID-D536B3B9-2888-4208-87B7-5D97F486E647 V1 EN-US

The log file can be opened by the restult window by clicking the Ok button.

GUID-F3FB5319-2D6D-45B1-8811-FFC4058CFD25 V1 EN-US

134 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

10.3 RCB Data Configuration GUID-CA953227-CF1E-47A5-AE29-56E4F3862490 v1

10.3.1 RCB Data Editor GUID-74B731A6-04F7-4E86-8721-5D34B0365CD3 v1

The RCB Data editor defines the parameters for the reporting service, according to IEC 61850 part
7-2.

Property Description
IED Type IED Type
IED IED Name
AP Access Point name
Srv Server name
LD Logical Device where RCB is defined
LN Logical Node where RCB is defined
RCB RCB name
Identifier (rptID) RptID uniquely identifies a RCB per client on each IED.
By default it is calculated from the full identification (path
name) of the RCB.
Status Describes how the RCB was created. This attribute is
automatically generated by IET.
Attached Dataset Select the name of the Dataset, as specified in the
Dataset Editor.
Conf.Rev. Version number will be incremented on changes of the
Dataset related to the control block. Changes are the
deletion or insertion of a member of the Dataset,
reordering of the member, or changing the Dataset
reference of the control block. Changes will increment
this value by 100.
Buffered In general, only buffered reporting is used for all kinds of
data, except for measurements.
Buffer Time (ms) Defines the amount of time that the report is delayed
(after a change) to wait for further changes before it is
sent.
Enabled Clients The number of instances or clients mapped to the RCB.
This value is automatically calculated by IET based on
the number of clients mapped in the RCB Clients editor.
By default, there is always 1 additional RCB instance,
unless number of clients = Max Enabled Clients.
DChg TRUE specifies the condition to trigger reporting on Data
Change, i.e. on value change
QChg TRUE specifies the condition to trigger reporting on
Quality Change.
DUpd TRUE specifies the condition to trigger reporting on Data
Update., i.e. whenever a value is updated, irrespective of
whether it has changed or not.
Cyclic TRUE specifies that the reporting for monitored data is
Cyclic, it will be triggered every Cycle Time.
Cycle Time (ms) Cycle time for cyclic-triggered reporting
GI TRUE indicates that RCB/Dataset can be queried via
General Interrogation.
Include SeqNum TRUE indicates the chronological order of reports is
used in RCBs
Table continues on next page

Integrated Engineering Tool 135


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

Property Description
Include BufOvfl TRUE indicates that a flag to indicate Buffer Overflow for
the BRCB is used.
Include Dataset TRUE indicates usage
Include Entry ID TRUE indicates usage
Include Entry Time TRUE indicates usage
Include DataRef TRUE indicates usage
Include Reason Code TRUE indicates usage
Include Config Rev. TRUE indicates usage

10.3.2 Create RCBs GUID-C4BAB2BC-EB0E-49C7-AF31-CBDC62601910 v1

If you know where you want to create your RCB, you can preselect an appropriate element in the
Substation, IEDs or Communication Navigation Tree. To have the full choice of IEDs, select the
project.

1. Open the RCB Data editor and select a row in the RCB list, right-click and select Insert New
Row from the context menu.

IEC202100447 V1 EN-US

2. Alternatively, select the Communication menu tab (the Communication Navigation tab will
automatically be selected) and select Create RCB(s).

IEC202100448 V1 EN-US

3. The dialog Create New RCB opens. The Tree in the dialog will show all IEDs below the element
you selected. Navigate to the IED and then to the LN where you want to create the new RCB.
Note that for ABB IEDs, the RCBs are allocated to the LD0/LLN0 logical node.

136 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

IEC202100449 V1 EN-US

4. Once you select an LN, the tool proposes a name, which you can adapt according to your
wishes. Invalid names are indicated by an error mark (Invalid names typically are either
duplicate names or contain characters that are not allowed for a particular element).
5. Click OK to create the new RCB or Cancel to close the dialog without creating an RCB.

If you created a new RCB from the Main Menu, the Navigation Tree will remain where it is and the
Editor will change to RCB Data. The new RCB will have a standard configuration, which you may
edit, if needed.

10.3.3 Delete RCBs GUID-11912D57-D330-468F-9478-B4C73392EE31 v1

Created RCB can be renamed and totally removed. It is important to remember that, once it is
exported, the RCB and its last configuration revision value (Column ‘Conf.Rev’, ‘configRev’ attribute
in IEC 61850) needs to be remembered. If this is not done, an RCB with the same name and the
same configuration revision number, but different content and/or behavior could be created at a later
time. This would lead to confusion and even potentially dangerous situations.

So an RCB is “deleted” by setting its status to ‘deleted’. Deleted RCBs will remain in the tool, but will
not be exported in SCD/ICD/IID files, and will not count when evaluating limits for RCBs. However, it
is possible to permanently remove ‘deleted’ and ‘recycled’ RCBs.

1. Select the RCB Editor.


2. Select any element that has RCBs below it in the Navigation Tree (the IED where you want to
create it, is usually a good choice).
3. Select one or several rows with the RCBs intended for deletion.
4. Right-click and select ‘Delete Row(s)’ or press the ‘Delete’ key. A confirmation dialog appears,
confirm the deletion or cancel it.

The RCBs will remain, but their Datasets will be removed and their status will go to ‘deleted’. After
that user can remove permanently these RCBs by clicking ‘Delete Row(s)’ again.

Integrated Engineering Tool 137


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

10.3.4 Edit RCBs GUID-AF0C8130-4A62-4EDE-875F-AB03BB316D6F v1

The RCB configuration can be edited in the RCB editor; however, this should normally not be
necessary. There are several specialties to be observed:

• An RCB can be renamed.


• Removing a Dataset from an RCB will automatically put the RCB into a ‘deleted’ state.

Configuration changes will cause its configuration revision value (Column ‘Conf.Rev’, ‘configRev’
attribute in IEC 61850) to be increased to the next multiple of 100. This will happen only once
between import and export, not with every change.

10.3.5 Reuse “Deleted” RCBs GUID-116D20CC-E5F0-4313-8739-EA8BA4C9A04B v1

Not permanently deleted RCB can be reused by simply attaching a Dataset to it. Instead of creating a
new RCB, it is recommended to reuse “deleted” RCBs first.

10.4 RCB Client Configuration GUID-628853AB-15D0-4A4D-A735-1C7469D2FEF6 v1

10.4.1 Prerequisites GUID-E39C8C9E-51B4-4057-8C16-6C2AC45EAFAB v1

To do a sensible RCB client configuration, the potential clients and their communication configuration
should be known (typically HMIs and NCC Gateways). Therefore add these IEDs (see chapter "HMI
Creation and Configuration") and configure them to the Subnetworks before doing the RCB client
configuration.

Bay-level IEDs can be added and configured easily also in later stages of the project.

10.4.2 RCB Client Editor GUID-3C7CD599-F5AB-4113-A2EC-A8EE08280F68 v1

The rows of this editor show IEDs (or their Access Points, respectively) and RCBs. The rows depend
on the element selected in the Navigation Tree.

The columns show the available Client IEDs (and their Access Points). Valid clients are IEDs that
have IHMI-, ITCI-, ITMI- or IARC-LNs. The columns do not depend on the element selected in the
Navigation Tree (i.e. all Client IEDs are always shown). The client IED names are vertical to save
space. To avoid neck strains, use the Tooltip to see the text horizontally.

If a Client IED is not on the same Subnetwork as a Server IED or RCB, it cannot be configured as a
Client. In the Editor, this shows as greyed-out cells that cannot be edited.

138 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

For those cells that can be edited, you can use ‘+’ or ‘*’ or ‘x’ to add an additional client to the existing
ones. You can use numbers to change the client sequence or add clients. You can use ‘-’, the space
bar or ‘Delete’ to delete existing clients. The result will always show the clients as sequential
numbers from 1 to the highest configured client.

The reason for this is that the IEC 61850 standard does not allow you to reserve slots for later clients
(e.g. to configure a sequence 1, 2, 4 with the intention to add a client 3 later). If you want to do that,
you need to create a dummy client.

On the right, the editor has a set of Radio Buttons that allow fast filter setting (show either Default
Clients or RCBs or both together; the latter is the default).

It also has some Buttons to allow fast, semi-automatic configuration of Default clients and RCB
clients. The buttons operate only on the rows displayed in the editor, so by cleverly choosing objects
in the Navigation tree and/or setting filters, one can do complex configurations for a big substation
quite rapidly.

10.4.3 Basic Workflow for RCB Client Engineering GUID-7622A281-9B43-4F4E-B076-078C9B5E2B6A v1

Configuring RCB Clients consists of two or three steps:

1. Configure the Default clients for each IED (or, more precisely, for its Access Points).
2. Propagate these defaults to all RCBs of the same IED/Access Point.
3. Configure individual clients for RCBs, if needed.

10.4.4 Configure Default Clients GUID-4FA49B68-2EDD-4EB0-81C3-C7AA5D0BE839 v1

For each IED, or rather, for each Access Point of an IED, Default clients should be configured. These
“Default clients” can then easily be propagated to all RCBs in that IED/Access Point.

In the Navigation Tree, select any element that has IEDs/Access Points below it in the Navigation
Tree (usually a Subnetwork, a Voltage Level or the whole project is a good choice).

1. Select the RCB Client Editor.


If you have IEDs with more than one Access Points, make the column ‘AP’ visible in the RCB
Client Editor.
To have a better overview, you may choose to select Show IEDs Only.

Integrated Engineering Tool 139


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

2. Configure the IEDs/Access Points with Default Clients:


• Clear All removes all Default Clients.
• Configure Empty automatically fills out only Default Clients for those IEDs/Access Points
that have no clients configured yet.
• Configure All deletes all existing Default clients and automatically fills them out
afterwards.

Use the mechanisms described above (see chapter "RCB Client Editor"), if you need to individually
configure RCBs.

10.4.5 Configure RCB Clients GUID-E2D7349E-25B5-4AA1-8695-099A615F3C59 v1

Precondition: you must have Default clients configured, otherwise the automatic RCB client
configuration will not work.

In the Navigation Tree, select any element that has RCBs below it in the Navigation Tree (usually a
Subnetwork, a Voltage Level or the whole project is a good choice).

1. Select the RCB Client Editor.


If you have IEDs with more than one Access Points, make the column ‘AP’ visible.
To have a better overview, you may choose to select Show RCBs Only.

140 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

2. Configure the RCBs with Clients.


• Clear All removes all RCB Clients in the editor.
• Configure Empty copies the Default Client Configuration of this IED/Access Point to its
RCBs (only for those RCBs that have no clients configured yet).
• Configure All deletes the existing RCB clients and then copies the Default Client
Configuration of this IED/Access Point to its RCBs.

Use the mechanisms described in the previous chapter if you need to individually configure the
clients of one or few RCBs.

10.5 LCB Data Configuration GUID-AE02DFFD-4232-4E4B-B208-80F1F6C763E9 v1

10.5.1 LCB Data Editor GUID-8B667A31-0B70-49DF-A496-C488CC765641 v1

The LCB Data editor defines the parameters for the reporting service, according to IEC 61850 part
7-2.

Property Description
IED Type IED Type
IED IED Name
AP Access Point name
Server Server name
LD Logical Device where LCB is defined
LN Logical Node where LCB is defined
LCB LCB name
Status Describes how the LCB was created. This attribute is
automatically generated by IET.
Attached Dataset Select the name of the Dataset, as specified in the
Dataset Editor.
Log Enabled Enables the LCB to write its data into the specified Log.
Log Name The name of the Log into which the LCB is writing.
Table continues on next page

Integrated Engineering Tool 141


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

Property Description
Reason Code Include the reason code in the log, if TRUE
DChg TRUE specifies the condition to trigger logging on Data
Change, i.e. on value change
QChg TRUE specifies the condition to trigger logging on
Quality Change.
DUpd TRUE specifies the condition to trigger logging on Data
Update., i.e. whenever a value is updated, irrespective of
whether it has changed or not.
Cyclic TRUE specifies that the logging for monitored data is
Cyclic, it will be triggered every Cycle Time.
Cycle Time (ms) Cycle time for cyclic-triggered logging
GI Specifies whether

10.5.2 Create LCBs GUID-7B3BBDB9-2E32-43D4-B16A-16762E2FE600 v1

If you know, where you want to create your LCB, you can preselect an appropriate element in the
Substation, IEDs or Communication Navigation Tree. To have the full choice of IEDs, select the
project.

1. Open the LCB Data editor and select a row in the LCB list, right-click and select Insert New
Row from the context menu.

IEC202100457 V1 EN-US

2. Alternatively, select the Communication menu tab (the Communication Navigation tab will
automatically be selected) and select Create LCB(s).

IEC202100458 V1 EN-US

3. The dialog Create New LCB opens. The Tree in the dialog will show all IEDs below the element
you selected. Navigate to the IED and then to the LN where you want to create the new LCB.
Note that for ABB IEDs, the LCBs are allocated to the LD0/LLN0 logical node.

142 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

IEC202100459 V1 EN-US

Once you select an LN, the tool proposes a name, which you can adapt according to your
wishes. Invalid names are indicated by an error mark (Invalid names typically are either
duplicate names or contain characters that are not allowed for a particular element).
4. Click OK to create the new LCB or Cancel to close the dialog without creating an LCB.

If you created a new LCB, the Navigation Tree will remain where it is and the Editor will change to
LCB Data. The new LCB will have a standard configuration, which you may edit, if needed.

10.5.3 Delete LCBs GUID-F8970767-34DD-415B-911B-8BB4B5231B20 v1

1. Select the ‘LCB Data’ Editor


2. Select any element that has LCBs below it in the Navigation Tree (the IED where you want to
create it, is usually a good choice).
3. Select one or several rows with the LCBs intended for deletion.
4. Right-click and select ‘Delete Row(s)’ or press the ‘Delete’ key. A confirmation dialog appears,
confirm the deletion or cancel it.

Unlike other Control Blocks, LCB(s) will actually be deleted; they are not just marked as “Deleted”.

10.5.4 Edit LCBs GUID-475BC607-AE6B-4332-A8BF-1E023108D5DD v1

The LCB configuration can be edited in the LCB editor; however, this should normally not be
necessary. To be observed:

• An LCB can be renamed.

Integrated Engineering Tool 143


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

10.6 GCB Data Configuration GUID-8EB7DF47-98BA-4883-B727-2F07A7224A73 v1

10.6.1 GCB Data Editor GUID-28162433-C1EF-4A65-9D0D-E6DEB0C3DB1C v1

The GCB Data editor defines the parameters for the reporting service, according to IEC 61850 part
7-2.

Property Description
IED Type IED Type
IED IED Name
AP Access Point name
Srv Server name
LD Logical Device where GCB is defined
LN Logical Node where GCB is defined
GCB GCB name
Application (appID) Identifies purpose or application of the GOOSE
message. It should be unique for an application within
the Subnetwork.
Status Describes how the GCB was created. This attribute is
automatically generated by IET.
Attached Dataset Select the name of the Dataset, as specified in the
Dataset Editor.
Connection Type Defines whether control block is connection is direct or
routable. When value is being set from direct to routable
‘Protocol’ element is added to GSEControl. In opposite
situation it is removed. It’s only enabled when parent IED
of control block has service GOOSE.rGOOSE = “true”
defined.
Security Enabled Shows security options per control block Instance:
Signature or SignatureAndEncryption. None by default.
Its value is not user-configurable but is automatically set
depending on the clients of the GCB and their Security
settings. The exact logic is described in chapter "MAC-
Layer Security configuration for GCBs" .
t(min) (ms) Minimum cycle time for sending messages (e.g. after a
change in Dataset)
t(max) (ms) Max cycle time for sending messages (e.g. used to
detect missing or delayed messages)
Conf.Rev. Version number will be incremented on changes of the
Dataset related to the control block. Changes are the
deletion or insertion of a member of the Dataset,
reordering of the member, or changing the Dataset
reference of the control block. Changes will increment
this value by 10000.
GCB Type GOOSE
MAC Address Identifies source and allow filtering of the GOOSE
message. It should be unique for an application within
the Subnetwork. MAC Address contains six groups of
two hexadecimal digits, optionally separated by hyphens
'-' or colon ':', i.e.'01-23-45-67-89-ab' or
'01:23:45:67:89:ab'. In case of using colon separator it
will be automatically replaced by hyphens separator.
APP-ID Identifies source and allow filtering of the GOOSE
message. It should be unique for an application within
the Subnetwork.
Table continues on next page

144 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

Property Description
VLAN-ID Controls the dataflow and real-time behavior of the
messages within a VLAN network. HEX value between
000-FFF is used, where value 000 (default) indicates that
only the VLAN user priority is used.
VLAN Priority Controls the dataflow and real-time behavior of the
messages within a VLAN network. Priority value between
0-7 is used, where higher numbers indicate higher
priority message. 4 is the recommended value for
GOOSE.
IP Address UDP/IPv4 destination address. shall be a IP multicast
address conform to RFC 5771. Recommended range is
from 232.0.0.0 to 232.255.255.255. Used for Routable
connection. Enabled only when “Connection Type” is set
to “Routable”.
IP IGMPv3Src Unicast IPv4 address to be used for IGMPv3
subscription. Used for Routable connection. Enabled
only when “Connection Type” is set to “Routable”.
IP Class of Traffic Class of traffic for IPv4. Specifies the TOS field of the
IPv4 header. Used for Routable connection. Enabled
only when “Connection Type” is set to “Routable”.

10.6.2 Create GCBs GUID-7FEEE767-BEE9-40C3-B44B-7611CD914FFB v1

If you know, where you want to create your GCB, you can preselect an appropriate element in the
Substation, IEDs or Communication Navigation Tree. To have the full choice of IEDs, select the
project.

1. Open the GCB Data editor and select a row in the GCB list, right-click and select Insert New
Row from the context menu.

IEC202100464 V1 EN-US

2. Alternatively, you can select the Communication menu tab (the Communication Navigation
tab will automatically be selected) and click on Create GCB(s).

Integrated Engineering Tool 145


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

IEC202100465 V1 EN-US

3. The Dialog Create New GCB appears. The Tree in the dialog will show all IEDs below the
element you selected. Navigate to the IED and then to the LLN0 where you want to create the
new GCB.
If there are several Access Points available, through which the GCB can be sent, select the one
you want in the Access Point combo box.
Note that for ABB IEDs, the GCBs are allocated to the LD0/LLN0 logical node.

IEC202100466 V1 EN-US

Once you select an LN (e.g. LD0/LLN0), the tool proposes a name, which you can adapt
according to your wishes. Invalid names are indicated by an error mark (Invalid names typically
are either duplicate names or contain characters that are not allowed for a particular element).
4. Click OK to create the new GCB or Cancel to close the dialog without creating a GCB.

If you created a new GCB, the Navigation Tree will remain where it is and the Editor will change to
GCB Data. The new GCB will have a standard configuration, which you may edit, if needed.

10.6.3 Delete GCBs GUID-E9F66407-1A8E-46F0-8FEE-B2F0C662826E v1

Created GCB can be renamed and totally removed. It’s important to remember that, once it is
exported, the GCB and its last version number needs to be remembered. If this is not done, a GCB
with the same name and the same version number, but different content and/or behavior could be
created at a later time. This would lead to confusion and even potentially dangerous situations.

So a GCB is “deleted” by setting its status to ‘deleted’. Deleted GCBs will remain in the tool, but will
not be exported in SCD/ICD/IID files, and will not count when evaluating limits for GCBs. However, it
is possible to permanently remove ‘deleted’ and ‘recycled’ GCBs.

146 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

1. Select the GCB Editor.


2. Select any element that has GCBs below it in the Navigation Tree (the IED where you want to
create it, is usually a good choice).
3. Select one or several rows with the GCBs intended for deletion.
4. Right-click and select ‘Delete Row(s)’ or press the ‘Delete’ key. A confirmation dialog appears,
confirm the deletion or cancel it.

The GCBs will remain, but their Datasets will be removed and their status will go to ‘deleted’. After
that user can remove permanently these GCBs by clicking Delete Row(s) again.

10.6.4 Edit GCBs GUID-89D50303-65F9-4E70-89F6-107A5274C9AA v1

The GCB configuration can be edited in the GCB editor; normally this should not be necessary
however. There are several specialties to be observed:

• An GCB can be renamed.


• Removing a Dataset from a GCB will automatically put the GCB into a ‘deleted’ state.

Configuration changes will cause its configuration revision value (Column ‘Conf.Rev’, ‘configRev’
attribute in IEC 61850) to be increased to the next multiple of 100. This will happen only once
between import and export, not with every change.

Although it is not demanded by the standard, some vendors do not allow address combinations of
the same MAC address with a different AppID or vice versa. It is recommended to follow an
addressing scheme that always changes both together.

10.6.5 Reuse “Deleted” GCBs GUID-401928A5-95C7-4A7B-9CE2-C1D7EAB05545 v1

Not permanently deleted GCB can be reused by simply attaching a Dataset to it. Instead of creating
a new GCB, it is recommended to reuse “deleted” GCBs first.

10.7 GCB Client Configuration GUID-3E4CF644-8006-4A90-A967-10104370A4B2 v1

10.7.1 Prerequisites GUID-022961B8-A6C9-40A9-B3B3-E3EB609B4974 v1

To do a sensible GCB client configuration, most of the Bay-level IEDs should be known and should
be attached to the correct Subnetworks.

10.7.2 GCB Client Editor GUID-373A1E19-81F1-4F55-9524-98B248617DF7 v1

The rows of this editor show GCBs (“Senders”). The rows depend on the element selected in the
Navigation Tree.

The columns show the IEDs available as GOOSE clients (“Receivers”). To save space the client IED
names are vertical. To avoid neck strains, use the Tooltip to see the text horizontally.

If the Client IED is not on the same Subnetwork as the GCB sender, it cannot be configured as a
GCB Client. In the editor, the respective cells are disabled and cannot be edited.

Integrated Engineering Tool 147


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

Also an IED cannot be configured to send GOOSE to itself; again the respective cells are disabled.

Upon adding or removing clients, the corresponding input sections are updated automatically
(excluding those that have their intAddrs set; the intAddrs serve as a reference to IED Configuration
Tools, e.g. to the Signal Matrix in PCM600).

10.7.3 Configure direct GCB Clients GUID-AA0E0994-70C1-4B2C-8441-DBDF2C889A80 v1

In the Navigation Tree, select any element that has GCBs below it in the Navigation Tree (usually a
Subnetwork, a Voltage Level or the whole project is a good choice).

1. Select the GCB Client Editor. The rows will display available GCBs and the columns will show
available GCB clients.
2. If you have IEDs with more than one Access Points, make the column ‘AP’ visible.
3. Configure the GCBs with Clients:
• Add a GCB client individually by selecting one cell and entering ‘+’ or ‘*’ or ‘x’.
• Remove a GCB client individually by selecting one cell and entering ‘-’ or pressing
‘Delete’.
4. Right-click and select ‘Remove GCB Clients in selection’ to remove all existing connections in
the selected cells, rows or columns (and all related inputs).
5. Right-click and select Connect GCBs to Clients in selection. This will connect all GCBs in the
selected cells, rows or columns, if allowed by the Subnetwork configuration.
6. Use the mechanisms described above in the previous chapter if you need to individually
configure clients.

148 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

10.7.4 Configure routable GCB Clients GUID-4870962B-C357-4106-8387-0748AC400F29 v1

In addition to conditions mentioned in chapter "Configure direct GCB Clients" for routable
connections Source and target IED need to meet following requirements:

• Source IED need to have service GOOSE.rGOOSE = true defined


• Target IED need to have service ClientsServices.rGOOSE = true defined

Additionally control blocks need to have Protocol element defined. It’s state is represented by
Connection Type column. When its value equals Routable, in opposite case value is set to Direct.

Routable Connections are represented with “r” instead of “x” as shown below.

GUID-85B6D32D-3B37-4EE9-B426-6F81B851844C V1 EN-US

10.7.5 Configure filter for GCB Clients GUID-A619DCE6-C803-44C4-8F3C-EAEDC8E39B66 v1

IET600 allows the user to add a regular expression, which will filter the clients based on their name.
Additionally it is possible to show/hide Edition 1 or Edition 2 GCB clients by checking “Show Ed.1/
Ed.2 clients” context menu items.

Integrated Engineering Tool 149


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

10.7.6 GCB monitoring configuration GUID-DF5707D9-52F2-4329-BD65-E21B2A25C35C v1

Enable GCB monitoring configuration by right clicking on column title in order to switch on/off GCB
monitoring configuration as shown below.

Now you are able to create supervision for clients in selection. Before next step you need to set
Configuration Of GCB Supervision for IED type that you are using. You can do it in IED
capabilities tab. You can find more information about it in chapter Annex: IED Capabilities.

After successful configuration of GCB supervision you can go back to GCB Client Editor in order to
create supervision for clients. You can achieve it by right clicking on cell and selecting from context
menu Create supervision for clients in selection as shown below.

150 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

Note that GCB monitoring configuration should be still enabled.

After that output section should inform you about success of the operation. In case of success
supervision creation process “xg” symbol should appear on grid. Example configuration shown
below.

Corresponding message in Output section is logged.

New logical node is added to tree view as shown below.

Integrated Engineering Tool 151


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

In order to delete previously created supervision, right click on cell and use Remove supervision for
clients in selection. Example shown below.

Corresponding message is logged and Navigation Tree updated.

10.7.7 MAC-Layer Security configuration for GCBs GUID-BE0B41BD-1A23-4C2F-8074-1AE2C2796AE2 v1

The MAC-Layer Security is correlated to the values of McSecurity Services defined on client and
server side. When you create GCB client, these values are evaluated on all Server and Client IEDs,
and their result is written into the “SecurityEnabled” property of each GCB. The principles of MAC-
Layer Security configuration are:

152 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

• Client and Server need to have at least one same value of McSecurity attributes to understand
each other, otherwise value of ‘SecurityEnabled’ will be set to none, however there is an
exception. If GCB is contrived in a way that the signature is added, so that a client can read the
contents of a GCB even if it does not understand the signature.
• A GCB is sent as encrypted only if all receivers understands “Encryption” and the sender
understands encrypted.
• A GCB is sent as signed if the sender understand “Signature” and at least one client
understands “Signature” and encryption is not possible due to previous rule.
• A GCB is sent as “None” if the sender does not understand either Signature or encryption, or if
none of the clients understands “Signature”.
• For Client values of McSecurity attributes are taken from ClientServices service where it occurs
as subservice.
• For Server values of McSecurity attributes are taken from GSESettings.McSecurity, however
standalone version of McSecurity is also required in order to achieve correct configuration.

10.8 SVCB Data Configuration GUID-D15E2726-4718-48A3-B3D9-549AADEFA153 v1

10.8.1 SVCB Data Editor GUID-2D02A349-DFF5-448F-9E8A-3A2569C7D50B v1

The SVCB Data editor defines the parameters for the reporting service, according to IEC 61850 part
7-2.

Property Description
IED Type IED Type
IED IED Name
AP Access Point name
Srv Server name
LD Logical Device where GCB is defined
LN Logical Node where GCB is defined
SVCB SVCB name
Status Describes how the SVCB was created. This attribute is
automatically generated by IET.
Attached Dataset Select the name of the Dataset, as specified in the
Dataset Editor.
SvId No default value, must be unique within the Subnetwork.
If it is editable, it is recommended to make unique within
substation to avoid reconfiguration when changing
Subnetworks.
Multicast FALSE indicates that this is a Unicast control block, a
maximum of one client IED shall be assigned to the
instance
Sample Mode Specifies if the sample rate is defined either in 1)
“SmpPerPeriod” in units of samples per nominal period,
2) “SmpPerSec” samples per second, or 3)
“SmpPerSmp” seconds per sample. If missing, default is
1)
Sample Rate The value shall be interpreted depending on the value of
Sample Mode
Reserved TRUE indicates that SVCB is currently exclusively
reserved for the client that has set the value to TRUE.
Other clients shall not be allowed to set any attribute of
that SVCB
Table continues on next page

Integrated Engineering Tool 153


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

Property Description
Conf.Rev. Version number will be incremented on changes of the
Dataset related to the control block. Changes are the
deletion or insertion of a member of the Dataset,
reordering of the member, or changing the Dataset
reference of the control block, or any change of a value
of an attribute of MSVCB. Changes will increment this
value by 10000.
Connection Type Defines whether control block is connection is direct or
routable. When value is being set from direct to routable
‘Protocol’ element is added to SampledValueControl. In
opposite situation it is removed. It is only enabled when
parent IED of control block has service SMVsc.rSV =
“true” defined.
Security Enabled Shows security options per control block Instance:
Signature or SignatureAndEncryption. None by default.
Its value is not user-configurable but is automatically set
depending on the clients of the SVCB and their Security
settings. The exact logic is described in chapter "MAC-
Layer Security configuration for SVCBs" .
NofAsdu Number of ASDU (Application service data unit).
MAC Address Identifies source and allow filtering of the SV message. It
should be unique for an application within the
Subnetwork.
APP-ID Identifies source and allow filtering of the SV message. It
should be unique for an application within the
Subnetwork.
VLAN-ID Controls the dataflow and real-time behavior of the
messages within a VLAN network. HEX value between
000-FFF is used, where value 000 (default) indicates that
only the VLAN user priority is used. If not used it shall be
set to 0
VLAN Priority Controls the dataflow and real-time behavior of the
messages within a VLAN network. Priority value between
0-7 is used, where higher numbers indicate higher
priority message.
IP Address UDP/IPv4 destination address. shall be a IP multicast
address conform to RFC 5771. Recommended range is
from 232.0.0.0 to 232.255.255.255. Used for Routable
connection. Enabled only when “Connection Type” is set
to “Routable”.
IP IGMPv3Src Unicast IPv4 address to be used for IGMPv3
subscription. Used for Routable connection. Enabled
only when “Connection Type” is set to “Routable”.
IP Class of Traffic Class of traffic for IPv4. Specifies the TOS field of the
IPv4 header. Used for Routable connection. Enabled
only when “Connection Type” is set to “Routable”.
Include RefreshTime True indicates usage
Include SampleRate True indicates usage
Include Security True indicates usage
Include SynchSourceId If true, the SV message contains the identity of the
synchronizing master clock according to IEC 61850-9-3.
Default = false
Include SampleSynchronized Value will be ignored. Kept to ensure backward
compatibility to IEC 61850-9-2 edition 1.0.
Include DataSet TRUE = SV buffer contains the attribute DatSet.
FALSE = attribute DatSet is not available in the SV
buffer.

154 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

10.8.2 Create SVCBs GUID-689D1D53-C127-495F-BEBE-F2C4D2A9A5A3 v1

1. If you know, where you want to create your SVCB, you can preselect an appropriate element in
the Substation, IEDs or Communication Navigation Tree. To have the full choice of IEDs,
select the project.
2. Open the SVCB Data editor and select a row in the SVCB list, right-click and select Insert new
MSVCB or Insert new USVCB from the context menu.

IEC202100478 V1 EN-US

3. Alternatively, you can select the Communication menu tab (the Communication Navigation
tab will automatically be selected) and click on Create MSVCB(s) or Create USVCB(s)
respectively.

IEC202100479 V1 EN-US

4. A new row is created in the editor. Select a Dataset to the SVCB in the Attached Dataset
column.
5. Modify the remaining properties as required.

10.8.3 Delete SVCBs GUID-5094ABDE-6BAA-4BD0-9065-AB60911C0010 v1

A SVCB once created cannot be renamed or totally removed entirely from the project to maintain a
consistent revision history of that SVCB. Once a SVCB has been exported, its last version number
needs to be remembered by the system tool. If this is not done, a SVCB with the same name and the
same version number, but different content and/or behavior, could be created at a later time, which
would lead to confusion and even potentially dangerous situations.

So a SVCB is “deleted” by setting its status to ‘deleted’. Deleted SVCBs will remain in the tool
forever, but will not be exported in SCD/ICD/IID files, and will not count when evaluating limits for
SVCBs.

1. Select the SVCB Data editor.


2. Select any element that has SVCBs below it in the Navigation Tree.
3. Select one or several rows with the SVCBs intended for deletion.
4. Right-click and select ‘Delete Row(s)’ or press the ‘Delete’ key. A confirmation dialog appears,
confirm the deletion or cancel it.

Integrated Engineering Tool 155


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

The SVCBs will remain, but their Datasets will be removed and their status will go to ‘deleted’.

10.8.4 Edit SVCBs GUID-6675B7C9-E92F-44A2-8FFA-17EC856C3FDD v1

The SVCB configuration can be edited in the SVCB editor; normally this should not be necessary
however. There are several specialties to be observed:

An SVCB cannot be renamed. To rename an SVCB, delete it and create a new SVCB with the
intended name.

Removing a Dataset from an SVCB will automatically put the SVCB into a ‘deleted’ state.

Configuration changes will cause the configRev value to be increased to the next multiple of 100.
This will happen only once between import and export, not with every change.

10.8.5 Reuse “Deleted” SVCBs GUID-5315A66E-11FD-45BD-BC8F-EC5B1CB8057C v1

A “deleted” SVCB can be reused by simply attaching a Dataset to it. Instead of creating a new SVCB,
it is recommended to reuse deleted SVCBs first.

10.9 SVCB Client Configuration GUID-5CB7D6B7-1906-4E2D-A2E6-42EA191C1A39 v1

10.9.1 Prerequisites GUID-1EF2C892-DE68-429D-A871-82D4119FA87F v1

To do a sensible SVCB client configuration, most of the Bay-level IEDs should be known and should
be attached to the correct Subnetworks.

10.9.2 SVCB Client Editor GUID-63794090-C8E8-4826-BE3C-6DBDE7DC7BAC v1

The rows of the SVCB Client editor show SVCBs from the selected element in the Navigation Tree.
The last columns in the editor shows the IEDs available as SVCB clients. To save space the client
IED names are vertical. Use the Tooltip to see the text horizontally.

If the Client IED is not on the same Subnetwork as the SVCB sender, it cannot be configured as a
Client. In the Editor, this shows as greyed-out cells that cannot be edited.

Also an IED cannot be configured to send SVs to itself, this shows as greyed-out cells too.

156 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

To send a SVCB to a receiving IED, enter ‘+’ or ‘*’ or ‘x’ in the IED column at the end of the SVCB
row. You can use ‘-’, the space bar or ‘Delete’ to remove an existing clients.

Upon adding or removing clients, the corresponding input sections are updated automatically
(excluding those that have their intAddrs set; the intAddrs serve as a reference to IED Configuration
Tools, e.g. to the Signal Matrix in PCM600).

10.9.3 Configure direct SVCB Clients GUID-E0AFFBE1-A0DC-4134-8880-EEB3A24E03D9 v1

In the Navigation Tree, select any element that has SVCBs below (usually a Subnetwork, a Voltage
Level or the whole project is a good choice).

1. Select the SVCB Client Editor.


2. If you have IEDs with more than one Access Points, make the column ‘AP’ visible
3. Configure the SVCBs Clients:
• Add an SVCB client individually by selecting one cell and entering ‘+’ or ‘*’ or ‘x’.
• Remove an SVCB client individually by selecting one cell and entering ‘-’ or pressing
‘Delete’.
4. Right-click and select Remove SVCB Clients in selection to remove all existing connections in
the selected cells, rows or columns (and all related inputs).
5. Right-click and select Connect SVCBs to Clients in selection. This will connect all GCBs in
the selected cells, rows or columns, if allowed by the Subnetwork configuration.

Integrated Engineering Tool 157


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

10.9.4 Configure routable SVCB Clients GUID-D8793233-6CAB-49D1-86BE-B23FDD079DC4 v1

In addition to conditions mentioned in chapter "Edit Datasets" for routable connections Source and
target IED need to meet following requirements:

• Source IED need to have service SMVsc.rSV = true defined


• Target IED need to have service ClientsServices.rSV = true defined

Additionally control blocks need to have Protocol element defined. It’s state is represented by
“Connection Type” column. When its value equals “Routable”, in opposite case value is set to Direct.

Routable Connections are represented with “r” instead of “x” as shown below.

10.9.5 Configure filter for SVCB Clients GUID-3A0A76F0-EFC5-4274-9300-4796A7EF7B49 v1

IET600 allows the user to add a regular expression, which will filter the clients based on their name.
Additionally it is possible to show/hide Edition 1 or Edition 2 SVCB clients by checking “Show Ed.1/
Ed.2 clients” context menu items.

158 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

10.9.6 SVCB monitoring configuration GUID-37D174AE-CA0D-4AAE-A155-084BB4A9572E v1

Enable SVCB monitoring configuration by right clicking on column title in order to switch on/off SVCB
monitoring configuration as shown below.

Now you are able to create supervision for clients in selection. Before next step you need to allow
“Configuration Of SVCB Supervision” for IED type that you are using. It can be done in “IED
capabilities” tab. You can find more information about it in chapter Annex: IED Capabilities.

After successful configuration of SVCB supervision you can go back to SVCB Client Editor in order to
create supervision for clients. You can do it by right clicking on cell and selecting from context menu
“Create supervision for clients in selection” as shown below.

Integrated Engineering Tool 159


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

Note that SVCB monitoring configuration should be still enabled.

After that output section should inform you about success of the operation. In case of success
supervision creation process “xs” symbol should appear on grid. Example configuration shown below.

Corresponding message in Output section is logged.

New logical node is added to tree view as shown below.

160 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

In order to delete previously created supervision, right click on cell and use “remove supervision for
clients in selection”. Example shown below.

Corresponding message is logged and Navigation Tree updated.

10.9.7 MAC-Layer Security configuration for SVCBs GUID-71DEE042-33AB-438F-9E03-74D2B2EA1B7F v1

The MAC-Layer Security is correlated to the values of McSecurity Services defined on client and
server side. When you create SVCB client, these values are evaluated on all Server and Client IEDs,

Integrated Engineering Tool 161


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

and their result is written into the “SecurityEnabled” property of each SVCB. The principles of MAC-
Layer Security configuration are:

• Client and Server need to have at least one same value of McSecurity attributes to understand
each other, otherwise value of ‘SecurityEnabled’ will be set to none, however there is an
exception. If SVCB is contrived in a way that the signature is added, so that a client can read the
contents of a SVCB even if it does not understand the signature
• A SVCB is sent as encrypted only if all receivers understands “Encryption” and the sender
understands encrypted.
• A SVCB is sent as signed if the sender understand “Signature” and at least one client
understands “Signature” and encryption is not possible due to previous rule.
• A SVCB is sent as “None” if the sender does not understand either Signature or encryption, or if
none of the clients understands “Signature”
• For Client values of McSecurity attributes are taken from ClientServices service where it occurs
as subservice.
• For Server values of McSecurity attributes are taken from SMVSettings.McSecurity, however
standalone version of McSecurity is also required in order to achieve correct configuration.

10.10 ‘Inputs’ Configuration GUID-60C85232-D2B6-41FA-87AC-D6684543F5F9 v1

‘Inputs’ is understood here in the sense of IEC 61850: as references to Data Attributes which an IED
is receiving via Dataflow Communication.

10.10.1 Overview GUID-83A41E43-9E59-4E28-BE54-7C3CC256CC0D v1

There are two ways how inputs are currently used.

1. By the System Tool: if the Target IED allows, IET600 automatically creates inputs for all DATA
sent via GCB or SVCB on the Client IED. (IET600 does currently not create inputs for RCB
Clients).
In this case IET600 configures all inputs in the LLN0 of the receiving server. If inputs on another
LN are requested by the IED Configuration Tool, they need to be manually remapped.
2. An IED can specify inputs to indicate what information is needed. This approach is called “Late
Binding” (for details how this specification is done, please read “Annex: Inputs and Late
Binding”). The System engineer has then the duty to map attributes from the desired source and
configure them to be sent via specified Control Block service (GCB, SVCB, RCB).
This is yet unexplored territory and may cause considerable manual work.
3. When IED is updated using Client Driven Engineering, IET600 generates all necessary Datasets
and Control Blocks for specified inputs in SCL file.

10.10.2 Inputs Editor GUID-36CE4C1F-747E-4FFC-B3E9-D8620BA96622 v1

The ‘Inputs’ Editor displays Inputs and allows a few things to be edited.

Property Description
Target IED IED where the Input is located
AP Access Point where the Input is located (default hidden)
Server Server where the Input is located (default hidden)
LD LD where the Input is located
LN LN where the Input is located
pServT predefined Communication Service Type for Late Binding
(for an explanation, see Annex: Inputs Predefined from
IED (Late Binding)
Table continues on next page

162 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

Property Description
pLN predefined Source LN (for an explanation, see Annex:
Inputs Predefined from IED (Late Binding))
pDO predefined Source DATA Object / Common Data (for an
explanation, see Annex: Inputs Predefined from IED
(Late Binding))
pDA predefined Source DATA Attribute (for an explanation,
see Annex: Inputs Predefined from IED (Late Binding))
Input Source IEC‑61850‑Reference to the Source of the Input,
typically a Data Attribute on another IED.
IEC 61850 allows also Data Objects to be defined as
Input Sources, but this is rare.
Service The Dataflow Service, by which this information is
received (GOOSE, SMV or Reporting)
Source Control Block IEC‑61805‑Reference to the Control Block used to
transmit this information.
Internal Address Address which an IED or its configuration tool can give
indicating internal address to which this information is
written to.
Main function of the internal address in IET600 is to
indicate that the information supplied by an Input section
is actually used by the target IED.
Status ‘Resolved’ indicates that the Data Object or Data
attribute referenced by ‘Input Source’ exists in the DATA
model of the source IED; and it is contained in a Dataset
and the Target IED is client of this Dataset.
‘Unresolved Configurable’ indicates that either the Data
Object or Data attribute referenced by ‘Input Source’
does not exist in the DATA model of the source IED, or
that it is not contained in a Dataset or that the Target IED
is not client of a Dataset with this attribute. The Input
does not have an Internal Address which allows it to be
reconfigured or removed.
‘Unresolved Fixed’ indicates an Input with an unresolved
reference (as described above), and which contains an
Internal Address, which prevents it from being
reconfigured or removed. If the Input Source of such an
Input is empty, this Input might require Manual Mapping,
see chapter "Configure Predefined Inputs (Late
Binding)").
Description A user-editable attribute where an engineer could
provide some additional information about this attribute

10.10.3 Create Inputs GUID-AD93F5BD-41FB-4F72-B334-FBFD408AD1D9 v1

Inputs are created automatically on the client IED, if GCB or SVCB Clients are configured unless the
client IED specifically forbids this (Service ClientServices.noIctBinding = true, introduced in Ed. 2).

10.10.4 Delete Inputs GUID-1F66B87C-DCBC-4F39-8B2D-01405FDEF0E6 v1

Inputs with Status Resolved (resulting from a GCB or SVCB Client mapping) cannot be deleted
manually, remove the associated GCB or SVCB client mapping to delete those inputs.

Inputs with Status Unresolved configurable can be deleted from the row context menu.

Inputs with Status Unresolved fixed should normally not be deleted:

Integrated Engineering Tool 163


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

• Internal Address indicates that this Input is actually required by the IED for its correct
functioning.
• Strictly according to IEC 61850, a System Configuration Tool is not allowed to delete Inputs with
an Internal Address. However, sometimes, a deletion of such Inputs may be required to clean up
an old configuration.

To delete Unresolved configurable or Unresolved fixed inputs:

1. Select the Inputs Editor.


2. Select any element that has IEDs below it in the Navigation Tree (the IED with the Inputs in
question is usually a good choice).
3. Select one or several rows with the Inputs intended for deletion (in IEDs with lots of Inputs, you
may want to set the filter to either an appropriate Status or to show only rows with errors).
4. Right-click and select Delete Row(s) or press the Delete key.

IEC202100488 V1 EN-US

If any of the rows to be deleted contains an Internal Address (i.e. Status is ‘Unresolved fixed’),
the following confirmation dialog appears:

IEC202100489 V1 EN-US

If you are sure about the deletion (confirmation from the engineer responsible for the IED
configuration is strongly recommended), continue with Yes.
5. The selected Inputs will be deleted.

164 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

10.10.5 Remapping Inputs to Different Parent LNs GUID-0C769119-2622-4014-88D2-1A2789FE7FA9 v1

Sometimes, a receiver IED requires an Input mapped to a particular LN different from the ABB
standardized mapping to LLN0.

For Ed. 2 IEDs, this can be done by using the Late Binding Parameters as described in chapter
"Configure Predefined Inputs (Late Binding)" below. For older IEDs, this information will have to be
provided by the engineer configuring the Target IED. Both procedures are cumbersome and should
be avoided as much as possible.

To map Inputs to a different LN:

1. Select the ‘Inputs’ Editor.


2. Select one or several Inputs which you want to map to a different Parent LN.

IEC202100490 V1 EN-US

3. Right-click in the row selector column of the editor -> the row context menu of the editor
appears.
4. Select Change Parent LN -> the following Dialog appears:

Integrated Engineering Tool 165


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

IEC202100491 V1 EN-US

5. Select the LN which you want as parent for the Input, click ‘OK’ to remap all the selected Inputs
to this LN.

While IET600 does its best to conserve Input configurations, any action deleting the Inputs will also
remove any customized mapping of Parent LNs. As there can be considerable work behind such
customized mapping, ensure that you create Backups of such configurations.

Any Inputs containing an Internal Address will not be deleted and are therefore safe against such
accidental deletions. Therefore it is best to:

• Do not do such Input re-mapping unless you absolutely have to.


• If you have an IED which absolutely needs it, require the IED Configuration Tool to complete the
turnaround by supplying you an IID file with Inputs completed with Internal Addresses.

10.10.6 Connections Resolving GUID-C62189B4-803A-41CE-8671-2AAE322BC8F4 v1

For some IEDs with Status Unresolved configurable or Unresolved fixed resolving method could
be applied by using Resolve Connection/Resolve All Connections command.

Resolve Connection will be applied only for selected Input. Resolve All Connections will be
applied for all Inputs with Status Unresolved. These commands available only if IEDs Use Client
Driven Engineering property set to true.

As a result of Resolving: necessary Datasets and Control Blocks would be created and Client
Connections to them would be arranged.

To resolve connection(s):

1. Correct Input Source values if it's necessary (see Configure Mapping to Predefined DATA
Attributes (DAs) or Configure Mapping to Predefined DATA Objects (DOs)).
2. Right-click in the row selector column of the editor -> the row context menu of the editor
appears.

166 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

GUID-D3DC0BE7-15F6-487B-89D6-02E2B01E4663 V1 EN-US

3. Select Resolve Connection/Resolve All Connections -> the following Dialog (contains list of
Server IEDs that would be changed) appears:

GUID-7FFADB1E-C772-4553-9936-9D3CEC4A5815 V1 EN-US

4. Click 'OK' to resolve connections. Or click 'Cancel' to revoke Resolving.

10.10.7 Configure Predefined Inputs (Late Binding) GUID-86B4C329-D281-4AC2-8EF8-C6A5C7718DA1 v1

For an explanation how predefined Inputs are intended to be used, see chapter Annex: Inputs
Predefined from IED (Late Binding) . This chapter just describes the practical steps to configure
predefined Inputs.

If an IED contains some predefined Inputs, they will appear in the ‘Inputs’ editor with empty ‘Input
Source’ cell. Accordingly, a warning is shown.

Integrated Engineering Tool 167


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

Per default, all the columns that show the (predefined) Attributes are hidden, you might want to show
them via the ‘Field Chooser’ Dialog (click on top left icon to open it).

10.10.7.1 Configure Mapping to Predefined DATA Attributes (DAs) GUID-3744CC86-62EE-4277-8446-11BC1007EC2D v1

To provide the mapping to a predefined DATA Attribute, do the following steps:

1. Open the Map IEC61850 DATA dialog by double-clicking into an Input Source Cell:

IEC202100493 V1 EN-US

In the bottom, the Dialog will show:


• the predefined items (Service Type, LN Class, DO, and DA)
• the selected DATA attribute.
• whether and in which Control Block the DATA Object or DATA Attribute is available (if this
remains empty, you may still select an item; however, the Inputs Editor will show this as a
warning to remind you to add this at a later time).

The dialog will allow any choice of IEDs and LDs, as they cannot be predefined.
The dialog will show only DATA Objects and DATA Attributes matching the predefined
specifications.
2. Select the appropriate attribute and click Update.

IEC202100494 V1 EN-US

The Map IEC61850 DATA dialog will close and the selected attribute will be added to the Input
Source field in the Inputs Editor.

168 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

Use Grid header context menu to enable or disable mapping dialog:

1. Click right mouse button on header of grid.


2. Check or uncheck Enable mapping dialog for "Input Source" menu item.

10.10.7.2 Configure Mapping to Predefined DATA Objects (DOs) GUID-CCD2FE29-1E4D-45AB-8FB9-19A86F2655DF v1

To provide the mapping to a predefined DO, do the following steps:

1. Open the ‘Map IEC61850 DATA’ dialog by double-clicking into an ‘Input Source’ Cell:

IEC202100495 V1 EN-US

In the bottom, the Dialog will show:


• the predefined items (Service Type, LN Class and DO)
• the selected DATA object or attribute.
• whether and in which Control Block the DATA Object or DATA Attribute is available (if this
remains empty, you may still select an item; however, the ‘Inputs’ Editor will show this as a
warning to remind you to add this at a later time)

The dialog will allow any choice of IEDs and LDs, as they cannot be predefined.
The dialog will show only DATA Objects and DATA Attributes matching the predefined
specifications.

Integrated Engineering Tool 169


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

Remember that DATA Objects with another name but with the same Common Data
Class are also eligible and will therefore appear in the list. However, preference
should always be given to DOs with a matching name.
2. IET600 allows you to map DOs directly. To enable this option need to configure a user setting
Allow mapping of DOs in inputs:

IEC202100496 V1 EN-US

Additionally, instead of selecting a DATA Object, you can create additional Inputs for some or all
attributes of the predefined DATA Object: Select one appropriate DATA Attribute and click Add
New Input; repeat till you have mapped all attributes you wish.

170 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

IEC202100497 V1 EN-US

With “Update”, you may add an attribute to the current Input; however, it is recommended to
leave this in its original configuration, till both sides agree which attributes to use.
You may use the FC combo box to sensibly limit the amount of Data Points to be selected; “ST”
and “MX” are normally sensible choices:

IEC202100498 V1 EN-US

It is also sensible to limit the amount of DATA Attributes configured as much as possible (in
discussion with the engineer who has configured the predefined inputs).

Take note that the same intAddr will be copied to all DATA Attributes. This behavior is mandated by
IEC 61850; however it may or may not be correct for the IED Configuration Tool. It is up to the IED
Configuration Tool to change those addresses appropriately.

Integrated Engineering Tool 171


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

Use Grid header context menu to enable or disable mapping dialog:

1. Click right mouse button on header of grid.


2. Check or uncheck Enable mapping dialog for "Input Source" menu item.

10.11 Dataflow Consistency Check GUID-2340040E-0BA7-4D93-A0C0-0C09ADDBC078 v1

The Dataflow Consistency Check provides a check for problems in the Dataflow configuration in an
SCD file. The check is always performed on the whole project; it is automatically called before
exporting an SCD file, but can also be called manually from the Communication tab in the Main
menu.

To check the consistency manually:

1. Select the Communication menu tab (the Communication Navigation tab will automatically be
selected) and select Check Dataflow Consistency.

IEC202100499 V1 EN-US

2. A dialog will appear, indicating a summary of found problems, e.g.:

172 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

IEC202100500 V1 EN-US

Details about the issues can be found in the Log.

The consistency check groups inconsistencies into errors and warnings:

• Errors will cause invalid SCD files or immediate problems when downloading such a
configuration to the IEDs.
• Warnings may be allowed during transitional engineering phases, they may or may not cause
problems when downloading such a configuration to the IEDs, but must be resolved before
finally commissioning the system.

As the Dataflow consistency check concerns different items in different editors, the problematic items
are not marked in the editors, but are logged.

The following issues are checked:

• Duplicate IP addresses (error).


• Datasets without any Dataset Entries (error, these will be removed on export).
• Datasets allocated to more than one Control Blocks of different types (e.g. RCB and GCB)
(error ).
• Connected Access Points not connected to a Subnetwork (warning).
• Control Blocks without any clients (warning).
• Datasets not allocated to any Control Block (warning).
• Datasets allocated to more than one Control Blocks of different types (e.g. RCB and GCB).
• IEDs which are mapped as GCB or SVCB clients, but do not have the corresponding inputs
configured (warning).
• Missing MAC Addresses or APP-IDs for GCBs (warning).
• Missing MAC Addresses or SmvIDs for SVCBs (warning).
• Duplicate SmvIDs for SVCBs (the IEC 61850 standard enforces uniqueness only in
Subnetworks, IET600 checks for uniqueness in the whole project; this may sometimes cause
false positives) (warning).
• GCBs or SVCBs with the same MAC address but different APP-ID/SmvIDs or vice versa (this is
basically allowed by the IEC 61850 standard, but IEDs of some vendors have a problem with it)
(warning).
• RCBs, GCBs and SVCBs incompatible clients subscriptions.

Note that IET600 will still allow you to export an invalid SCD file in spite of errors or
warnings.

Integrated Engineering Tool 173


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 10 1MRK500114-UEN Rev. X
Dataflow Engineering

10.12 Dataflow Communication - IEC61850 Signal List GUID-5118D256-4C29-4227-8FC8-9481F6DCC616 v1

IET600 can generate Excel document, which contains the configuration of the dataflow
communication among RCBs, GCBs and SVCBs and their clients. The datasets are also included
with their entries.

10.13 Dataflow Communication - IEC61850 Dataflow GUID-0D3B9F8C-C064-4D8E-B7C4-1F21B83ACC71 v1

IET600 can generate Excel document, which contains the GCBs and SVCBs signals and their
details. To export such document user should use Main Menu/Communication/IEC61850 Dataflow.

GUID-654ED9BF-EF1E-4A2B-89C7-E70CC55BA319 V1 EN-US

After clicking button shown above, such dialog will be displayed.

GUID-0154B42F-37F3-4813-83DF-85E7634F7733 V1 EN-US

This dialog allows to select destination path and whether to export additional details. After exporting,
a user is presented with choice to see the results.

• Export without details


Exports an Excel in which each Data Object is represented as one row and all Data Attributes
are listed.

GUID-35749B39-A262-4149-8A5B-56F8CC2619CA V1 EN-US

• Export with details


Exports an Excel with additional details in which each Data Object and Data Attribuets are
presented as separate rows. Also Internal Address column is present for Data Attributes with
that property.

174 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 10
Dataflow Engineering

GUID-694A2087-ABF5-4C22-8333-286103ADD7C3 V1 EN-US

Integrated Engineering Tool 175


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
176
1MRK500114-UEN Rev. X Section 11
Customer Name Engineering

Section 11 Customer Name Engineering GUID-97F067EE-8583-494D-A90C-642B3788C2DA v1

11.1 Overview GUID-5F0D1B93-98F3-4A64-BB24-2DFF8352753C v1

For a general explanation how “Internal Name” and “Customer Name” are intended to be used,
please read chapter "Naming of Objects". This chapter describes the functionality of the ‘Naming’
Editor.

In IET600, the following elements can have customer names:

• Substations, Voltage Levels, Bays, Functions and Subfunctions


• Equipment and Sub-Equipment
• IEDs
• Subnetworks
• Logical Devices (IEC 61850 Ed.2 IEDs may allow modifying the LD Name attribute. IET600
treats this attribute as the customer name of an LD). As this has some additional implications,
see chapter LD Naming for a detailed explanation)

11.2 The 'Naming' Editor GUID-6DE49967-36CD-4588-92A2-395C420C100D v1

The central components of this editor are the two columns ‘Internal Name’ and ‘Customer Name’.
The remaining columns are mainly for information; additionally, by clever sorting and/or filtering, they
support rapid (re)naming of many items.

11.2.1 Rename IED, Internal Name GUID-F36BAEE8-98BD-444B-9D0C-726239678C82 v1

Renaming the internal name of an IED will cause the updating of several related items (e.g. GCB
default Application or appID, RCB default rptID, Input source references in other IEDs etc.)

Changing an IED internal name will affect the communication and require a reloading of all clients of
the affected IED. Once a project is in the testing/commissioning phase, this is therefore not
recommended.

Integrated Engineering Tool 177


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 11 1MRK500114-UEN Rev. X
Customer Name Engineering

11.2.2 Rename Bay, Internal Name GUID-B32FC74D-194C-4B40-8A72-B6C6FCA0626B v1

If you rename a Bay name and the Bay contains IEDs with the Bay name as a part of their name
(e.g. IED AA1D1Q01KF1 in Bay Q01), IET offers you the possibility to rename all IEDs in that Bay
accordingly. The following Dialog will appear:

It is strongly recommended to rename the IEDs along with the Bay. However, communication items
will be affected (see chapter "Rename IED, Internal Name").

If you do not follow a hierarchical naming scheme, the dialog will not appear and the Bay will be
renamed without further confirmation.

11.2.3 Rename Substation or Voltage Level, Internal Name GUID-BEE64D5A-C8EA-4F7B-BB0B-3DD0D3434314 v1

If you rename a Substation or Voltage Level and it contains IEDs with the Substation or Voltage Level
name as a part of their name (e.g. IED AA1D1Q01KF1 in Substation AA1), IET offers you the
possibility to rename all IEDs in that Voltage Level accordingly.

As when renaming Bays, a dialog will appear and you can confirm or refuse to rename the IEDs
along with the Substation or Voltage Level:

178 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 11
Customer Name Engineering

It is strongly recommended to rename the IEDs along with the Bay; however, communication items
will be affected (see chapter "Rename IED, Internal Name").

As a great number of IEDs and all their related communication items need to be renamed (especially
when renaming a Substation with all IEDs contained in it), this may take several minutes in a big
Substation.

If following the IEC 81346 naming scheme, Communication Subnetworks will also contain the
Substation Name. However, they are not automatically renamed together with the Substation. To
rename these Communication Subnetworks efficiently, sort on ‘Type’ and ‘Internal Name’ columns,
then use ‘Search and Replace’.

11.2.4 Hierarchical Customer Names GUID-F625DC7B-99B3-4388-8C28-1BC382C56C2B v1

A typical example is a customer which was using the older variant IEC 61346 for naming, which is
also hierarchical. In this case, the naming structure is the same, only the standard names are
different (e.g. the Circuit Breaker of a Bay is named Q0 instead of QA1, Disconnector Q1 instead of
QB1 etc.)

In such cases, Customer names can be given (or renamed) very efficiently by sorting on ‘Type’ and
‘Internal Name’ columns and then using either ‘Search and Replace’ or ‘Fill Down’ to give a defined
Customer Name for all equipment with a specific Internal Name.

11.2.5 Non-hierarchical Customer Names GUID-4C328C01-0232-418C-AC08-A0234A2D64BF v1

Certain customers have specifications for their names that are not hierarchical (a typical example is
the Power System Designation System, used in Power Generation Plants).

The “Customer Path/Name” in such cases is usually not needed (the hierarchy is implicitly contained
in the naming); therefore the engineer may want to hide the respective column to avoid confusion.

11.2.6 Customer Path/Name Display GUID-AD1233C3-D93A-423D-9B24-BD982BBA626F v1

If an external name for any item is missing, its internal name will be shown in brackets, e.g. Sils.220
kV.(Q01). This is done to provide sensible paths for equipment, even if higher levels are not named
yet (e.g. Sils.220 kV.(Q01).CT1 instead of Sils.220 kV.CT1 which would not allow identifying the CT
in question properly).

11.3 LD Naming GUID-C8CDB45F-2424-4523-BBAB-C72A96E6BC78 v1

IEC 61850 Section 8-1 – defining the online communication – always refers to an LD Name as part of
a reference of any IEC61850 DATA object.

As a default value, this LD Name is a concatenation of IED name and Logical Device Name (LDInst
in the SCL file). As an example, a Logical Device ‘LD0’ in an IED ‘AA1C1Q01KF1’ would have the LD
Name ‘AA1C1Q01KF1LD0’.

In some situations, it was considered useful to allow this LD Name to be customized. So in the above
example, a customer might want to rename this into ‘Main1_Control’, i.e. give it a name which is
more appropriate in his own environment. So IEC 61850 Ed. 2 introduced the appropriate SCL
element and IEC 61850 Ed. 2.1 introduces the appropriate services that allow an IED to declare
whether it can handle LD renaming or not.

LD Naming has two implications:

Integrated Engineering Tool 179


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 11 1MRK500114-UEN Rev. X
Customer Name Engineering

1. An IED must allow the customization of this LD Name.


2. An IED which is a communication client of an IED with customized LD Names must understand
it.

11.3.1 Customization of Logical Device Names GUID-AA00CAD4-0DB6-480F-A7DB-A7B55DBFFE4F v1

As currently, not many IEDs are allowing such a customization, per default, the corresponding rows
are hidden in the ‘Naming’ Editor

To make them visible, check the Menu item ‘Show LD’ in the ‘Column’ Context menu of the ‘Naming
editor:

IEC202100505 V1 EN-US

You will need to do this every time you open IET600.

The Logical Devices will then also appear as rows. If an IED does not allow its LD Names to be
customized, they will appear greyed out in the editor (as in the example above). To allow it, the IED
must have the Service ‘ConfLdName’ defined.

11.3.2 Configuring Control Block Clients GUID-AE063D69-F82E-4CB5-9E57-07B07D40EACA v1

If a Server IED has actually changed LD Names, only IEDs that have
ClientServices.supportsLdName defined and set to “true” can be configured as Clients for Control
Blocks of the Server IED.

However, if the Server IED does allow a customization, but does not have any customized names, an
IED can be configured as Client even though it may not be able to handle customized LD Names.

11.3.3 Displaying LDs Hierarchically GUID-10CE20DF-1543-4D11-B2F0-209C32EFDB63 v1

Using the options menu, the user is able to select whether the Logical Devices display hierarchically
or not.

Navigate to Options -> Appearance and press the “Show Logical Devices Hierarchical (requires
reopen project).”

Without the option enabled, the LDs and LNs will display in a “flat” tree. Example:

180 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 11
Customer Name Engineering

IEC202100506 V1 EN-US

With the option enabled, the LDs and LNs will display in a hierarchy. Example:

Integrated Engineering Tool 181


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 11 1MRK500114-UEN Rev. X
Customer Name Engineering

IEC202100507 V1 EN-US

Changing this setting requires reopening the project to see changes.

182 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 12
HMI Engineering

Section 12 HMI Engineering GUID-A41FFD1B-B711-40A8-B399-407093AFB639 v1

12.1 Introduction GUID-1581DE3A-19D8-4317-B482-A7C1B6F78075 v1

HMI data are basically organized as “signals”; a signal can be understood as what appears on one
line in an Event List or Alarm List.

12.1.1 User Interface GUID-C1356B80-6159-4343-9ECC-35868B7AD797 v1

To do HMI engineering, you will use the following editors:

• ‘Signal Clients’: to configure signals to different HMIs (direct or via Mirroring) and NCCs.
• ‘HMI’ Data to configure attributes of signals.
• ‘NCC Offset’ and ‘NCC Data’ to configure attributes for sending data to NCCs.

If these Editors are not visible as Tabs, see chapter Editors, the last section explains how to make
them visible.

12.1.2 Engineering Workflow GUID-862C6977-576D-4D7E-B79D-76FC85CED5ED v1

Following are the several ways to engineer HMI Signals.

• Importing or copying Bays or IEDs (from a Library, another project etc.). HMI signals will be
imported/copied along with the Bay/IED. Inheritance mechanisms will apply as usual.
• Importing a MicroSCADA ‘lof’ file or a MicroSCADA ‘csv’ export of Process Objects.
• Importing individual preconfigured signals from a Library.
• Inserting HMI Signals from user-defined Signal Templates.
• Copying signals from another project.
• Creating individual signals and configuring them.

Efficient Substation engineering will be based on several or all possibilities mentioned above.

HMI signals have some attributes configured via formula; the evaluation of these formula depends on
a LN Mapping. IET600 allows you to do LN Mapping even if there is no IED DATA configuration yet
which has distinct advantages:

• Signals can be configured (and exchanged with the HMI configuration tool), before actually
knowing the DATA structure of an IED.
• IED DATA can be deleted or reconfigured without losing the respective HMI information.

Station-level engineering and bay-level engineering can therefore be done in parallel and merged at
a relatively late engineering stage.

To allow this, IET600 treats the attribute ‘Mapped To’ in the HMI Data editor as a “virtual” reference to
an LN. This virtual reference will then be resolved when the IED DATA model is imported.

The status of an HMI signal reference can be seen in in the column ‘Mapping Resolved’ in the HMI
Data editor.

It can also be seen in the SLD editor in the LN Mapping table under the column ‘Status’. The status
can have the following values:

Integrated Engineering Tool 183


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 12 1MRK500114-UEN Rev. X
HMI Engineering

• “resolved” for mappings which reference an actual IED DATA model (irrespective of any signals)
• “virtual” for mappings which have a reference to an HMI signal, but not to an actual IED DATA
model
• “unresolved” for LN references which has not been mapped to an IED nor to an HMI signal. This
situation may occur if a signal and its corresponding LN in the IED model have been deleted;
another possibility is via Import of an SSD file with LN Mappings.

12.2 HMI Creation and Configuration GUID-046D88C9-51D2-4F49-9F7F-9D2B101DF4F5 v1

12.2.1 Overview GUID-A482EE81-C301-45C2-A7BF-DAA98C03C299 v1

IET600 allows engineering multiple HMI Clients and configuring different signals or different signal
configurations for each HMI.

IET600 allows also the configuration of Hot-Standby systems. They consist of a Hot-Standby element
with two related HMIs. The signals of all HMIs participating in a Hot-Standby system are identical,
while the communication configuration of each HMI is different.

There are 3 types of HMI IEDs

• HMIs (a physical IED).


• Hot-Standbys (a cluster of several HMIs that are redundant and have identical HMI Signals, but
different communication configurations).

IEC202100508 V1 EN-US

OPC servers are modeled as IEDs only for historical reasons, in reality they are just pieces of
software that run in the HMI. They are displayed in the HMI tree as children of their HMI, and still
appear as IEDs in the IED tree.

As multiple HMIs are possible, it is important to be aware how the HMI signals are presented:

184 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 12
HMI Engineering

• A Bay-Level IED in the IED tree may send different signals to different HMIs. The IED has a
collection of signals for each HMI it is sending signals to. When selecting a Bay-Level IED in the
IED tree; the user needs to choose one HMI to display the signals that this particular Bay-Level
IED is sending to this particular HMI. So in this case, it is a server’s or sender’s view (which
process signals are sent from this IED).
• When selecting an HMI in the IED or HMI Navigation tree, you see all the process signals that
belong to this particular HMI. This is a client’s or receivers view (which process signals are
received by this particular HMI).

The following icons are used in the HMI navigation tree to represent the various HMI and Gateway
configurations:

Icon Description
Stand-alone HMI

Stand-alone HMI, linked

Hot-Standby HMI

Hot-Standby HMI, linked

Stand-alone Gateway

Stand-alone Gateway, linked

Hot-Standby Gateway

Hot-Standby Gateway, linked

Stand-alone NCC

Hot-Standby NCC

The next chapters will describe how to configure the HMI clients in IET600. Gateways and NCC
configuration will be described in subsequent chapters.

12.2.2 Preliminary: Configure Project OI GUID-98C038BD-B10A-4362-8A4B-52C4F7B1141F v1

If you work with MicroSCADA and use OI Settings different from the default, adapt the OI Settings
before creating any MicroSCADA HMIs. For details, see chapter Annex: MicroSCADA OI Settings.

12.2.3 Create an HMI GUID-437049D6-93F8-4A8D-BA46-496E06509D47 v1

An HMI can be created from the HMI tab in the Main menu.

IEC202100511 V1 EN-US

Integrated Engineering Tool 185


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 12 1MRK500114-UEN Rev. X
HMI Engineering

It can also be created from the context menu of several Navigation Tree objects:

IEC202100512 V1 EN-US

The details are described in chapter "Create New HMI". The configuration of OPC servers running on
HMIs of defined types (e.g. MicroSCADA) is also described there.

Although not mandatory, it is recommended to add some HMI parameters now, e.g. configure the
MicroSCADA OI length in the Properties Window.

12.2.4 Create a Hot-Standby (HSB) HMI System GUID-F0B82FD3-D2AA-4E92-9253-40685A8B29E3 v1

A Hot-Standby system can be created from the HMI tab in the Main menu.

An HMI can be created from the HMI tab in the Main menu.

IEC202100513 V1 EN-US

It can also be created from the context menu of the ‘HMIs’ Navigation Tree:

1. Select the HMI tab in the Navigation Panel, right-click the HMIs element -> the context menu for
that element appears.
2. Select Create new HSB ….

186 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 12
HMI Engineering

IEC202100514 V1 EN-US

3. The Dialog Create New Hot Stand By appears:

Integrated Engineering Tool 187


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 12 1MRK500114-UEN Rev. X
HMI Engineering

IEC202100515 V1 EN-US

4. IET600 proposes a name, which you can adapt according to your wishes. Invalid names are
indicated by an error mark.
5. Click OK to create the new HSB or Cancel to close the dialog without creating an IED.
6. Drag'n'drop two existing HMIs on the newly created Hot-Standby element.
If the HMIs were created earlier and already contain HMI signals, the HMI signals of the first
HMI will be used for the HSB, the signals of the subsequent HMIs will be thrown away).

12.3 Signal Creation GUID-8F4557F4-73B0-4D90-BBB0-E099ACA5AD4E v1

12.3.1 Overview GUID-9911C27F-CB0F-4994-B50A-0D740C4780C6 v1

HMI signals are created and configured in the HMI Data editor, as described in chapter "HMI Data
Editor". There are several ways to create HMI signals:

• Copy HMI signals from other IEDs or other HMIs.


• Insert HMI Signals from user-defined Signal Templates.
• Import a MicroSCADA Loadfile (‘lof’ file) or ‘csv’ file.
• Create HMI signals manually.

The decision which method to use to create the HMI signals depend on the project. For example, if
one is starting a new project with mostly ABB devices, importing from the Library is likely the best
method. On the other hand, if similar projects or IEDs are available, then reusing the previously
engineered data by copying the HMI signals from another IED or HMI could be faster.

12.3.2 Copy HMI Signals from another IED GUID-06B88C6F-CE5C-4C08-96AE-00A570B7AC69 v1

This is basically done as a simple copy (the selected signals from one IED) and paste (these signals
to another IED).

188 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 12
HMI Engineering

1. Select any Navigation Tree (except the ‘HMI’ Navigation Tree).


2. Select the IED whose signals you want to copy.
3. Select all the rows with the signals you want to copy (from the leftmost “row selector” column of
the editor).

IEC202100526 V1 EN-US

4. Right-click in the row selector column of the editor -> the row context menu of the editor
appears.
5. Select Copy row(s) -> all the selected rows will be copied.
6. Select the another IED (destination for signals) in the Navigation Tree
7. Right-click in the row header of the HMI editor -> the row context menu appears.
8. Select Insert copied rows.
The signals are inserted to this IED.

Note that when copying and pasting a complete IED (or any element containing
IEDs, e.g. a Bay), its HMI signals are copied along.

12.3.3 Insert HMI Signals from Signal Templates GUID-809E4B9B-9680-4D34-B286-A61C48D3377D v1

See chapter "Working With User Defined Signal Templates" to learn how to prepare and use Signal
Templates.

12.3.4 Import a MicroSCADA Database File GUID-D1B008B5-9528-4397-9527-090EC14D2B2A v1

A MicroSCADA database file can be in different formats: ‘lof’ file or ‘csv’ file.

To engineer a new project from scratch, it is best to work with HMI signals from a similar project or
from the Library.

For retrofits or upgrades of old HMIs however, signals from the existing HMI have to be used. An
import of such signals is currently only possible for MicroSCADA.

• For MicroSCADA versions 8.x, it is recommended to export a ‘lof’ file from MicroSCADA and use
this for import into IET600.
• For MicroSCADA versions 9.x and newer, it is recommended to use a ‘csv’ Export from the
Database (described below).

Integrated Engineering Tool 189


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 12 1MRK500114-UEN Rev. X
HMI Engineering

Only if neither is feasible, use a ‘lof’-file export from an IET 4.x project. Be aware, though, that this
may not represent the actual state of the MicroSCADA process database, as customers may have
made modifications directly in MicroSCADA.

A database file import takes advantage of existing IN attributes to map imported HMI signals to
current IED data. To take full advantage of this mapping mechanism, the Substation and bay-level
IED data should already exist (e.g. from an SCD import) and LN mapping should be done before a
database file import.

For detailed steps of the import, see chapter "Import a MicroSCADA ‘lof’ File".

12.3.5 Create HMI Signals manually GUID-9BB30FDC-BD2D-4EA9-A9ED-9CE792D382C0 v1

HMI / MicroSCADA signals can also be created manually in IET600.

1. Select an IED in any of the Navigation Trees (except the ‘HMI’ Navigation Tree) and open the
HMI Data editor.
2. Right-click in the row selector column of the editor -> the row context menu of the editor
appears.
3. Select Insert New Row.

IEC202100527 V1 EN-US

4. A new row is created with default HMI / MicroSCADA properties.

12.4 Signal Configuration GUID-5C351CEF-8235-488B-BE88-4B0D1CFB00DE v1

12.4.1 Overview GUID-DFC7E2E9-018B-4CBF-BBF6-408EA650C2BA v1

An HMI signal has two parts: a generic part that is useful for any HMI and a MicroSCADA-specific
part that is useful for MicroSCADA engineering only. Currently, an export is possible only for
MicroSCADA data (see chapter "HMI Signal Information Exchange"); in future, an export of generic
HMI data for configuration of other HMIs like 800xA or RTU560 is planned.

In the HMI Signals Editor, you can select whether you want to see the generic part or the
MicroSCADA part or both by selecting the checkboxes shown above the grid.

190 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 12
HMI Engineering

IEC202100528 V1 EN-US

The HMI data engineering consists of configuring the individual HMI (MicroSCADA) signal properties.
These properties can be set in the HMI Data editor.

Moreover, HMI signals are attached to IEDs in the project. This is achieved via a mapping to the IEC
61850 model of the IED, as described in chapter "Mapping Signals to IEC 61850 Attributes".

12.4.2 HMI Data Editor GUID-17FAD42A-7865-4604-BC1E-8A9FE653CAF3 v1

The HMI Data Editor provides the signal specification or MicroSCADA properties of each signal, in
particular:

• Generic HMI signals – a generic description of the signal and its behavior
• MicroSCADA signals – MicroSCADA Process Object attributes
• IEC 61850 Mapping – mapping of signals to the IEC 61850 model of an IED
• HMI Rules – rule-based configuration for several HMI attributes
• Signal and status text in multiple languages

To view all available columns in the HMI Data editor, click on the Column Chooser icon to view
all available columns.

12.4.3 Generic HMI Signals GUID-28C3C789-CBFF-412E-AEB4-33A0B4B31358 v1

To view the generic HMI signals in the HMI Data editor, select ‘Show generic part’ in the header. Most
of these generic HMI signals correlate to specific MicroSCADA attributes, as shown in the table
below:

Generic Signal Attributes Equivalent MicroSCADA Attribute


In Use IU
Station Text n/a*
Signal Text (Internal) OX/Signal text(Customer)

Status Text (Internal) (Derived from EH)


Internal Signal n/a*
Table continues on next page

Integrated Engineering Tool 191


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 12 1MRK500114-UEN Rev. X
HMI Engineering

Generic Signal Attributes Equivalent MicroSCADA Attribute


Event List HE (History
Enabled)
Event List Update Condition HA
Alarm Class AC
Alarm Delay AD
Printer n/a*
Printer Update Condition PA
Comment n/a*

Signals marked with n/a* indicate that these generic signal attributes do not have a direct relation to
a MicroSCADA attribute. They are however useful for identifying the signal within the project. For
example, ‘Comment’ can be used to store some additional information for a signal.

12.4.4 HMI Text Rules GUID-C5408501-878B-443D-8C9D-4EDE774E176A v1

IET600 provides flexible rule-based configuration of the following HMI properties:

• LNRule: rule-based configuration of MicroSCADA LN attribute


• OIRule: rule-based configuration of MicroSCADA OI attribute
• INRule: rule-based configuration of MicroSCADA IN attribute
• ONRule: rule-based configuration of MicroSCADA ON attribute
• Station Text Rule: rule-based configuration of generic signal
• Signal Text (Customer) Rule: rule-based configuration of MicroSCADA OX attribute

You can use the following variables to assemble a station text:

(for a detailed explanation of Function, Subfunction etc., see chapter "IEC 61850 Modelling of a
Substation".)

Variable Description
SS Substation internal name
SS_C Substation customer name
VL Voltage Level internal name
VL_C Voltage Level customer name
BAY Bay internal name
BAY_C Bay customer name
FN Function internal name
FN_C Function customer name
SFN Subfunction internal name. In case of recursive
Subfunctions, this variable includes the name of all
Subfunctions, not of only one level.
SFN_x Subfunction internal name. This variable includes the
name of the Subfunction of only one level x.
SFN_C Subfunction customer name. In case of recursive
Subfunctions, this variable includes the customer name
of all Subfunctions, not of only one level.
SFN_C_x Subfunction customer name. This variable includes the
name of the Subfunction of only one level x.
EQ Equipment internal name
EQ_C Equipment customer name
Table continues on next page

192 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 12
HMI Engineering

Variable Description
SEQ Sub-Equipment internal name
SEQ_C Sub-Equipment customer name
EQFN Equipment Function internal name
EQFN_C Equipment Function customer name
EQSFN Equipment Subfunction internal name. In case of
recursive Equipment Subfunctions, this variable includes
the name of all Equipment Subfunctions, not of only one
level.
EQSFN_x Equipment Subfunction internal name. This variable
includes the name of the Subfunction of only one level x.
EQSFN_C Equipment Subfunction customer name. In case of
recursive Equipment Subfunctions, this variable includes
the customer name of all Equipment Subfunctions, not of
only one level.
EQSFN_x_C Equipment Subfunction customer name. This variable
includes the name of the Subfunction of only one level x.
SN Subnetwork internal name
AP Access Point internal name
IED IED internal name
IED_C IED customer name
IED_S IED internal short name (the non-hierarchical part of a
hierarchical IED name, e.g. KF1 in case of
AA1C1Q01KF1
IED_S_C IED customer short name (the non-hierarchical part of a
hierarchical IED customer name) (rarely useful)
LDInst IEC 61850 Logical Device instance
LN IEC 61850 Logical Node name
DOI IEC 61850 Data object name
DARef IEC 61850 Data attribute reference
DARef_IN IEC 61850 Data attribute reference, stripped by “.f” and
“.i” (no distinction between float and integer values), to
be used only for INRule
DARef_ON IEC 61850 Data attribute reference, stripped by “.f” and
“.i”, and “.” replaced by “\\”), to be used only for ONRule

In IET600 is possible to define custom variables using the HMI Text Rule Variable Editor, which can
be activated from the HMI ribbon.

Integrated Engineering Tool 193


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 12 1MRK500114-UEN Rev. X
HMI Engineering

IEC202100529 V1 EN-US

The above variables can be constructed into an expression which defines the text rule, with the help
of the following syntaxes:

Syntax Description
{expression} Contains expression
@variable@ Contains variable
variable! Must include variable (mandatory)
| Field Separator in OI Rules

For example, for the station shown below, the rule evaluates as follows:

LNRule : {@SS@}{@VL@}{@BAY@}{@FN@}{@SFN@}{@EQ@}

LN: AA1C1Q01BI2

194 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 12
HMI Engineering

IEC202100530 V1 EN-US

You may also use normal text strings in the above expressions. For example, if a string “Demo” is
added to the end of the LNRule:

LNRule : {@SS@}{@VL@}{@BAY@}{@FN@}{@SFN@}{@EQ@}Demo

LN: AA1C1Q01BI2Demo

Be aware whether you include separators in the brackets or not, the evaluation is different:

{.@EQ_C@} The dot will be the prefix of variable IED, e.g. “.REC670”. If the variable does not exist,
the dot will not be visible

{@BAY_C@}.{@EQ_C@} The dot will always be shown, even if one or both variables don’t exist.

If IET600 cannot resolve a mandatory rule (using “!” syntax), cell and row will be
marked with an error. These errors must be resolved by the user, either by satisfying
the rule or by changing it.

A rule can be set back to the default value from the context menu item ‘Set to Default rule(s)’. This
context menu is available from cell, row and column context menu, so you can easily set reset either
a single cell, all rules of a signal (row) or all rules of a certain type (e.g. Station Text Rule).

Integrated Engineering Tool 195


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 12 1MRK500114-UEN Rev. X
HMI Engineering

12.4.5 Mapping Signals to IEC 61850 Attributes GUID-70F53AD4-A47C-4C45-9E12-C88AF5B385FA v1

The ‘Mapped To’ property for each HMI signal provides the link or association to the IEC 61850
model of an IED. When an LN has been mapped to the primary equipment – as described in chapter
"Mapping LNs to Substation Elements (“LN Mapping”)" – IET600 can automatically assign several
HMI and MicroSCADA properties according to this mapping. Of course, to map the signal, you must
have the IEC 61850 DATA model of the IED available.

Click on the Mapped To cell to open the Map IEC 618560 Data Attribute dialog:

IEC202100531 V1 EN-US

The Map IEC 61850 Data Attribute dialog shows the IEC 61850 model of the IED and allows you to
select which attribute to allocate to the signal.

If the dialog does not appear and the cell just allows you to enter text, the IED does
not have an IEC 61850 DATA model.

In rare cases (e.g. Switches created in IET600), an IED may have an IEC 61850
model, but will still communicate via a different protocol. In this case, the dialog will
open, but OK will be disabled. In this case the ‘Application’ column for this signal will
show “SNMP” rather than “IEC 61850”.

12.4.6 Mapping Signals to SNMP OIDs GUID-B92E24F3-1D01-4340-9E87-35B18C207B1F v1

(OID mappings are only useful if you use a recent SNMP-OPC-Gateway on a MicroSCADA system.
Older configurations which work with a 3rd party SNMP-OPC-Gateway will not profit from this
mapping).

The SNMP equivalent of a Signal Address is the SNMP OID (Object Identifier). Essentially, it is a
sequence of numbers, separated by dots. While few OIDs are standardized, most communication
equipment uses a private model. The equipment vendor will normally provide those addresses. For
some more information see https://en.wikipedia.org/wiki/Object_identifier.

196 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 12
HMI Engineering

For SNMP Signals, the ‘Mapped To’ must contain the OID (or optionally some static text); it cannot
be configured via ‘Mapped To’ dialog, but must be entered manually from a vendor-specified list of
OIDs.

12.4.7 HMI Data Consistency Check GUID-BBA9F8F4-474C-4FAA-9754-6678EB64CBB1 v1

The HMI Data Consistency Check provides a check for problems in the configuration file exported to
MicroSCADA. It is automatically called on per HMI basis before exporting such a file, but can also be
called manually from the HMI Data editor.

There are a few differences between those checks. Logical Nodes check and
differences between In Use and IU columns are checked only in HMI Data editor
and "Empty Disturbance Recording Directory" check is only performed while
exporting to the "sasmsc" format.

The checks performed depend on the element selected in the Navigation Tree:

• If an element in any but the ‘HMIs’ Navigation Tree is selected, checks will be performed for all
related IEDs on a ‘per-IED’ base. So if this check shows no errors, it means, that an IED has no
consistency errors such as duplicate LN/IX in itself.

GUID-FCE415AD-C3CF-4136-8767-E2E8B2D3C6C0 V1 EN-US

• If in the ‘HMIs’ Navigation Tree, a single HMI or Gateway is selected, the check is performed on
that HMI for all signals that it is receiving (which is equivalent to the check performed before a
‘lof’ file export). This is more reliable as e.g. two IEDs can be internally consistent, but if they
have the same UN, there can still be duplicate UN/OA/OB combinations.

GUID-258C2A86-52D5-4817-B9F3-67195D68BB91 V1 EN-US

Early in the project, you will probably perform consistency checks per IED or per Bay. Once these are
ok, you will probably check the station-level IEDs, such as switches, HMIs and Gateways (with their
respective supervision signals). Finally you will perform a final check on each HMI before exporting
its ‘lof’ file.

To check the consistency:

1. Select an element in any Navigation Tree, taking the above criteria into account.
2. Select the HMI Data editor and click on Check Consistency button.

Integrated Engineering Tool 197


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 12 1MRK500114-UEN Rev. X
HMI Engineering

IEC202100532 V1 EN-US

The consistency check groups inconsistencies into errors, warnings and infos:

• Errors will cause an error when importing the ‘lof’ file into MicroSCADA, they need to be
corrected before exporting a ‘lof’ file.
• Warnings are caused e.g. by incomplete translation of texts, they may be allowed during
transitional engineering phases and will not cause import errors, but must be resolved before
finally commissioning the system.

Rows and cells being the cause of a warning will be marked in the HMI Data editor.

The following issues are checked:

• Duplicate LN: IX combinations or missing LN or IX values (error).


• Duplicate UN:OA:OB or missing UN, OA or OB values (error).
• Invalid OB values (error).
• Duplicate ON values (error)
• Invalid AN values (error)
• Invalid DX attributes (warning)
• Missing Status texts in internal and customer language (warning)
• Aspect references which are not contained in a Dataset (info)
• Concatenated AN values (info)
• LNs in the IEC-61850 DATA model that have no signals attached (info)

Note that IET600 will still allow you to export a MicroSCADA ‘lof’ file in spite of errors
or warnings.

Warnings in HMI Data Editor can be filtered not only using Column Context Menu/Show only
Rows with Warnings but also by specific warnings using Column Context Menu/Filter by these
Warnings.

198 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 12
HMI Engineering

GUID-5864D1A8-539F-4566-8E70-70E39CA80477 V1 EN-US

Selection of more than one warning is possible. In that case the filtering logic is as follows:

• OR - for warnings in the same column


• AND - for warnings in different columns

GUID-4D64A84A-5F24-4EA7-9D4E-2C50BDC2BC40 V1 EN-US

For example, if two warnings (W1, W2) from "Mapped To" column and one (W3) from "AA" column
are selected, then the result will be all rows matching: ROW_CONTAINS((W1 OR W2) AND (W3)).

12.5 Signal Client Configuration GUID-6D423DF8-F71F-4E2E-8F84-96F7B7E1DCDD v1

12.5.1 Overview GUID-9BC89E05-140F-4B0D-94A3-98B5C7D4BF65 v1

Once HMI signals have been created for a particular IED, they can now be “mapped” to the available
HMI clients. Mapping to the HMI clients allows IET600 to generate the corresponding configuration
files for that HMI, for example ‘lof’ files for MicroSCADA.

12.5.2 The Signal Clients Editor GUID-DC3BF453-95B7-4E44-9C15-90DDD2B89211 v1

The Signal Clients Editor allows the mapping of the available signals in the project to a specific
station-level client, which could be an HMI or Gateway.

Integrated Engineering Tool 199


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 12 1MRK500114-UEN Rev. X
HMI Engineering

IEC202100533 V1 EN-US

This editor is also used for mapping signals and groups to an NCC, as described in chapter "The
Signal Clients Editor".

12.5.3 Select Signals to be Sent to HMI Manually GUID-75D1C652-3A41-4265-9A82-FE99B788E0AF v1

Use the Signal Clients editor to define the signals to be sent to the HMI client.

1. Select an IED and open the Signal Clients editor.


2. Find signal row(s) which shall be sent to the HMI (these signals should be generated in the HMI
configuration file).
3. Find the column on the right side labeled with the HMI name and mark the cell with an “x” or
double click the cell.

In most cases, one would send all of the signals to the HMI. To do this, use the ‘Fill Down’ function as
described in chapter "Context Menus".

12.5.4 Copy Full Signal Client HMI Configuration from Existing HMI GUID-0B4DEB18-8330-4ED4-B946-333E0338FCE7 v1

It is possible to transfer the full configuration from an existing, configured HMI to another HMI.

1. In the Signal Client Editor, right-click in the Column Header of the Destination HMI, then click on
Copy Configuration from ➤-> a sub-menu with available HMIs will appear.
(If the Copy configuration from context menu is disabled, the right-click was in an unsuitable
place).

200 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 12
HMI Engineering

IEC202100534 V1 EN-US

2. Click on the desired source HMI in this context menu -> one of the two following dialog will
appears.
If the data can potentially be copied, a dialog will ask you for confirmation, as the current
configuration of the destination HMI is about to be overwritten:

IEC202100535 V1 EN-US

If the destination HMI is also a Gateway and has some existing NCC configuration, IET600 will
refuse to copy the HMI configuration, as there are too many things that may go wrong. The
dialog will give you advice how to proceed:

Integrated Engineering Tool 201


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 12 1MRK500114-UEN Rev. X
HMI Engineering

IEC202100536 V1 EN-US

3. If copying is possible and you confirm with Yes, the HMI configuration will be copied to your
destination HMI.
If the copying is successful, no further confirmation is given (in case of an error, the standard
warning dialog appears telling you to check for warnings in the log). You can easily check the
result by selecting the HMIs element in the HMIs Navigation tree and then sort on either HMI
column: the marks in source and destination columns must match.

12.6 Configuration of Signals of Non-IEC-61850 IEDs GUID-DB162E35-BC87-4957-89C9-AB96694526DF v1

12.6.1 Introduction GUID-6C69D9ED-97CA-4CDD-B6F3-C4EB58F35775 v1

For IEC‑61850-Signals, the ‘Mapped To’ is the equivalent of addresses for other protocols within a
Substation.

For other protocols, only MicroSCADA attributes for entering such addresses exist (UN/OA/OB), no
generic attributes. To configure other HMIs and/or Gateways is currently not supported.

12.6.2 Supported Protocols GUID-0A70BFF7-D7B2-4F8A-A0E7-17ADD2198EFA v1

For MicroSCADA, support is provided for the following protocols:

• IEC 101/104
• DNP 3.0
• Modbus
• SPA
• LON
• SNMP

12.6.3 Engineering Workflow GUID-9ADD1BA5-D816-45D2-8E22-58BE67F0AC58 v1

The workflow is very similar to working with the IEC-61850-Protocol, except that there is not data
model of the IED.

202 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 12
HMI Engineering

1. Create IEDs.
2. Create a Subnetwork and configure it for the protocol you need.
3. Attach the IEDs to this Subnetwork.
4. Import signals.
5. Configure ‘Mapped To’ attribute of signals.
6. Provide LN Mapping.
7. Configure the signal addresses (OA/OB) according to the protocol specifications.
8. Configure signals and signal groups for NCCs (see chapter "Grouping Signals").

Below, you will find a description only for steps 5 and 7, which are slightly different from engineering
signals in an IEC 61850 IED.

12.6.4 Configure 'Mapped To' Attribute of Signals GUID-64F9BC34-7635-4B67-9A1A-617593014D39 v1

This attribute has also a function in non-IEC-61850 protocols:

• in SNMP it contains the OID (and optionally some additional information needed for SNMP
Signal configuration).
• for internal Signals, it can be used for LN mapping which in turn serves to automatically
configure all attributes that can be calculated with formula (see chapter "HMI Text Rules").

12.6.4.1 Pseudo Mapping to Resolve References GUID-054E9CDE-A075-4211-BDED-0E4D8FBADC0C v1

If no mapping is configured, then the structure to which the IED is attached, is taken as default.
Therefore, if an IED is attached to a Bay, formulas which reference Substation, Voltage Level or Bay
will resolve even without 'Mapped To' Attribute. If an IED is attached to a Substation, only references
to the Substation will resolve.

For any signal that needs to be attached to another structure, a Pseudo-LN must be configured, e.g.
AA2C1Q01KF1.LD0.CSWI1 for a signal belonging to a circuit breaker or disconnector. This Pseudo-
LN will then appear in the LN mapping table and can be mapped to a primary equipment, e.g.
AA2.C1.Q01.QA1. All formulas referencing this structure (QA1 in the above example) should now
properly resolve.

Alternatively, the LN mapping can be skipped and the information written hardcoded to the rule
attributes, as described in chapter "HMI Text Rules". However, this approach needs usually more
work and does not guarantee automatic update in case of name changes. It is recommended to limit
this approach to substations with no IEC-61850 IEDs, and few signals to be edited. In all other cases,
a configuration of the 'Mapped To' attribute will be more efficient.

12.6.5 Configure Signal Addresses GUID-2B288371-0CC1-49C1-959F-397672553134 v1

Older implementation of protocols often reserved specific address ranges for specific data types.
Newer protocols like IEC 101/104 often provide one address per information, irrespective of whether
it is a simple bit (binary value) or a larger value (e.g. 16bit analogue value).

MicroSCADA additionally also enforces certain address ranges for certain protocols even though the
protocol itself may not require this.

To make this configuration as simple as possible, IET600 provides 3 columns:

Integrated Engineering Tool 203


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 12 1MRK500114-UEN Rev. X
HMI Engineering

1. OA Offset, a read-only column, is the offset for the given data type and protocol. It may be
empty which is equal to an offset of 0.
2. OA Index is the address within a certain offset range. This attribute is for convenient
configuration by the user so that he need not bother about offsets for each protocol. This is the
column where the address should normally be configured.
3. OA is calculated as (OA Offset + OA Index), it is the final address as it appears in MicroSCADA
data exchange files and also in the actual communication. This value is important when
debugging data exchange files and analyzing online communication of MicroSCADA.

12.7 HMI Status Text Configuration GUID-7862B754-608D-4B71-9458-FFE6F155EE13 v1

12.7.1 Overview GUID-5E12B163-5BD1-424C-9A17-751CEC286635 v1

In IET600, the term “Status Texts” is used to describe the part of a signal that describes the process
state, e.g. “on/off” or “intermediate/open/close/faulty”.

To imitate the mechanism of most current HMIs, Status Texts have been implemented as follows:

Each signal has a reference to a status text, the “key”. E.g. the MicroSCADA EH attribute references
Status Texts.

Depending on the signal type, the signal can take different values (2 in case of a binary value or
binary command, 4 in case of a double binary, an irregular number in case of analogue values). So,
Status Texts come in groups; the number of items in such a group is determined by the signal type it
refers to.

A collection of Status Texts exists in the project, independent of HMI Signals. If HMI signals are
created or imported, the Status Texts are connected via its key, if it exists in the import. Otherwise
they have to be configured manually.

So sometime very early in the project, before configuring any HMI signals, you need to import such a
Status Text collection.

To import and export the HMI Status text from IET to MicroSCADA, see chapter "Import Status Texts"
and chapter "Export Status Texts", respectively.

12.7.2 View/Edit Status Texts GUID-A8C6DAB0-9C0E-4E75-AC8A-0633797EE2F2 v1

Imported Status Text from MicroSCADA can be edited and re-exported from IET600 and imported
into the MicroSCADA application, thereby ensuring that changes to the Status Text during IET600
engineering will be consistent to the MicroSCADA project.

To view/edit the Status Texts which have been imported into IET:

1. Select the HMI menu and under Configure Data, click Status Text:

IEC202100537 V1 EN-US

2. The following dialog appears:

204 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 12
HMI Engineering

IEC202100538 V1 EN-US

12.7.3 Add Status Texts GUID-2E81A814-C7FD-4AA7-ABE1-311E524338AB v1

There is a possibility to add a new Status Text by selecting predefined values from a context menu:

GUID-D6E5F5DC-E260-40CD-836E-E0E6BFCAC6E2 V1 EN-US

Depending what is selected - signal type is used to create Identifier value according to name
convention, for example for Binary Input it is BI. Accordingly for the rest signal types.

GUID-22D124F9-CE45-4351-A74A-5DC416A1C1A3 V1 EN-US

Binary Input, Double Binary Input and Binary Output have fixed ammount of process values, and
appropriate Signal Type is set. For others it is not defined how many enties are expected. That`s why
Signal Type is 'Other' and a user can add or detele entries. In case of fixed ones- when try to add a
new entry, following warning appears:

Integrated Engineering Tool 205


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 12 1MRK500114-UEN Rev. X
HMI Engineering

GUID-D4E45D70-F489-43CD-822A-E6820C814B7B V1 EN-US

Also when a number of entries is less than needed - following warning is shown:

GUID-40CDE0FE-718C-457B-AB42-A557C521B2C1 V1 EN-US

12.8 Merge HMI Data in MicroSCADA GUID-E50FE4FB-B481-4124-89AA-8293AA166F35 v1

The engineering procedure described in this section applies only to IET600 5.3 FP1 or later and
HMIs/Gateways based on MicroSCADA 9.4 FP1 or later. It does not apply to other Gateways.

12.8.1 Introduction GUID-4B39AAFE-6653-4D7F-B51D-F2912150E83C v1

Sometimes, a Substation needs to be split into 2 IET600 projects for performance or project
management reasons. A typical example is a project of a Substation which contains an HV part,
operated by one utility, and an MV part, operated by another utility, but where all Data should be
collected in the HV HMI in the end.

12.8.2 Engineering Procedure and Restrictions GUID-F8BD05AD-FC9D-4F51-AB64-805C8E4E44A9 v1

Basically, both projects are engineered independently. The data are transferred to MicroSCADA via 2
‘sasmsc’ file, where the ‘MIET’ Tool is used for import; both ‘sasmsc’ files are imported independently
of each other.

206 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 12
HMI Engineering

IEC202100539 V1 EN-US

It is important that the two ‘lof’ files in both ‘sasmsc’ files do not contain any duplicate
signals, i.e. signals with the same LN and IX: the importing MIET is not designed to
handle such situations. If this condition is not adhered to, signal attributes may
unexpectedly overwritten; or signals may accidentally and unexpectedly be added or
deleted. In worst case, this can lead to an inconsistent Process Object Database in
MicroSCADA.

12.8.3 Preparation of Projects GUID-AA12EE3D-3686-444F-93CA-9DA22A23FBF4 v1

1. In both MV and HV project, create the HV MicroSCADA with its name.


2. From the very beginning of the project, define an appropriate naming scheme to avoid duplicate
LN:IX combinations for signals in the HV project and in the MV project.
When the two projects concern different voltage levels, using the ABB naming conventions
(where the Voltage Level appears in the LN) will ensure unique LNs this for all signals that are
related to primary objects and IED supervision signals for IEDs on Bay and Voltage Level.
However, special care must be taken for signals on Substation Level; these should be mapped
to the HV HMI only in the HV project, but not in the MV project. It is the responsibility of the
engineer to ensure uniqueness.
3. For the IEC 61850 Dataflow configuration, use OPC Servers Subnetworks with different names
in MV and HV projects.
As an example, use OPC Servers AA1OPC1, AA1OPC2 etc. and Subnetworks AA1WF1,
AA1WF2 etc. in the MV substation; OPC Servers AA1OPC5, AA1OPC6 etc. and Subnetworks
AA1WF5, AA1WF6 etc. in the HV substation.

12.9 Working With User Defined Signal Templates GUID-F8C8A66B-F15A-4B8B-91B6-FC17ADF6F08E v1

12.9.1 Overview GUID-26270185-DA7A-462F-B04E-678D6675C298 v1

To increase the signal engineering efficiency when creating HMI signals manually, IET600 allows to
save signals as template for later reuse. The signal templates belong to the user and can be used in
any project.

Integrated Engineering Tool 207


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 12 1MRK500114-UEN Rev. X
HMI Engineering

12.9.2 Create new Signal Template GUID-D2C64F12-31F2-40D5-87DC-135C60F8C984 v1

1. Select an IED and open the HMI Data editor.


2. Select all the rows with the signals you want to save as template (from the leftmost ‘row selector’
column of the editor).
3. Right-click in the row selector column of the editor -> the context menu for the editor rows
appears.
4. Select Signal Templates/Save As User Template….

IEC202100540 V1 EN-US

A ‘Save As’ dialog will appear, save the signal templates under a meaningful filename.
The root folder is defined by IET600 and cannot be changed. You can create sub-folders to
organize your templates in a structured way.

The template contains for each signal the same configuration as the original signal with the exception
of attributes that make only sense in the current context. These are the rule results (Station Text, LN,
IN, OI, ON) and address information (OA, OB, UN, TI, RI).

The template contains the signal texts and status texts for the internal language and all translations
that are available in the current project.

12.9.3 Insert Signal Template GUID-6CDED5DA-C88E-4159-A7B1-CB040B915C2D v1

1. Select an IED and open the HMI Data editor.


2. Right-click in the row selector column of the editor -> the context menu for the editor rows
appears.
3. Select Signal Templates/Insert Standard Template. If this menu item is inactive than your
template library does not contain any template to insert.

208 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 12
HMI Engineering

GUID-1F9FB55C-97C9-4EE0-99F0-23DBB61FC9AA V1 EN-US

4. Browse the available templates provided by the context menu and select the one to insert. The
hierarchy of the context menus reflects the folder hierarchy of the templates.
New rows are created for the signals contained in the template.

IET600 provides a set of very basic default templates for IEC-61850-signals as shown above. Among
them are Command signals via OPC and via ISS. However, if you have already some signals
available, it is probably a better idea to create your own Signals Templates from existing signals as
described in chapter "Create new Signal Template" above.

If the current project does not already contain the signal texts or status texts for the customer
language, they are copied from the template, if available.

12.9.4 Maintaining Templates GUID-4861562E-588E-4202-861D-293B45C17A82 v1

To modify existing signal templates, insert the template into an IED, modify the signals and save
them as template using the old name. This will overwrite the existing template with the new one.

Removing or renaming of templates can be solved by Windows file system operations.

The templates are stored in the IET600 users application data folder, e.g. C:\Us-ers\<username>
\AppData\Roaming\HITACHI\IET600 in the sub-folder VersionIndependent\SignalTemplates
\1.0.1.0.

The easiest way to retrieve the actual template location is from the Save As dialog used to save the
templates.

Templates can be transferred between different users (or the same user on a different PC) by
manually copying the files.

Integrated Engineering Tool 209


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
210
1MRK500114-UEN Rev. X Section 13
HMI Mirroring

Section 13 HMI Mirroring GUID-1D35CA78-CA41-494B-9E1B-97A8C2EFE133 v1

13.1 Overview GUID-02CABBBA-43F9-44BB-A41B-12A4C6B5024E v1

Many HMIs have the capability to forward their signals to another HMI. Examples are MicroSCADA
or OPC Client/Server combinations. This capability is mostly referred to as “Mirroring”

The term “Mirroring” is slightly misleading: it is not a mirroring between two devices on an equal
footing which continuously synchronize their data, but a transfer of process values from a dedicated
server (sender, host) to a dedicated client (receiver, image). As the term “Mirroring” has become
common-place for this type of data transfer, it is used here; we will refer to Mirroring Clients and
Mirroring Servers to indicate their roles in the configuration.

13.1.1 User Interface GUID-B55F4859-3C14-4904-B09F-7CDB31300800 v1

To configure mirroring of HMI signals, you will use the following editors:

• ‘Signal Clients’: to configure signals to different HMIs (direct or via Mirroring) and NCCs.
• ‘HMI Data’ to configure attributes of mirrored signals, if required.

If these Editors are not visible as Tabs, the last section of chapter "Editors" explains how to make
them visible.

13.2 Configure Clients and Servers GUID-77C4CB98-35B2-494A-A5CA-70EDDFE59D00 v1

To configure mirroring, two basic steps are needed:

1. Configure clients and servers in the ‘HMIs’ Navigation Tree.


1.1. Configure HMIs as Mirroring Clients.
1.2. For each Mirroring Client, configure its Mirroring Servers.
2. For each Client/Server(s)-Combination: configure the signals to be mirrored (i.e. sent from client
to server) in the Signal Client Editor.

13.2.1 Configure an HMI to be a Mirroring Client GUID-4A9CEA57-D8E4-4807-A64E-A6CE43F28D4E v1

You can only configure mirroring for already existing HMIs and/or Gateways.

Prerequisites:

• Existing HMIs that are suitable for Mirroring (e.g. MicroSCADA).

Procedure:

1. Select the ‘HMIs’ tab in the Navigation pane


2. Drag’n’drop an HMI from the ‘HMIs’ element to the Mirroring element.

13.2.2 Configure an HMI to be a Mirroring Server for one Specific


Client GUID-073247A7-5B83-4EB7-96BE-5B491D488645 v1

Prerequisites:

• Existing HMIs that are suitable for Mirroring (e.g. MicroSCADA).


• At least one mirroring client configured.

Integrated Engineering Tool 211


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 13 1MRK500114-UEN Rev. X
HMI Mirroring

Procedure:

1. Select the HMIs tab in the Navigation pane.


2. Drag’n’drop an HMI from the ‘HMIs’ element to a mirroring client.

A mirroring-capable HMI can be server to several clients.

13.3 Configure Signals to be Mirrored GUID-28C7FE23-A916-4C24-A2AF-E086A524889E v1

Prerequisites:

• Existing HMIs that are suitable for Mirroring (e.g. MicroSCADA).


• At least one mirroring client configured.
• At least one server configured for the mirroring client.
• For MicroSCADA: UN configured, OA/OB configured.

Procedure:

1. Select the HMIs tab in the Navigation pane.

212 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 13
HMI Mirroring

IEC202100542 V1 EN-US

2. Select any element in the mirroring branch:


The Example shows a cross-configuration as described in chapter "Mutual Mirroring in the Same
Project":
A Hot-Standby MicroSCADA (HSB 12/13) is HMI on the HV side, two individual MicroSCADAs
(AA1KF14 and AA1KF15) are configured as HMIs on the MV side.
HSB 12/13 is configured as client with AA1KF14 and AA1KF15 as its mirroring servers.
AA1KF14 is configured as mirroring client with HSB 12/13 as its mirroring server.
AA1KF15 is configured as mirroring client with HSB 12/13 as its mirroring server.
3. Select the Signal Clients Editor. Depending what kind of element you have selected, you will
see the following:
If you select a Mirroring Client (e.g. HSB 12/13 as client in the above example), you will see the
signals of all IEDs configured as mirroring servers for this client, and you will see only the client
itself as column:

Integrated Engineering Tool 213


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 13 1MRK500114-UEN Rev. X
HMI Mirroring

IEC202100543 V1 EN-US

As the same process data can be made available via different mirroring servers, an additional
column ‘Source HMI’ is shown.
This selection is recommended for doing the initial configuration of a client.
If you select a Mirroring Server (e.g. HSB 12/13 as a server below AA2KF14 as client in the
above example), you will see all its signals as rows, and you will see all its possible Mirroring
Clients (AA1KF14 and AA1KF15 in the above example) as columns:

IEC202100544 V1 EN-US

As you have selected only one server, only signals of this server will be available; Source HMI
will show the name of this server for all signals.
This selection is useful mostly to compare mirroring to 2 different clients (e.g. in the above
example, AA2K14 and AA2K15 are supposed to be redundant, although not configured as a
Hot-Standby-System and therefore to have identical configurations)
If you select the Mirroring Islands element, you will see all signals from all possible servers as
rows, and all possible Mirroring Clients as columns:

214 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 13
HMI Mirroring

IEC202100545 V1 EN-US

This selection is recommended to check the overall configuration and reconfigure individual
signals at a late stage of the project.
4. Configure signals to clients:
Signals configured to be mirrored will be indicated with an “m” (mirrored) or “c” (copied), to
distinguish them from signals directly from the process which are marked with “x”. For the
distinction between mirrored and copied signals, see chapter "Mirrored vs. Copied Signals".
• to add individual signals to a client, double-click an empty cell, or enter “x” or “m” or “c”.
After successfully mirroring a signal, the cell will indicate either “m” for mirrored or “c” for
copied signals.
• to remove individual signals from a client, double-click an “m”/“c” cell, select a cell and
press Delete, delete the cell content or enter [Space] or ‘-’.

Normal mechanisms like ‘Fill Down’ or marking multiple cells and pressing Delete are available
to rapidly configure multiple signals.
By additionally using filters, you can easily map a group of specific signals to a client. E.g. in the
above example, a typical configuration would be to configure switch positions and protection
trips from an MV transformer Bay to the HMI of the HV and vice versa. So by filtering the station-
dependent text on “Trafo” and the signal text on “Switch position”, you see only the relevant
signals and can configure them with ‘Fill Down’.
5. Control HMI configuration:
To finally check an HMI configuration, select the HMI (e.g. HSB 12/13) in the HMIs tab below the
HMIs element. You will see all directly configured (“x”), mirrored (“m”) and copied (“c”) signals:

Integrated Engineering Tool 215


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 13 1MRK500114-UEN Rev. X
HMI Mirroring

IEC202100546 V1 EN-US

This selection gives you an overview of all signals to a specific HMI (whether direct or mirrored)
and it shows you which signals will be exported into the configuration file for the HMI (e.g. ‘lof’
file for MicroSCADA).
As described in chapter "Select Signals to be Sent to HMI Manually", you can reconfigure direct
signals in this selection. However, you cannot edit mirrored signals; to add/remove a mirrored
signal, select the appropriate element in the Mirroring Islands section and configure it there as
described above.

13.3.1 Mirrored vs. Copied Signals GUID-DA570677-3EC2-44E6-B35A-F1642246B096 v1

For Process Signals (SS=2), MicroSCADA provides an automatic mechanism to transfer the signal
status from the mirroring server to the mirroring client; no special configuration is needed.

However, internal signals (SS=1 or 3) are not automatically mirrored; they need to trigger a command
procedure which must then write the signal status from mirroring server to mirroring client.

The decision whether a signal is mirrored rather than copied is made based on the
MicroSCADA attributes SS, UN and OA: SS must be 2 and UN and OA must not be
0. If a signal is copied rather than mirrored although you think it should be mirrored,
check in the ‘HMI Data’ editor whether UN and OA are configured.

13.3.2 Configuring Copied Signals GUID-299F2CAD-45AD-48DD-B19D-1F339DEA823C v1

IET600 automatically reconfigures the signal on the server as follows:

1. AN (Event Channel Name): "MIRR_COMMON” is added.


2. AA (Action Activation): is set to 1 (New Value), except if its value was at 2 (Update) before.
3. AF (Action on First Update): is set to 1 if SS=2 (automatic) or SS=3 (fictive) to ensure that the
Event Channel is also triggered on startup.

When “unmirroring” a copied signal, IET600 automatically reconfigures the signal on the server as
follows:

216 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 13
HMI Mirroring

1. AN (Event Channel Name): "MIRR_COMMON” is removed.


2. AA (Action Activation): is set to 0 only if the Event Channel AN is empty, otherwise, it is left at its
value of 1 or 2. In rare cases, this may need to be changed manually by the engineer, if as its
former value before mirroring the signal was at some other value.
3. AF (Action on First Update): remains where it is, as its former value before mirroring the signal is
unknown. In rare cases, this may need to be changed manually by the engineer.

Although, there are situations where such copied signals need to be mirrored via MIRR_COMMON
command procedure. IET600 attaches it via Event Channel to all such signals. The logic which
signals to mirror and which not needs to be implemented in this command procedure.

13.3.3 Signals Which Cannot be Mirrored GUID-59E09233-0B67-429D-B3C2-F64A26374F3B v1

If a cell is greyed out, you cannot mirror the signal from the source HMI to the destination HMI. There
are several reasons why this might be the case:

• The source HMI is not configured to be a server to the client HMI representing the column.
To mirror signals, you need to explicitly configure clients and their servers. This helps to prevent
misconfigurations in complex situations.
• The signal is already mapped to the destination HMI directly or mirrored via another HMI.

To avoid circular and duplicate mapping, a signal can only be configured via exactly one way from
the process to an HMI. So if, in the above example (where AA2KF14 and AA2KF15 are configured
exactly the same way), you configure a signal, e.g. ‘Sils.Trafo 1.Q0.Position indication’ to HSB 12/13
via AA2KF14, the same signal cannot be configured anymore via AA2KF15. If you decide that it
would better be configured via AA2KF15, you must remove the existing configuration via AA2KF14
first.

13.4 Edit Mirrored signals GUID-22B1A66E-E067-4105-B7A0-5731AEB6192E v1

The editing of mirroring signals is done in the HMI Data editor and is basically the same as for other
signals.

13.4.1 Inheritance GUID-BF71AB8D-9ECE-478A-9003-1AE6F1422D2A v1

Hierarchy: signal attributes are propagated along the arrows. Modifying an attribute at any level will
propagate to the levels below, but break the propagation from the levels above:

IEC202100547 V1 EN-US

This rule can be used to configure signals differently on the mirrored HMI. E.g. if in the above
example, the MV owner insists on signal texts different from those on the HV HMI, the signal text on
the mirrored instance on the HMI MV can be changed without affecting the signal text on the direct
instance on HMI HV.

13.4.2 Blocked Attributes GUID-47CD1F48-E534-40C0-BDE7-F52291C231B6 v1

OA/OB attributes are relevant for mirroring, they cannot be modified in mirrored signals.

Integrated Engineering Tool 217


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 13 1MRK500114-UEN Rev. X
HMI Mirroring

13.5 Common Mirroring Configurations GUID-5474E458-82E2-41FB-A005-9F37DF38E48F v1

13.5.1 Mutual Mirroring in the Same Project GUID-CEFEAE4C-3AD9-4C5D-901A-C4367AD016BF v1

This situation often occurs in big substations with redundancies. If you have too many clients (HMIs
or Gateways), you may not be able to configure them directly to RCBs/Datasets. Mirroring is then a
solution which allows you to overcome this limitation in an indirect way.

Another fairly common occurrence is in Substations with different owners/operators for HV and MV.
The HV owner often does not want that the MV owner accesses his IEDs directly and vice versa;
they want to use their own HMI as a filter that passes on only restrictively defined data to the other
owner/operator.

In both cases, a possible solution is:

• configure HMI HV as mirroring client, configure HMI MV as server to this client.


• configure HMI MV as mirroring client, configure HMI HV as server to this client.

IEC202100548 V1 EN-US

13.5.2 Mirroring with one NCC Connection GUID-B2382263-47DA-4C54-8683-E7ECEAB3FDBF v1

Additionally to the situation described above in chapter "Mutual Mirroring in the Same Project", one
HMI (typically the HMI HV may have an NCC connection.

218 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 13
HMI Mirroring

IEC202100549 V1 EN-US

A possible solution is:

• configure HMI HV as mirroring client, configure HMI MV as server to this client.


• mirror all signals needed for the NCC to the HMI HV.
• configure the NCC signals as usual in the Signal Client Editor (signals from the HMI MV will
appear similar to the process signals and can be configured, grouped etc. identical to those).

13.5.3 Mirroring with two NCC Connections GUID-CE171CD2-F1C7-4A85-8F08-CDBE46ED3B05 v1

This is a combination of the situations described in chapters "Mutual Mirroring in the Same Project"
and "Mirroring with one NCC Connection" above: HMI HV and HMI MV exchange both data via
mirroring, additionally both HMIs have an NCC connection.

IEC202100550 V1 EN-US

A possible solution is:

• configure HMI HV as mirroring client, configure HMI MV as server to this client.


• configure HMI MV as mirroring client, configure HMI HV as server to this client.
• mirror all necessary signals.
• configure the NCC signals as usual in the Signal Client Editor (signals from the mirrored HMIs
will appear similar to the process signals and can be configured, grouped etc. identical to those).

Integrated Engineering Tool 219


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 13 1MRK500114-UEN Rev. X
HMI Mirroring

13.5.4 Mirroring to a Control Center GUID-B7A38132-DEBB-458A-9240-9FA2FF7F5D4F v1

If a customer has several substations with MicroSCADA and a control center on a higher level which
is also a MicroSCADA HMI, this can be configured more easily via mirroring than via a generic
protocol like IEC101/104.

IEC202100551 V1 EN-US

An efficient solution is:

• configure the higher-level control center (HMI NCC) as mirroring client.


• configure Substation HMIs (HMI SS1-5) as server to this client.

13.5.5 Mirroring Across Two Projects With one Common NCC


Gateway GUID-7FDCA9BA-7823-4119-90F9-FDD33DDDC85A v1

In big substations, due to size/performance restrictions, the Substation may be split into two IET
projects; often the MV part and HV part are even engineered by two different engineering
departments.

However, there may be one common NCC connection with one common NCC Gateway (in this
example shown as a combined HMI HV and Gateway). To configure this NCC Gateway correctly, all
signals need to be available on that Gateway.

One possible way to do this is to mirror the HMI MV data into the HMI HV and then do the complete
NCC configuration on the HMI HV/Gateway.

220 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 13
HMI Mirroring

IEC202100552 V1 EN-US

The solution is:

• configure HMI HV as mirroring client in Project HV.


• configure HMI MV as mirroring server to this client.
• transfer the complete HMI MV data via ‘lof’ file from the MV project to the HV project and import
them into the “mirrored” HMI MV there (this needs to be repeated whenever signals are added
to the HMI MV that need to be sent to the NCC).
• (use the facility to put the internal signal text into the OX attribute - described in chapter "Import
a MicroSCADA ‘lof’ File" - to transfer also the internal signal text to the destination HMI).
• (In case of repeated ‘lof’ transfer: if you import the ‘lof’ file over the old configuration, signals will
be added and updated, but not deleted).
• mirror the desired signals from HMI MV to HMI HV so that they e.g. can be sent to the NCC.

13.5.6 Mirroring Across Two Projects With Restricted Data Exchange GUID-070205DB-F8BC-4199-A6AF-659E8CF90536 v1

Let us assume a situation similar to the one described in chapter "Mirroring Across Two Projects With
one Common NCC Gateway" above, but additionally the owner of the MV substation forbids us to
pass the full HMI configuration to the other owner/operator for security reason. He insists that he
wants to do a pre-selection of signals, and only those preselected signals are allowed to be passed
on to the other owner/operator.

Integrated Engineering Tool 221


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 13 1MRK500114-UEN Rev. X
HMI Mirroring

IEC202100553 V1 EN-US

Here, the best solution is to apply mirroring in both projects:

• configure HMI HV* as mirroring client in Project MV.


• configure HMI MV as mirroring server to this client.
• configure HMI HV as mirroring client in Project HV.
• configure HMI MV* as mirroring server to this client.
(Note the naming of HMI MV* and HMI HV*, both HMIs should have an identical signal
configuration on both sides; but from a customer/engineering point of view it is probably more
suitable to name them as proposed here).
• mirror the desired, restricted signals from HMI MV to HMI HV* in the MV project (this serves only
to restrict the signals transferred to the other HMI).
• transfer the HMI HV* data via ‘lof’ file from the MV project to the HV project and import them into
the HMI MV* there.
(use the facility to put the internal signal text into the OX attribute - described in chapter "Import
a MicroSCADA ‘lof’ File" - to transfer also the internal signal text to the destination HMI)
(In case of repeated ‘lof’ transfer: if you import the ‘lof’ file over the old configuration, signals will
be added and updated, but not deleted.)
• mirror the desired signals from HMI MV* to HMI HV so that they e.g. can be sent to the NCC.

222 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 14
NCC Gateway Engineering

Section 14 NCC Gateway Engineering GUID-C504347C-67C0-4E20-8061-10FED7AB4232 v1

14.1 Introduction GUID-3BFDDAE1-FC91-49AC-836C-E6EFF68A80E9 v1

NCC Gateway engineering refers to the engineering needed to exchange data between a Gateway in
a substation and a client outside of the substation, typically a regional or national Network Control
Center (NCC).

14.1.1 Supported Gateway Products GUID-461948A0-8B81-4C66-902A-0DEB6DB0F215 v1

Currently, IET600 provides full support to engineer MicroSCADA-based Gateways (COM500;


SYS600 MicroSCADA Pro and SYS600C with integrated Gateway).

IET600 provides limited support for RTU560 Gateways:

1. Signals can be mapped to a Gateway.


2. Specific command signals can be mapped to a Gateway to indicate that this command is to be
configured for NCC operation (the configuration itself is to be done in the Gateway Configuration
Tool).
3. No alarm groups can be configured.
4. No addresses can be configured and passed to the Gateway Configuration Tool.

14.1.2 Supported Gateway Protocols GUID-52E85B46-58C6-4765-B560-3C7996C91C4F v1

The following protocols between Gateway and NCC are currently supported:

• IEC101
• IEC104
• DNP 3.0
• 8-MMS

14.1.3 User Interface GUID-FC0A4FBC-9C0F-4071-8E0E-D9FC238D5F95 v1

To do Gateway engineering, you will use the following editors:

• ‘Signal Clients’: to configure signals to different NCCs, either directly or grouped.


• ‘NCC Offset’ and ‘NCC Data’ to configure attributes for sending signals to NCCs.

14.1.4 Prerequisites GUID-8494975C-519E-4A63-B6F9-1153212B50B6 v1

NCC engineering is a general term for the functionality needed to exchange data between the station
computer or gateway to clients outside of the substation, such as the Network Control Center (NCC).
To configure this data exchange, the data model of the IEDs in the system and the communication
(between the IED and station computer/gateway) must be defined.

14.2 Engineering Workflow GUID-C0C4A242-00A2-44A3-9879-BEACE82205FE v1

To configure this data exchange, the data model of the IEDs in the system and the communication
(between the IED and station computer/gateway) must be defined.

Note that all gateways (except COM500) are treated as IEDs and require an import
of an ICD file to generate the IEC 61850 structure.

Integrated Engineering Tool 223


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 14 1MRK500114-UEN Rev. X
NCC Gateway Engineering

The following steps are required for engineering of the gateway for one NCC connection:

1. define Gateway devices and data connection to NCCs (e.g. single connections, hot standby
configuration).
2. define data points or signals which are to be sent to the NCC, including conditions for
transmission.
3. define grouping of data signals.
4. configure protocol-specific information (addressing information, data type mapping, etc.).
5. export signal list (if needed for customer discussions or verification).
6. export device-specific configuration files.

One important goal of NCC engineering is to provide the customer with a list of data points which will
be delivered to the NCC. This list is normally required at an early stage in the project and should be
consistent with the final engineered system.

For more than one NCC, IET provides support to copy or duplicate the configuration data from one
NCC to reuse for other NCC connections (e.g. 2 redundant gateways with identical configuration).

14.3 Creating and Configuring Gateways GUID-94669785-73E0-4256-8516-07CE60AE1014 v1

14.3.1 Overview GUID-8FE49583-00E7-42D6-9ED3-8875B2C79AC4 v1

The Gateway or Proxy device must be defined in the HMI Navigation pane. There are two types of
Gateways:

• A stand-alone Gateway
• A Gateway with integrated HMI

Note that the communication configuration of the Gateway (e.g. the Subnetwork to
which the Gateway belongs) may need to be defined separately in the
Communication navigation tab.

Two types of Gateway nodes are supported:

• a single Gateway
• a hot standby (HSB) Gateway

A Hot Standby (HSB) configuration is a cluster of several Gateways or NCCs that are redundant and
have identical HMI Signals, but different communication configurations. Devices which are defined in
a HSB configuration will be treated as one device in the NCC Data Editor.

The following icons are used in the HMI navigation tree to represent the various HMI and Gateway
types:

Icon Description
Stand-alone HMI

Stand-alone HMI, linked

Hot-Standby HMI

Hot-Standby HMI, linked

Table continues on next page

224 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 14
NCC Gateway Engineering

Icon Description
Stand-alone Gateway

Stand-alone Gateway, linked

Hot-Standby Gateway

Hot-Standby Gateway, linked

Stand-alone NCC

Hot-Standby NCC

14.3.2 Create a Stand-Alone Gateway GUID-6F209EA6-8D97-4F9B-8F6D-8AFF958D193A v1

A Gateway can be created from the HMI tab in the Main menu.

IEC202100705 V1 EN-US

It can also be created from the context menu of several Navigation Tree objects:

Integrated Engineering Tool 225


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 14 1MRK500114-UEN Rev. X
NCC Gateway Engineering

IEC202100554 V1 EN-US

The details are as described in chapter "Create a Gateway combined with HMI". The configuration of
OPC servers running on HMIs of defined types (e.g. MicroSCADA) is also described there.

14.3.3 Create a Gateway combined with HMI GUID-0AAE5F84-7533-499F-B6EF-7C2E10A94CC1 v1

Combined HMI/GW IEDs need to be defined under both the HMIs and the GWs / Proxies element of
the HMI navigation tab.

1. Select the HMIs Navigation Tree and select an existing HMI or Hot Standby (HSB) HMI device.
2. Drag and drop the HMI device (e.g. HSB12/13) onto the GWs / Proxies element.

226 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 14
NCC Gateway Engineering

IEC202100555 V1 EN-US

3. The HSB 12/13 device is now defined as a Hot-Standby Gateway.

14.3.4 Create a Hot-Standby (HSB) Gateway System GUID-9B97D4D9-CDA9-4ABC-ACDD-2184FFCCF4DA v1

1. Select the HMIs Navigation Tree and select the GWs / Proxies element.
2. Right-click it to open the context menu and select Create new HSB…

Integrated Engineering Tool 227


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 14 1MRK500114-UEN Rev. X
NCC Gateway Engineering

IEC202100556 V1 EN-US

3. Specify the name of the new HSB à click OK.

228 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 14
NCC Gateway Engineering

IEC202100557 V1 EN-US

4. The new HSB Gateway is now shown under the GWs / Proxies node.
5. Create two stand-alone Gateways as described in the previous sections.
6. Select the first Gateway device, drag and drop it into the HSB node.
7. Select the second Gateway device, drag and drop it into the HSB node.

14.4 Creating NCCs GUID-D5F48CF7-EE4E-409F-B7E5-79EF1DDFE0D9 v1

14.4.1 Overview GUID-5CBEA135-8329-41D8-B631-43DD43D3E4FC v1

An NCC device defines a remote client outside of the substation perimeter. Consequently, the NCC
node in the HMI navigation pane provides the client view within each Editor. For each NCC node,
one needs to define:

• the Gateway server(s) providing data to a particular NCC

Two types of NCC nodes are supported:

• a single NCC
• a hot standby (HSB) NCC

A Hot Standby (HSB) configuration is a cluster of two Gateways or NCCs that are redundant and
have identical HMI Signals, but different communication configurations. Devices which are defined in
a HSB configuration will be treated as one device in the NCC Data Editor.

14.4.2 Create a Stand-Alone NCC GUID-D400E7CA-CE6B-4D7D-A267-CCC9B4FD1D2F v1

A Gateway can be created from the HMI tab in the Main menu.

IEC202100558 V1 EN-US

It can also be created from the context menu of several Navigation Tree objects:

Integrated Engineering Tool 229


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 14 1MRK500114-UEN Rev. X
NCC Gateway Engineering

IEC202100559 V1 EN-US

14.4.3 Create a Hot-Standby (HSB) NCC System GUID-75FF1426-A193-4B31-9AB6-0FFCAED21814 v1

1. Select the HMIs Navigation Tree and select the NCCs element.
2. Right-click it to open the context menu and select Create new HSB….

230 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 14
NCC Gateway Engineering

IEC202100560 V1 EN-US

3. Enter the HSB name in the dialog and click OK.

Integrated Engineering Tool 231


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 14 1MRK500114-UEN Rev. X
NCC Gateway Engineering

IEC202100561 V1 EN-US

4. The HSB device is now created under the NCCs element.


5. Create two stand-alone NCCs as described in the previous section.
6. Select the first NCC a drag and drop it onto the HSB element.
7. Select the second NCC a drag and drop it onto the HSB element.

14.4.4 Hot-Standby(HSB) HMI synchronization GUID-6CF126CB-EB63-4FB9-88F8-9AD4EE5AB35E v1

In order to keep HMIs of an HSB in synchronization, follow the steps below.

1. Select Hot-Standby in HMIs tree.


2. Go to properties.
3. Change Value of Property HMI Synchronization to True:

232 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 14
NCC Gateway Engineering

IEC202100562 V1 EN-US

If HMIs of the HSB whose synchronization property value was just changed to True are not same in
terms of Access Points, a notification will be raised and changing the value will not be possible until
the differences between access points of both HMIs are fixed.

Setting value of HMI Synchronization to True comes with following consequences:

• Operations such as adding or deleting an access point in Configure IED dialog will be
performed on both HSB members. Let’s consider an example where HSB called hsb1 has two
connected HMIs: ‘hmi1’ and ‘hmi 2’, which are the same in terms of Access Points. The user
adds a new access point called ‘ExampleAP’ to ‘hmi1’ using the ‘Configure IED’ dialog. After
confirming the operation, ‘ExampleAP’ is added to both ‘hmi1’ and ‘hmi 2’.
• OPC server addition or removal is also performed on other HSB member.
• Renaming an OPC Server Name is only supported if the new name contains HMI name at the
beginning. E.g. User changes OPC Server Name from ‘AA3KF12OPC1’ to ‘AA3KF12OPC222’.
Corresponding OPC server on second HMI in the same HSB is renamed from ‘AA3KF13OPC1’
to ‘AA3KF13OPC222’.
• All ports settings are propagated to other HSB member
• Clicking Delete Content on one HSB member will affect both.

Integrated Engineering Tool 233


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 14 1MRK500114-UEN Rev. X
NCC Gateway Engineering

14.5 Connecting Gateways to NCCs GUID-F35AF54A-0F45-44CA-9ED7-D1A80D6C4C5F v1

14.5.1 Overview GUID-086654BC-AA1A-4C40-AA68-4268C8C1801D v1

Once the NCCs and Gateway devices have been created, the logical connection between these
devices can be defined.

An NCC can be connected to one Gateway only. A Gateway, however, can be connected to one or
several NCCs.

Possible Gateway and NCC configurations include:

• Single Gateway to single NCC


• Single Gateway to multiple independent NCCs
• Single Gateway to HSB NCCs
• HSB Gateway to single NCC
• HSB Gateway to multiple independent NCCs
• HSB Gateway to HSB NCCs

Connecting the Gateway to the NCCs in the HMI navigation tab specifies which data is available to
the NCCs, or in other words which Gateways send data to which NCCs. However, it does not specify
the physical or communication configuration of the Gateway and NCCs (e.g. if they belong to the
same network). The communication configuration has to be defined separately in the Communication
navigation tab.

14.5.2 Connect Gateway to NCC GUID-E667A457-1CD8-43D1-9599-21D8EC23E6A7 v1

1. Select a single or Hot Standby Gateway, drag and drop it into a single or NCC Hot-Standby
NCC.

234 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 14
NCC Gateway Engineering

IEC202100563 V1 EN-US

2. IET600 asks you immediately after dropping the Gateway to specify the physical connection
properties of the link between the Gateway access points and the NCC access points.
• For the case that you connect a single Gateway to a single NCC

Integrated Engineering Tool 235


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 14 1MRK500114-UEN Rev. X
NCC Gateway Engineering

GUID-173365BF-1E0C-4269-BD16-20C83D2807B5 V1 EN-US

• For the case that you connect a single Gateway to a HSB NCC

GUID-710AD42F-090A-4F17-A5F8-56C5F6FE4691 V1 EN-US

• For the case that you connect a HSB Gateway to a single NCC

236 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 14
NCC Gateway Engineering

GUID-7AB7C45D-291E-441E-9F97-D158828539FE V1 EN-US

• For the case that you connect a HSB Gateway to a HSB NCC

GUID-A787DC1A-BADF-442D-974F-4F254E257625 V1 EN-US

3. The Gateway now appears under the NCC node.

If you have a more complicated situation, e.g. a Hot-Standby Gateway to a Hot-Standby NCC, you
need to configure their Subnetworks yourself in the Subnetworks editor. It is best done immediately
after creating the Gateway-to-NCC links in the 'HMIs' tab.

If you work with MicroSCADA, you always should use Access Point name from S11 to S18.

Integrated Engineering Tool 237


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 14 1MRK500114-UEN Rev. X
NCC Gateway Engineering

14.5.3 IEC 101/104 Special Parameters GUID-DCA0DA0B-8C50-43BF-820B-9B84EABE142B v1

IEC101/104 protocol requires to specify the size of the Common Address of ASDU (1 or 2 bytes) and
of the Information Object Address (2 or 3 bytes).

As default, IET600 assumes a Common Address of ASDU size of 1 byte (allowing addresses of
1-255) and an Information Object Address size of 2 bytes (allowing addresses of 1-65535).

Historically, these address ranges were sufficient in most project. However, more and more
customers require the full range of addresses. To reconfigure these address sizes, please proceed
as follows:

1. Select the NCC IED (in the Substation, IEDs, or Communication Trees).
2. Open the Subnetworks Editor.
3. Click on Edit Addresses in the row with the Access Point of the NCC that needs the extended
address range -> the following dialog opens:

IEC202100565 V1 EN-US

Right-click in the row header to get the row context menu and click Insert new Row.
4. Add the following as needed (exact spelling is required):
• To set Common Address of ASDU to 2 byte size:
Address: 2
Address Type: CommonAddressOctets
• To set Information Object Address to 3 byte size:
Address Type: InformationObjectAddressOctets
Address: 3

The following dialog shows the above configuration:

238 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 14
NCC Gateway Engineering

IEC202100566 V1 EN-US

14.6 Selecting Signals for NCCs GUID-66F0B7DF-3538-472C-9FBE-4483824340D8 v1

14.6.1 Overview GUID-4ABF4DAF-19F5-400F-83FE-50BB20D73878 v1

Once the Gateway and NCC devices nodes have been created, the next step is to configure the
specific signals to be sent to the remote client in the 'Signal Clients' editor.

14.6.2 The Signal Clients Editor GUID-E3F53A9A-9819-46BA-8806-0E59923E8A20 v1

The 'Signal Clients' editor shows the station signals which are available to the Gateway and
connected NCCs. It provides the server view of the Gateway and shows:

• as rows: signals which are available from the process


• as columns: Gateway(s) and their associated NCCs, and columns for Signal selection and
grouping for each NCC:
• Sel (Select): type ‘x’ or double-click to assign a signal to a Gateway and NCC.
• Address: (configured automatically for 8-MMS / IEC 61850 protocol) enter any valid
address, either as an integer or as a structured 2-3 octet address (depending on the
NCC’s settings)
• Grp (Group): enter any identifying string to group signals. Signals with the same string in
the same NCC belong to the same group.
• GrpInd (Group Index): An automatically generated incremental number for each member
of the group. A positive number indicates a signal going to the process (downlink) and a
negative number indicates a signal going to the NCC (uplink).

Integrated Engineering Tool 239


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 14 1MRK500114-UEN Rev. X
NCC Gateway Engineering

IEC202100567 V1 EN-US

To view all available columns in the Signal Clients editor, click on the Column Chooser icon to
view all available columns.

The Signal Clients editor is empty when an NCC element is selected in the HMIs
navigation Tree.

14.6.3 Select Signals to Be Sent to NCC GUID-16D73ACC-C1A0-49C3-A88B-2C4C34FE10BC v1

1. Select any element in any Navigation Tree.


• If you select any element in the ‘Substation’ ‘IEDs’ or ‘Communication’ Tree, the signals of
all IEDs belonging to the selected element will be shown. This is useful if you want to
configure (or check the configuration of) all signals of a Bay to different Gateways/NCCs.
If you select the project in this tree, you will see all available signals and all available
Gateways and HMIs. This This is useful to give you an overview over the complete
configuration.
• If you select a Gateway in the ‘HMIs’ Tree, all signals of the project will be shown, and
only the selected Gateway. This is useful if you want to check the configuration of a single
Gateway and its NCCs.
2. Place an ‘x’ in the matrix under the column heading ‘Sel’ to assign a station signal to a Gateway
and NCC
3. These signals are now configured to be sent from the original IED to the Gateway and further to
the NCC.

14.7 Grouping Signals GUID-479A715C-15E0-45E7-8B9D-7D704FB9A084 v1

The grouping of signals is currently possible only for MicroSCADA Gateways.

Other Gateways, like RTU560 can have only direct signals mapped. As a workaround for command
signals (which need to be processed on the Gateway), specific signals can be mapped to the

240 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 14
NCC Gateway Engineering

Gateway. The proper configuration of these signals needs to be done in the respective IED
configuration tool.

14.7.1 Overview GUID-952FE2DC-EA1B-43DB-ACA9-57FA98892CEC v1

IET600 distinguishes 2 types of groups

• Indication groups (needed to configure group alarms)


• Command groups (needed, because typically commands need to be processed on the Gateway,
so all involved signals, including an optional feedback indication are grouped together)

Each group is identified by its name which must be unique within an NCC connection. All signals with
the same name in a 'Grp' column belong to the same group.

Within a group, IET600 distinguishes between:

• Downlink Signals (i.e. Signals exchanged between local IEDs and the Gateway, their GrpInd is
positive).
• Uplink Signals (i.e. Signals exchanged between the Gateway and the NCC, their GrpInd is
negative).

When configuring Groups, the uplink signals are created automatically when the first Group member
is created; they are deleted automatically when the last Group member is deleted.

14.7.2 Create an Indication Group GUID-0F61D3BA-59FC-4F6E-8B2B-4D8FDF14C896 v1

1. Select a suitable object in one of the Navigation trees.


Usually, a good idea is to first select a Bay to create/configure groups of signals within this Bay
(a typical example are alarms of switching equipment in a Bay).
When all groups within Bays are done, then select a Voltage Level or Substation to configure
group signals that span across several Bays (a typical example are communication equipment
alarms).
2. Select the first signal which you want to add to group.
3. Enter a group name under 'Grp' column (e.g. “Al1”) which does not exist yet.

IEC202100706 V1 EN-US

An uplink signal (e.g. Group Alarm 1 for NCC NCC51) is automatically generated by IET600.

Integrated Engineering Tool 241


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 14 1MRK500114-UEN Rev. X
NCC Gateway Engineering

The visibility of the uplink signal depends on the object selected in the Navigation
tree. While the other signals belong to a bay-level IED, the uplink signal belongs to
the Gateway. It will therefore only appear, if you have selected the Gateway in any of
the Navigation Trees. The only way to see all signals of a group is to select an
appropriate object in the ‘HMIs’ Tree.
4. Add more signals to this group by putting the same group name (e.g. “Al1”) into the group
column for other signals. They will be added to this group.
5. The ‘GrpInd’ column shows the index of the signal within the group, for the uplink signal, a
negative index is used.

Note that a signal does not need to be selected in the Sel column to be part of a
group. Selecting it in the Sel column will cause the signal to be sent to the NCC
directly.

Note that the uplink signal is initialized in a way that limits group signals to 240 (this
is a limitation of the ‘lof’ file used for data exchange with MicroSCADA). If you are
configuring more group signals into a group (which IET600 will allow you to do), you
will need to initialize the uplink signal in MicroSCADA with an appropriate command
procedure, otherwise the signals with GrpInd > 240 will not trigger the Group Alarm.

14.7.3 Create a Command Group GUID-4534E314-4E64-4ED5-A5BB-71F1ED2FE035 v1

For some command groups, a specific number of signals is required for proper functioning. IET600
supports this by collecting all required signals and creating a group, whenever just one signal is
selected.

The logic for collecting these groups depends on the gateway and on the protocol between Gateway
and bay-level IEDs. For a more detailed description, see chapter Annex: NCC Command Group
Logic .

To create a command group:

1. Select a signal suitable as command (one of the signal types listed above (e.g. Position
indication) and enter a group name in the ‘Grp’ column (e.g. “CC1”).

IEC202100707 V1 EN-US

2. IET600 will automatically find the remaining signals in the group and assign these also to the
same group (e.g. “CC1”).

242 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 14
NCC Gateway Engineering

If there is no suitable logic for assembling the group, it will behave like an indication group: The
group will be created with one command, you can then add additional command signals to this
group.
Please note that the visibility of the uplink signal depends on the object selected in the
Navigation tree. While the other signals belong to a bay-level IED, the uplink signal belongs to
the Gateway. It will therefore only appear, if you have selected the Gateway in any of the
Navigation Trees. The only way to see all signals of a group is to select an appropriate object in
the ‘HMIs’ Tree.

14.8 Copying a Configuration from an Existing NCC GUID-C096C719-CD29-42E0-B64D-A83ADCE58529 v1

14.8.1 Copy Full Signal Client NCC Configuration from Existing NCC GUID-516DA087-62D5-4181-9E36-B97E219D95E6 v1

It is possible to transfer the full configuration from an NCC to another NCC, provided the NCC
Gateway is the same type (e.g. from RTU560 to RTU 560 or from COM500 to COM500).

1. In the Gateway column headers, right-click in the NCC part of the destination NCC, then click on
Copy Configuration from ➤ -> a submenu with available NCC configurations will appear (if a
menu item is greyed out, it cannot be copied; e.g. because the Gateway is of a different type
that has an incompatible configuration).
(If the Copy configuration from context menu is disabled, the right-click was in an unsuitable
place -> make sure that you clicked in the NCC part as indicated.)

IEC202100804 V1 EN-US

2. Click on the desired source NCC in this context menu -> a dialog will appear, asking you for
confirmation (be aware that the current configuration of the destination NCC will be overwritten).

Integrated Engineering Tool 243


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 14 1MRK500114-UEN Rev. X
NCC Gateway Engineering

IEC202100805 V1 EN-US

3. If you confirm with Yes, the NCC configuration will be copied to your destination Gateway/NCC.
If the destination Gateway is also configured as an HMI, existing HMI signals will be preserved;
however, some HMI signals may be added, if required by the Gateway configuration (identical to
when you configure NCC signals manually on a combined HMI/Gateway).
4. If the copying is successful, no further confirmation is given (in case of an error, the standard
warning dialog appears telling you to check for warnings in the log). You can easily check the
result by selecting the GW/Proxies element in the HMIs Navigation tree and then sort on either
Sel or Grp/GrpInd column: the configurations in source and destination columns must match.

14.9 Configure NCC Data GUID-083DF525-6A1E-4ECD-B029-46C6CE392C30 v1

14.9.1 Overview GUID-10F962B0-124E-4291-B5E6-B07BAAD66BD0 v1

The NCC Data editor provides the functionality to configure the signal specific parameters at the
NCC.

14.9.2 NCC Data Editor GUID-A1F782C2-FAFF-436E-A06A-1D497B220656 v1

The NCC Data Editor is available from the HMI Navigation pane. The editor provides a filtered view
of the station signals which are available to the specified NCC only.

Note that the NCC Data Editor provides the “client” view to the Gateway. It shows the signals which
are mapped to the specific NCC only.

The editor shows on the left hand side the station signals which have been selected in the Signal
Clients editor. On the right hand side, the editor shows a matrix for configuration of the NCC signals.

244 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 14
NCC Gateway Engineering

IEC202100567 V1 EN-US

To view all available columns in the NCC Data editor, click on the Column Chooser icon to
view all available columns.

14.9.3 Configure NCC Signal Properties GUID-83295D15-FC03-40E0-A8BF-24BFB25502EA v1

The following sub-headings are available on the NCC Signal Properties section:

• Address (configured automatically for 8-MMS Protocol)


• Signal Handling
• Command Type
• Transmission Class
• Scale Name
• Send Trigger (default: OnChange, currently not used)
• IEC 61850 Reference (visible only for 8-MMS Protocol)

Note that only the white cells in the NCC signal properties columns are editable fields, meaning that
one can manually specify the attribute in the field. The grey cells are automatically defined by the
tool.

14.9.4 Configure NCC Addresses GUID-8A15719F-8A23-45E8-B89A-BFEB19207FBA v1

The functionality described in this section works for both the Signal Clients editor,
and the NCC Data editor.

NCC addresses are manually configurable, with the exception of NCCs using IEC61850 / 8-MMS, in
which case configuration is automatic.

Addresses can be displayed in two formats:

• Unstructured – address displays as an integer, ranging from 1 to:

Integrated Engineering Tool 245


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 14 1MRK500114-UEN Rev. X
NCC Gateway Engineering

• 65535 if the amount of octets is set to 2


• 16777215 if the amount of octets is set to 3

IEC202100569 V1 EN-US

• Structured – address displays as two or three octets, ranging from 0.0 to 255.255 or from
0.0.0 to 255.255.255.

IEC202100569 V1 EN-US

• The address field is not visible for 8-MMS / IEC 61850 NCCs.
• NCC12/13 (HSB) seen on the screenshots above is configured to 2 octet
addresses
• NCC14 seen on the screenshots above is configured to 3 octet addresses

Changing between the address display formats can be done by right-clicking on the column headers
in the Signal Clients editor or the NCC Data editor, then clicking Show Address in structured
format.

IEC202100571 V1 EN-US

The amount of octets can be set for each NCC individually, using the Edit Addresses button
accessible in the Subnetworks editor, then changing the value of “InformationOjectAddressOctets”. It
determines the amount of octets, meaning the available range of addresses described above.

246 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 14
NCC Gateway Engineering

IEC202100572 V1 EN-US

14.9.5 Data Model Generation for IEC 61850 Server GUID-A853104B-DC2C-47E0-9F3B-C01598AA350D v1

To generate a Gateway Data Model, IEC 61850 Reference values need to be configured first.

The default value of IEC 61850 References is copied from the Mapped To reference of the
corresponding signal. This value can be changed in the NCC Data editor and reverted to default
value from the context menu. Values can be set manually or using IEC 61850 Reference Creation
Dialog (for more information see "Annex: IEC 61850 Reference creation").

Custom values that override the default ones will be highlighted with a pale blue background.

List of some references that might be missing can be found in Annex: IEC 61850 Mapping.

IEC202100573 V1 EN-US

Addresses are automatically assigned to each item. They can be seen in the LN Data editor. When
configuration is complete, the user can Generate Gateway Data by right-clicking on the NCC’s
column header.

Integrated Engineering Tool 247


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 14 1MRK500114-UEN Rev. X
NCC Gateway Engineering

IEC202100574 V1 EN-US

Before the generation of Gateway Data Model validation is performed. All invalid signals will be
skipped and won’t be present in the final model.

GUID-81C3F00A-A095-4859-B522-BEF04D5F1ECB V1 EN-US

After successfully generating the Data Model (see application Output window), a new server will be
attached to the corresponding access point of the HMI(s) connected to the NCC.

IEC202100578 V1 EN-US

In case the configuration is changed, an indication will appear to let the user know that the currently
generated Gateway Data Model is not up-to-date and should be generated again.

248 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 14
NCC Gateway Engineering

IEC202100579 V1 EN-US

14.10 Merge NCC Data in MicroSCADA GUID-597CAEFF-6D9B-453C-80E1-49F8D2CD50DD v1

The engineering procedure described in this section applies only to IET600 5.3 FP1 or later and
HMIs/Gateways based on MicroSCADA 9.4 FP1 or later. It does not apply to other Gateways.

14.10.1 Introduction GUID-08291F5A-7F8D-48E4-8A22-A8C6E3A7D908 v1

Sometimes, a Substation contract is split into 2 IET600 projects. A typical example is a project of a
Substation which contains an HV part, operated by one utility, and an MV part, operated by another
utility. Often, these two projects have different timelines, owners etc. and are given to the vendor as
two different contracts.

We will assume the above situation. Additionally, we assume that an NCC connection is engineered
from a MicroSCADA in the HV substation, but which should also include information from the MV
part.

There are two ways to proceed with this:

1. Use mirroring as described in chapters "Mirroring Across Two Projects With one Common NCC
Gateway" or "Mirroring Across Two Projects With Restricted Data Exchange".
This is recommended under the following conditions:
• The engineers do not have extended experience in MicroSCADA engineering.
• At least the project on the MV side is fairly stable, no or very few changes are expected to
happen.

This is the more common situation, as typically, the NCC engineering is done late in the project,
when engineering on Substation level is more or less finished. This procedure is safer, because
the owner of the NCC connection has full control over the NCC engineering.
2. Use the engineering procedure described in the following chapter, where both projects are
engineered independently, but are merged only in MicroSCADA.
This is recommended only under the following circumstances:
• The naming of both Substation parts (MV and HV) are free of conflicts.
• The projects have many ongoing changes in HMI and/or NCC Gateway configuration.
• Both responsible project engineers cooperate well and have extended experience in
MicroSCADA engineering.
• No Alarm Groups containing signals from both MV and HV project are required.

This procedure may be more efficient in certain situations than the one above, but the risk of
unexpected conflicts is higher. It requires experienced engineers and a good co-ordination
between the projects to mitigate this risk to acceptable levels.

Integrated Engineering Tool 249


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 14 1MRK500114-UEN Rev. X
NCC Gateway Engineering

14.10.2 Engineering Procedure and Restrictions GUID-7114B917-38CB-4621-9852-309515E2AB53 v1

Basically, both projects are engineered independently. The data are transferred to MicroSCADA via 2
‘sasmsc’ file, where the ‘MIET’ Tool is used for import; both ‘sasmsc’ files are imported independently
of each other

IEC202100539 V1 EN-US

It is important that the two ‘lof’ files in both ‘sasmsc’ files do not contain any duplicate
signals, i.e. signals with the same LN and IX: the importing MIET is not designed to
handle such situations. If this condition is not adhered to, signal attributes may
unexpectedly overwritten; or signals may accidentally and unexpectedly be added or
deleted. In worst case, this can lead to an inconsistent Process Object Database or
NCC configuration in MicroSCADA.

14.10.3 Preparation of Projects GUID-5CCDBCF8-EBC9-40B4-9A07-5045274D136E v1

1. In both MV and HV project, create the HV MicroSCADA with its name.


2. From the very beginning of the project, define an appropriate naming scheme to avoid duplicate
LN:IX combinations for signals in the HV project and in the MV project.
When the two projects concern different voltage levels, using the ABB naming conventions
(where the Voltage Level appears in the LN) will ensure unique LNs this for all signals that are
related to primary objects and IED supervision signals for IEDs on Bay and Voltage Level.

However, special care must be taken for signals on Substation Level; these should
be mapped to the HV HMI only in the HV project, but not in the MV project. It is the
responsibility of the engineer to ensure uniqueness.
3. For the IEC 61850 Dataflow configuration, use OPC Servers Subnetworks with different names
in MV and HV projects.
As an example, use OPC Servers AA1OPC1, AA1OPC2 etc. and Subnetworks AA1WF1,
AA1WF2 etc. in the MV substation; OPC Servers AA1OPC5, AA1OPC6 etc. and Subnetworks
AA1WF5, AA1WF6 etc. in the HV substation.

250 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 14
NCC Gateway Engineering

14.10.4 Calculate the NCC Gateway Group Offset GUID-9ADB466E-D12C-4FE7-AC92-C9EBA084CB76 v1

While you can change the offset later in the project, it is recommended to set it correctly from the
very beginning. To calculate it, estimate the number of required NCC Command Groups and NCC
Alarm Groups in one project to calculate the offset for the other project:

1. For commands, add all the planned commands for all NCCs that will be connected to this
Gateway. E.g. if in project HV, you have 2 NCC connections, and 1 NCC will have 72 commands
(e.g. 10 Bays with 7 remotely operated Switches each + 2 Tap Changer Commands), the other
70 (e.g. 10 Bays with 7 remotely operated Switches, but no Tap Changer Operation), the
minimal offset to be set in the MV project is 72.
2. For Alarm Groups, take the biggest number of alarm groups to be sent to a single NCC (as each
NCC has signals with a different LN; groups need not be added across all NCCs). E.g. if in
project HV, you have 2 NCC connections, and 1 NCC will have 35 Alarm Groups, the other 30,
the minimal required would be 35.
3. Take the bigger of those two numbers (in this case 72) and add a considerable safety margin to
allow project changes and later expansion without having to change the offset. In this example,
probably an offset of 200 would be suitable.

14.10.5 Configure the NCC Gateway Group Offset GUID-E4EDD844-1847-4CE9-B746-A1EB0CE35028 v1

Use this offset only, when using ‘sasmsc’ files for Data Exchange in MicroSCADA, not when using
‘lof’ and ‘xref’ files.

After calculating the offset, as described above, configure this offset in one project, e.g. the MV
project. Leave it at 0 (the default value) in the other project.

1. In the Navigation Tree ‘HMIs’, in the ‘GWs/Proxies’ section, select a MicroSCADA Gateway or
MicroSCADA Hot-Standby system and right-click it ‑> the context menu for the element appears:

Integrated Engineering Tool 251


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 14 1MRK500114-UEN Rev. X
NCC Gateway Engineering

IEC202100584 V1 EN-US

2. Select Configure NCC Gateway Group Offset (if the menu is not visible, you have selected a
non-MicroSCADA Gateway) -> the following dialog appears:

IEC202100585 V1 EN-US

Enter an offset that is big enough to prevent overlapping of any NCC-relevant items.
3. After setting this offset, IET600 will automatically recalculate some attributes which are
automatically given when configuring NCC groups:
• NCC Alarm Group Uplink Signals will have the IX recalculated, beginning with the offset +
1 and continuing sequentially:
BNCCy_GRP:P1 -> BNCCy_GRP:P2001
BNCCy_GRP_AS:P1 -> BNCCy_GRP_AS:P2001
BNCCy_GRP:P2 -> BNCCy_GRP:P2002

252 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 14
NCC Gateway Engineering

BNCCy_GRP_AS:P2 -> BNCCy_GRP_AS:P2002


etc.
• NCC Command Group Uplink Signals will have their LN recalculated, beginning with the
offset + 1 and continuing sequentially:
BNCC_00001:P10 -> BNCC_02001:P10
BNCC_00001:P11 -> BNCC_02001:P11
BNCC_00001:P12 -> BNCC_02001:P12
BNCC_00002:P10 -> BNCC_02002:P10
etc.
• NCC Command Group TI attributes will have the offset added.
• NCC Indication Group TI attributes will not be modified, as they refer either to the number
of signals (on the Uplink Signal) or to the position within a bit string (on the Downlink
Signals)
This can be verified in checking the appropriate attributes in the HMI Data Editor.
4. Additionally, on the export of the Alarm Groups into [HMI]_xrefind.txt in the ‘sasmsc’ file, the Ag
attributes will not start at 1, but at offset + 1 (this is not visible in IET600 directly, but is only
calculated upon export).

Integrated Engineering Tool 253


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
254
1MRK500114-UEN Rev. X Section 15
Bay-level Gateway Engineering

Section 15 Bay-level Gateway Engineering GUID-A4CD5C8E-4D7F-4EFC-8F26-24296EB5EBBD v1

15.1 Overview GUID-118B3C87-D006-4F9C-B1E0-6411F45D6608 v1

IET600 supports the integration of all IEC 61850 bay-level gateways using the ICD/IID file of the
gateway (Bottom-up). The ICD/IID file contains the IEC 61850 model of the gateway itself as well as
an IEC 61850 representation of the connected devices. This file must be generated by the gateway
configuration tool and will be imported into IET600 for system engineering.

15.2 SPA-ZC40x GUID-527C3925-AAE2-4010-93D9-D6A0125C2444 v1

The CET for SPA-ZC40x is the configuration tool for the SPA/IEC 61850 gateway. Use CET to
configure and download the configuration of the SPA-ZC40x gateway and create a CID file. Please
refer to the CET for SPA-ZC40x manual for further information.

Integrated Engineering Tool 255


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
256
1MRK500114-UEN Rev. X Section 16
VLAN Engineering

Section 16 VLAN Engineering GUID-47830B1A-7F74-4F09-9693-6528A3F0FC94 v1

16.1 Introduction GUID-F39FCF1A-BF5D-4717-9C37-B6F86F6B45C3 v1

In IET600, you have two ways of engineering VLANs

• In VLAN Data Editor.


• In subeditor of CCD Editor called Ports VLANs.

Both editors contain the same data but calculation can only be triggered from VLAN Data Editor, on
the other hand, Ports VLANs subeditor allows to visualize calculated VLANs.

16.1.1 VLAN Properties GUID-6ACE8C40-D325-4B57-9500-54F09539D2B8 v1

In most cases VLAN management happens in switch belonging ports. Each port has several
properties that will be described in this paragraph.

The egress from a port of a switch is controlled by the 'port VLAN member set' (PVMS). It defines
from which VLANs this port will forward the frames, and if it sends them tagged or untagged. An
egress port sends the frame only if the PVID belongs to the port membership set PVMS. Thus, if no
port has been configured to be member of a certain VLAN, network traffic in this VLAN is dropped
inside the switch. Equivalence of PVMS in VLAN Data Editor are:

• VLAN IDs of GCBs (VLAN IDs used by GCBs)


• VLAN IDs of SVCBs (VLAN IDs used by SVCBs)
• Required Egress(VLAN IDs used by RCBs and other Signals)

The ingress from a port of a switch is controlled by port VLAN ID (PVID). It has a capability of tagging
a frame with its PVID but only in situation when a frame does not have any PVID assigned already.

A port can forward frames either tagged or untagged. If configured to forward tagged, the port sends
the frame without a change. If configured to forward untagged, the port removes the VLAN tag. In
this case frame receives first encountered PVID.

Modification of GCB and SVCB VLAN-IDs happens, as today in GCB and SVCB Data Tabs. Such
frames are getting tagged inside source IED and are entering switches with PVID already assigned.

16.2 VLAN Editor GUID-37FDC220-8B1B-49B5-8AE5-7D4355AB11B3 v1

The VLAN Data editor defines the parameters for configuration of switches and contains general
information about the port and related IEDs.

Integrated Engineering Tool 257


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 16 1MRK500114-UEN Rev. X
VLAN Engineering

Property Description
Connected IED Name Name of the IED that this port is connected to. If the cell
is empty, then the port is not connected to any IED with a
link.
AP Access point(s) assigned to this port.
Required Ingress The equivalent of PVID assigned to the port used for
tagging frames without any PVID.
VLAN IDs of GCBs The equivalent of PVMS dedicated to GCB frames
flowing through this port.
VLAN IDs of SVCBs The equivalent of PVMS dedicated to SVCB frames
flowing through this port.
Required Egress The equivalent of PVMS dedicated to RCBs and other
frames that are sent out without any PVID assigned(e.g.
SNMP).

Port Name Name of the port assigned in the IED Configuration


dialog.
Subnetwork Subnetwork assigned to ports Access Point.

IED Name Name of the IED that this port is assigned to.
IED Role Role of the IED that this port belongs to.
Protocol Protocol(s) of the port.
PVMS Added User-defined equivalent of PVMS added to PVMS result
of this port.
PVMS Result Concatenated values of VLAN IDs of GCBs, VLAN IDs of
SVCBs, Required Egress and PVMS Added cells.

Tagging Behavior on Egress Defines whether a tag of the frame should be kept or
removed. This cell is only enabled when port belongs to
an IED that is an end device and does not have any of
the following redundancy protocols: RSTP, HSR.
"KeepTag" is a default value.

VLAN IDs of GCBs, VLAN IDs of SVCBs and Required Egress are set to IEDs with
roles different than switch only in "virtual" manner so that user can see which IEDs
are source and destination of each VLAN. In real cases those properties are only
used by ports that belong to switches.

Addition feature of VLAN Data Editor is a refresh sign that appears on one of the following columns:

• Required Ingress
• VLAN IDs of GCBs
• VLAN IDs of SVCBs
• Required Egress

GUID-1C8DDF9D-A4C8-4BCA-9022-D242DEF2C713 V1 EN-US

This sign means that it is recommended to rerun VLAN Calculation due to changes in the following
areas:

• Removal or modification of a Control Block(GCB/RCB/SVCB Data Editors) or Signal that had


any clients configured.
• Modification of any client connection (Signal/RCB/GCB/SVCB Client Editors).
• Modifiaction of topology in CCD diagram.

258 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 16
VLAN Engineering

In addition, there is a possibility to show VLAN related values in hexadecimal numbers with
appropriate column header context menu item "Display switch configuration as hexadecimal".

16.3 VLAN Calculation GUID-0BF998E3-793A-4900-9550-3A520136D07E v1

Majority of VLAN Properties (Except PVMS Added and Tagging behavior on egress) can be only set
through a process called "Automatic Calculation".

Before Starting any VLAN Calculation it is highly recommended to meet following conditions,
otherwise results might be incorrect:

• There should be no Warnings or Errors in the CCD editor.


• All physical connections in CCD editor should be established.
• All IED Client and Senders should be physically connected.
• All Control Blocks should be assigned to correct Access Points, same for clients.

After proper configuration of a CCD diagram and meeting all of above conditions, there are only a
few steps left before calculations can be made.

Next step is to open VLAN Data Editor and hit "Automatic Calculation" button in upper right section of
the Editor and configure input values.

GUID-ECFABB03-9899-44CD-96B8-E1490402FB3F V1 EN-US

Here's a description of Automatic Calucation dialog settings:

GUID-3408AEDA-43D4-4855-9219-91B55086AE40 V1 EN-US

Integrated Engineering Tool 259


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 16 1MRK500114-UEN Rev. X
VLAN Engineering

1. "Calculate" setting defines whether VLAN would be calculated for relevant sections (GCBs,
SVCBs, RCBs and other signals). This setting might be helpful in situation where You only need
to recalculate VLAN properties for one of the sections e.g. When some GCB clients were
modified and recalculation is required but SVCBs and other stayed untouched.
2. "VLAN Range" setting defines a range of VLAN IDs that will be assigned during calculation.
Those values cannot overlap.
3. "Replace existing VLAN ID definitions" setting that is only used in GCB and SVCB section. It
defines whether VLAN-IDs defined in GCB and SVCB Data editors should be overridden by
values defined in "VLAN Range" or taken as reference for VLAN IDs used by Calculation
Algorithm.
4. "Display as hexadecimal/decimal" setting that allows displaying "VLAN Range" in different
numbering systems.

After running calculation process, details are logged in Diagnostic tab. When the process is finished
warning window will show up if any issue was detected during calculation.

After Successful calculation Editor should be filled VLAN-related data. To check correctness of the
result there is a possibility to visualize VLAN using CCD Editor.

To visualize VLAN You need to select CCD editor and its "Ports VLANs" subeditor, then You need to
set filter with VLAN that is desired to be seen on one of the following columns:

• VLAN IDs of GCBs


• VLAN IDs of SVCBs
• Required Egress

Then You need to select filtered cells to achieve Visualization in CCD. Example below:

GUID-927B36E2-64D9-401F-B22D-466D2767614F V1 EN-US

260 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

Section 17 Data Import/Export GUID-3D39E363-47DF-427B-A2B8-03F91ABD8E71 v1

17.1 ICD/IID File Exchange within a Project GUID-19CC4A3A-0DC4-4C71-9C79-49B2DADA7E84 v1

17.1.1 Import an ICD/IID File to Update IEDs GUID-9F75333F-D9BD-46DD-B9F7-3801EEBFBEBA v1

This can be done only from the context menu in the Navigation Trees, not from the Main menu.

1. Right-click on a Project, Substation, Voltage Level, Bay or IED ‑> the context menu appears.
2. Choose Update IED (from an IED context menu) or Update IEDs (from all other context
menus).

Proceed as described in "Updating IEDs".

17.1.2 Export an ICD/IID File GUID-C8E2F5FE-1F8F-44FB-9D0D-C683AE0125D2 v1

In the normal engineering workflow, this should never be needed, as per IEC 61850, a System Tool
should only export an SCD file including the complete configuration with all IEDs, it should not export
single IEDs.

In some few cases, legacy IED configuration tools had problems in importing a full SCD file, due to
XML errors, too big SCD files etc. Also for some support questions, it may be helpful to export only
one IED instead of a big SCD file. Only in such special cases, these IID/ICD files should be used;
they are to be understood as a workaround.

This export can be done only from the context menu of IEDs in in Navigation Trees.

1. Right-click on an IED ‑> the context menu appears:


2. Choose Export to SCL file... -> a ‘File Save’ Dialog appears.
3. Optionally adapt the filename.
4. Save the file.

The exported file will contain 1 IED with its DATA model and Dataflow; and it will also contain all
related Subnetworks with their Connected Access Points. A Substation Section will not be exported.

17.2 SCD File Exchange Within a Project GUID-E6142D03-447B-4CC6-BE94-F1F2507A2BAF v1

17.2.1 Import an SCD File to Create a Project GUID-A9CDB5FC-745A-4B78-8C4E-2F65E41587A2 v1

You can import a whole SCD file (including Substation and Communication structure) only once per
project. The idea is that an SCD file can be used as an initial starting point for a retrofit or extension
project.

After the first import, any additional SCD import will treat the SCD file as a collection of IEDs and
allow you to selectively import some or all IEDs.

An SCD file can be imported either from the Home menu or from the navigation tab.

1. Open a new project.


2. Select the Home menu tab and click on Import.

Integrated Engineering Tool 261


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

IEC202100592 V1 EN-US

3. Alternatively, from the context menu of a project in any Navigation Tree, select Import SCD File.

IEC202100593 V1 EN-US

4. The normal dialog for selecting a file appears. Select an appropriate SCD file and click Open.
The contents of the file will be imported without further confirmation.
5. Check the contents of the project after the import.
• If you choose the wrong SCD file or you are not satisfied otherwise, close the project
without saving. You will not be able to import another SCD file in this project, therefore it
would be no use to attempt to delete e.g. the Substation structure in the hope to import it
again from another SCD file.
• If you choose an ICD/IID file (probably by accident; an ICD/IID file will not make much
sense in this situation), you will probably find only one or several IEDs, but no Substation
structure. Again, close the project without saving; do not try to attempt any other way to
correct it.

For more information regarding SCL file security, consult Annex: SCL document security.

262 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

17.2.2 Import an SCD File to Update IEDs GUID-AE0FFB72-707D-4149-B28E-6E8A191411BC v1

This can be done only from the context menu of a project, not from the Main menu.

1. Right-click on a Project, Substation, Voltage Level, Bay or IED ‑> the context menu appears.
2. Choose Update IED (from an IED context menu) or Update IEDs (from all other context
menus).
3. Proceed as described in Updating IEDs.

17.2.3 Export an SCD File GUID-5747D866-480C-4D8E-ABD3-CF910C99CCAC v1

(This chapter describes and SCD file export for projects which contains either Edition 1 or Edition 2
IEDs only. For projects which contain both – so-called “mixed” systems – see chapter Export an SCD
File, Mixed Systems ).

An SCD file can be exported either from the Home menu or from the navigation tab.

1. Select the Home menu tab and click on Export.

IEC202100592 V1 EN-US

2. Alternatively, right-click on the project in any Navigation Tree and select Export SCD File from
the context menu.

Integrated Engineering Tool 263


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

IEC202100589 V1 EN-US

3. If the project is not mixed, a normal File save dialog appears. Select the directory where you
want to save the file and give it an appropriate name.
(If any SPAZC40x Gateways exist in the project, their Loadfiles will automatically be exported on
an SCD file export, they will be found in a subfolder named “SPAZC40x” to the folder the SCD
file is exported to.).
Under Save as Type in the File Save Dialog, you may have several options available:
• ‘SCL version 2003’ refers to an Edition 1-compatible SCL format (only available for Ed.1
projects).
• ‘SCL version 2007 Rev.B’ refers to an Edition 2-compatible SCL format.
• ‘SCL version 2007 Rev.B’ including Switch model will also export the DATA model of
Switches, although it is neither Edition-1- nor Edition-2-compliant.

This is only recommended if you need the Switch model to be included in the
SCD file.

For more information regarding Edition 1 and Edition 2 issues in general, see chapter Annex:
IET600 and IEC 61850 Edition Handling.

264 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

17.2.4 Export an SCD File, Mixed Systems GUID-B46EAD30-78B3-4417-92D3-7711AF4AD796 v1

(This chapter describes and SCD file export for projects which contains both Edition 1 or Edition 2
IEDs, so-called “mixed” systems. For projects containing only either Edition 1 or Edition 2 IEDs, read
Export an SCD File above).

An SCD file can be exported either from the Home menu or from the navigation tab.

Preliminary: check the allocation of IEDs to Subnetworks in the Communication Navigation Tree:

• IEC 61850 Subnetworks with only Edition 1 IEDs will show a small ‘E1’ in the icon.
• IEC 61850 Subnetworks with only Edition 2 IEDs will show a small ‘E2’ in the icon.
• IEC 61850 Subnetworks with mixed Edition 1 and Edition 2 IEDs will show a small ‘M’ in the
icon. These Subnetworks can only be exported into Edition 2 files and have some restrictions; in
a fully engineered project, they should be avoided as much as possible for compatibility
reasons.
• Non- IEC 61850 Subnetworks will not have any marker.

IEC202100590 V1 EN-US

1. Select the Home menu tab and click on Export.

Integrated Engineering Tool 265


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

IEC202100592 V1 EN-US

2. Alternatively, right-click on the project in any Navigation Tree and select Export SCD File from
the context menu.

IEC202100589 V1 EN-US

3. The following dialog appears:

266 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

GUID-8468896B-0810-4A7F-8149-BBDA9D7F4D31 V1 EN-US

For more details see "SCD Export".


4. Once you have made your choice, click ‘Export’ -> the appropriate files will be exported. Click
‘Cancel’ to close the dialog without exporting anything.
(If any SPAZC40x Gateways exist in the project, their Loadfiles will automatically be exported on
an SCD file export, they will be found in a subfolder named “SPAZC40x” to the folder the SCD
file is exported to.).

For more information regarding Edition 1 and Edition 2 issues in general, see chapter Annex: IET600
and IEC 61850 Edition Handling.

17.3 SSD File Import GUID-4E77B62B-075F-4D5F-89DD-39D6DC652E17 v1

17.3.1 Overview GUID-073B4E19-41A4-461F-AF47-1A19126E9019 v1

IEC 61850 allows a customer to specify a Substation via so-called SSD file (System Specification
Description). This was not used very much until now. However, some customers have discovered this
format and have started to provide specifications with an SSD file.

An SSD file can specify a Substation on at least 5 different levels of detail; each level must include
lower-level specifications:

1. Substation.
2. LN Mapping.
3. Data Type Templates (defining the details of an LN).
4. IEDs.
5. Communication.

You can import an SSD file only once per project. The idea is that an SSD file can be used as an
initial starting point for a retrofit or extension project.

Integrated Engineering Tool 267


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

17.3.2 Substation Specification GUID-02BC5931-559B-438E-A279-6CBDF4F492D5 v1

This is the lowest level. It essentially contains the information that a customer would otherwise
provide in a Single Line Diagram.

This can easily be imported into IET600. However, often the Substation Topology is not correctly
designed, the coordinate system does not match the one of IET600 etc.; usually the engineer needs
to invest some time to rearrange items.

17.3.3 LN Mapping Specification GUID-2F66D9C6-09EA-48CE-ACBB-2213C7D96F9B v1

Additionally to the specification of Substation containers and equipment, an SSD file can contain LN
Mapping.

This can be used to define required functionality; e.g.:

• by allocating a PDIS to a Bay or a Circuit Breaker, the customer specifies a Distance Protection.
• by allocating CSWI, CILO and XSWI, the customer specifies a remotely operated Disconnector,
while by allocation only an XSWI, he could specify a switch which can only be hand-operated.

This allocation can be used in IET600. However, as the unspecific LNs in the file may not match the
LNs of specific IEDs (e.g. CSWI1 in the SSD against SCSWI1 in an ABB REC670 IED), manual work
by the engineer is typically required to reuse this mapping.

17.3.4 Data Type Templates Specification GUID-E05A295F-76A7-4B02-85B4-0EBF5EE91BC6 v1

While LN mapping can be used to specify certain LNs, an LN itself is still not very well defined. As
many LNs contain very few mandatory, but many optional DOs and DAs, the implementation may
vary considerably from vendor to vendor.

By specifying Data Type Templates, a customer can define that he also wants certain optional DOs
and DAs for his project. The vendor must then ensure that his LNs match the specification of the
customer.

IET600 does not provide support for this comparison. A comparison in this case is difficult: the full
structure of the Data Type Templates needs to be manually checked. This can only be done by
persons thoroughly familiar with IEC 61850 and the Data Type Template Structure; it is not
recommended for the average engineer.

17.3.5 IED Specification GUID-160A331B-9A74-461F-AD97-839F3202E5C3 v1

By not only specifying Data Type Templates, but IEDs with a DATA structure, a customer can also
specify which functionality he wants to reside in which IED. A typical application of that would be the
case of two protection IEDs Main 1 and Main 2, where the customer could specify which IED
contains which protection functionality.

As with Data Type Templates, IET600 does not provide support for this comparison. In this case,
however, there is some possibility of comparison: import the SSD file into one IET600 project and
some actual IEDs into another project, and then compare their details manually, e.g. in the ‘LN Data’
Editor.

17.3.6 Subnetwork Specification GUID-06D3B891-40BD-446B-9854-65008725B1C9 v1

Using this last level, a customer could e.g. also specify communication addresses, e.g. IP
Addresses.

268 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

17.3.7 Import an SSD File GUID-F1A7C9D4-EBB2-4F67-B84C-5C4F8845EF41 v1

You can import an SSD file only once per project. The idea is that an SSD file can be used as an
initial starting point for a retrofit or extension project.

An SCD file can be imported either from the Home menu or from the navigation tab.

1. Open a new project.


2. Select the Home menu tab and click on SSD Import.

IEC202100592 V1 EN-US

3. Alternatively, from the context menu of a project in any Navigation Tree, select Import SSD File.

IEC202100593 V1 EN-US

4. The ‘Import SSD File’ dialog appears. Select an SSD file to open.

Integrated Engineering Tool 269


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

IEC202100594 V1 EN-US

5. Once you have selected the SSD file, IET600 will analyze it and show you a summary of its
contents. Select those levels you want to import (selecting a higher level will always include
lower levels):

IEC202100595 V1 EN-US

6. If you have made your choice, click Import -> the selected items will be imported into your new
project.

17.4 SED File Exchange Between Projects GUID-767A9FB2-5254-4571-9445-D2EE929DDF14 v1

17.4.1 Introduction GUID-E5836779-60D0-4034-85D9-84835D3CE425 v1

In certain situations, Dataflow configuration between two projects is needed; which means that two
System Configuration tools must exchange IED data and modify their Dataflow in a way that
preserves consistency.

To allow this, IEC 61850 defines a Data exchange between two System Configuration tools via so-
called SED file (SED stands for System Exchange Description).

To ensure that only one System Configuration tool can edit Dataflow (thereby ensuring consistency),
IEC 61850 specifies two attributes for each IED:

1. “Engineering rights” which can be:


• full (this is the normal state, DATA and Dataflow can be changed)
• Dataflow (only Dataflow can be changed)
• fix (neither DATA nor Dataflow can be changed)
2. “Owner”, which determines to which project an IED belongs.

270 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

The workflow is a bit complex. We will describe the following:

• Basic workflow for SED exchange ("Basic Mechanism")


• Pre-conditions for successful SED exchange ("Pre-Conditions for SED Data Exchange.")
• IET600 specific behavior and good engineering practices regarding SED Exchange ("IET600
behavior in SED Data Exchange." and "Good Engineering Practices in SED Data Exchange.")
• Example with detailed step-by-step guidance ("Example Transformer Interlocking via GOOSE" -
"Step 8: Re-Import of SED File into Project B")
• IET600 SED file contents ("IET600 SED File Content")

17.4.2 Basic Mechanism GUID-76426EC6-649D-4DAC-A16C-F551868A1599 v1

Based on the engineering rights and ownership defined in IEC 61850, IET600 implements a check-
out/check-in mechanism:

IEC202100596 V1 EN-US

IED owned by the project:

• Project A owns an IED A which has “full” engineering rights.


• Project A checks out IED A by exporting it into an SED file with “Dataflow” engineering rights.
• After checking it out, IED A has “fix” engineering rights in Project A, i.e. you cannot change its
DATA (via ‘Update IED’) or its Dataflow.
• After checking it back in (by importing an SED file containing these same IEDs), it has again
“full” engineering rights.

Foreign IED:

• Project B gets IED A with “Dataflow” engineering rights by importing an SED file.
• Project B changes the Dataflow in IED A.
• Project B checks out IED A by exporting it into an SED file, afterwards IED A has “fix”
engineering rights in Project B.

17.4.3 Pre-Conditions for SED Data Exchange. GUID-8AE68118-4F2E-43E6-B1F7-4EF4EA6E4E6D v1

An SED Data Exchange has some pre-conditions which should be checked before planning to use it
in the engineering process:

1. Ensure that there are no IED name conflicts.


If a project has an IED with the same name as an IED to be transferred from another project,
then an SED exchange is not possible!
This cannot be resolved by changing an IED name on the fly just for the data exchange,
because the IED name will also appear in real-time communication.

Integrated Engineering Tool 271


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

If possible, the name of one of the conflicting IEDs must be changed in its owning project.
However, if this happens late in the project, or – even worse – when configuring a Data
exchange between operating substations, this may result in a lot of unexpected reconfiguration
work.
(When using the ABB naming scheme, substations should therefore not always be named
“AA1”, but “AA1”, “AA2” etc.; at least within the substations of one customer or area. Otherwise,
a naming conflict is very likely).
2. Agree about a common Subnetwork for the Dataflow exchange between the projects.
To configure Dataflow, both sending and receiving IEDs must be on the same Subnetwork. As
IEDs can only be connected to Subnetworks via Access Points, the number of Access Points in
the IEDs participating in the SED exchange limits possible (re-)configurations.
3. Ensure that there are no IP-Address and MAC-Address conflicts.
For IT security reasons and to keep the amount of data transferred between projects small, not
all IP addresses or MAC addresses of a project will be provided in the SED file.
The engineer has to ensure that there are no conflicts. In case of conflicts, however, a
reconfiguration is typically quite simple.

17.4.4 IET600 behavior in SED Data Exchange. GUID-C413BBE6-F71F-4DFF-BE4C-6F0D56651D2C v1

IEC 61850 does not specify an SED change completely. To guarantee a safe exchange, IET600
implements some additional logic for SED Data exchange:

1. You can initiate only one export session at a time.


IEC 61850 would theoretically allow to open a Session X with Project B and a Session Y with
Project C at the same time. IET600 however, forces you to finish one session before opening
another.
2. When returning foreign IEDs which you have imported at an earlier time, you always need to
return all of them. IET600 does not allow you to return some and keep some others to do some
more changes.
3. IET600 currently does not import the Substation Section of a foreign Substation on SED import.
4. Already existing Dataflow items of foreign IEDs cannot be edited, only new Datasets and Control
Blocks can be added/edited.
5. IET600 allows to add own IEDs as clients for Control Blocks, however, you cannot change the
Control Block Parameters (e.g. addresses). If you need to do so, you need to add another
Control Block (which may use an existing Dataset, if it already contains the right data entries).
6. IET600 allows you, after user confirmation, to delete foreign IEDs, even though they have “fix”
engineering rights.

If such an IED has some Dataflow configured to your own IEDs, take any warning
dialog very seriously! Depending on the functionality of the configured Dataflow,
serious malfunction up to faulty or missing protection trips may result, if you
reconfigure your own IEDs without doing the necessary re-engineering of the foreign
IED which you are deleting.

Also, once you have deleted such an IED, you have lost the information what
functionality its Dataflow was providing; therefore you must note down all information
relevant for the necessary re-engineering before you delete the IED.

17.4.5 Good Engineering Practices in SED Data Exchange. GUID-F7CD81B9-49BF-4FE5-A5E8-758DE3FF2A3C v1

During SED export, the editing of your own IEDs is restricted. Also foreign IEDs, once imported,
cannot be deleted.

It is therefore strongly recommended to:

272 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

1. keep the period of SED Exchange as short as possible (e.g. do not initiate an SED exchange, if
the engineer from the other project tells you he will do the changes only in two weeks from now:
your engineering might be severely hindered by this.)
2. backup your database before starting the SED exchange (and preferably after each exchange
as well).

17.4.6 Example Transformer Interlocking via GOOSE GUID-F194B904-2AF1-464B-B84B-76FA3053FCB7 v1

Let's assume the following situation (the exact procedure will be described step by step in the
following chapters "Step 1: Export of an SED File in Project A" - "Step 8: Re-Import of SED File into
Project B"):

• a substation, where Vendor A engineers the HV part and Vendor B the MV part.
• the customer wants both vendors to implement switch interlocking across two Transformers with
GOOSE.
• the participating IEDs are IED A1 and A2 (the Control IEDs on the HV side) and IEDs B1 and B2
(the Control IEDs on the MV side).

The picture below demonstrates the workflow and shows the engineering rights in the projects after
each step (only one IED per project shown):

1. Engineer A exports IED A1 and A2 with Dataflow engineering rights to Project B.


2. Engineer B imports the SED file into Project B. During import, the IEDs will be added to the
Subnetwork as defined in the SED file; if the Subnetwork does not exist, it will be created.
3. Engineer B adds a Dataset/GCB to IED A1 and A2 each with the needed interlocking
information. He checks whether IEDs A1 and A2 are on the same Subnetwork as IEDs B1 and
B2; then adds his own IEDs B1 and B2 as clients to the new Dataset/GCBs.
4. Engineer B exports an SED file with IEDs A1 and A2 (engineering rights not important, IET600
always returns foreign IEDs with the same rights as it has received them) and IEDs B1 and B2
with Dataflow engineering rights.
5. Engineer A imports the SED file into Project A. During import, the IEDs will be added to the
Subnetwork as defined in the SED file; if the Subnetwork does not exist, it will be created.
6. Engineer A adds a Dataset/GCB to IEDs B1 and B2 with the needed interlocking information. He
configures IEDs B1and B2 to the same Subnetwork as IED A and adds his own IED A as client
to the new Dataset/GCB.
7. Engineer A exports an SED file with IED A and IED B (IED A is exported again to ensure that
engineer B has the up-to-date version of it; it may have changed between the last SED import
and this export).
8. Engineer B imports the SED file into Project B.

In the end, each project must have its own IEDs with “full” rights and foreign IEDs with “fix” rights, no
IEDs in either project must be “Checked out” any more.

Integrated Engineering Tool 273


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

IEC202100597 V1 EN-US

17.4.7 Step 1: Export of an SED File in Project A GUID-5ACDC354-B0C9-4606-A783-630B36426103 v1

Before starting the export, you should be in a situation that you can save the project after the export
(e.g. no changes which you want to throw away). To close the project without saving it after an SED
export will render the SED file invalid.

An SED export will initiate a “pending SED Transfer” with the receiving project. While
this transfer is pending, you cannot exchange another SED file with a third project.

1. In the Main menu, select Communication /SED Exchange /SED Export .


2. A dialog will open.
As an IED can be connected via different Access Points to several Subnetworks, select the one
that connects it to the Subnetwork to which you agreed during the preparation, because that
Subnetwork (and only that Subnetwork) will also be exported into the SED file.
Select the IEDs/Access Points for export and configure the engineering rights that you want to
give to the receiving project (“fix” if the other project is using your IED just as a RCB or GCB
client; “dataflow”, if the other project needs to create Datasets/Control Blocks in your IED.

274 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

IEC202100598 V1 EN-US

3. Select file path and name for export -> select Export, an SED file will be created:

IEC202100599 V1 EN-US

If you have already an open SED session, you will be prevented to export another SED file and
the following dialog will appear:

Integrated Engineering Tool 275


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

IEC202100600 V1 EN-US

4. In Project A, the IEDs transferred to Project B with Dataflow rights, have now “fix” rights in
Project A:
• ‘Update IED’ is not possible
• Dataflow changes, including adding clients, is not possible.
• Signal engineering, however, can be done as normal.

In the IED Status Editor, you can check the SED exchange in more detail by looking at the marked
columns:

IEC202100601 V1 EN-US

In the IED Navigation Tree, the exported IEDs are displayed with a red lock to indicate their checked-
out state:

276 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

IEC202100602 V1 EN-US

It is recommended to save the project immediately after SED export.

If you try to close the project without saving it, a warning dialog will appear:

IEC202100603 V1 EN-US

Integrated Engineering Tool 277


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

17.4.8 Step 2: Import of SED File into Project B GUID-E067649B-E9E1-439F-BCEB-1CA81C2575AA v1

Before importing an SED file, it is strongly recommended to back up your project.


After importing foreign IEDs and saving the project, it is not possible to remove those
foreign IEDs anymore; the only way to do so is to restore a backup from before the
import.

You should be in a situation that you can close the project after the import with or without saving.

An SED import will initiate a “pending SED Transfer” with project A. While this
transfer is pending, you cannot exchange an SED file with any other project.

1. In the Main menu, select Communication /SED Exchange /SED Import .


2. A standard ‘File open’ dialog appears. Select the SED file which you want to import -> the SED
file will be imported.
If you already have previously imported some IEDs, you will not be able to import the SED file,
the following warning dialog will appear:

IEC202100604 V1 EN-US

You will need to return those IEDs first (see chapter Step 4: Re-Export Foreign IEDs and own
IEDs from Project B), before you can import another SED file.
3. In Project B, the imported IEDs transferred from Project A appear in the IED Status Editor as
foreign IEDs and have either “dataflow” rights (those you need to edit) or “fix” rights (those that
have been transferred to resolve references in the SED file):

278 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

IEC202100605 V1 EN-US

In the Navigation Trees, the foreign IEDs appear dimmed and are displayed with a blue lock:

Integrated Engineering Tool 279


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

IEC202100606 V1 EN-US

Again, not only the two IEDs selected before, but also additional IEDs (those that were configured as
RCB Clients of any RCBs of the selected IEDs) can be seen. However, the Navigation Tree does not
show any difference between IEDs with “dataflow” or “fix” rights.

After SED import, check that you received the IEDs you need for the agreed-upon configuration. Also
check the Subnetwork configuration and ensure that it matches your expectations.

If all your expectation are met, save the project now. If not, then exit the project
without saving and request a correct SED file from the project A. If you save the
Project, you will not be able to delete any foreign IEDs anymore.

17.4.9 Step 3: Add Dataflow to Foreign IEDs in Project B GUID-48E8C839-6EDE-4C5A-B5BD-4F4EEB8365D2 v1

Engineer B can now add Datasets and Control Blocks as required to the imported IEDs and add
clients to them. This is not different from adding Datasets/Control Blocks to own IEDs as described in
chapter Dataflow Engineering.

280 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

17.4.10 Step 4: Re-Export Foreign IEDs and own IEDs from Project B GUID-FB4DF5B4-1087-4AA5-A6A3-A699208E6CA9 v1

Again, before starting the export, you should be in a situation that you can save the project after the
export (e.g. no changes which you want to throw away). To close the project without saving it after an
SED export will render the SED file invalid.

1. In the Main menu, select Communication /SED Exchange /SED Export .


2. A dialog will open.
Those foreign IEDs which have a “Pending SED Transfer” and “dataflow” rights will
automatically be selected for Export; they cannot be unselected
If required, select some own IEDs/Access Points for export and configure the engineering rights
that you want to give to the receiving project (“fix” if the other project is using your IED just as a
RCB or GCB client; “dataflow”, if the other project needs to create Datasets/Control Blocks in
your IED.

IEC202100607 V1 EN-US

3. Select file path and name for export -> select Export -> an SED file will be created:

Integrated Engineering Tool 281


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

IEC202100608 V1 EN-US

17.4.11 Step 5: Import of SED File into Project A GUID-26CE9D4C-0E17-4019-86FF-316F996E1C17 v1

You should be in a situation that you can close the project after the import with or without saving.

1. In the Main menu, select Communication/SED Exchange/SED Import.


2. A standard ‘File open’ dialog appears. Select the SED file which you want to import -> the SED
file will be imported.
3. In Project A, the re-imported own IEDs will have engineering rights “full”, they are not checked
out anymore.
The newly imported foreign IEDs from Project B have either “dataflow” rights (those you need to
edit) or “fix” rights (those that have been transferred to resolve references in the SED file):

IEC202100609 V1 EN-US

Check carefully whether the imported IEDs match your expectations. If so, save the
project now. If not, then exit the project without saving. If you save the project, you
will not be able to delete any foreign IEDs anymore.

282 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

17.4.12 Step 6: Add Dataflow to Foreign IEDs in Project A GUID-3C2068A2-E69C-42AE-ADB4-6FBCA8E0B5A6 v1

Engineer A can now add Datasets and Control Blocks as required to the imported IEDs and add
clients to them.

This is not different from adding Datasets/Control Blocks to own IEDs as described in Dataflow
Engineering.

17.4.13 Step 7: Re-export Foreign IEDs from Project A GUID-6FB765D5-7F03-4DDB-8DE5-7B4223B783C0 v1

Again, before starting the export, you should be in a situation that you can save the project after the
export (e.g. no changes which you want to throw away). To close the project without saving it after an
SED export will render the SED file invalid.

1. In the Main menu, select Communication/SED Exchange/SED Export.


2. A dialog will open.
Those foreign IEDs which have a “Pending SED Transfer” and “dataflow” rights will
automatically be selected for Export; they cannot be unselected
Your own IEDs A1 and A2 which you exported to project B earlier in step 1, should have their
final configuration. However, if you have done some changes of their DATA model, you might
want to pass them to project B again by selecting them and set the engineering rights to “fix” for
this export.
(The figure below shows only the IEDs to be exported, the other IEDs are filtered out)

3. Select file path and name for export -> select Export -> an SED file will be created:

Integrated Engineering Tool 283


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

IEC202100611 V1 EN-US

4. After this export, check in the IED Status editor.


No IEDs should have “Pending SED transfer” or be “Checked Out”.
All your own IEDs should have “full” IEC 61850 engineering rights.
All foreign IEDs should have “Foreign IEDs” and “Protected” checked and IEC 61850
engineering rights “fix”.

IEC202100612 V1 EN-US

If this is correct, the SED exchange is finished as far as project A is concerned.

17.4.14 Step 8: Re-Import of SED File into Project B GUID-5CB8AD39-35FA-47F7-B31B-089EA7CF2A79 v1

You should be in a situation that you can close the project after the import with or without saving.

1. In the Main menu, select Communication /SED Exchange /SED Import .


2. A standard ‘File open’ dialog appears. Select the SED file which you want to import -> the SED
file will be imported.
3. After this re-import, check in the IED Status editor:
No IEDs should have “Pending SED transfer” or “Checked Out” checked anymore.
All your own IEDs should have “full” IEC 61850 engineering rights.

284 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

All foreign IEDs should have “Foreign IEDs” and “Protected” checked and IEC 61850
engineering rights “fix”.
No additional foreign IEDs should appear anymore.

IEC202100613 V1 EN-US

Check carefully whether the imported IEDs match these expectations. If so, save the project
now, the SED exchange is finished as far as project B is concerned. If not, then exit the project
without saving.

17.4.15 IET600 SED File Content GUID-7CAB1689-806B-4C0E-BC99-957735ED83CE v1

IET600 tries to keep the amount of data exchanged via SED file as small as possible:

• a project should not be cluttered with unnecessary foreign IEDs, but should contain only IEDs
relevant for the desired communication.
• Communication data are IT-security-relevant, therefore only the needed communication data
should be exchanged.

However, IEC 61850 also demands that all references in an SED file are resolved, i.e. an IED must
e.g. contain IEDs that appear as Control Block clients.

To fulfill both above-mentioned requirements, an SED file exported by IET600 contains the following
items:

• selected IEDs with their full DATA, Dataset and Control Block configuration, except that GCB
clients and SVCB clients will be removed (unless the client IEDs are also selected to appear in
the SED file).
• all RCB clients referenced by any of the above IEDs (they cannot be removed, because the
sequence of RCB clients is relevant and needed, if the receiving project wants to add some of
its own IEDs as RCB clients); however, their DATA model will be stripped down to an absolute
minimum.
• all Subnetworks, to which the selected IEDs/Access Points are connected.
• all IP Addresses for the selected IEDs/Access Points connected to those Subnetwork.
• GCB and SVCB address information for GCBs/SVCBs connected to this Subnetwork (required
for a valid and consistent configuration of additional clients for these Control Blocks).
• a Substation section with all Bay and their respective Equipment, if the IED belongs to this Bay.

Integrated Engineering Tool 285


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

17.5 HMI Status Texts Exchange GUID-FE8716C2-1617-4C88-B265-FA77F17CA50C v1

17.5.1 Format of Status Text Files GUID-6B3EE28A-80FC-43C9-A6C7-818B8CAB0ABC v1

Status Texts can be exchanged with other tools via text files in ‘csv’-format. Translations into different
languages are kept in different files, so each file contains texts of only one single language.

The file name must have the format [filename].[language code].csv with the following specifications:

[filename] can currently be freely chosen; it is recommended to use “StatusTexts” to distinguish it


from other files following a similar naming pattern (e.g. “SignalTexts”).

[language code] must be a two-letter language code according to ISO 639-1. The tool will recognize
capital letters “EN” instead of “en” although it is not according to ISO 639-1.

“csv” as extension.

One line of the file must contain the following information:

1. A key to identify a set of Status Texts.


2. The type of the signal (AI for “analogue input”, AO for analogue output etc.).
Value is empty in case of not fixed number of process values.
3. A set of process values. They can be specified in two different ways:
• Plain number represents a set of continuous values from 0 to the number minus one, e.g.
a double binary value will have a “4”, representing the consecutive values 0, 1, 2 and 3
• Set of numbers in vector format to represent an irregular sequence of numbers, e.g. “(0, 5,
6, 10, 100)”
4. A sequence of status texts, their count must match the count of the process values (e.g. if the
process values are specified by a number “4”, there must be 4 status texts “intermediate”, “on”,
“off”, “faulty”.

Items 1, 2, 3, and each text under 4 must be separated by a “;”. The line must not be terminated with
a “;” .

Texts must not start or end with delimiters such as " or " (such characters will be interpreted as
belonging to the texts, not as delimiters).

The file must also contain a header with defined information. Any file not following the above
specifications cannot be imported.

A default file with English status texts, as well as the command procedures scripts to import and
export these texts into MicroSCADA, are provided with the IET600 baseline installation. These files
can be found at:

C:\Program Files\HITACHI\IET 5.x.x\SADesigner\ApplicationTemplates\HMI-\StatusTexts.

17.5.2 Import Status Texts GUID-AFC4F91B-18D2-483A-85A7-7DD7866B97FE v1

Status Texts can only be imported from the Main menu:

1. Select the ‘HMI’ tab in the Main menu.


2. Click Status Texts in the ‘Import’ group -> the ‘Import Status Texts’ dialog appears (the default
path is the subdirectory “Import” in your local project path).
3. Select one or more Status Text files (typically named “StatusText.[language code].csv.
The part [language code].csv is mandatory; a file with a different name cannot be imported.
You can select several files in different languages to import Status Texts in several languages at
the same time.
4. Click Open -> the files are imported.

286 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

If the import succeeds, you will not get any feedback directly. If something goes wrong, an error
message will appear.

If you have HMI signals without Status Texts but with valid Status Text keys (e.g. EH attribute for
MicroSCADA signals), Status Texts will be added in the HMI Signal Editor immediately after import.

A Re-Import of a Status Texts file will add new Status Texts and will overwrite Status Texts that have
changed, but it will not delete existing Status Texts that may not exist in the imported file.

17.5.3 Export Status Texts GUID-A3DE0173-939E-449D-A7F7-130BB34A992D v1

Status Texts can only be exported from the Main menu:

1. Select the ‘HMI’ tab in the Main menu.


2. Click Status Texts in the ‘Export’ group -> an ‘Export Status Texts’ dialog appears (the default
export path is the subdirectory “Export” in your local project path).
3. Choose a basic name (“StatusTexts” is recommended and may become mandatory at some
point in the future).
If you have status texts in different languages, they will be exported as “StatusTexts.en.csv”,
“StatusTexts.de.csv”, “StatusTexts.fi.csv” etc. Files with those names in the export directory will
be overwritten,
4. Click Save -> the files are exported.
If the export succeeds, you will not get any feedback directly. If something goes wrong, an error
message will appear.

17.6 HMI Signal Information Exchange GUID-2AEB7BD3-4C25-4667-84F1-147C3E9B08CF v1

17.6.1 Overview GUID-2BD5000B-6C14-46A0-8780-4645833F4B57 v1

There is no standard describing how to exchange Signal Texts and other HMI-related information via
SCD file. So the tendency is to exchange these data in additional files, with references to IEC-61850
objects.

Currently, HMI information can only be exchanged with MicroSCADA in specific formats:

• ‘lof’ file
• ‘sfx’ file
• ‘csv’ file in a MicroSCADA-specific format.
• ‘sasmsc’ file (available for MicroSCADA 9.4, FP1 and higher)

For information about additionally exchanging Gateway/NCC information, see chapter NCC Gateway
Signal Information Exchange.

17.6.2 Exchange File Formats GUID-F0C15AAC-CB98-4ED7-AA25-B4A30C88D890 v1

‘lof’ stands for Loadfile. It is a MicroSCADA-specific format and contains information for the
MicroSCADA Process Object Database. The data are saved in a (badly) human-readable text file. It
is currently the default format to export HMI Data from IET600 to MicroSCADA. Its usage is
recommended in the following situations:

• In a retrofit project, if you do not have an IET600 project, but only a running MicroSCADA 8.x (or
an up-to-date ‘lof’ file) with or without an SCD. This ‘lof’ file can be used to import the existing
signals from MicroSCADA into IET600. Before the import, you should have configured your IEDs
and done the LN mapping (this will be used by IET600 to automatically map signals on import).
• To exchange data with MicroSCADA 8.x. In this case you are sure to have valid IN attributes for
the mapping of the data.

Integrated Engineering Tool 287


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

‘sfx’ stands for Safe Exchange. The format is basically the same as for ‘lof’ files, but an ‘sfx’ file
contains only attributes that are considered “safe” (see chapter 19.2.8, HMI Engineering Protection,
for more detailed information). Its usage is recommended in the following situations:

• In late project phases, e.g. commissioning, to be able to respond to customer requirements like
changed texts, event listings etc. while ensuring that no communication-relevant configuration is
changed.

‘csv’ is a generic format; however, MicroSCADA exports signals in a hierarchical file structure with
one file being the master file containing the file names of the other files, and additional ‘csv’ files –
one per signal type – containing the actual signal information. Its usage is recommended in the
following situations:

• In a retrofit project, if you do not have an IET600 project, but only a running MicroSCADA 9.x (or
up-to-date ‘csv’ files) with or without an SCD. These ‘csv’ files can be used to import the existing
signals from MicroSCADA into IET600. Before the import, you should have configured your IEDs
and done the LN mapping (this will be used by IET600 to automatically map signals on import).
• To import HMI Data from MicroSCADA 9.x into IET600. In this case you are sure to have valid
IN attributes for the mapping of the data.

‘sasmsc’ stands for SAS MicroSCADA. It is a format to export the complete data required to
configure OPC Servers, the MicroSCADA Process Object Database, OPC DA Clients and NCC
signals for one MicroSCADA-based HMI or Gateway within one file.

The ‘sasmsc’ file is a ZIP-format file which contains internally the following files:

• A System Identifier file which contains basic information about the System to be configured and
the content of the ‘sasmsc’ file.
• optionally an SCD file (required for OPC Server configuration).
• ‘lof’ file for one HMI (required for MicroSCADA Process Object and OPC DA Client
configuration).
• ‘xref’ files for one Gateway (if it is a MicroSCADA with Gateway functionality).
• Status values Text files for the ABB Standard and customer languages.
• Additional files providing information for OPC Server configuration (e.g. Disturbance Recording).

Its usage is recommended in the following situations:

• To exchange data with MicroSCADA 9.4 FP1 and higher.


• To transfer data from MicroSCADA to IET600, the above-mentioned formats needs to be used.

17.6.3 Import Behavior of IET600 GUID-A2A4C005-EF52-4CD7-A26D-19D39FB70552 v1

On import, the user must always specify the Target HMIs, to which these files with HMI information
belong.

IET600 will use the MicroSCADA IN attribute (which contains typically the IED name) to attach the
imported signals to IEDs and then map them to the Target IED.

If an IN does not exist or if there is no IED with the same name as in the IN reference, the signals are
attached to the target HMI directly (this is typically the case for so-called “internal” signals). The
engineer may need to shift them from the target HMI to the proper IED manually.

The MicroSCADA Database file import can use files of type ‘lof’ (with or without ‘xref’ files), ‘sfx’, ‘csv’
or ‘sasmsc’ (with or without ‘xref’ and SCD files).

‘lof’ files and ‘csv’ files will always update existing signals and add new signals; no signals will be
removed. If a Gateway/NCC configuration exists, ‘xref’ files should always be imported together with
the corresponding ‘lof’ files to ensure consistency.

288 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

‘sfx’ files contain only attributes that are considered “safe” (see HMI Engineering Protection, for
detailed information about what is considered to be safe in this context). An ‘sfx’ import will only
update existing signals, it will neither add nor remove any signals.

‘sasmsc’ files will act like a ‘lof’ file import; additionally, the Disturbance Recording information will be
updated from information contained in the ‘sasmsc’ file. Any SCD file contained in the ‘sasmsc’ file is
disregarded, as the danger of interference with the current configuration is too high (accordingly, it is
the responsibility of the engineer to ensure that the IET600 SCD DATA model is matching the one in
the SCD file).

17.6.4 Import Considerations GUID-DC28754D-0F74-4FD1-ABEA-7DCBDFAC5B03 v1

During normal engineering, HMI Data engineering should always be done in IET600 and exported to
MicroSCADA.

However, there are certain specific situations where a MicroSCADA file import is necessary:

At the start of a project, if you do not have an IET600 project, but only a running MicroSCADA 9.x
with or without an SCD. Before the import, you should have configured your IEDs and done the LN
mapping (this will be used by IET600 to automatically map signals on import).

To exchange data with MicroSCADA 8.x. In this case you are sure to have valid IN attributes for the
mapping of the data.

Late in project engineering, to transfer changes of ‘safe’ attributes which have been made directly in
MicroSCADA back to IET600.

17.6.5 Import a MicroSCADA ‘lof’ File GUID-18D30F3D-0C83-482F-A020-35F51230DBAD v1

A MicroSCADA Database file import can only be initiated from the Main menu.

1. Select the ‘HMI’ menu tab -> the ‘HMIs’ Navigation Tree is selected automatically.
2. Click MicroSCADA Database File(s) in the ‘Import’ group of the Main menu.

IEC202100623 V1 EN-US

3. The ‘Import MicroSCADA Database File(s)’ dialog appears. Click on the file selector button to
the right to choose a file for import:

Integrated Engineering Tool 289


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

IEC202100624 V1 EN-US

4. A ‘File Open’ dialog appears.


5. Select a ‘lof’ file.

IEC202100625 V1 EN-US

6. Select the HMI into which the ‘lof’ file will be imported.

290 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

IEC202100635 V1 EN-US

In case of a ‘lof’ import, you can also decide to import ‘Only Safe Attributes’ to simulate an ‘sfx’
import. This can be used in connection with MicroSCADA versions older than 9.3 which cannot
import/export the ‘sfx’ format yet.
The Tool Tip of this check box will show you which attributes are considered safe.
7. Click Preferences button to define MicroSCADA comparison preferences (see MicroSCADA
Comparison Preferences dialog for more details).

8. To preview the signals to be imported, click the Signal Overview button:

Integrated Engineering Tool 291


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

IEC202100628 V1 EN-US

Signals which are different will be marked; selecting such a signal will display the differences
(see Import Signal Overview for more details).
9. Click Import/Update Signals to start the file import (only enabled in the ‘Signal Overview).
10. The dialog will inform you how many signals have been imported to each HMI.
11. Repeat 3, 4, 5 and 6 for more imports from other files, if needed.
12. Click Close Dialog to close the dialog.

17.6.6 Import a MicroSCADA ‘sfx’ File GUID-7A820049-9D24-4C6D-AE82-6DC92D398047 v1

A MicroSCADA Database file import can only be initiated from the Main menu.

1. Select the ‘HMI’ menu tab -> the ‘HMIs’ Navigation Tree is selected automatically.
2. Click MicroSCADA Database File(s) in the ‘Import’ group of the Main menu.

IEC202100623 V1 EN-US

3. The ‘Import MicroSCADA Database File(s)’ dialog appears. Click on the file selector button to
the right to choose a file for import:

292 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

IEC202100624 V1 EN-US

4. A ‘File Open’ dialog appears.


5. Select an ‘sfx’ file.

IEC202100625 V1 EN-US

6. Select the HMI into which the ‘sfx’ file will be imported.

Integrated Engineering Tool 293


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

IEC202100626 V1 EN-US

In this case, the ‘Only Safe Attributes’ is mandatorily checked. The Tool Tip of ‘Only Safe
Attributes’ check box will show you which attributes are considered safe.
The ‘Import XRF Files is mandatorily unchecked, as anything related to XRF files is not
considered a ‘safe’ import.
7. Click Preferences button to define MicroSCADA comparison preferences (see MicroSCADA
Comparison Preferences dialog for more details).

IEC202100627 V1 EN-US

8. To import the signals, or to preview the signals to be imported, click the Signal Overview
button:

294 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

IEC202100628 V1 EN-US

Signals which are different will be marked; selecting such a signal will display the differences
(see Import Signal Overview for more details).
9. Click Import/Update Signals to start the file import (only enabled in the ‘Signal Overview).
10. The dialog will inform you how many signals have been imported to each HMI.
11. Repeat 3, 4, 5 and 6 for more imports from other files, if needed.
12. Click Close Dialog to close the dialog.

17.6.7 Import a MicroSCADA ‘csv’ File with Process Object Data GUID-76E54C9B-5C2A-40FD-93C8-4DFCB9997A0F v1

The import of MicroSCADA ‘csv’ files is limited to those containing the configuration of the
MicroSCADA Process Object Database.

A MicroSCADA Database file import can only be initiated from the Main menu.

1. Select the ‘HMI’ menu tab -> the ‘HMIs’ Navigation Tree is selected automatically.
2. Click MicroSCADA Database File(s) in the ‘Import’ group of the Main menu.

IEC202100623 V1 EN-US

3. The ‘Import MicroSCADA Database File(s)’ dialog appears. Click on the file selector button to
the right to choose a file for import:

Integrated Engineering Tool 295


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

IEC202100624 V1 EN-US

Select ‘csv’ file, then select the ‘csv’ Master file, (“TEST.CSV” in this example, the dependent
files must be in the same folder):

IEC202100625 V1 EN-US

To successfully import such ‘csv’ files into IET600, ensure that the following settings are used to
export the ‘csv’ files from MicroSCADA:

296 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

IEC202100631 V1 EN-US

To ensure consistency, make sure that all attributes are selected for export (configurable under
the Menu of this dialog -> ‘csv’ attributes -> if you have any other configuration, a ‘Reset’ should
achieve the desired result).
The Attribute Name Header is mandatory for data exchange between MicroSCADA and IET600.
A comma as delimiter is not supported. OI split is not supported.
4. Select the HMI into which the ‘csv’ file will be imported.

IEC202100626 V1 EN-US

In case of a ‘csv’ import, you can also decide to import ‘Only Safe Attributes’ to simulate an ‘sfx’
import. This can be used in connection with MicroSCADA versions older than 9.3 which cannot

Integrated Engineering Tool 297


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

import/export the ‘sfx’ format yet. (see "HMI Engineering Protection" for detailed information
about what is considered to be safe in this context).
5. To preview the signals to be imported, click the Signal Overview button:

IEC202100633 V1 EN-US

Signals which are different will be marked; selecting such a signal will display the differences
(see Import Signal Overview for more details).
6. Click Import/Update Signals to start the file import (only enabled in the ‘Signal Overview).
7. The dialog will inform you how many signals have been imported to each HMI.
8. Repeat 3, 4, 5 and 6 for more imports from other files, if needed.
9. Click Close Dialog to close the dialog.

17.6.8 Import a MicroSCADA ‘sasmsc’ File GUID-29130946-19EF-4382-97FA-9090FCB09BE5 v1

A ‘sasmsc’ file may contain an SCD file. However, the ‘sasmsc’ import will disregard
this SCD file because MicroSCADA should not modify it in any way. If you need the
information in this file, you need to extract the SCD file from the ‘sasmsc file and
process it manually.

A MicroSCADA Database file import can only be initiated from the Main menu.

1. Select the ‘HMI’ menu tab -> the ‘HMIs’ Navigation Tree is selected automatically.
2. Click MicroSCADA Database File(s) in the ‘Import’ group of the Main menu.

IEC202100623 V1 EN-US

3. The ‘Import MicroSCADA Database File(s)’ dialog appears. Click on the file selector button to
the right to choose a file for import:

298 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

IEC202100624 V1 EN-US

4. A ‘File Open’ dialog appears.


5. Select an ‘sasmsc’ file:

IEC202100625 V1 EN-US

6. Select the HMI into which the ‘sasmsc’ file will be imported.

Integrated Engineering Tool 299


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

IEC202100635 V1 EN-US

In this case, the ‘Only Safe Attributes’ is mandatorily unchecked.


7. Click Preferences button to define MicroSCADA comparison preferences (see MicroSCADA
Comparison Preferences dialog for more details).

IEC202100627 V1 EN-US

8. To import the signals, or to preview the signals to be imported, click the Signal Overview
button:

300 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

IEC202100628 V1 EN-US

Signals which are different will be marked; selecting such a signal will display the differences
(see Import Signal Overview for more details).
9. Click Import/Update Signals to start the file import (only enabled in the ‘Signal Overview).
10. The dialog will inform you how many signals have been imported to each HMI.
11. Repeat 3, 4, 5 and 6 for more imports from other files, if needed.
12. Click Close Dialog to close the dialog.

17.6.9 Import Signal Overview GUID-521A6C03-70D9-4D3A-A812-D339DEFE8190 v1

Signal Overview shows whether imported signal and signal in project are equal.

Every row in a list of signals can have in several states:

• signals do not have any differences (“Comparison” column has green background)
• imported signal does not exist in a project (“Comparison” column has gray background)
• signals have some differences (“Comparison” column has red background)
• signals have some differences, but all different attributes are excluded from comparison
(“Comparison” column has yellow background. “Import/Update” check box is in undefined state.
No data is presented in Difference view)
• signal attributes are different, but some of them are excluded from comparison (“Comparison”
column has red background. In Difference view presented only attributes which are included into
comparison)

Attributes excluded from comparison are not imported/updated into a project.

Integrated Engineering Tool 301


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

IEC202100637 V1 EN-US

For multi selected rows Difference View shows green cells for attributes without difference and red
for different ones:

IEC202100638 V1 EN-US

Also there is a possibility to create Excel document by exporting Difference View from context menu:

302 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

IEC202100639 V1 EN-US

17.6.10 MicroSCADA Comparison Preferences dialog GUID-61EB09A1-594D-4F11-90A8-A63BEE4F31EB v1

A dialog gives a possibility to choose which MicroSCADA attributes include to comparison.

User can check/uncheck Include Addresses to select address attributes at once and define own set
of attributes to compare.

After pressing Close Dialog button, Signal Overview list is automatically regenerated according to
current preferences.

IEC202100640 V1 EN-US

17.6.11 Export a MicroSCADA ‘lof’ File GUID-57A2ACD6-3D98-4323-B508-93501F5E5B6A v1

‘lof’ files can only be exported from the Main menu.

Integrated Engineering Tool 303


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

1. Select the ‘HMI’ menu tab -> the ‘HMIs’ Navigation Tree is selected automatically.
2. Click MicroSCADA Loadfile(s) in the ‘Export’ group of the Main menu.

IEC202100641 V1 EN-US

3. The ‘Export MicroSCADA DB Loadfile’ dialog appears:

IEC202100642 V1 EN-US

4. Select the HMIs whose HMI signals you want exported. For each stand-alone or each Hot
Standby System, one ‘lof’ file will be created.
For each file, the last known export folder and file name are preselected (the default is <Projects
Root Folder>\<Project Name>\Export\MicroSCADA\<HMI Name>). To change an individual path
and/or name click on the button in the ‘Edit Filepath’ Column in the same row. To rapidly change
several folder to the same value, change one, then right-click into the changed cell and select
‘Apply Export Folder Path to all/selected HMIs’ from the cell context menu.
5. Check ‘lof/xref’ as File Format.
Check ‘ABB Standard’ only if you want the OX attribute to contain the internal rather than the
customer signal text. This is mainly relevant when configuring mirroring between two projects
(see "Mirroring Across Two Projects With one Common NCC Gateway" and "Mirroring Across
Two Projects With Restricted Data Exchange").
Check ‘Backup old Loadfile’ if you want IET600 to create backups of older files with the same
name.
(If the MicroSCADA is a Gateway and has NCC connections, XREF files are exported
automatically to the same folder as the MicroSCADA ‘lof’ files)
6. Before the file is actually exported, a consistency check is performed (for more details see "HMI
Data Consistency Check") and the result is presented in a dialog:

304 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

IEC202100643 V1 EN-US

Errors will probably make an import into MicroSCADA impossible; you should not continue the
export, but correct the errors first.
Warnings are acceptable in earlier phases of engineering (if e.g. the engineering is not
completed yet, but a MicroSCADA Process Object Database is already needed for picture
engineering), but should be rectified before testing.
7. The dialog will stay open to allow you to export additional HMI configurations. After finishing all
exports, close the dialog.

17.6.12 Export a MicroSCADA ‘sfx’ File GUID-F24DAFF2-5097-48C1-952C-6B45E40015F1 v1

SFX files can only be exported from the Main menu.

1. Select the ‘HMI’ menu tab -> the ‘HMIs’ Navigation Tree is selected automatically.
2. Click MicroSCADA Loadfile(s) in the ‘Export’ group of the Main menu.

IEC202100641 V1 EN-US

3. The ‘Export MicroSCADA DB Loadfile’ dialog appears:

Integrated Engineering Tool 305


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

IEC202100642 V1 EN-US

4. Select the HMIs whose HMI signals you want exported. For each stand-alone or each Hot
Standby System, one ‘sfx’ file will be created.
For each file, the last known export folder and file name are preselected (the default is <Projects
Root Folder>\<Project Name>\Export\MicroSCADA\<HMI Name>). To change an individual path
and/or name click on the button in the ‘Edit Filepath’ Column in the same row. To rapidly change
several folder to the same value, change one, then right-click into the changed cell and select
‘Apply Export Folder Path to all/selected HMIs’ from the cell context menu.
5. Check ‘sfx’ as File Format.
Check ‘ABB Standard’ only if you want the OX attribute to contain the internal rather than the
customer signal text. This is mainly relevant when configuring mirroring between two projects
(see chapters "Mirroring Across Two Projects With one Common NCC Gateway" and "Mirroring
Across Two Projects With Restricted Data Exchange").
Check ‘Backup old Loadfile’ if you want IET600 to create backups of older files with the same
name.
6. Before the file is actually exported, a consistency check is performed (for more details see "HMI
Data Consistency Check") and the result is presented in a dialog:

IEC202100643 V1 EN-US

An ‘sfx’ file itself does not contain items which could cause errors or warnings. However, the
consistency check analyses the whole HMI Data configuration. An ‘sfx’ file export with errors or

306 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

warnings probably does not make sense, because it means that the HMI Data are not consistent
yet, whereupon an ‘sfx’ export is typically used in late project stages where consistent HMI Data
are mandatory.

17.6.13 Export a MicroSCADA ‘csv’ file with Process Object Data GUID-1FFC40BC-94A9-47C8-BA43-225EDE226124 v1

This is not possible. To transfer data from IET600 to MicroSCADA, only ‘lof’ files (or ‘sasmsc’ files
which include the ‘lof’ files) are available.

17.6.14 Export a MicroSCADA ‘sasmsc’ file GUID-A9677EAC-C90C-4C5A-AFE1-47292645C272 v1

When exporting an ‘sasmsc’ file, a new SCD file is generated within the ‘sasmsc’ file.
If this does not match the SCD file exported separately and passed to the IED
Configuration tool(s), this can result in communication problems which may be
difficult to detect!

When importing the file into MicroSCADA, the IET600 customer name is checked
against the computer name of the Target System -> as a prerequisite to the export,
please provide the customer name for those MicroSCADA System.

‘sasmsc’ files can only be exported from the Main menu.

1. Select the ‘HMI’ menu tab -> the ‘HMIs’ Navigation Tree is selected automatically.
2. Click MicroSCADA Loadfile(s) in the ‘Export’ group of the Main menu.

IEC202100641 V1 EN-US

3. The ‘Export MicroSCADA DB Loadfile’ dialog appears:

IEC202100642 V1 EN-US

4. Select the HMIs whose HMI signals you want exported. For each stand-alone or each Hot
Standby System, one ‘lof’ file will be created.
For each file, the last known export folder and file name are preselected (the default is
<Projects Root Folder>\<Project Name>\Export\MicroSCADA\<HMI Name>). To change an
individual path and/or name click on the button in the ‘Edit Filepath’ Column in the same row. To
rapidly change several folder to the same value, change one, then right-click into the changed
cell and select ‘Apply Export Folder Path to all/selected HMIs’ from the cell context menu.
5. Check ‘sasmsc with SCD’ as File Format, if you want to configure OPC Servers as well; this will
be the case in early project stages, and if the IEC-61850-Dataflow is changed.
Alternatively, check ‘sasmsc without SCD’ as File Format, if you want to leave the OPC Servers
untouched. This is e.g. recommended if you are configuring an NCC connection and want to

Integrated Engineering Tool 307


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

make sure that the local configuration between bay-level IEDs and OPC servers remains
untouched. OPC DA Client configuration files may be recalculated, depending on changes in the
Process Object Database.
Check ‘ABB Standard’ only if you want the OX attribute to contain the internal rather than the
customer signal text. This is mainly relevant when configuring mirroring between two projects
(see "Mirroring Across Two Projects With one Common NCC Gateway" and "Mirroring Across
Two Projects With Restricted Data Exchange").
Check ‘Backup old Loadfile’ if you want IET600 to create backups of older files with the same
name.
6. Before the file is actually exported, a consistency check is performed (for more details see "HMI
Data Consistency Check") and the result is presented in a dialog:

IEC202100643 V1 EN-US

Errors will probably make an import into the OPC Server Configurator or MicroSCADA
impossible; you should not continue the export, but correct the errors first.
Warnings are acceptable in earlier phases of engineering (if e.g. the engineering is not
completed yet, but a preliminary OPC Server configuration and/or a MicroSCADA Process
Object Database is already needed for picture engineering), but should be rectified before
testing.
7. The dialog will stay open to allow you to export additional HMI configurations. After finishing all
exports, close the dialog.

17.7 NCC Gateway Signal Information Exchange GUID-332CF2D9-ED5E-4161-A0B8-EC2A1A90F20A v1

17.7.1 Overview GUID-4040C261-BBBB-4B5C-92DA-2042D3D06D90 v1

Configuration exchange with the NCC Gateway is only supported for MicroSCADA COM500 or
SYS600C gateways. The following files are exchanged between IET600 and the COM500
configuration tool:

• COM_XRIND.XRF
• COM_XCMD1.TXT

308 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 17
Data Import/Export

The above files are imported and exported together with the MicroSCADA Loadfile(s), as described
in the previous section.

Note that while the Loadfiles can have different names per HMI, the name of these
cross-reference files are fixed and cannot be changed. Therefore you cannot export
several HMIs into one folder, as the cross-reference files would overwrite each other.

17.7.2 Import COM500 Configuration File (XRF) GUID-320E2D75-30E7-453B-8281-806FE2578D69 v1

The COM500 configuration files are always imported with the corresponding MicroSCADA ‘lof’ file.

An important task to be done before importing the COM500 files is to prepare the NCCs in the ‘HMIs’
Navigation Tree. The NCCs shall be defined in the order of the NCC line numbers in the COM500
file. Furthermore, the UN numbers of the NCCs must also be specified according to the file. IET600
will use these two references to correctly map the COM500 configuration to the correct NCC during
the import.

The COM500 files must be stored in the same folder as the MicroSCADA ‘lof’ file. So
e.g. to import this configuration into an HMI, the following files need to be present in
the folder:

• AA2KF14.LOF
• COM_XRIND.XRF
• COM_XCMD1.TXT

or

• AA2KF14.CSV (‘csv’ master file)


• AA2KF14_IX_BI.CSV
• … (more ‘csv’ files)
• COM_XRIND.XRF
• COM_XCMD1.TXT

To import the MicroSCADA ‘lof’ files, follow the steps described in chapter "Import a MicroSCADA
‘lof’ File". In the import dialog, select the check box ‘Import XRF files’.

Integrated Engineering Tool 309


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 17 1MRK500114-UEN Rev. X
Data Import/Export

Note that this checkbox will only appear, if the two XRF files are found in the same
folder as the selected ‘lof’ or ‘csv’ master file:

IEC202100646 V1 EN-US

17.7.3 Export COM500 Configuration File (XRF) GUID-AF3DC0D4-E9BF-468A-90A8-92CF16810DE3 v1

To export the COM500 signal configuration files, select ‘Export MicroSCADA Loadfile(s)’ from the
Main menu, ‘HMI’ tab (as described in the "Export a MicroSCADA ‘lof’ File"). The COM500 files will
be exported automatically to the same folder as the MicroSCADA Loadfiles.

Alternatively, for MicroSCADA 9.4 FP1 and newer, you can export an ‘.sasmsc’ file (as described in
"Export a MicroSCADA ‘sasmsc’ file"). If the MicroSCADA is a Gateway, the XREF files will
automatically be included in the ‘.sasmsc’ file

17.7.4 Export Configuration Data for Other NCC Gateways GUID-CE0BBC90-EA5C-446A-9D22-710408462808 v1

Currently, only the SCD file is available for other NCC Gateways. No specific signal configuration
files are available for other Gateways at this time.

310 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 18
Customer Signal Lists

Section 18 Customer Signal Lists GUID-B6897E87-2783-4E2B-8412-15BFA881CF1B v1

18.1 Introduction GUID-A439A1C5-76F5-4796-9242-162818C89758 v1

In any project, signal lists of some form need to be exported for discussion with the customer and as
documentation of a project. Unfortunately, each customer has his/her own idea of how these lists
should look like. IET600 allows you to customize such lists to a considerable extent to accommodate
customer’s requirements.

• IET600 provides a Default Template as a starting point with columns for all possible attributes
that can be exported.
• Either modify this default template, or – better – create a copy of this default template, give it a
sensible name and to the changes to this renamed template.
• You can customize a template by
• removing columns as suitable to adapt the exported attributes to customer requirements.
• defining grouping, filtering and sorting criteria to filter, group and sort the rows according to
customer criteria.
• saving one or several such configurations as customized templates in your project.
• You can export your data based on those templates and additionally customize the exported
workbook by adding formatting, e.g. by coloring group headers, changing the font and making it
bold etc.
• You can re-export your project data into the same Excel Workbook without losing such
customized formatting.
• You can ask the customer to make changes in those Excel Workbooks and import those
changes into IET600.

18.2 Customizing a Template GUID-004E1DCE-4B83-4819-9448-927D3D3FC6B7 v1

Before customizing a Template, please be aware of the following:

To allow a re-import of such customer lists into IET600, each column must be defined as a ‘Named
Range’ in Excel with a specific name. Therefore:

• You can change the text or colors of the headers, rearrange columns etc. Export and re-import
will work correctly, as long as the ‘Named Ranges’ are defined correctly.
• If you have accidentally removed a column which is designed for re-import, do not try to repair
this by copy/pasting an existing column and adjusting its header; but rather start with the original
template again.
• You can add additional columns with information which is not expected to be re-imported into
IET600, e.g. engineering/customer comments etc. Such columns can also be removed later. To
avoid confusion, it is recommended to mark these columns in a way which clearly distinguishes
them from the columns with ‘Named Ranges’.

18.2.1 Copy the Default Template into Your Project Folder GUID-BFE9EE89-06D6-4236-8AEE-91FDBCAE33F4 v1

1. The Default Template provided by IET600 is located in the Program Directory of IET600 (in
Windows 7 typically C:\Program Files (x86)\HITACHI\IET600\5.4.xxx\SADesigner
\ApplicationTemplates\Reports\TemplateSignalReport.xlsm).
Copy this Default Template (TemplateSignalReport.xlsm) into the ‘Reports’ folder in your project,
i.e. <Project Folder>\ApplicationTemplates\Reports\TemplateSignalReport.xlsm.
(The fastest way of doing this is to open the ‘Export Customer Signal List’ dialog once, this will
automatically copy the template into your project folder.)
2. If you intend to use more than one template, it is recommended to rename this template into
something more meaningful, e.g. “<Project> Report - HMI Signal List.xlsm”.

Integrated Engineering Tool 311


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 18 1MRK500114-UEN Rev. X
Customer Signal Lists

18.2.2 Customize the Template GUID-B759BF12-9C39-4A32-BE68-65A05A3D6576 v1

1. Open your Project Default Template (as prepared in "Copy the Default Template into Your
Project Folder" above).
2. Configure the ‘Title’ worksheet with general information about your project.
As this general information will probably be the same for all Customer Signal Lists for one
particular customer, you might want to save it now into TemplateSignalReport.xlsm before
deriving additional customized Templates from it.
3. Remove those columns you do not want in your customized Template.
4. Rearrange the remaining columns according to your needs (by using cut/paste for columns).

Excel does not allow to cut/paste columns, if they contain horizontally merged cells
(e.g. the first header row in the default template). In such cases, you need to
“unmerge” the cells, move the columns and the “remerge” the cells as desired.
5. Customize the column headers according to your needs (color, font, header text etc.)
6. Save the customized Template under a sensible name, e.g. “Signal Text - Event List - Alarm List
Configuration” into <Project Folder>\ ApplicationTem-plates\Reports.

Repeat the above for as many customized lists you want. You might want to configure Templates for
the following Signal Lists:

• Signal List with all MicroSCADA attributes for MicroSCADA documentation.


• Signal List with attributes that the customer might want to edit (e.g. Signal Texts, Alarm and
Event Listing, Printout).
• NCC Signal List with communication information for each NCC.

Of course, you can create customized Templates also at any time later in your project.

18.3 Customizing Filtering, Grouping, Sorting and


Formatting GUID-FD6DA322-5845-4F48-8701-D9F2AE3791FF v1

The configuration of filters, groups and sorting are saved into the particular template you use for
creating your signal list.

The configuration of these items is done in the ‘Export Customer Signal List’ dialog. While you can
create the configuration without exporting an actual Signal List, you will probably want to see the
result of your configuration by trying an export immediately; this is the reason why those two
functionalities have been combined in the same dialog.

18.3.1 Open the ‘Export Customer Signal List’ Dialog GUID-C9BAB7C5-26FA-49B5-81BB-A86B596AD89D v1

This dialog can only be opened from the Main menu.

1. Select the ‘HMI’ menu tab.


2. Click Customer Signal List in the ‘Export’ group of the Main menu.

IEC202100661 V1 EN-US

3. The ‘Export Customer Signal List’ dialog appears:

312 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 18
Customer Signal Lists

IEC202100733 V1 EN-US

4. As default template, the “TemplateSignalReport.xlsm” is selected. Select the template which you
want to use / configure. You can select either Excel Workbook (.xlsx) or Excel Macro-Enabled
Workbook (.xlsm).

5. At any time, if you want to save the template configuration, use “Save Rules”. Any changes in
filtering, grouping, sorting or formatting will be written into the selected template.
If you want to remove all changes since opening the template, use “Reset Rules”:

GUID-995786AC-BCCB-4847-8526-2D672CF5B646 V1 EN-US

Integrated Engineering Tool 313


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 18 1MRK500114-UEN Rev. X
Customer Signal Lists

18.3.2 Configure Filtering GUID-ECC529E2-6272-4E3E-959C-E3B013B8A737 v1

Currently, the Signal Groups and the MicroSCADA attributes can be used to create filter conditions.

After opening the ‘Export Customer Signal List’ as described in "Export a Customer Signal List", add
filters as required:

1. Select the Template whose filters you want to add or edit. Caution: initially always the default
template is selected.
2. Make sure the Filtering tab is selected (default).
3. Right-click into the empty space in the ‘Filtering’ Tab -> a row context menu appears:

IEC202100802 V1 EN-US

4. Select Insert New Row -> a new filter group is added. Give the filter group a descriptive name
in the ‘Group’ column Expand its child rows to define filter conditions.
5. Right-click into the row header in any existing filter condition row and use Insert New Row to
add filter conditions as required.
The conditions within one filter condition row will be AND-combined, the conditions of several
rows will be OR-combined. The tool tip of any cell will show the result of the whole filter group
configuration:

314 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 18
Customer Signal Lists

IEC202100729 V1 EN-US

The example shows a filter that will include all signals that appear on the event list or on the
printout or both.
6. Right-click into the row header in any existing filter condition row and use Delete Row(s) to
remove filter conditions as required.
Removing the last condition of a group will also remove the group itself.
7. You can add more filter groups, if you want. However, only one filter group at a time can be
active.
This can be used, if you want to export signals according to different criteria into different lists,
but based on the same template. In the above example, you could create a second filter
condition for all alarm signals and export it from the same template into a different Customer
Signal List.
8. You can move individual rows up and down, this is purely for convenience and does not affect
the filtering logic. Right-click into the row header in any existing filter condition row and use
‘Move Row(s) Up’ or ‘Move Rows(s) Down’ to remove filter conditions as required.
9. If you want to save your current configuration before continuing, click on Save Rules. If you
want to reset the rules to their original state after loading the template, click on Reset Rules.

18.3.3 Configure Grouping GUID-D3E5AE46-DF74-4089-BCF9-5B15963570AA v1

‘Grouping’ in IET600 has a double function:

• It brings the signals selected for a group to the beginning of the Customer Signal List, before
other signals. This is typically used to adapt to customer-specific requirements, e.g. a customer
may want to see all measurements or all switch positions on top of the list.
• It inserts ‘Grouping’ Headers before each group. This is typically used for additional text and
formatting.

Grouping in IET600 is not behaving like the ‘group by’ directive in SQL statements,
this may be a bit misleading for persons with experience in SQL.

Currently, the Signal Groups and the MicroSCADA attributes can be used to create grouping
conditions.

Integrated Engineering Tool 315


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 18 1MRK500114-UEN Rev. X
Customer Signal Lists

After opening the ‘Export Customer Signal List’ as described in chapter "Configure Filtering", add
groupings as required:

1. Select the Template whose filters you want to add or edit. Caution: initially always the default
template is selected.
2. Select the Grouping tab.
3. Right-click into the empty space in the ‘Grouping’ Tab -> a row context menu appears:

IEC202100734 V1 EN-US

4. Select Insert New Row -> a new ‘Grouping’ group is added. Give this group a descriptive name
in the ‘Group’ column Expand its child rows to define grouping conditions.
5. Right-click into the row header in any existing grouping condition row and use Insert New Row
to add grouping conditions as required.
The conditions within one grouping condition row will be AND-combined, the conditions of
several rows will be OR-combined. The tool tip of any cell will show the result of the whole
‘Grouping’ group configuration:

316 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 18
Customer Signal Lists

IEC202100735 V1 EN-US

The example shows a grouping that will have all Protection signals that cause an Alarm in the
first group, all Protection signals that do not cause an alarm in the second group, all
measurements in the 3rd group and all other signals will automatically be configured in an
additional group which appears after all defined groups.
6. Right-click into the row header in any existing grouping condition row and use Delete Row(s) to
remove grouping conditions as required.
Removing the last condition of a group will also remove the group itself.
7. You can move individual rows up and down, this will affect the sequence in which the groups are
exported. Right-click into the row header in any existing filter condition row and use ‘Move
Row(s) Up’ or ‘Move Rows(s) Down’ to remove filter conditions as required.
8. As the example shows, you can configure as many filter groups as required, if you want.
If you uncheck the ‘Active’ flag of a group, the signals specified by this group will appear in the
‘collect all other signals’ group at the end, they will not be missing. This may make sense when
experimenting with groupings to fulfil customer requirements. After finalizing the Grouping, it
probably does not make sense to change the Grouping activations between repeated exports.

18.3.4 Configure Sorting GUID-B5BA5850-29F7-4772-AD99-FA9146C17CA2 v1

Currently, the Signal Groups and the MicroSCADA attributes can be used to create sorting
conditions.

After opening the ‘Export Customer Signal List’ as described in "Export a Customer Signal List", and
configuring filtering and grouping, configure the sorting as required:

1. Select the Template whose filters you want to add or edit. Caution: initially always the default
template is selected.
2. Select the Sorting tab.
3. Right-click into the empty space in the ‘Sorting’ Tab -> a row context menu appears:

Integrated Engineering Tool 317


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 18 1MRK500114-UEN Rev. X
Customer Signal Lists

IEC202100736 V1 EN-US

4. Select Insert New Row -> a new sorting criterion is added. Add and configure as many rows as
you need to specify your sorting criteria:

IEC202100737 V1 EN-US

The example shows a typical sorting that uses the Substation Hierarchy and then Signal
Categories / Groups to provide sorting.

318 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 18
Customer Signal Lists

Grouping has preference over sorting: First the Grouping criteria will be used, and
then the sorting criteria will be applied to signals within each group.
5. Right-click into the row header in any existing sorting criterion row and use Delete Row(s) to
remove rows as required.
6. You can move individual rows up and down, this is purely for convenience and does not affect
the filtering logic. Right-click into the row header in any existing filter condition row and use
‘Move Row(s) Up’ or ‘Move Rows(s) Down’ to remove filter conditions as required.

18.3.5 Configure Formatting GUID-D595945E-0E45-4871-9058-566A661B71FE v1

‘Formatting’ collects some miscellaneous items which all have to do how data are displayed in the
exported Customer Signal List. It includes:

• Whether Alarm Groups and Command Groups are shown as groups.


• Whether NCC Addresses are displayed as structured or unstructured addresses (or both).
• The formatting of Title Rows (Color, Font etc.) to make them stand out more distinctly in the
Customer List.

After opening the ‘Export Customer Signal List’ as described in "Export a Customer Signal List", and
configuring grouping, configure the formatting as required:

1. Select the Template whose filters you want to add or edit. Caution: initially always the default
template is selected.
2. Select the Formatting tab.
3. Configure Data Grouping as required:

IEC202100738 V1 EN-US

If this is set to true, Alarm Groups and Command Groups will show as collapsible groups in the
Customer Signal List:

Integrated Engineering Tool 319


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 18 1MRK500114-UEN Rev. X
Customer Signal Lists

IEC202100657 V1 EN-US

4. Configure NCC Address format as required:

IEC202100739 V1 EN-US

5. Configure Title Formatting (a default format for all group titles is preconfigured).
You can add additional formattings for the title of each group. To do so, right-click into the row
header of this section and choose ‘Insert New Row’:

320 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 18
Customer Signal Lists

IEC202100740 V1 EN-US

6. After inserting a row, you must configure for which group title this formatting shall be valid. You
can select groups which you have defined in the ‘Grouping’ Tab.

IEC202100741 V1 EN-US

Integrated Engineering Tool 321


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 18 1MRK500114-UEN Rev. X
Customer Signal Lists

In the example, the title for the group ‘Protection Alarms’ is configured to have a red font color;
all other titles will use the default (black font color).
7. Right-click into the row header in any existing sorting criterion row and use ‘Delete Row(s)’ to
remove rows as required. You cannot remove the row Default for All Title Rows.
8. You can move individual rows up and down, this is purely for convenience and does not affect
the filtering logic. Right-click into the row header in any existing filter condition row and use
‘Move Row(s) Up’ or ‘Move Rows(s) Down’ to remove filter conditions as required.

18.4 Export a Customer Signal List GUID-FF42B54E-5C52-4EDD-B852-84B69CAE69F7 v1

18.4.1 First Export GUID-88814791-1550-4F0D-B675-A5A943666C46 v1

A Customer Signal List can only be exported from the Main menu.

1. Select the ‘HMI’ menu tab -> the Navigation Panel switches to the ‘HMIs’ tab.
2. Click Customer Signal List in the ‘Export’ group of the Main menu -> the ‘Export Customer
Signal List’ dialog appears.

IEC202100661 V1 EN-US

3. Select a suitable Template (which contains the filtering, grouping and sorting configuration) for
the export.

For a later re-export of the same Customer Signal List (see chapter 18.4.2 below), it
is important that you remember which template you used for a particular list. Ensure
that you have some way of knowing which Template belongs to which Customer
Signal List.
4. Select the HMI or Hot Standby System whose data you want to export (several HMIs can be
selected to export in one file.).

322 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 18
Customer Signal Lists

IEC202100663 V1 EN-US

Depending on the selected HMI, IET600 proposes a filename. You may change it according to
your needs by clicking on the ‘…’ button.

Changing the HMI will reset this filename to the default filename for the new HMI
export.
5. If the selected HMI is a combined HMI/Gateway, select which NCCs you want to include in the
export (per default, all are selected). If you select at least one NCC, you can decide to export ‘All
Signals’ or ‘Only Signals to NCC(s)’. There is no a possibility to select NCCs for multiselected
HMIs.

Integrated Engineering Tool 323


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 18 1MRK500114-UEN Rev. X
Customer Signal Lists

IEC202100663 V1 EN-US

IEC202100730 V1 EN-US

6. You can define how data are distributed to Excel Sheets by selecting an appropriate container:

324 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 18
Customer Signal Lists

IEC202100732 V1 EN-US

The most common choice is probably ‘Bay’ which will export one sheet per bay and an
additional sheet for all signals that are not allocated to a Bay.
If you want all signals in one single sheet, you might want to select ‘Substation’.
Other criteria are available to adapt to more special customer requirements. As you can
configure the MicroSCADA Object Identifiers according to your needs, you can use its parts to
create very specific containers, if this is required.
7. Depending on the selection of a container, the corresponding objects will appear now for
individual selection (Bays in the example).
Only those containers with signals mapped to the selected HMIs will appear. By default, all
objects are pre-selected.

Integrated Engineering Tool 325


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 18 1MRK500114-UEN Rev. X
Customer Signal Lists

IEC202100732 V1 EN-US

You can de-select those containers you do not want. E.g. early in the project, you may want to
export only few Bays (e.g. 1 Line, 1 Trafo and 1 Bus Coupler Bay) for discussion with the
customer. For documentation, you will want to select all containers.

Changing the HMI or the container will cause this list to change and the selection to
revert to the default (all containers selected).
8. Click on Export to finally export the data of the selected HMI.
9. In exported file for each selected HMI a column is created with cell value “x” in case signal is
sent to this HMI.
10. Click Close to finally close the dialog.
You may now apply additional formatting in the exported Excel Sheet (e.g. color rows and
individual cells.

18.4.2 Update an Existing Customer Signal List GUID-923BB0F9-93C6-4B3D-AAE2-ABF56BDC1029 v1

Based on the Template and an existing Customer Signal List, IET600 allows you to re-export the
signals while keeping the formatting information.

The logic is as follows:

• The column configuration is taken from the Template. You can move columns around or delete
columns from the Template which the customer does not require.
• For signals which existed in the previous Customer Signal List, the formatting is preserved and
any changed attributes will be exported with the new values. IET600 will identify signals
correctly, even if grouping and/or sorting have changed.
• New signals will be inserted according to grouping and sorting rules, with default formatting
(black text on white background).
• Deleted or filtered-out signals will be removed from the list, their formatting is lost.

326 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 18
Customer Signal Lists

If you are experimenting with filter settings, it is recommended to have a backup of


the old Customer Signal List: if you accidentally misconfigure the filter so that no
signals are exported, all your formatting will be lost irrecoverably.

The configuration of a re-export is identical to the first export as described above.

1. Do steps 1 to 7 above.
2. If IET600 detects that a Customer Signal List with the same name exists as you have configured
in step 4, it will offer you to either update the existing list or overwrite it by recreating the list from
scratch:

IEC202100667 V1 EN-US

If you answer with ‘No’, the existing list will be overwritten and all its row and group
formatting information will be lost!

A re-export is only possible, if you choose the same container as in the old Customer Signal List. If
by accident, you choose a different container, IET600 will stop the export and warn you accordingly:

IEC202100668 V1 EN-US

18.4.3 Editing exported Customer Signal List GUID-F598F09F-CBA0-4839-8DB1-6AF7064268AB v1

There is a possibility to create new signals in Excel file.

Integrated Engineering Tool 327


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 18 1MRK500114-UEN Rev. X
Customer Signal Lists

1. Select ‘Review’ menu tab->’Unprotect Sheet’.


2. Create a new signal:
2.1. From scratch:
a Select a row below which you want to create a new signal.
b Select HMI menu tab->’Create signal’.
2.2. With copy/paste:
a Select single or multiple rows and copy them.
b Select a row below which you want to insert copied signals.
c Select HMI menu tab->’Insert signals’.

IEC202100669 V1 EN-US

After inserting new row(s) you can update all needed attributes. Consider that if there is no value for
MicroSCADA attribute – default value will be set while import.

Another way to add a signal is to find the column labeled with the HMI name and mark the cell with
an “x” or remove “x”.

IEC202100670 V1 EN-US

After import signals will be added or removed from the project according to changes in excel file. As
in Customer Signal List there is no information about rule variables - after creation of a new signal
they either have result values, default or empty values. For example ONRule is empty, OIRule and
LN Rule have result values instead of rules, Station Text Rule and INRule are set to defaults.

328 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 18
Customer Signal Lists

Certain columns are not meant to be edited. They are protected and changes to
such cells will not be imported.

GUID-8007E18F-D49C-440F-AF20-04789E6BC51C V1 EN-US

IEC Type value depends on Process Object Type and Signal Handling:

GUID-8D1EFCED-5202-4A31-9B4F-6A277AC760CE V1 EN-US

Dependencies are provided as below:

IEC Type Process Object Type Signal Handling


30 BI 32

31 DB 32

32 DI 6
9 AI 0
11 AI 16
13 AI 4
14 AI 6

45 AO 8
46 AO 4
47 AO 0

18.5 Import a Customer Signal List GUID-2CDF4E57-0224-4DB0-A472-7F90C4C8E3D0 v1

A Customer Signal List can only be imported from the Main menu.

1. Select the ‘HMI’ menu tab -> the Navigation Panel switches to the ‘HMIs’ tab.
2. Click Customer Signal List in the ‘Import’ group of the Main menu.

Integrated Engineering Tool 329


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 18 1MRK500114-UEN Rev. X
Customer Signal Lists

IEC202100671 V1 EN-US

3. The ‘Import Customer Signal List’ dialog appears. Click the ‘…’ button to select a Customer
Signal List for import:

IEC202100672 V1 EN-US

The Customer Signal List knows to which HMI it belongs and will select the corresponding HMI
automatically. From HMI(s) combo box you can select to what HMIs import signals. By default all
HMIs are pre-selected.

IEC202100673 V1 EN-US

If it is a combined HMI / Gateway you can decide to unselect NCCs. As a general rule, it is
recommended to import the complete information for consistency reasons (this is also the
default: all NCCs are pre-selected). There is no a possibility to select NCCs for multiselected
HMIs.

330 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 18
Customer Signal Lists

IEC202100674 V1 EN-US

4. Per default, all containers are preselected (in the example, on export the containers have been
defined as Bays; each such container is represented as a sheet in Excel).
If you are sure that changes affect one container only, you may decide to unselect the other
containers for efficiency reasons (e.g. .when expanding an existing Substation with an additional
Bay); however, a better approach would be to reduce the number of containers already on
export.
5. Select Import to finally import the data.
6. Repeat steps 3, 4 and 5 to import data from other Customer Signal Lists to other HMIs.
7. Click Close to finally close the dialog.

Integrated Engineering Tool 331


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
332
1MRK500114-UEN Rev. X Section 19
Protecting IEDs Against Changes

Section 19 Protecting IEDs Against Changes GUID-F3BE36C3-BAEB-4B09-961A-89DB94999B53 v1

19.1 Introduction GUID-000C27F6-310C-47BF-A2BC-D1AFCD4B08B4 v1

IET600 has many mechanisms to provide data consistency across a project. While this is very useful
in early engineering stages in the project, it can cause problems in late stages of commissioning: if a
customer requests a change, this change may automatically propagate to other IEDs, thereby
potentially changing already commissioned IEDs.

Therefore a way of protecting such IEDs against inadvertent changes is needed. However, just
protecting a whole IED would limit engineering too much. IET600 therefore provides several
protections:

• Protecting RCB Dataflow


• Protecting GCB Dataflow
• Protecting SVCB Dataflow
• Limiting HMI engineering (HMI Engineering Rights)

These protections can be set individually for each IED.

Additionally, IEDs may be protected against changes due to an SED file Exchange. This is additional
to the user-configurable protection described here; its details are described in chapter SED File
Exchange Between Projects.

19.2 Applying Protection GUID-EDFB7179-560F-45F8-95E2-52F5A10DD2DC v1

19.2.1 General Principles GUID-29B89C00-C2CE-41BA-A255-CB67421D73E7 v1

The basic idea behind Dataflow protection is to prevent the engineer from doing a change that
requires a reloading of the protected IED. Therefore, all Dataflow protection of an IED protects
basically against the following changes:

• the reconfiguration of the Dataflow items on the IED itself, i.e. Datasets and Control Blocks
• if the IED is a client to other IEDs, the reconfiguration of Dataflow items on all these server IEDs.
E.g. if an IED A is GCB Dataflow protected and is a GCB client to IED B, the subscribed GCBs
on IED B can also not be modified. This is necessary: although in an SCD file, the Data model of
IED A is not modified and looks as before, it needs to be reloaded as its communication stack
needs to be reconfigured to the new situation.
• importing an ICD/IID file to an IED: IET600 allows to import IEDs with a changed DATA model in
spite of existing Control Blocks and Datasets; however, this can potentially alter Datasets or
require the reconfiguration of Dataflow items; therefore it is not allowed on dataflow-protected
IEDs.
• changes of any names that may affect communication, such as the IED name.

The basic idea behind reducing HMI Engineering rights is to prevent the engineer from doing a
change that requires a reloading of its clients as configured in the ‘Signal Clients Editor’ (HMIs or
Gateways). Reducing HMI Engineering rights of an IED protects against the following changes:

• Signals of an IED with HMI Engineering Rights ‘Fix’ cannot be changed at all; neither can its
attributes be edited, nor can their configuration in the ‘Signal Clients’ or ‘NCC Data’ Editors be
changed.
• Signals of an IED with HMI Engineering Rights ‘Safe Only’ allow the change of few selected
attributes in the ‘HMI Data’ Editor. ‘Safe’ attributes essentially are those that do not affect
communication in any way (for a detailed listing, see "HMI Engineering Protection").

Integrated Engineering Tool 333


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 19 1MRK500114-UEN Rev. X
Protecting IEDs Against Changes

19.2.2 Configuring and Editing Protection GUID-10B5E008-5568-4C72-A52D-2383C2672EBB v1

The protection settings are configured in the ‘IED Status’ Editor. The example shows a situation
where SVCB and GCB configuration are protected for a whole voltage level, while RCB configuration
is protected for two commissioned Bays Q01 and Q02; for the same Bays, HMI Engineering Rights
have been set to “Safe Only”

IEC202100675 V1 EN-US

19.2.3 Displaying Protection GUID-21D76D9A-807E-47BA-B631-CA8E8600EADD v1

To indicate protection, IEDs that have any protection set, are indicated with a blue lock in all trees.
This blue lock will also appear on the column header of the corresponding IED in the relevant CB
Clients editor, or the Signal Clients editor.

334 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 19
Protecting IEDs Against Changes

IEC202100676 V1 EN-US

(However, IEDs that are e.g. clients to a protected and whose engineering is therefore also restricted,
do not show such an indication in the tree).

If a protection forbids editing, the appropriate rows, columns or cells in grid-based editors are set to
read-only and therefore appear greyed out.

19.2.4 RCB Dataflow Protection GUID-63E56E19-56E1-4E1E-8033-C7AB6832F187 v1

Protecting an IED against RCB Dataflow changes does the following:

• The IED DATA model cannot be changed (by import of an ICD/IID file).
• The IED name cannot be changed.
• All RCBs and their related Datasets in this IED cannot be changed anymore.
• All RCBs clients of these RCBs cannot be changed anymore.
• All RCB client mappings from another IED/RCB that have the protected IED as a client of a
smaller index cannot be changed anymore (an example: if IED A has an RCB A which has
protected HMI X as client 3, then not only client 3 cannot be changed, but also clients 1 and 2:
deleting client 2 would shift HMI X/client 3 to client 2 position, which must be prevented by
protection; adding another client 3 would shift HMI X/client 3 to position 4 which again must be
prevented by protection.)

Integrated Engineering Tool 335


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 19 1MRK500114-UEN Rev. X
Protecting IEDs Against Changes

The above recommends that RCB clients (typically HMIS and Gateways) should be protected
only very late in commissioning, as their protection will prevent almost all editing of RCB
Dataflow).
• The IED cannot be removed from/added to another Subnetwork, as this would affect the RCB
Client mapping.

19.2.5 GCB Dataflow Protection GUID-87A28E0E-257D-42F9-84C0-20BCB361656C v1

Protecting an IED against GCB Dataflow changes does the following:

• The IED DATA model cannot be changed (by import of an ICD/IID file).
• The IED name cannot be changed.
• All GCBs and their related Datasets in this IED cannot be changed anymore.
• All GCBs clients of these GCBs cannot be changed anymore.
• All GCB client mappings from another IED/GCB that have the protected IED as a client cannot
be changed anymore.
The above means that protecting an IED which is GCB client to many other IEDs/GCBs will
prevent most client reconfigurations. It should typically be done when the functionality provided
by GCBs is tested and approved by the customer.
It is a known issue that a reconfiguration of GCBs typically requires a reloading of many IEDs.
This can only be helped partly by separating different functions into different GCBs and zones
(e.g. separate Interlocking from Protection, or Bus Coupler Interlocking from Transformer
interlocking), partly by ensuring GCB functionality is working correctly during or soon after
Factory Acceptance Test.
• The IED cannot be removed from/added to another Subnetwork, as this would affect the GCB
Client mapping.

19.2.6 SVCB Dataflow Protection GUID-31BEDBBE-FFDC-46F6-9C33-52AE8DC31747 v1

Currently, most IEDs providing Sampled Value Streams via SVCBs have a fixed, predefined SVCB
Dataflow configuration, where only the clients need to be added. As these are also typically known
early in the project, SVCB protection offers less during commissioning than the other Dataflow
protections. Typically this protection can be done together with SVCB Dataflow protection. It probably
should not be done before other protections, as it is easy to reconfigure (little gain in protection) but
may prevent many changes like IED reimport of an IID file (severe hindrance).

Protecting an IED against SVCB Dataflow changes does the following:

• The IED DATA model cannot be changed (by import of an ICD/IID file).
• The IED name cannot be changed.
• All SVCBs and their related Datasets in this IED cannot be changed anymore (however they are
mostly pre-defined anyway).
• All SVCB clients of these SVCBs cannot be changed anymore.
• All SVCB client mappings from another IED/SVCB that have the protected IED as a client
cannot be changed anymore. This is useful when commissioning the client IEDs of a Sampled-
Value-Stream (a protection or control IED): turning on the SVCB protection of this client IED
after commissioning prevents client changes that might affect its functionality (e.g. Protection or
Synchronization).
• The IED cannot be removed from/added to another Subnetwork, as this would affect the SVCB
Client mapping.

19.2.7 HMI Engineering Protection GUID-0FB6CF07-EDC3-49A7-BE9F-D1BC5BF836DC v1

HMI Signals have three levels of rights:

336 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 19
Protecting IEDs Against Changes

• “Full” allows all changes.


• “Fix” allows no changes at all.
• “Safe only” allows limited changes: Customers want to be able to easily change certain
attributes affecting the display of signals, such as event listing, printout and alarming. However,
they also want to be sure that they do not accidentally change something that affects
communication (and therefore requires reloading the HMI Database and/or retesting). “Safe
Only” therefore allows the change of a limited set of attributes, while preventing adding or
removing signals or changing address parameters etc.

“Safe Only” allows modification of the following attributes:

• Station text, Signal text and Status text (MicroSCADA attributes OI, OX, EH).
• Event Listing, Event Update Condition (MicroSCADA attributes EE HA, HE, HF, HL).
• Printer, Print Update Condition (MicroSCADA attributes PA, PH, PU, LD).
• Alarm List, Alarm Class, Alarm Delay (MicroSCADA attributes AG, LA, AC, AD).
• MicroSCADA attribute CX.

19.3 Engineering Workflow and Protection GUID-EA84C42D-3531-4C14-80CE-C8C136F408DA v1

During the engineering of a project, the different protections will probably be applied during different
phases of the project. In this chapter, a basic way when to protect which items is suggested.

19.3.1 GCB Dataflow Protection After FAT GUID-B3EE0896-57A2-49A9-ACD0-FFD4AF190FE1 v1

Usually, any bay-to-bay logic (Bus Coupler interlocking, Double Command Blocking, Breaker Failure
Protection etc.) should be defined during engineering; an adaptation may happen during Factory
Acceptance Test. Once the FUP of an IED and the interlocking/protection logic is finalized, i.e. in the
early phases of commissioning, probably all IED should be GCB protected to prevent accidental
changes.

However, any re-import of the IED DATA model (ICD/IID-Import) is blocked by GCB protection. You
may need to selectively unblock an IED to reload its DATA model.

19.3.2 GCB Dataflow Protection of Third-Party Engineered IEDs GUID-3C9C572B-10B1-492D-856A-350AC931B7F1 v1

A fairly common situation is a Substation with an MV part, an HV part and a common HMI. Often, the
MV part is provided by one party; HV and HMI by another party. The HV engineer may then be
required to do RCB Dataflow engineering on the MV IEDs, but may not be allowed to change their
DATA model or (safety-relevant) GCB Dataflow configuration.

With the provided Protection, this can easily be enforced by putting all MV IEDs under GCB Dataflow
protection.

19.3.3 Commissioning Bays GUID-35E8C8D5-5954-408D-B2AC-FCF9D57A2A45 v1

After successfully commissioning a Bay, i.e. testing protection and control functionality and ensuring
the appropriate signals are correctly sent to the HMI, it makes sense to apply RCB Dataflow
protection to its IEDs and reduce the HMI Engineering rights.

If you are fairly sure that you do not change any signal attributes, you can set the HMI Engineering
rights to “Fix”.

However, it often happens that some attributes need to change very late in commissioning. E.g. after
commissioning the 5th Bay, the customer may decide to change the Signal Text of a protection
signal, and he wants to change it for all signals consistently, even those from the already
commissioned Bays. In this case, set the HMI Engineering rights to “Safe Only”. Attributes that would

Integrated Engineering Tool 337


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 19 1MRK500114-UEN Rev. X
Protecting IEDs Against Changes

affect communication are blocked, while attributes that affect text, printout, event and alarm listing
can still be edited. This is the recommended setting after commissioning Bays.

19.3.4 Protecting HMIs While Engineering a Gateway GUID-E6833FAF-37FE-4AB8-9B50-9B9581729653 v1

It is typically not recommended to apply RCB Dataflow protection and/or limit the HMI engineering
rights on clients (HMIs or Gateways), as this will block changes on their servers as well.

However, in special situations this may make sense, e.g. when adding a Gateway/NCC connection to
an existing substation which is already commissioned or even in operation.

In this case, one can protect the Dataflow of all IEDs and set the engineering rights of an existing
HMI to “Fix”, while leaving the HMI engineering rights of the IEDs and of the Gateway on “Full”. This
allows to do Signal client configuration and NCC configuration for the Gateway while ensuring that
the HMI configuration cannot be changed. E.g. signal texts can then only be changed on the
Gateway, not on the IED (as this would affect the HMI as well).

338 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 20
Migration of Engineering Data from Older Projects

Section 20 Migration of Engineering Data from


Older Projects GUID-F919501A-DD4E-4795-916D-9D8D96B87550 v1

20.1 Overview GUID-12A9A82C-9465-4B0A-B206-F6F8D0C0576F v1

Till now, we have assumed that we start a new project from scratch. This chapter describes how to
proceed, if we need to work with an existing substation that has been created using older ABB tools.

The following Migration Scenarios are described

• Migration an existing IET600 -61850-system with MicroSCADA as Station HMI.


• Existing LON/SPA system with MicroSCADA station level.

20.2 Migration Effort Considerations GUID-2EE24C15-4AD5-41D4-B4FC-434020B9287B v1

20.2.1 Scenarios That Will Profit from Migration to IET600 GUID-79A1A1B3-8161-400F-8EB2-6B15F5C139DA v1

The following cases will strongly profit from the Basic Migration:

• A customer with several similar projects and quite a defined data structure that is similar from
project to project.
• A project that is following ABB engineering standards closely.
IET600 offers many automatic calculations, based on ABB engineering standards. These
automatic calculations will make migration fairly easy.

20.2.2 Scenarios to be Evaluated for Migration to IET600 GUID-F27A280D-6C39-44DC-91FF-8EC27C46D1ED v1

• An extension of a non-IEC 61850 based Substation with an IEC-61850-based Bay.


Here the new Bay, including its HMI part, can be engineered with IET600. Also, potentially,
improvements of older HMI process data can be done. On the other hand, IET600 cannot
generate configuration files for e.g. LON/SPA communication and also not configure HMI data
for these communication protocols.
• A replacement of an HMI.
In this case, IET600 can be profitably used for modification of HMI data, as long as those parts
relating to non-IEC-61850 communication can be taken from the old HMI without modification
and no reconfiguration of a COM500 NCC gateway is needed.

20.2.3 Scenarios not Very Suitable for Migration to IET600 GUID-732CE20A-803C-4EBD-9889-2C33294DACBB v1

• An extension of a non-IEC 61850 based Substation with a non-IEC-61850-based Bay.


IET600 does not offer any facilities for any communication data keeping and/or editing in this
scenario.
• A small extension that affects a COM500 NCC gateway.
In this case the work to transfer all the data to do a consistent and automated COM500
engineering would probably far outweigh any gain.

Integrated Engineering Tool 339


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 20 1MRK500114-UEN Rev. X
Migration of Engineering Data from Older Projects

20.3 Migration of Systems of Different Types GUID-4D4C6AE9-59EA-409E-BA92-915AD9C692B7 v1

20.3.1 Existing IEC 61850-based System with MicroSCADA Station


Level GUID-31BA5BBC-90B4-4AC5-B0B3-0DDF7AEF16CF v1

We assume an old system based on IEC 61850 with a valid and up-to-date SCD configuration and a
MicroSCADA HMI and COM500i gateway.

The migration steps are.

1. Export the current MicroSCADA configuration with the most recent Data Exchange format
available (typically ‘lof’ and XREF files).
2. Create a new project in IET600 5.x.
3. Import an SCD file with substation, communication and IED information.
4. Create HMIs devices for HMI signal import.
5. Create Gateways and NCCs for COM500 configuration import.
6. Import HMI signals (e.g. MicroSCADA ‘lof’ files).
7. Import COM500 configuration.

For a detailed description of the steps, see chapter "Migration Step Details".

20.3.2 Existing Non-IEC 61850 System with MicroSCADA Station Level GUID-0323B4A8-2646-45BB-AF9B-A7C24F30AE5A v1

Direct migration of LON, SPA, IEC 101/103/104 etc. configuration from a legacy IET 3.x/4.x project is
not supported.

We assume an old system based on any non-IEC 61850 configuration with a MicroSCADA HMI and
COM500i gateway.

1. Create a new project in IET600 5.x.


2. Create HMIs devices for HMI signal import.
3. If applicable: Create Gateways and NCCs for COM500 configuration import. Configure the
NCCs with the correct Line numbers as described.
4. Optional:
• create IEDs
• create Subnetworks for the Protocols involved
• attach IEDs to these Subnetworks
• from the MicroSCADA System Configuration (Editor, sys_bascon.com file), enter the
MicroSCADA Unit numbers to the IEDs/Access Points in the ‘Subnetwork Editor’.
5. Import HMI signals (e.g. MicroSCADA ‘lof’ files).
With correctly configured UN Numbers in step 4 above, the signals will be allocated to their
respective IEDs. Signals without UNs will be allocated to the HMI itself. Manual allocation for
some signals may be required.
6. If applicable: Import COM500 XREF files.

20.3.3 Integration of Non-61850 IEDs into a 61850 Substation GUID-02C6AC4A-88D6-4AA5-8979-F37960074E82 v1

Non-IEC 61850 IEDs can be integrated into an IEC 61850-based Substation Automation system
using a Gateway.

In this scenario, existing LON and other third party protocol IEDs are connected to a Gateway which
translates them into IEC 61850. Whatever is available as signal and communication configuration is
used as input to the Gateway Configuration Tool. This tool produces an ICD/IID file as output which
can then be imported into an IET600 project.

340 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 20
Migration of Engineering Data from Older Projects

20.4 Migration Step Details GUID-B5A18627-9FCD-49A4-9DED-918F64B495D7 v1

20.4.1 Prerequisites GUID-D7C2AA56-0408-4C0B-A196-7DC4F106CE03 v1

A valid and up-to-date SCD file of the Substation must be available.

The MicroSCADA process database must be exported from MicroSCADA in a suitable format (or
valid and up-to-date export files must be available).

If applicable: the COM500 configuration must be exported from MicroSCADA in a suitable format (or
valid and up-to-date export files must be available).

20.4.2 Import SCD file GUID-B3BC1859-E7A6-4FB6-A7FD-5C7FF1AE92BC v1

1. Create a new project as described in chapter "Create a New Project".


2. Import the SCD file to this project as described in chapter "Import an SCD File to Create a
Project".

20.4.3 Create HMIs and Gateways GUID-2B32965F-F872-41FB-A1B9-88D3CA2958EF v1

The SCD file from IET 4.x will typically already contain HMI devices. However, not all attributes for
the HMI devices are available in this SCD file, for example the MicroSCADA OI settings. Therefore,
these imported HMI devices must be deleted and replaced by HMI objects from IET600 5.x, as
described below:

1. Go to the HMIs Navigation Tree. You will most likely find an element Unallocated IEDs with
some IEDs below it.
2. Drag n drop unallocated HMIs or Gateways to the HMIs or GWs / Proxies element.
3. Drag n drop unallocated OPC servers to the HMIs to which they belong.
4. Check and/or redefine the OI length of the HMIs according to the system configuration (for
details, see chapter Annex: MicroSCADA OI Settings).

20.4.4 Create NCCs GUID-A349161D-22D5-4998-933E-31DFB462BB23 v1

If COM500 engineering is used, then the NCC nodes must also be created. NCC nodes are not
defined in the SCD file from IET 4.x and shall therefore be defined manually in the new IET600
project:

1. Go to the HMIs Navigation Tree and select the NCCs node.


2. Create new NCC or new HSB as described in chapter "Creating NCCs".
3. Connect the Gateways to the NCCs as described in chapter "Connecting Gateways to NCCs".
4. Define the NCC line numbers and addresses according to the system configuration.

NCC line numbers and addresses cannot be extracted from the files available for import (SCD, lof or
XRF files). The COM500 X-Ref tool can export a COM_XRNCC.XRF file which contains information
about NCC addresses and line numbers. The line number must be entered manually, but they must
be entered manually in IET600. Also, the NCC names in the SCD file and the COM500 x-Ref tool
can differ.

20.4.5 Import HMI and COM500 Configuration GUID-980E93C7-87F1-462A-9E45-C95AE4C51C53 v1

Import the MicroSCADA Signals for each HMI as described in chapters "Import a MicroSCADA ‘lof’
File" or "Import a MicroSCADA ‘csv’ File with Process Object Data".

Integrated Engineering Tool 341


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 20 1MRK500114-UEN Rev. X
Migration of Engineering Data from Older Projects

The signals in these files will be allocated to IEDs based on the IN attribute (if available) or based on
the UN attribute as a fallback.

The COM500 configuration files can be imported together with the corresponding MicroSCADA
Loadfiles as described in chapter "Import COM500 Configuration File (XRF)".

Check that the imported signals have appeared under the individual bay-level IEDs.

342 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 21
Diagnostics

Section 21 Diagnostics GUID-A1BCE3C5-FAD7-49B2-A1C4-3EEA7A3EE480 v1

IET600 has a feature to analyze and detect inconsistencies inside the project. In order to use this
feature the Analyzer must be first activated.

IEC202100680 V1 EN-US

If problems are detected, then in IET600 will pop up a Diagnostics Manager dialog, where all issues
are stated. The user can find the reason for the issue and what can solve it. Detailed information is
logged in the lowest part of the dialog. The same messages are present inside the IET600 Logging
and can be investigated after closing the Diagnostics Manager dialog.

IEC202100681 V1 EN-US

In some case, IET600 can automatically resolve the issues. If it is possible to resolve a problem, the
Select checkbox is active and it can be ticked at the beginning of the row. To resolve problems,
select all the rows and press the Resolve button. If the resolve operation was successful, the status
will be updated and additional information is logged.

IEC202100682 V1 EN-US

Integrated Engineering Tool 343


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 21 1MRK500114-UEN Rev. X
Diagnostics

The detection of problems in IET600 Analyzer is based on predefined rules and for the moment
covers just a small group of well-known issues. Often they are related to misconfiguration of IED
Services and Capabilities. The settings for IED Services and IED Service capabilities can be
observed in the IED Services and IED Capabilities editors. The following issues can be detected:

Problem Description Auto Correction


IEC61850 SCL model configuration During operations with SCL files, the NO
may be invalid or corrupted. SCL model in IET600 is validated.
The detected issues will be logged.
The Analyzer does not differentiate
SCL error types and it will observe
just for any error related to SCL
model.
Solution: Check the error(s), if
applicable, correct them and reload
the configuration file(s).
CB(s) or Dataset(s) cannot be IED Services for CB or Dataset are YES
modified. set to 'Fix' or the IED Service
capability "Enforce Fix Service
Settings" are set to TRUE.
Solution: Set the IED capability
"Enforce Fix Service Settings" to
FALSE for this device type. Thus, it
will be ignored this rule to protect the
CB(s) and Dataset(s) introduced with
tissues in Ed.2.
Client LN(s) cannot be assigned to The IED Service Yes
buffered/unbuffered RCB(s). "ClientServices.bufReport" or
"ClientServices.unbufReport" is
missing.
Solution: Set the corresponding IED
capability "Default For Client Service
Buffered RCB" to TRUE or "Default
For Client Service Unbuffered RCB"
to TRUE for this device type.
Client IED(s) cannot be assigned to The IED Service YES
GCB(s)/SVCB(s). "ClientServices.goose" or
"ClientServices.sv" is missing.
Solution: Set the corresponding IED
capability "Default For Client Service
Goose" to TRUE or "Default For
Client Service Sampled Values" to
TRUE for this device type.
GCB(s) and client IED(s) cannot be No IED Service "GOOSE.max". NO
configured. Solution: Check the IED Service
"GOOSE.max" and if appropriate,
define a value for the IED Capability
"Override For Service Goose Max".
Cannot create Dataset(s). The value for IED Service NO
"ConfDataset.max" is reached.
Solution: Check the IED Service
"ConfDataset.max" and if
appropriate, define a value for the
IED Capability "Override For Service
Conf Dataset Max".
Table continues on next page

344 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 21
Diagnostics

Problem Description Auto Correction


Cannot create RCB Clients(s). No Service "DynAssociation.max". NO
Solution: Check the IED Service
"DynAssociation.max" and if
appropriate, define a value for the
IED Capability "Default Max
Concurrent Report Clients".
The value of the RCB Property YES
"RptEnabled.max" is reached.
Solution: If the RCB property
"RptEnabled.max" can be modified,
set the IED Capability "Can Modify
Report Enabled Max" to TRUE.
The value of the IED Service NO
"ConfReportControl.max" is reached.
Solution: Check the IED Service
"ConfReportControl.max" and if
appropriate, define a value for the
IED Capability "Override For Service
ConfReportControl Max".
Dataset(s) cannot be sent to the Ethernet frame of the Dataset(s) is NO
Client(s). bigger than 1527 octets.
Solution: Reduce the side of the
Ethernet frame by making the
Dataset(s) smaller.

Integrated Engineering Tool 345


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
346
1MRK500114-UEN Rev. X Section 22
Annex: Naming Conventions

Section 22 Annex: Naming Conventions GUID-5BDF954D-E9EF-47D1-A0D8-18DBB8D12554 v1

22.1 Introduction GUID-39794CF3-5274-4003-8C61-9BAD342C1864 v1

22.1.1 Introduction GUID-B94EE200-E716-40AE-B852-4EF80B83041E v1

IEC 81346 defines a comprehensive system to name all kinds of objects in a technical environment.

One crucial requirement of IEC 81346 is that it is hierarchical. Each level is a combination of
characters followed by a combination of ciphers. This allows to figure out a hierarchy from any name,
independent of separators.

To be able to figure out this hierarchy is important in IET600 regarding IED names: many renaming
rules (e.g. renaming an IED and all its references when renaming a Bay) depend on correctly
evaluating this hierarchy.

22.1.2 General Conventions in IEC 81346 GUID-8D00726A-BFCB-497F-A662-0EABBCB31F9D v1

The internal names proposed by IET follow IEC 81346 as closely as possible. However, as IEC
61850 naming conventions are much less strict (e.g. all Unicode Characters are allowed for naming
elements in the Substation Tree); customers may require to use names not consistent with IEC
81346. It is recommended to use the ‘Customer Name’ for such names, where you are free to use
any character combination.

22.1.3 Hierarchies in IEC 81346 and IEC 61850 GUID-57254AA9-37DF-420D-B76B-41BB785216EF v1

Level IEC 81346 IEC 61850


1 Plant level Substation
2 Subplant level Voltage level, Function
3, 4, 5 Further division Bay, Function, Subfunction
3, 4, 5 Apparatus, Components Equipment, Subequipment

22.2 Default Substation Naming GUID-E9A9BF05-69CD-47C4-9C50-972CBF1437AD v1

The following chapters show some standard feeder configurations and the structuring and naming of
primary equipment according to IEC 81346.

For a detailed description how IEC 81346 is used by ABB Substation Automation (including naming
of secondary equipment), please refer to [1]. The document can be made available to external
customers as well.

22.2.1 Typical Bay, Line GUID-468EDDA6-B284-4FE7-8024-9DED054DCEAC v1

The voltage transformer BA1/2 may also sit at edge QB9/QC9.

Integrated Engineering Tool 347


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 22 1MRK500114-UEN Rev. X
Annex: Naming Conventions

IEC202100687 V1 EN-US

348 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 22
Annex: Naming Conventions

22.2.2 Typical Bay, Transformer GUID-F52912F9-65FA-4A5B-B29B-35E8A37A90A3 v1

IEC202100688 V1 EN-US

Integrated Engineering Tool 349


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 22 1MRK500114-UEN Rev. X
Annex: Naming Conventions

22.2.3 Typical Bay, Bus Coupler GUID-7B409FD2-B52A-492B-882D-E9366DE2C8B9 v1

IEC202100689 V1 EN-US

22.2.4 Typical Diameter, Line/Transformer GUID-7D39D9E8-60E4-422F-A43D-8AD785199D21 v1

The voltage transformer BA1/2 may also sit at edge QB9/QC9.

350 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 22
Annex: Naming Conventions

IEC202100690 V1 EN-US

Integrated Engineering Tool 351


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
352
1MRK500114-UEN Rev. X Section 23
Annex: Switch Configuration

Section 23 Annex: Switch Configuration GUID-B557B42C-100D-4B02-9F87-78B40AE9F3D6 v1

23.1 The Switch Data Model GUID-3E162FA9-9F6D-4409-AEFD-A8EB8DC97FE3 v1

IEC/TR 61850-90-4 specifies a DATA model for Switches. It is relatively complex, consisting of the
following LN Classes:

LPHD represents the physical device properties (e.g. physical


health).
LLN0 represents the properties (e.g. local/remote operation) of
the Logical Device.
LPCP represents the physical properties of a port.
1 LPCP per physical port
LPLD represents the port link discovery properties of a port
(e.g. the TCP/IP address of its remote partner etc.).
1 LPLD per physical port, references 1 LPCP
LBSP represents the RSTP properties of 1 port (e.g. “Edge” or
“Trunk”).
1 LBSP per physical port, references 1 LPCP.
LCCH represents the channel properties of a port or a
redundant port pair.
1 LCCH per port or port pair, references 1 or 2 LPCP.
LBRI represents the connection of all ports (typically called a
“Bridge”) and its related properties (e.g. RSTP weight of
this node etc.).
1 LBRI per Switch, references all LBSPs.

23.2 MAUs GUID-6508A87D-D080-449D-89CB-9D3A147E3586 v1

23.2.1 Short description GUID-38231D11-4E88-4B7B-905D-253FB642FF7C v1

A Medium Attachment Unit (MAU) is a technical term for what a normal user would call a ‘Port’ of a
switch. However, MAU includes more information. As an example:

23 1000baseLXHD 1000BASE-LX half duplex mode


24 1000baseLXFD 1000BASE-LX full duplex mode
29 1000baseTHD 1000Base-T half duplex mode
30 1000baseTFD 1000Base-T full duplex mode

The xxxxBase-YY specifications are standards defined in IEEE 802.3xx. These specifications do not
always contain exactly the same information, however. E.g.:

• 1000Base-T defines an electrical connection, a plug type (RJ45), the wiring in the cable and a
maximum length of the cable (100 m).
• 1000BASE-LX defines a fiber-optic connection, the wavelength of the laser used for
transmission (1,270–1,355 nm), two possible fiber types (multi-mode and single-mode),
maximum cable lengths (550 m for multi-mode, 5 km for single-mode fibers), but no plug types.
• 1000BASE-LX10 defines a fiber-optic connection, the wavelength of the laser used for
transmission (1,270–1,355 nm), two possible fiber types (multi-mode and single-mode),
maximum cable length (10 km for single-mode fibers), but no plug types.

Currently, IET600 uses the MAU type only for Switch specifications, as they are a part of the IEC/TR
61850-90-4 DATA model.

Integrated Engineering Tool 353


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 23 1MRK500114-UEN Rev. X
Annex: Switch Configuration

23.2.2 References GUID-BFAFDF4A-11D1-4A00-9A41-63A95FBA1FD0 v1

https://www.ietf.org/rfc/rfc4836.txt offers a complete List of MAU types as used in IEC/TR


61850-90-4.

https://en.wikipedia.org/wiki/Fast_Ethernet describes the 100MB Ethernet standards.

https://en.wikipedia.org/wiki/Gigabit_Ethernet describes the 1GB Ethernet standards.

https://en.wikipedia.org/wiki/10_Gigabit_Ethernet describes the 10GB Ethernet standards.

354 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 24
Annex: MicroSCADA OI Settings

Section 24 Annex: MicroSCADA OI Settings GUID-6EFA7196-90AD-41BF-8C2A-3D6DAE79C6E2 v1

The OI Settings for MicroSCADA can be done on the Project and on each MicroSCADA individually.

24.1 Setting the OI Attribute GUID-5848CE72-F7F3-4E26-B208-0EB138DEE29D v1

MicroSCADA splits the OI field into a maximum of 5 parts. All fields together including separators
must be <= 63.

If you exceed this length, IET600 will give you only a very discrete warning; check this carefully, if
you edit these settings:

IEC202100691 V1 EN-US

There is currently no transfer of this setting between IET600 and MicroSCADA. It is the responsibility
of the engineer to synchronize the OI settings in both IET600 and MicroSCADA.

24.2 OI Settings on Project GUID-55391084-D894-48A2-8C78-1AC493E18717 v1

These settings are used for 3 purposes:

• To calculate OIs from formulas for signals on IEDs, which have not been mapped to any
MicroSCADA yet.
• As default values when creating a new MicroSCADA HMI (if you have a project with different
settings, but which are the same for all MicroSCADAs, it is therefore most efficient to adjust the
Project OI Settings accordingly).
• Changes to these settings will also be propagated to all other OI Settings which have the
same value as project-wide settings.
• To calculate OIs when using HMI Mirroring.

24.2.1 Default Settings GUID-802AFCA8-B98A-47E6-8806-606E1DEC91BF v1

The default settings for a newly created Project are:

Integrated Engineering Tool 355


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 24 1MRK500114-UEN Rev. X
Annex: MicroSCADA OI Settings

Field Field Mapping Field Length OI Separator Length


1st Station Name 9 1
2nd Bay Name 14 1
3rd Device Name 5 1
4th Optional Field 4 0 0
5th Optional Field 5 0 0

The Field Mapping is not used in any IET600 logic, it just serves as a reminder what MicroSCADA
expects in Fields 1, 2, 3… The OIRules in the ‘HMI Data’ Editor of IET600 may need to be adjusted,
if some other configuration than the default Field Mappings are used.

24.2.2 Configuration GUID-4A23331C-859B-4987-B3EB-9C3A9F070CA8 v1

1. Select the Project node in any Navigation Tree.


2. Search for the property MicroSCADA Object Identifier Settings.
3. Open it, configure the individual properties.

If you have several MicroSCADAs with different OI Settings for each MicroSCADA, it is
recommended to set each of the Project OI Field Lengths to the biggest any MicroSCADA has in the
respective field, e.g.:

HMI 1 HMI 2 Project


1st Field Length 9 12 12
2nd Field Length 14 8 14
3rd Field Length 5 10 10
4th Field Length 0 0 0
5th Field Length 0 0 0

It is possible in this case, that the total length of the Project OI will exceed 63
characters. This will may cause problems, unless the setting of each MicroSCADA
HMI does not exceed 63 characters. Remember in such a case to adjust the OI
Settings immediately after creating a new HMI.
When using HMI Mirroring, the Project OIs are used to calculate the OIs for mirrored
signals. If, in the above example, e.g. the project settings were not adjusted (e.g.
leaving 1st OI at 9), the 1st OI for HMI 2 will be truncated to a length of 9 although
the 1st OI Setting at HMI 2 is correctly set at 12.

24.3 OI Settings for MicroSCADA GUID-68D26569-B460-4995-B4B7-C3E5102C9107 v1

24.3.1 Configuration GUID-E87F397B-E71A-40B7-8241-87359C4D337F v1

1. Select a MicroSCADA IED in the Substation or IEDs Navigation Tree; or an HMI or Gateway in
the HMIs Navigation Tree.
2. Search for the property MicroSCADA Object Identifier Settings.
3. Open it, configure the individual properties.

When creating an HMI, the OI Settings from the Project are copied to the HMI as initial values.

356 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 24
Annex: MicroSCADA OI Settings

24.4 Known Limitations GUID-E26E987B-0D5D-49B3-B23F-974409338609 v1

IET600 does not support ‘Field Mapping‘, i.e. meanings of fields. E.g. if on Project Level, the first 3
parts are given the meaning of Station – Bay – Device, and on an individual HMI, the first 3 parts are
given the meaning of Station – Device – Bay, IET600 will not magically reverse Device and Bay part;
the calculated OI will be identical. Also there is no automated logic that would adapt OIRules in the
‘HMI Data’ Editor, if ‘Field Mappings’ are changed; this is up to the engineer.

IET600 currently does not support to split the OI attributes into 5 separate fields as has been
introduced in more recent MicroSCADA versions.

Integrated Engineering Tool 357


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
358
1MRK500114-UEN Rev. X Section 25
Annex: Mirroring Command Group Logic

Section 25 Annex: Mirroring Command Group


Logic GUID-4A486224-D583-40BF-B57B-B131CDC72ED7 v1

25.1 Introduction GUID-FF2607FB-D155-42B4-81C8-CA8CFF25E749 v1

MicroSCADA requires a specific number of signals to be present for the proper handling of a
command from the MicroSCADA HMI.

When mirroring a command, it is important that all signals needed for this proper command handling
are mirrored, as the MicroSCADA-internal handling of switching operations is based on signals with
defined LNs/IXs to have a specific meaning.

IET600 provides a logic that automatically mirrors all required signals, if any single command is
selected.

25.2 Predefined Mirroring Group GUID-8AA6B353-823A-4EEB-BC8A-326A4BA3C3D4 v1

Mirroring Groups are applicable only for MicroSCADA; the MicroSCADA-internal logic for handling
switching operations is based on these signals with defined IXs (where each IX also has a defined
meaning). It depends on the MicroSCADA LN/IX attribute.

The logic for assembling such a Mirroring Command Group depends on the MicroSCADA LN and IX
attributes:

1. All Signals must have the same LN.


2. The Signals with the following IX attributes and meaning are selected for the group:
Commands:
• 11 (Command select open)
• 13 (Command execute open)
• 12 (Command select close)
• 14 (Command execute close)
• 25 (Command cancel)

Indications:
• 10 (Position indication)
• 15 (Device control blocked)
• 16 (Open interlocked)
• 17 (Close interlocked)
• 19 (Selection on monitor)
• 20 (Command enabled)
• 22 (Synchrocheck) (only for Circuit Breakers)
• 41 (Block for opening)
• 42 (Block for closing)
• 55 (AddCause of command)

Integrated Engineering Tool 359


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
360
1MRK500114-UEN Rev. X Section 26
Annex: NCC Command Group Logic

Section 26 Annex: NCC Command Group Logic GUID-BCCB24BD-9012-4F56-BC4E-C97DCC849256 v1

26.1 Introduction GUID-E57F9171-AB92-4CA4-AAAC-D761AB597E76 v1

MicroSCADA requires a specific number of signals to be present for the proper handling of a
command that is sent from the NCC and must be passed on to a local IED.

The logic to build these command groups depends not so much on the protocol between NCC and
MicroSCADA (as a Gateway), but on the Protocol between MicroSCADA and the local IED.

For some known and predefined command groups, IET600 automatically builds the whole group if
just one signal is pre-selected.

If no such group of signals can be found, IET600 will allow you to create a flexible command group.

26.2 Predefined Command Groups GUID-34994766-7D9F-4BD6-AEA0-FCBBD7EEA9A8 v1

Specific groups are pre-defined for the following protocols between MicroSCADA and local IEDs in a
Substation:

1. IEC 61850 via OPC


• group of 5 fixed commands and 1 fixed feedback indication for circuit breaker,
disconnector and earth switch operation.
• group of 1 command and 1 optional feedback indication for all other commands (e.g. tap
changer operation).
2. IEC 61850 via ISS
• group of 1 fixed command and 1 fixed feedback indication for circuit breaker, disconnector
and earth switch operation.
• group of 1 command and 1 optional feedback indication for all other commands (e.g. tap
changer operation).
3. IEC 101/104
• group of 1 fixed command and 1 fixed feedback indication for circuit breaker, disconnector
and earth switch operation.
• group of 2 fixed commands and no feedback indication for circuit breaker, disconnector
and earth switch operation.
4. DNP 3.0
• group of 1 fixed command and 1 fixed feedback indication for circuit breaker, disconnector
and earth switch operation.
• group of 2 fixed commands and no feedback indication for circuit breaker, disconnector
and earth switch operation.
5. LON
• group of 1 fixed command and 1 fixed feedback indication for circuit breaker, disconnector
and earth switch operation.
• group of 4 fixed commands and 1 fixed feedback indication for circuit breaker,
disconnector and earth switch operation.

The logic for building these groups will be described in the following chapters.

26.2.1 Group of 5 Fixed Commands with 1 Fixed Feedback Indication GUID-FBA9B9F7-6EAA-4A2C-9246-4411E14E2C25 v1

This group is used for operation of switches in IEDs connected to the Gateway with protocol IEC
61850 via OPC.

Integrated Engineering Tool 361


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 26 1MRK500114-UEN Rev. X
Annex: NCC Command Group Logic

The logic for assembling this group depends on the MicroSCADA IN attribute or on internal signal
texts. The Signal Text logic is a backup for the IN logic, as the IN is not always available (e.g. in
mirroring configurations).

The IN-based logic is:

1. All Signals must be mapped to a Logical Node with 'CSWI' or 'GGIO' as LNClass.
2. All Signals must reference the same Logical Node.
3. Exactly one signal in the same LN must meet the following conditions:
• IN ends with “ctlSelOff”
• IN ends with “ctlSelOn”
• IN ends with “ctlOperOff”
• IN ends with “ctlOperOn”
• IN ends with “ctlCan”
• IN contains “Pos.stVal”

The Signal-text-based logic is:

1. All Signals must have the same MicroSCADA LN.


2. All Signals must have Analogue Output as MicroSCADA Process object type (PT).
3. Exactly one signal with the same MicroSCADA LN must meet the following conditions:
• Internal Signal text contains both select and open
• Internal Signal text contains both select and close
• Internal Signal text contains both execute and open
• Internal Signal text contains both execute and open
• Internal Signal text contains cancel
• Internal Signal text contains position and MicroSCADA IX = 10
(here, the MicroSCADA IX is intended to prevent conflicts with duplication in redundancy
configurations, which typically contain several “position” signals on indexes 10, 110 and
210)

(Sequence and capitalization do not matter, e.g. “Command open select” and “Select open” would
both fulfill the first condition above).

26.2.2 Group of 1 Fixed Command with 1 Fixed Feedback Indication GUID-103E66B1-06FD-410C-9278-94FD05560C36 v1

This group is used for operation of switches in IEDs connected to the Gateway with protocols IEC
101/104, IEC 61850 via ISS, DNP 3.0 or LON.

The logic for assembling this group depends on the MicroSCADA LN and IX. It is:

1. All Signals must have the same MicroSCADA LN.


2. Exactly one signal in the same LN must meet the following conditions:
• IX is 13 and is of any “output” Process object type (this signal will be taken as command)
• IX is 10 and is of Process object type “Double Binary Indication” (this signal will be taken
as feedback indication)
3. No signal in the same LN is allowed to meet the following conditions:
• IX is 11
• IX is 12
• IX is 14

(So a group of signals with LN C1Q01QA1 containing indexes 10, 13 and 20 would allow to form
such a group, whereupon a group of signals with LN C1Q01QA1 containing indexes 10, 11, 12
and 13 would prohibit the creation of such a group)

For protocol IEC 61850 via ISS before assembling a group depending on the MicroSCADA LN and
IX, the logic tries to assemble a group depending on the MicroSCADA IN attribute.

362 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 26
Annex: NCC Command Group Logic

The IN-based logic is:

1. All Signals must be mapped to a Logical Node with 'CSWI' or 'GGIO' as LNClass.
2. All Signals must reference the same Logical Node.
3. Exactly one signal in the same LN must meet the following conditions:
• IN ends with “Pos.Oper.ctlVal”
• IN contains “Pos.stVal”

26.2.3 Group of 2 Fixed Commands with no Feedback Indication GUID-707A6961-B8F0-4916-9120-DB88F28E5CF7 v1

This group is used for operation of switches in IEDs connected to the Gateway with protocols IEC
101/104.

The logic for assembling this group depends on the MicroSCADA LN and IX. It is:

1. All Signals must have the same MicroSCADA LN.


2. All Signals must have the same Process object type which must be of an “output” type.
3. Exactly one signal in the same LN must meet the following conditions:
• IX is 11
• IX is 12 (this signal will be taken as feedback indication)
4. No signal in the same LN is allowed to meet the following conditions:
• IX is 10
• IX is 13
• IX is 14

(So a group of signals with LN C1Q01QA1 containing indexes 11, 12 and 20 would allow to form
such a group, whereupon a group of signals with LN C1Q01QA1 containing indexes 10, 11, 12
and 13 would prohibit the creation of such a group)

26.2.4 Group of 4 Fixed Commands with 1 Fixed Feedback Indication GUID-ECC76AC2-6BDB-4F98-921E-1D1287240172 v1

This group is used for operation of switches in IEDs connected to the Gateway with protocol LON.

The logic for assembling this group depends on the MicroSCADA LN and IX. It is:

1. All Signals must have the same MicroSCADA LN.


2. All Signals must have the same Process object type which must be of an output type, except
the one with IX = 10.
3. Exactly one signal in the same LN must meet the following conditions:
• IX is 10 and is of Process object type Double Binary Indication (this signal will be taken
as feedback indication)
• IX is 11
• IX is 12
• IX is 13
• IX is 14

(So a group of signals with LN C1Q01QA1 containing indexes 10, 11, 12, 13 and 14 would allow to
form such a group, whereupon a group of signals with LN C1Q01QA1 containing indexes 10, 11, 12
and 13 would prohibit the creation of such a group).

26.3 Flexible Command Groups GUID-4B793FF2-ACD0-4FD9-B1D4-1238EFC7D8D3 v1

A flexible command group is created, if none of the predefined command groups defined above can
be found.

Integrated Engineering Tool 363


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 26 1MRK500114-UEN Rev. X
Annex: NCC Command Group Logic

To a flexible command group, an unlimited number of unspecified commands can be added.


However, a flexible command group may contain either 0 or 1, but not several feedback indications.

364 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 27
Annex: IED Capabilities

Section 27 Annex: IED Capabilities GUID-D7FE4582-8DCE-47D6-80E2-EDF908CDE657 v1

27.1 Introduction GUID-D7DF40B9-16CD-45BE-9AAD-68B00B01BD46 v1

When engineering Dataflow with IEC-61850-based configuration tools, some problems appeared:

1. IED services were not always properly defined.


2. The IED services defined in IEC 61850 were interpreted differently by different vendors.
3. Some IED services/restrictions were not defined in IEC 61850.

To deal with these issues, IET600 introduced ‘IED Capabilities’ which allowed to either define default
values for service that were often missing or define override values for services which are known to
often be defined wrongly.

Most of the problems/ambiguities have been corrected and missing services added in IEC 61850,
Ed.2; their proper usage will hopefully render the IED capabilities described in this chapter obsolete
at some stage. However, as there are still many ICD files with incomplete information, IET600 still
provides these capabilities to allow proper engineering with such files. Chapter "OI Settings on
Project"describes the capabilities provided by IET600 in detail, chapter "OI Settings for MicroSCADA"
shows how to resolve some known problems via IED capabilities.

27.2 Capabilities Description GUID-86CD3682-EAC3-4CD3-A76C-C5CEFE22FAFA v1

The IED Capabilities editor is shown in the IEDs tab and shows the following properties:

1. General IED properties that serve as identification of a set of IED Capabilities:

Property Description
Manufacturer IED manufacturer
IED Type IED Type / Family
Configuration Version IED configuration version, allows to define capabilities
for a specific version of an IED

To apply IED capabilities to a specific IED, IET600 first looks for a capability that matches the
IED in question by Manufacturer, IED Type and Configuration Version; then by Manufacturer and
IED Type only, then by Manufacturer only. If still no matching template is found, then the Default
capability (without Manufacturer or IED Type or Configuration Version) is applied.

Be aware that the Default Capability is very conservative, it does not allow editing of
Dataflow items. This has historical reasons (most “unknown” IEDs did not allow the
editing of its Dataflow), it may not apply in every case.

2. Capabilities related to RCB Client configuration:

Property Description
Update Report Client Mapping TRUE will cause the Report Clients to be set from
default clients automatically, e.g. when importing an
ICD/IID file with RCBs but without clients.
Can Modify Report Enabled Max TRUE if Report Enabled Max attribute can be
modified.

3. Capabilities related to serve as initialization values for IET600-specific attributes:

Integrated Engineering Tool 365


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 27 1MRK500114-UEN Rev. X
Annex: IED Capabilities

Property Description
Default Report Control Block Status Default status of RCB when imported from SCL file.
“IED-defined, read-only” prevents any changes to the
imported RCB. “IED-defined, configurable” allows
changes to be made to the imported RCB.
Default Goose Control Block Status Default status of GCB when imported from SCL file.
“IED-defined, read-only” prevents any changes to the
imported GCB. “IED-defined, configurable” allows
changes to be made to the imported GCB.
Default Sampled Values Control Block Status Default status of SVCB when imported from SCL file.
“IED-defined, read-only” prevents any changes to the
imported SVCB. “IED-defined, configurable” allows
changes to be made to the imported SVCB.
Default Dataset Status Default status of Dataset when imported from SCL
file. “IED-defined, read-only” prevents any changes to
the imported Dataset. “IED-defined, configurable”
allows changes to be made to the imported Dataset.

Declaring any of the above items as “IED-defined, read-only” will prevent their editing, even
though the IED services might allow editing.
Declaring any of the above items as “IED-defined, configurable” will allow their editing only
insofar, as it is allowed by the IED services also.

4. Capabilities related to limitations not defined via SCL file.


While IEDs may specify a maximum number of instances per RCB in the SCL file, this does not
correspond to the number of concurrent connections which are possible. This property provides
an additional parameter to take such limits into account:

Property Description
Default Max Concurrent Equivalent to the IED Service DynAssociation.Max,
Report Clients any value in the ICD/IID file will be observed. In Ed. 1
the service exists, but as a Boolean, not as a number.
Therefore it may be set here.
Maximum number of RCB clients that can
concurrently connect to an IED, therefore indirectly
the maximum number of allowed RCB clients/
instances.

In IEC 61850, Ed.2, the service “DynAssociation.Max” has been given the meaning covered by
this capability. If service DynAssociation.Max is specified, it takes precedence over the above
parameter.

5. Capabilities that serve to set default values or override values of an SCL file in project.
The override properties serve to override values contained in an SCL file. If these values are not
defined, values from the SCL file will be observed.

The default values serve only to set default values, if none are defined by IEC 61850. This is typically
the case for IED Services which were introduced only in Ed.2; for Ed.1 IEDs, no default values can
safely be assumed, therefore they may need to be configured here.

366 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 27
Annex: IED Capabilities

Property Description
Override for Service Change the maximum number of Datasets from the
ConfDataset Max value specified in the SCL file. If not defined, values from
the SCL file will be observed.
Override for Service Change the maximum number of Dataset attributes from
ConfDataset Max Attributes the value specified in the SCL file. If not defined, values
from the SCL file will be observed.
Override for Service TRUE means that a preconfigured Dataset may be
ConfDataset Modify modified.
Override for Service Specifies the buffer modes (buffered, unbuffered, both)
ConfReportControl BufMode allowed to configure for new control block types. If not
defined, values from the SCL file will be observed.
Default for Service Any value of the IED Service in the ICD/IID file will be
ConfReportControl BufConf observed. In Ed. 1 the service does not exists and there
is no default value, therefore it may be set here.
Checked means that the buffered attribute of
preconfigure report control blocks can be changed via
SCL
Unchecked means that they cannot be changed.
Override for Service Maximum number of instantiated report control blocks. If
ConfReportControl Max this number is equal to the number of preconfigured
instances, then no new instances can be created.
Override for Service Goose Max Maximum number of GOOSE control blocks, which can
be configurable for publishing (max=0 means that the
device is only a GOOSE client)
Default for Client Service Goose Any value of the IED Service in the ICD/IID file will be
observed. In Ed. 1 the service does not exists and there
is no default value, therefore it may be set here.
Checked means that an IED can be configured as a
GOOSE Client.
Default for Client Service SampledValues Any value of the IED Service in the ICD/IID file will be
observed. In Ed. 1 the service does not exists and there
is no default value, therefore it may be set here.
Checked means that an IED can be configured as an
SVCB Client.
Default for Client Service Buffered RCB Any value of the IED Service in the ICD/IID file will be
observed. In Ed. 1 the service does not exists and there
is no default value, therefore it may be set here.
Checked means that an IED can be configured as a
Client for buffered RCBs.
Default for Client Service Unbuffered RCB Any value of the IED Service in the ICD/IID file will be
observed. In Ed. 1 the service does not exists and there
is no default value, therefore it may be set here.
Checked means that an IED can be configured as a
Client for unbuffered RCBs.
Table continues on next page

Integrated Engineering Tool 367


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 27 1MRK500114-UEN Rev. X
Annex: IED Capabilities

Property Description
Enforce Fix Service Settings A Tissue for IEC 61850 has specified a more precise
logic in which configurations Datasets and Control
Blocks may or may not be deleted. One important rule
was that deletion is not possible if any of the Control
Block handling attributes is “fix” (i.e. they cannot be
edited by the System Configuration Tool).
Unfortunately, many IED Configuration Tools have not
backported this logic to Ed. 1 IEDs, which may cause
IET600 to refuse to delete Datasets and CBs for such
IEDs. ‘Override for Fix Service Settings’ allows to
override this behavior.
Related to 'xxxSettings' IED Services (ReportSettings,
GSESettings, etc.) and their attributes.
TRUE - CBs cannot be deleted or added and datasets
and their references cannot be modified, independently
from IED Services 'xxxSettings' configuration.
FALSE - CBs can be deleted or added and datasets and
their references can be modified, independently from IED
Services 'xxxSettings' configuration.
UNDEFINED - The rule below will be taken into account
in order to delete or add CBs and datasets.
'xxxSettings' IED Services rule:
According to a rule inside the IEC61850 standard, if one
of the 'xxxSettings' attribute has 'Fix' value, then CBs
cannot be deleted or added.
Additionally, if some 'xxxSettings.datSet' is 'Fix', the data
set and its references cannot be modified.
If 'Enforce Fix Service Settings' has some value, then the
'xxxSettings' configurations will be ignored.
Override for SMVSettings Service Samples Per Sec Provides a way to override the value of
'SMVSettings.samplesPerSec'.
Override for SMVSettings Service nofASDU Allows to override 'SMVSettings.nofASDU' (Number of
Application Service Data Unit). Possible values are:
Conf - Allows for configuration.
Fix - Does not allow for configuration. Number is fixed.

1. Capabilities related to Disturbance Recording.


These properties serve to provide default values. Values from the SCL file take precedence over
these default values.

Property Description
Default Disturbance Recorder Capability Allows to specify whether an IED provides
Disturbance Recording (normally, an IED should
indicate this by providing an RDRE LN in its DATA
model, this is mainly intended for legacy IEDs)

2. Capabilities related to File Transfer


These properties serve to provide default values if respective elements are missing in the.
Values from the SCL file take precedence over these default values.
This is mainly used in connection with Disturbance Recording to specify the possible File
Transfer protocols.

368 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 27
Annex: IED Capabilities

Property Description
Default for MMS File Any value of the IED Service in the ICD/IID file will be
Transfer Capability observed. In Ed. 1 the service does not exists and
there is no default value, therefore it may be set here.
Allows to specify whether an IED supports File
Transfer via MMS
Default for FTP File Any value of the IED Service in the ICD/IID file will be
Transfer Capability observed. In Ed. 1 the service does not exists and
there is no default value, therefore it may be set here.
Allows to specify whether an IED supports File
Transfer via FTP
Default for FTPS File Any value of the IED Service in the ICD/IID file will be
Transfer Capability observed. In Ed. 1 the service does not exists and
there is no default value, therefore it may be set here.
Allows to specify whether an IED supports File
Transfer via FTPS

3. Miscellaneous Capabilities
These properties serve to provide default values to configure some behavior which is not
adequately represented by IED services.

Property Description
Enforce Single MMS message Allows to enforce that an IED sends RCB/Datasets in
a single telegram (equivalent to the parameter Send
single message MMS writes in the 61850-OPC-
Gateway configuration tool).
Indexed RCBs Allows to specify whether an IED understands a
request for indexed RCBs (some Ed.1 IEDs require
specifically that the client ask for a non-indexed RCB;
Ed.2 specifies that all IEDs must understand indexed
RCBs).
Dynamic Datasets Allows to specify whether a 61850-OPC-Gateway
Client shall configure dynamic Datasets on a Server
IED (up to the limit that the services of the Server IED
allows).
Main usage is to set this property to false to tell a
61850-OPC-Gateway Client not to use dynamic
Datasets even though the Server IED may be capable
to provide them.

4. Capabilities related to GCB/SVCB Supervision


These properties serve to define possibility to create supervision for GCB and SVCB.

Integrated Engineering Tool 369


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 27 1MRK500114-UEN Rev. X
Annex: IED Capabilities

Property Description
Configuration of GCB Supervision Allows to specify possibility to create supervision for
clients in GCB Clients tab. There are three possible
states:
None – creation of supervision is not allowed.
Manual – creation of supervision can be done by
clicking Create supervision for clients in selection
on Grid in GCB clients Tab.
Automatic – Supervision will be created if possible
automatically by clicking Connect GCBs to Clients in
selection on Grid in GCB clients Tab.
Configuration of SVCB Supervision Allows to specify possibility to create supervision for
clients in SVCB Clients tab. There are three possible
states:
None – creation of supervision is not allowed.
Manual – creation of supervision can be done by
clicking Create supervision for clients in selection
on Grid in SVCB clients Tab.
Automatic – Supervision will be created if possible
automatically by clicking Connect SVCBs to Clients
in selection on Grid in GCB clients Tab.

5. Capabilities related to multicast message security handling options.

Property Description
Override for Service McSecurity Signature If true – calculation of a signature is supported.
Override for Service McSecurity Encryption If true – message encryption is supported.

27.3 Common Corrections with IED Capabilities GUID-3C0CFC72-4D65-4E94-B196-5EB0ABD29C07 v1

There are typical cases where IED capabilities are needed, they are described here.

27.3.1 Service ConfReportControl, Max attribute GUID-66ED8398-17E4-47CC-A178-50456430DA3C v1

Due to a vague wording in the IEC 61850, this attribute has been misinterpreted to be the maximum
number of possible Report Control Blocks, rather than being the maximum number of possible
Report Control Block instances.

A typical example is an IED with 8 fixed RCBs where IET600 is supposed to add clients only. To
prevent an addition of RCBs, the IED manufacturer delivers an IED file with ConfReportControl.Max
= 8; each RCB has RptEnabled.Max = 4. The intention is to allow up to 4 clients for each RCB,
allowing a total number of 32 clients (and therefore 32 RCB instances). However, if you try to
configure clients in the RCB Client Editor, IET600 will allow you to configure a total of 8 clients only
and will block you from configuring more (which is not the intention of the IED manufacturer).

To allow proper configuration of such an IED, define a new IED Capability for its Manufacturer and
Type and provide an override value for the Service ConfReportControl, Max as shown below:

370 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 27
Annex: IED Capabilities

IEC202100692 V1 EN-US

27.3.2 Service ConfDataset, maxAttributes attribute GUID-0021CD86-C1EF-444A-9A9F-05F24A723F1A v1

The interpretation of this attribute has changed due to a clarification in the IEC 61580 standard.

Up to IET600 5.2, this value was interpreted to mean the maximum numbers of Data Attributes
(DAIs) that could be contained in a Dataset. So an entry CSWI.Pos[ST] has 3 attributes (stVal, q and
t) and therefore contributed 3 attributes to the total.

However, after clarification in IEC 61850, this must be interpreted to mean Dataset entries. So a
CSWI.Pos[ST] is one entry, irrespective of how many attributes it has, and therefore contributes 1
entry to the total.

To stay compatible with existing, already engineered projects, IET600 FP1 uses the following logic:

Integrated Engineering Tool 371


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 27 1MRK500114-UEN Rev. X
Annex: IED Capabilities

• in all ABB Ed.1 IEDs, the value is interpreted to mean attributes. This corresponds to the
behavior of the IED Configuration tool PCM600, which keeps existing maxAttributes values for
Ed.1 IEDs and counts attributes for Ed.1 IEDs.
• in all ABB Ed.2 IEDs, the value is interpreted to mean Dataset entries. This corresponds to the
behavior of the IED Configuration tool PCM600, which adjusts the maxAttributes values for Ed.2
IEDs accordingly and counts entries for Ed.2 IEDs.
• in all non-ABB IEDs, the value is interpreted to mean Dataset entries. This conforms to the
interpretation of most, if not all, 3rd-party vendors.

If any IED does not fit the above logic, an engineer can use the IED capabilities and set Override for
Service ConfDataSet Max Attributes to an appropriate value.

27.3.3 Service ConfDataset, Modify attribute GUID-262D241B-CF15-4C76-8895-0CC5337BAE11 v1

The specification of this service in IEC 61850 says: “TRUE means that preconfigured datasets may
be modified”. Unfortunately, in an SCD file, there is no way to distinguish a preconfigured Dataset
from one that has been generated at some stage during the engineering process.

Some vendors that do not provide preconfigured Datasets, set ConfDataset.Modify to false with the
idea that as there are no preconfigured datasets, they cannot be modified either. IET600 however,
interprets this flag as meaning that no Dataset can be modified, not even the ones configured in
IET600 and will give an appropriate error message when the user tries to do so. In such cases, it is
necessary to configure an IED Capability for this IED Type and Vendor with “Override for Service
ConfDataset Modify” set to TRUE.

27.3.4 Client Services GUID-8DBD4B63-150E-4C2B-A2C2-92A8DC7297CA v1

Client Services have been introduced in IEC 61850 Ed.2 to allow to specify precisely for which
Control Blocks an IED can serve as a client. Default value in case of a missing service is that an IED
cannot be a client to the particular Control Block in question.

Older IET600 versions had a fixedly programmed logic that all IEDs containing an IHMI, ITCI or ITMI
node were assumed to be possible RCB clients. In IET600, this is not the case anymore; such clients
need either to have appropriate services or appropriate overrides configured.

When creating a new project in IET600, IED capabilities will be configured to take missing services
into account:

IEC202100693 V1 EN-US

372 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 27
Annex: IED Capabilities

However, if you migrate a project created in an older version to IET600 5.3, you may experience that
you suddenly cannot configure RCB clients as you used to. This is because these client overrides in
the IED capabilities are missing; please take the above picture as a template how to configure them
to avoid problems in RCB Client configuration.

27.3.5 Dataflow Cannot be Created or Edited at All GUID-CEA1C89D-A17D-499B-88AF-DF3A01295241 v1

This will most commonly happen when you try to create or edit Dataflow of an IED whose type is not
yet know to IET600. In this case, IET600 uses the Default Capability which sets all Dataflow items to
read-only; to prevent accidental misconfiguration.

To allow proper configuration of such an IED, look up the Manufacturer and IED Type in the ‘IED
Status Editor’. Then define a new IED Capability for this Manufacturer and IED Type, and set the
capabilities as shown below:

IEC202100694 V1 EN-US

This is the most neutral configuration; if all IED services are defined correctly (which is possible only
for an Ed.2 IED), Dataflow configuration should be possible now as intended by the IED
manufacturer.

Integrated Engineering Tool 373


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 27 1MRK500114-UEN Rev. X
Annex: IED Capabilities

If Dataflow configuration still does not work as intended, you will most likely get a
hint which service is at fault in a Log entry or Dialog message. You may try to
change some IED capabilities to get the desired result. However, please be very
careful when doing this: consult Manufacturer documentation and test and verify
results of such changes with extreme care, as they may otherwise result in improper
functioning of a system.

374 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 28
Annex: IET600 and IEC 61850 Edition Handling

Section 28 Annex: IET600 and IEC 61850 Edition


Handling GUID-B371DFA5-55BB-4A40-9F97-5BAA9FB9FAFB v1

28.1 IEC 61850 Classification GUID-4EED9CA5-4C73-4828-BF89-A3A4ABADD569 v1

28.1.1 IEC 61850 Edition, Version and Revision GUID-AE267A5E-0209-4B12-AF2D-C67BCA567354 v1

To classify IEC 61850 releases, the standard has defined a version and a revision.

• “Version” refers to the year of publication of the specification.


• “Revision and Release” refers to a revision indicator. This indicator is required to differentiate
revisions and releases of the standard between two versions. If it is missing in any versioning,
“A” is assumed.

The following table provides an overview:

Edition Year of release Version Revision and Release


Edition 1 2003 2003 A
Edition 2 2007 2007 A/B2
Edition 2.1 2018 2007 B4

28.1.2 IEC 61850 Namespaces GUID-C87597E7-4A80-4409-B7BC-5E5F34163978 v1

A “namespace” in IEC 61850 terminology is uniquely defined by a version/revision combination.

Regarding the configuration of a Substation, IEC 61850 has 2 particularly relevant parts:

• IEC 61850‑6, which defines the “System Configuration description Language” or SCL schema
(which is an XML namespace).
The namespace of an SCL file is defined by the “version” and “revision” attributes of the topmost
‘SCL’ element (not to be confused with “version” and “revision” attributes of the ‘Header’
Element, a sub-element to the ‘SCL’ element).
• IEC 61850‑7‑1/2/3/4, which defines the namespaces of the DATA of an IED, i.e. the definitions
of Common Data Classes, Data objects, Logical Nodes etc.
The DATA namespace of an IED is declared in the DATA attribute “[first Logical
Device].LLN0.NamPlt.ldNs”

It is a bit confusing, but important to understand that the above-mentioned two namespaces are
completely independent of each other.

It is possible to have:

• an IED which contains a CDC with a new Attribute Type that requires IED Namespace 2007B,
but which is exported into an ICD file which declares the SCL namespace as 2003A.
• an IED with a ServerAt element that requires an Export into an ICD file with XML Namespace
2007A, but the IED DATA model itself is namespace 2007B

28.1.3 SCL Elements Conflicting With SCL Namespace Version 2003 GUID-0A4A2123-99E2-4DC0-B0F5-1962415A9DAA v1

The following elements require an SCL file to declare a namespace with a version of 2007:

• Functions that are attached to Voltage Levels or Bays (in the Edition 1 XML scheme, a Function
could only be attached to a Substation).

Integrated Engineering Tool 375


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 28 1MRK500114-UEN Rev. X
Annex: IET600 and IEC 61850 Edition Handling

This is a helpful element to provide an additional layer of elements in the Substation Tree and
can make modeling e.g. of a 1.5-CB-Bay easier. However, this can often be worked around by
using a clever naming scheme to avoid upgrading a project to a newer version.
• ServerAt element which makes it possible that a server can supply its data via several Access
Points; this did not exist in the in the Edition 1 XML scheme).
This will probably be required by bay-level protection and control IEDs which receive
measurement data via sampled value streams (e.g. from an ABB SAM600 IED) on a process
bus and at the same time participate in GOOSE and RCB communication on the station bus. If
an IED configuration tool specifies a ‘ServerAt’ element in an ICD file, there is no workaround in
IET600; a project with such IEDs must have version 2007.
• IEC 61850 Edition 2 allows to define IED capabilities more precisely by adding new services. It
also allows to specify services on the level of an Access Point, not only for the IED as a whole.
This is helpful for Dataflow configuration. If an IED configuration tool specifies such services in
an ICD file, there is no workaround in IET600; a project with such IEDs must have version 2007.
• SED Data exchange.
The SED file and its related attributes are specified only in IEC 61850 Edition 2.
As a workaround, one could exchange IEDs with an IEC 61850 Edition 1 project in the form of
ICD or SCD files.
However, an SED data exchange has a Dataflow configuration as purpose. When using the
above workaround, all participating IEDs should be of the same version/revision to avoid
compatibility problems.
Also, the above workaround does not provide a checkout/protection mechanism; it therefore
requires an experienced engineer to prevent incorrect or erroneous configuration changes.

28.1.4 IED DATA Conflicting With Namespace Version 2003 GUID-DDFFFDEB-1DF1-4F30-995A-15396156460B v1

The following elements require an IED to declare its DATA namespace with a version of 2007:

• Usage of any DATA element with new Attribute data types defined only in in IEC 61580, Edition
2.
• DATA attributes with new Functional Constraints defined only in in IEC 61580, Edition 2.
• Usage of DATA item names with lengths that exceed allowed maximum lengths as defined in
IEC 61580, Edition 1 (the allowed lengths for miscellaneous names have been extended in IEC
61580, Edition 2). However, this can often be worked around by using a naming convention for
those items specified in IET600 (e.g. IEDs, Datasets, Control Blocks) which respects the limits
of Edition 1 and should not be a problem in practice.

28.2 IEC 61850 Compatibility Issues GUID-252A457A-F576-4E64-927B-5D21A70C2FBE v1

28.2.1 SCL Namespace compatibility Problems. GUID-6C36B6CB-4CFF-42F4-A303-8199C4B94B38 v1

Several Edition 1 configuration tools have implemented a strict XML checking when importing an
SCL file and reject an import, if this strict check fails. Such tools may reject an SCL file with a 2007
XML schema, because it contains elements unknown to the Edition 1 configuration tool.

As the migration of all tools of all vendors to IEC 61580, Edition 2 will take some time, one has to be
aware of this issue in retrofit projects.

From Edition 2 (2007A) onwards, it has been defined that a configuration tool must not reject a file
based on XML Schema checking only; it must be able to simply skip unknown elements. The
intention is to provide backward and forward compatibility at least regarding the SCL files. However,
this still may cause engineering problems. E.g. if an IED version 2007B defines IED Services to
restrict Dataflow engineering which a System Tool version 2007A does not know, a misconfiguration
may result.

376 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 28
Annex: IET600 and IEC 61850 Edition Handling

28.2.2 Name Length Problems GUID-4CE07004-6499-4496-8C96-3905BB1C6447 v1

Edition 2 has extended the length allowed for most names (DATA items, Dataflow items, IED names
etc.).

Edition 1 tools can be expected to either reject or misinterpret files with longer names than permitted
by Edition 1. This makes e.g. Ethernet Switch models according to IEC/TR 61850-90-4 non-
compliant with Edition 1.

28.2.3 Dataflow Compatibility Problems GUID-555402C2-E5D3-4CC9-9D90-4FB23C9E1E83 v1

IEDs which use new Attribute types according to the Edition 2 specification cannot have Edition 1
IEDs as clients, as those clients will not know about the lengths of the new data types and therefore
cannot analyze and interpret a Dataset properly.

28.2.4 CDC compatibility problems GUID-BAEF08FC-A57C-4DCC-9585-65B44E4DFE48 v1

Edition 1 of IEC 61850 allowed user-defined Common Data Classes (CDCs), Edition
2 does not allow this anymore. This is a serious forward compatibility break: an
Edition 1 IED may declare a user-defined CDC; an Edition 2 IED (or its IED
configuration tool) which is configured to receive Dataflow based on such CDCs may
refuse import or proper configuration in such a case.

Integrated Engineering Tool 377


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
378
1MRK500114-UEN Rev. X Section 29
Annex: IET600 Mixed System Engineering

Section 29 Annex: IET600 Mixed System


Engineering GUID-D8634AAA-1953-497A-B1F6-998C00C8DAB5 v1

29.1 Mixed Systems, Engineering Scenarios GUID-525792F0-6C49-43CA-BCAB-6871FD9B76CC v1

Below, some engineering scenarios and potential solutions and restrictions will be described:

1. Extension of an existing Substation that was created as IEC 61580, Edition 1 project.
2. Creating a new Substation, which needs to integrate some 3rd-Party IEDs that are not yet
available in Edition 2.
3. Engineering a Mixed Substation, where Edition 1 and Edition 2 IEDs are required by the
customer.

29.1.1 Extension of an Existing Substation with Edition 1 IEDs GUID-33844E14-CA92-468A-B932-3E10BD79CB7E v1

Recommended approach is not to use any Edition 2 IEDs at all, but use Edition 1 IEDs, preferably of
the same generation that are already used in the existing substation.

IEC202100695 V1 EN-US

This has several advantages:

Integrated Engineering Tool 379


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 29 1MRK500114-UEN Rev. X
Annex: IET600 Mixed System Engineering

• The customer does not need to update all configuration tools and migrate existing substation
configurations to a new version.
• New IEDs are identical to old IEDs, the customer does not need to keep IEDs of different
versions as spare parts.

Features introduced with IET600 5.3 FP8 allows to combine Edition 1 and Edition 2 IEDs via
GOOSE/SVCB/RCB and export Edition 1 SCD with downgrade of Edition 2 IEDs, however it comes
with some costs. Detailed description of such procedure is in the following chapters

29.1.2 Mixed Substation Specified by Customer GUID-FE6A114C-EEEE-493F-AD44-54D726B2E9DA v1

A customer might already be using Edition 1 IEDs of a certain manufacturer and type in his other
substations and wants to use the same ones to keep maintenance and spare parts efficient; but on
the other hand he might want to use some new technology available only in Edition 2 IEDs.
Therefore to fulfil his specification, a Substation with both Edition 1 and Edition 2 IEDs needs to be
engineered.

Another situation which frequently occurs, is a new project where the customer requires some
protection IEDs from a 3rd-Party vendor (e.g. Main 1 and Main 2 protection from 2 different vendors;
or e.g. Distance protection with remote trip, which requires specific IEDs of the same vendor and
type at both ends). In this case, the control IEDs are typically from one vendor and of the same
Edition.

If Your target version is Edition 2 You can freely configure GCBs (or SVCBs) between Edition 1 and
Edition 2 IEDs, however experience shows that in many cases, an Edition 1 IED configuration tool
will not be able to import an SCD file with Edition 2 IEDs (which is necessary, if clients are mixed). In
that case to achieve Edition 1 SCD file, downgrade of Edition 2 IEDs is required. Such option is
provided in SCD export dialog, but comes with some costs. You can find more details about it in the
following chapters.

29.2 IET600 Mixed System Engineering GUID-9F8CD6FF-7157-4C77-B137-1CE697405819 v1

Basically the main issue for mixed systems is to create SCD files which all concerned tools can
import and interpret. To solve this issue, IET600 allows to export several SCD files, either as
complete SCD file, subset files (all Edition 1 IEDs into one SCD file and all Edition 2 SCDs into one
SCD file) or complete Edition 1 project with downgraded Edition 2 IEDs. Subset SCD export,
however, is only possible, if there is no Dataflow exchange between these IEDs, otherwise, the
communication cannot be configured correctly. Third option will be exported as one file only if there
are no ServerAts which would cause split into several files divided by subnetworks. Before using this
option it is recommended to get along with following scenarios that You can encounter during such
downgrade:

• In case there are no ServerAt access points, the project can be exported as one Edition 1 SCD
file. In this case the Edition 2 IEDs are downgraded according to rules, defined in Edition 2.1 of
IEC 61850-6.
The following picture indicates such a case:

380 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 29
Annex: IET600 Mixed System Engineering

IEC202100718 V1 EN-US

• If project contains any IED of Edition 2 with ServerAt element, splitting of project into several
files might be necessary. It is done so, because ServerAt is not supported in Edition 1 SCL,
therefore it must be substituted with well-known in Edition 1 Server. Having Edition 2 IED with
S1 Server in one subnet-work and S2 ServerAt connected to the other means that the project
must be divided into two SCD files. The first contains the whole model (IEDs, Substation,
Communication) of the first subnetwork with S1 Server. The second SCD file contains the model
of the second subnetwork with S2 ServerAt transformed into Server. The following picture
indicates such a case:

Integrated Engineering Tool 381


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 29 1MRK500114-UEN Rev. X
Annex: IET600 Mixed System Engineering

IEC202100719 V1 EN-US

Subnetwork1.scd contains only ‘S1’ of IED2, Subnetwork2.scd contains only ‘S2’ converted to a
Server. It is done so to avoid duplication of servers models in one IED.

There is a number of downgrading rules specified in IEC61850-6 Annex I, which are applied, if
needed, when including Edition 2 IEDs in Edition 1 SCL files. It is recommended to get familiar with
those rules before performing such operation.

29.2.1 Put IEDs of Different Versions Into Different Subnetworks GUID-13400F7B-9D89-4EB7-ACBE-60E003A384AC v1

If no data exchange between IEDs of different IEC 61850 editions is required, the approach of
solving mixed system engineering is to put IEDs of different versions into different Subnetworks. You
can easily identify subnetwork version by looking at the icons of communication tree:

382 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 29
Annex: IET600 Mixed System Engineering

IEC202100697 V1 EN-US

• If the Subnetwork Protocol is not IEC 61850, the Subnetwork icon will be missing (e.g.
AA3WF912, an NCC connection with an NCC 104 protocol).
• If all IEDs on the Subnetwork evaluate to Edition 1, the Subnetwork icon ‘E1’ will be shown.
• If all IED on an IEC 61850 subnetwork evaluates to Edition 2, the Subnetwork icon ‘E2’ will be
shown.
• If some IEDs on an IEC 61850 subnetwork evaluate to Edition 1 and some to Edition 2, the
Subnetwork icon ‘M’ for ‘mixed’ will be shown.

29.2.2 SCD Export GUID-65A3C9AA-B2FD-467D-9B12-D5D7E7C7C32A v1

To export an SCD file you can choose one or many of following options:

Integrated Engineering Tool 383


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 29 1MRK500114-UEN Rev. X
Annex: IET600 Mixed System Engineering

GUID-46F0633A-BEEC-4A49-9132-4AAE5B9BC808 V1 EN-US

1. Allows to select destination path and file name.


2. An SCD file of all Subnetworks (Edition 2 and Edition 1 upgraded to be compatible with Edition 2
- a subset of the overall SCD file). Purpose of this file is that Edition 2 IED configuration tools
can import and use it. Therefore, it should contain nothing which is not Edition 2 compatible
(customer-defined CDCs). This file will contain all IEDs in Subnetworks, the Data Type
Templates of those IEDs, the Subnetworks and the Substation Section (stripped of LNodes
referenced by IEDs not contained in the SCD file, but containing all Voltage Levels and Bays,
independent of the exported IEDs).
3. Edition 1 SCD files per subnetwork. These files contain all IEDs. Edition 1 IEDs are exported
directly, Edition 2 are downgraded accordingly to rules specified in the standard. If any of the
Edition 2 IEDs contains ServerAt access points, they will be substituted by normal Servers. In
that case the project is splitted into several SCL files divided by subnetworks to avoid duplication
of servers. The files are listed in the SCD export dialog with names created out of subnetwork
name and description. If You select more than one item form the list – same amount of files will
be exported.
4. Legacy Exports
4.1. An overall SCD file, containing everything in the project with version defined by its content.
This file will contain all IEDs, the full Substation Section and the full communication
section.

May not be compatible with Edition 1 or Edition 2.

4.2. An SCD file of all Edition 1 Subnetworks only (a subset of the overall SCD file). Purpose of
this file is that Edition 1 IED configuration tools should be able to import this file. Therefore
it should contain nothing which is not Edition 1 compatible. This file will contain all IEDs in
Subnetworks classified as Edition 1, the Data Type Template of those IEDs, the
Subnetworks, and the Substation Section (stripped of LNodes referenced by IEDs not
contained in the SCD file; and stripped of items which are not Edition-1-compliant, e.g.
Functions below a Voltage Level or a Bay, but containing all Voltage Levels and Bays,

384 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 29
Annex: IET600 Mixed System Engineering

independent of the exported IEDs). This option is disabled if there are no Edition 1
subnetworks in the project.

A Switch DATA model is neither Edition 1 nor fully Edition 2 compliant. However, IET600 creates a
Switch DATA model for saving configuration information, even if the Switch is in the end
communicating with SNMP rather than IEC 61850.

Due to these compatibility issues, a Switch is typically only exported as IED with its Access Points
and Connected Access Points (including addressing information). When exporting an Edition 2 file,
the user may explicitly check ‘Include Switch Model’ to also export the Switch DATA model. This is
currently only useful, if a Switch is actually communicating with IEC 61850 with e.g. the Station HMI
for supervision In such cases, ITT600 Explorer may also use the SCD file with the full Switch model
for analyzing the communication.

29.2.3 SCD files Version 2007A GUID-1F96D542-090D-4183-A55E-7C5991886A23 v1

IET600 does not provide SCL files according to version 2007A.

This should not normally cause a compatibility problem for SCL file import and export: IEC 61850
demands from version 2007A onwards that an older configuration tool must not refuse the import of a
newer SCL version because it does not understand its elements.

However, an IED configuration tool may not be able to display or use newer features;
also it may not understand newer DATA objects from the DATA model. If you have
such a combination (an IED and its configuration tool of Version 2007A,
communicating with IEDs of version 2007B and working with IET600 as a System
configuration tool exporting files according to 2007B), verify in advance whether this
combination has been tested and is known to work.

29.3 IET600 Versioning of IEC 61850 Items GUID-5ED34DFF-22E0-42D3-9ACF-702ECC662C2F v1

Due to compatibility issues, as mentioned in "IEC 61850 Compatibility Issues", IET600 needs to
evaluate the versions of IEC 61850 items. IET600 needs this versions to then put a version to the
project and to Subnetworks.

The project version is used to export SCL files accordingly. So an “Edition 1” project will export an
SCL file 2003A by default, an “Edition 2.1” project will export an SCL file 2007B.

The Subnetwork version is used in case of mixed projects, to allow the export of partial SCD files
which should be Edition 1 or Edition 2 compliant respectively.

The following chapters describe the logic how IET600 determines project and Subnetwork versions.

29.3.1 Versioning Based on IED DATA Namespaces GUID-8290FD38-1B35-4311-AF1A-A9A4FBD98EA7 v1

A project or Subnetwork which has at least one IED with a Version 2007 Revision B will be classified
as “Edition 2” or “2007B”.

An IED, in turn is classified as “2007B” by IET600, if:

• the ICD/IID file has an appropriate version/revision (2007A or 2007B) e.g. if it is declaring
services according to 2007A or 2007B, or using a ServerAt element
• or if the IED declares its DATA model namespace to be 2007A or 2007B, which means that all
its communication services are behaving according to the specified version/revision. The
relevant attribute to determine this is “[first Logical Device].LLN0.NamPlt.ldNs”.

Integrated Engineering Tool 385


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 29 1MRK500114-UEN Rev. X
Annex: IET600 Mixed System Engineering

29.3.2 Versioning Based on XML Namespace GUID-ADFC8565-0B41-441A-87AB-B8E25760A724 v1

A project which has all IEDs with a DATA namespace 2003A, but uses a function below a Bay would
also be classified as “Edition 2” or “2007B”.

However, as the gains of using this functionality are minor and the restrictions are considerable
(particularly the loss of GCB/SVCB dataflow between Edition 1 and Edition 2 IEDs), any functionality
originating in IET600 which requires a higher version/revision, is disabled. To enable it, the user
needs to reclassify a project manually as 2007B. When trying to do so, IET600 will issue an
appropriate warning and ask the user to confirm the version change.

29.3.3 Versioning of Switch IEDs GUID-F45EBAE9-5987-4B88-ACFB-266DD76D43AB v1

IET600 relies on the DATA model of a Switch to save certain configuration information. However, as
the Switch model is neither Edition 1 nor fully Edition 2 compatible, its versioning is faked by IET600
to be Edition 1 (to avoid incrementing a project version just because of Switches and creating a
mixed system with all its restrictions).

386 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 30
Annex: Client Driven Engineering

Section 30 Annex: Client Driven Engineering GUID-9AB5F5FC-177E-4568-92F8-E9EA6863CE38 v1

30.1 Introduction GUID-7C531DF9-D643-451C-953B-9C4560BECA8C v1

The core of Client Driven Engineering is (as name suggests) the client. In this approach we mainly
focus on client IED, it decides what it needs and then server sends appropriate data to the client. The
default approach is server based engineering where clients can take everything or part of what
server can send. In Client Driven Engineering the server is configured to suit clients’ needs.

30.2 Client Driven Engineering Workflow GUID-D68EF383-888C-4389-BE76-885DA16A40EA v1

30.2.1 Requirements GUID-AC657E8C-C150-4192-B004-46FD2466DCF6 v1

30.2.1.1 IED Capabilities GUID-FDC212DD-CE45-4D34-9FB4-71AE80814F09 v1

In order to use Client Driven Engineering we need client IEDs that support that functionality. In IED
Capabilities Editor there is a special column that indicates whether specific IED type supports Client
Driven Engineering.

IEC202100722 V1 EN-US

30.2.1.2 IED Settings GUID-9F80DDFC-B287-4315-B0C3-CA45E64A0537 v1

When IED has the capability to use Client Driven Engineering you can choose to use Client Driven
Engineering for specific IED in IED Setting Editor.

Integrated Engineering Tool 387


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 30 1MRK500114-UEN Rev. X
Annex: Client Driven Engineering

IEC202100723 V1 EN-US

30.2.1.3 SCL File and Server IED GUID-5BB2B86A-1CF8-4D37-B2FD-AF3B0B90B284 v1

IED from SCL file selected as source must contain ‘inputs’ section and Server IED must exist and not
be protected (protected or missing Server IEDs will be omitted during update).

IEC202100724 V1 EN-US

30.2.2 Workflow GUID-A669EBE3-0418-4308-B915-66242FDB839B v1

Client Driven Engineering is used in process of updating an IED (or IEDs).

388 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 30
Annex: Client Driven Engineering

IEC202100725 V1 EN-US

In Update IED dialog there is a column indicating whether an IED will use Client Driven Engineering
or not. It is a read-only field that follows logic presented below.

Use Client Driven Engineering in Update file has “Inputs” for this IED “Client Driven Engineering” state
IED Settings and at least one Server IED is
selected in “Server IEDs to update”
No - Will not use Client Driven
Engineering
Yes No Will not use Client Driven
Engineering
Yes Yes Will use Client Driven Engineering

The column “Server IEDs to update” (read-only) shows which Server IEDs will be updated. Server
IEDs for update are selected automatically. If Server IED is protected or missing, then adequate
warning is displayed. For update to use Client Driven Engineering, there needs to be at least one
Server IED selected.

IEC202100726 V1 EN-US

When we proceed with the update every IED that has “Client Driven Engineering” checked (and
server IEDs selected for update) will be updated according to new inputs of a client.

All errors and warnings can be seen in Output.

Integrated Engineering Tool 389


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 30 1MRK500114-UEN Rev. X
Annex: Client Driven Engineering

30.3 Elements affected by Client Driven Engineering GUID-72B6F3BC-61F6-454F-BD77-6F268CA8B36C v1

30.3.1 Server IEDs GUID-35A5A141-AAD1-4942-A2AB-85A635D93EB9 v1

If Server IED is selected for an update that uses Client Driven Engineering then adequate datasets
and control blocks are generated (if necessary Datasets and Control Blocks already exist, they are
not generated again). Those datasets have status Generated by Client Driven Engineering and
cannot be changed. All necessary connections will be created.

IEC202100727 V1 EN-US

30.3.2 Client IEDs GUID-F0A39021-A546-48C7-A930-BAED5F717B42 v1

All Client IEDs will be set as subscribers to the “inputs” datasets and control blocks. Inputs will be
added in Inputs Editor.

390 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 31
Annex: Inputs Predefined from IED (Late Binding)

Section 31 Annex: Inputs Predefined from IED


(Late Binding) GUID-B0622903-FA50-480D-91A0-68189F6AC505 v1

31.1 Introduction GUID-5EC8D9D0-C4D2-40FD-BB1B-76B5DB5ADDBB v1

While an IED Configuration Tool could always create an Input section (LN -> Inputs -> extRef) with
an internal Address (intAddr), there was no standardized way to indicate what information should be
delivered to this input. At best, the description (desc) attribute contained some text so that the user
could look for the appropriate DATA item in another IED and map it.

In Edition 2007B2, some attributes were added to the SCL schema, so that an IED Configuration
Tool could specify the meaning of the expected Input (extRef) in a more precise way. This whole way
of working was termed Late Binding; i.e. the IED specifies something and later, the System
Configuration Tool is obliged to bind the appropriate DATA item from another IED to it.

31.2 Late Binding SCL Attributes GUID-1CD6089E-F84F-42C2-9658-778816063F84 v1

The following attributes can be specified by an IED Configuration Tool:

ExtRef Attribute Meaning


intAddr must be set to a non-empty value
pDO “predefined DATA Object”; specifies the name of the
CDC (Common Data Class) of the DO (DATA Object)
which is expected.
pDA “predefined DATA Attribute”; specifies the name of the
DA (DATA attribute) which is expected.
pLN “predefined LN”; specifies the name of the LN Class
which is expected
pServT “predefined Service Type”; specifies the Service Type
(RCB, GCB etc.) which is expected to supply the
information.

The System Configuration Tool may not delete an Input ExtRef with a non-empty intAddr.

The System Configuration Tool may not add any Input ExtRefs on its own, if
ClientServices.NoIctBinding = true; in this case, only Input ExtRefs specified by the IED
Configuration Tool may be configured by the System Tool.

The System Tool may not modify any of the p-Attributes, they are owned entirely by the IED
Configuration tool (however, it may delete whole ExtRefs, if they do not contain any intAddrs).

31.3 Late Binding Workflow GUID-71FCE059-6DE5-4000-8DFB-8310ACB9E180 v1

31.3.1 IEC 61850 Intended Workflow GUID-6C2950FD-DFA0-42A5-A18B-773B805733DA v1

This chapter specifies the workflow as intended in IEC 61850 for Late Binding.

1. The IED Configuration Tool creates ExtRefs for signals it expects as input (for its control or
protection logic) and provides attributes for the expected configuration (p-Attributes).
It puts an intAddr to prevent the System Configuration Tool from deleting such ExtRefs.
It configures as a minimum a pDO, optionally a pDA and / or a pLN to specify what type of signal
is expected.

Integrated Engineering Tool 391


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 31 1MRK500114-UEN Rev. X
Annex: Inputs Predefined from IED (Late Binding)

It configures a pServT, if it expects the information sent via a particular communication type (e.g.
GOOSE).
It may put a user-understandable description into the ‘desc’ attribute (as the above defined
attributes do not allow a complete specification of the meaning of the expected information)
2. It exports its ICD/IID file with those ExtRefs.
3. The System Configuration Tool imports the ICD/IID file.
4. The System Configuration Tool must configure all such ExtRefs which contain an intAddr; the p-
Attribute data serve as a guidance what to map.
5. The System Configuration Tool must not modify the intAddr or any p-Attributes, they belong
entirely to the IED Configuration Tool.
6. The System Configuration Tool may configure additional Inputs.
7. The System Configuration Tool exports the SCD file.
8. The IED Configuration Tool imports the SCD file and has now all the information needed to
configure its communication.

The above sequence can be repeated, if the IED Configuration Tool requests additional ExtRefs (e.g.
when changing the protection or control logic).

31.3.2 IEC 61850 Late Binding Mapping Rules GUID-2D794262-6375-4320-A854-79DA0EDAB352 v1

If only a pDO is specified:

• It is mandatory that a DATA item with the same Common Data Class (!) but not necessarily the
same DO is mapped. So e.g if a “Pos” is specified, the mapping of either CSWI.Pos or
GGIO.DPCSOxx is allowed as both have the same Common Data Class “Double Point
Controllable” (DPC).
This allows some flexibility, if the sender IED uses some alternative way of implementation (e.g.
if a Breaker command is implemented as GGIO rather than as CSWI as in the above-mentioned
example).
However, it is the responsibility of the user to map a DO with the same meaning. E.g. according
to the above rule, if pDO = “Health” is specified, the user would be allowed to map “Beh” of the
same LN also. This does not make sense, however: while both have the same Common Data
Class (Single Point Status), their meaning is quite different. Therefore, if it is possible to give a
DO as specified by the pDO, this should be done; mapping an item with different DO, but same
Common Data Class should be a fallback solution only.
• The System Configuration Tool may create ExtRefs for each individual DA of the specified pDO,
rather than just specifying the DO. This is actually the preferred way: the receiver IED does not
necessarily know what optional DAs the sender implements; therefore specifying Inputs for all
the DAs rather than just the DO makes it transparent to the receiver what he will be receiving.
In this case, the p-Attributes and intAddr must be copied to all entries created by the System
Configuration Tool.

If a pDO and a pDA are specified:

• The DA of a DO with the same Common Data Class (!) needs to be mapped. Again, it is allowed
to use another DO, provided Common Data Class and DA name are the same.
So e.g if “Pos” and “stVal” are specified, the mapping of either CSWI.Pos.stVal or
GGIO.DPCSOxx.stVal is allowed as both have the same Common Data Class “Double Point
Controllable” (DPC).

If a pLN and a pDO are specified:

• A DATA item with the same LN Class and same Common Data Class shall be specified.
To use not the specified, but an alternative DO makes sense only in special situations, e.g. if
GGIO.DPCSO01 is specified, but from some other information, the user knows that the
information with the required meaning is coming from GGIO.DPCSO02.
Other than that, it should not happen that an LN Class has several DOs (with the same
Common Data Class) with the same meaning, therefore the common case will be to map a
DATA item with the same LN Class and DO as specified in the P-Attributes.

392 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 31
Annex: Inputs Predefined from IED (Late Binding)

If a pLN and a pDO and a pDA are specified:

• A DATA item with the same LN Class, same Common Data Class and same DA shall be
specified.
The same logic as specified for pLN and pDO applies.

31.4 Configuration of Late Binding in the System


Configuration Tool GUID-DEFEBA32-01D4-42D1-B3BD-F3547331126A v1

From the added attributes, it is clear that the mapping cannot be done automatically (e.g. it cannot be
specified which IED is supposed to deliver the information).

If Late Binding is used, it may be necessary to map each specified Input ExtRef manually.

31.4.1 Implementation in IET600 GUID-5DB07737-859D-48E6-816C-DCCDABFA0574 v1

As it is not very clear yet how efficiently this may be used, IET600 implements only the mandatory
subset of functionality:

• If p-Attributes are provided, you can map an existing DATA Object or attribute to an ExtRef
according to the mapping rules given above.
• IET600 currently does not support a split of an attribute specified on pDO level into several
ExtRefs on DA level (although this would be the preferred workflow).

Integrated Engineering Tool 393


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
394
1MRK500114-UEN Rev. X Section 32
Annex: OPC server to ISS client conversion

Section 32 Annex: OPC server to ISS client


conversion GUID-4ED34C58-9605-4C08-8A7C-B596F2CEF765 v1

While newly created ISS clients could be configured using Signal Library, there is also a possibility to
convert already existing projects with fully engineered OPC servers.

Conversion mechanism could be triggered on following tree view items:

IEDs/Substation tree:

• OPC IED
• HMI IED
• OPC Access Point

HMIs tree:

• GWs/Proxies
• HMIs
• Hot-Standby
• HMI
• OPC server

GUID-890754E3-EB1D-465D-B0CC-B283F8FFA6DB V1 EN-US

Running conversion on any of mentioned above tree items will trigger a validation that will check
whether there any additional OPC servers that need to be converted due to fact that one Ied cannot
send same dataset to an OPC server and ISS client at the same time. The following dialog will
appear:

GUID-685E0235-3A19-423D-B9F0-95713881D69F V1 EN-US

Users should review list of OPC servers that will be converted. Accepting dialog will create project
backup and run actual conversion.

Integrated Engineering Tool 395


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 32 1MRK500114-UEN Rev. X
Annex: OPC server to ISS client conversion

Conversion process includes following aspects:

• OPC IEDs and OPC Access points will be removed and replaced is ISC Access Points
• Command groups will be converted to 1 command with back indication
• Sender-receiver relations will be restored
• HMI signals on sender IEDs will be converted to "IEC 61850 via ISS"

HMI signal will not be converted to "IEC 61850 via ISS" in several cases:

• Signal is not included into any dataset. This is because the conversion is done from the
perspective of a client. So converted are signals which are sent to a particular OPC
• Attribute reference is not resolved for IED with 61850 model

396 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 33
Annex: SCL document security

Section 33 Annex: SCL document security GUID-2A4C41B6-FE2D-4DA5-83A1-19DDA1AB9E67 v1

IET600 can import signed SCL file, but without signature verification. In this case there is a question
dialog to confirm file import or not.

IEC202100699 V1 EN-US

File signature is not used when export SCL file, so in case of importing signed file – it can be then
exported only without signature.

IET600 does not support import of encrypted SCL files. When try to open such a document there is
an error message and document is not imported.

IEC202100700 V1 EN-US

Integrated Engineering Tool 397


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
398
1MRK500114-UEN Rev. X Section 34
Annex: IEC 61850 Mapping

Section 34 Annex: IEC 61850 Mapping GUID-29120D68-8D50-4ED1-9264-F2C7C39220D5 v1

Signal Text (ABB Standard) Description Comment


Clock state (LAN n) LTIMx.TmDT.stVal
Connected (LAN n) LCCHx.ChLiv.stVal
Communication Status LCCHx.ChLiv.stVal
CPU Temp STMPx.Alm.q
Communication error LCCHx.ChLiv.stVal
Door open GGIO.Almx.stVal
Toner low LPHDx.PhyHealth.stVal
Toner empty LPHDx.PhyHealth.stVal
Temp. next to power supply STMPx.Alm.q
Temp. next to hard disk STMPx.Alm.q
Temp. next to front fan STMPx.Alm.q
Status power supply GGIOx.Ind.stVal
Status OPCn LCCHx.ChLiv.stVal
Status WS GGIOx.Ind.stVal
Status SNMP OPC GGIOx.Ind.stVal
Status Raid intern GGIOx.Ind.stVal
Status RAID GGIOx.Ind.stVal
Status of MU GGIOx.Ind.stVal
Status of device GGIOx.Ind.stVal
Status NIC/OPC LCCHx.ChLiv.stVal
Status LAN n LCCHx.ChLiv.stVal
Status LPHDx.PhyHealth.stVal
Station selection on monitor Not possible MicroSCADA internal only
Sound Block GGIO.Blk.stVal
Sound acknowledged GGIO.Ind.stVal
Relay ready OPC connection LCCHx.ChLiv.stVal
Power supply n - No specific mapping, info is
contained in dU.
Port n LCCHx. ChLiv.stVal
Paper low GGIOx.Ind.stVal
Paper empty GGIOx.Ind.stVal
OPC Status LCCHx.ChLiv.stVal
Offline LCCHx.ChLiv.stVal
NTP sync LTMS.TmSyn.stVal
NTP current state (LANn) LCCHx. ChLiv.stVal
MOXA Status LPHDx.PhyHealth.stVal
MOXA Firmware Version LPHDx.PhyNam. swRev
MOXA Digital Output n Command GGIOx.SPCSO.ctlVal
MOXA Digital Output n GGIOx.SPCSO.ctlVal
Table continues on next page

Integrated Engineering Tool 399


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 34 1MRK500114-UEN Rev. X
Annex: IEC 61850 Mapping

Signal Text (ABB Standard) Description Comment


MOXA Digital Input n GGIOx.SPCSO.stVal
MOXA Check Health LPHDx.PhyHealth.stVal
Link state NICnA/B (LANn) LCCHx.ChLiv.stVal
Jammed GGIOx.Ind.stVal
GPS Sync LTMS.TmSyn.stVal
GPS state (LANn) LCCHx.ChLiv.stVal
Antenna LPHDx.PhyHealth.stVal

n, x – stands for number(e.g. LPHD1, LPHD2 … or Port 1, Port 2 …)

400 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 35
Annex: IEC 61850 Reference creation

Section 35 Annex: IEC 61850 Reference creation GUID-CC0E4456-8EB7-43EE-BB1E-A00EF9549427 v1

In NCC Data Editor IEC 61850 References can be entered manually (as text) or set using IEC
61850 Reference Creation Dialog. In order to open that dialog user must double click on a cell in
IEC 61850 Reference column.

GUID-761B57B8-F343-4FE7-B48D-5B346099D4F8 V1 EN-US

Integrated Engineering Tool 401


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 35 1MRK500114-UEN Rev. X
Annex: IEC 61850 Reference creation

IEC 61850 Reference Creation Dialog can be enabled/disabled using a column


context menu.

GUID-F7C3BDEF-B430-46AB-A0EE-D23017B4F3CD V1 EN-US

This dialog is divided into 10 segments.

1. IED/LD - allows to select an IED and an LD from a project or to enter them manually.
2. Namespace - allows selecting a namespace from those that are valid in IET 600.
3. LN Class Prefix and Instance - allows entering a prefix and an instance number for an LN Class.
4. DO Indication - allows entering an indication number for DOs that require an indication number
(marked with "+" on DO/SDO list).
5. FC - allows selecting a functional constrain.
6. LN Class - allows selecting an LN Class from all defined in a previously selected namespace.
7. DO/SDO - allows selecting a DO and SDO for a selected LN Class.
8. DA/DA Component - allows selecting a DA and DA Components for a selected DO/SDO.
9. Preview - shows generated reference.
10. Buttons
10.1. Update - updates a reference in a selected cell.
10.2. Undo - goes back to the original value.
10.3. Close - closes the dialog.

402 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 35
Annex: IEC 61850 Reference creation

GUID-088964ED-15B1-43E8-A34A-CCE106FAD853 V1 EN-US

Integrated Engineering Tool 403


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
404
1MRK500114-UEN Rev. X Section 36
References

Section 36 References GUID-25045C11-E1CF-48EE-A430-32664794FFFF v1

1. 1KHF330831 - Reference designations for secondary equipment and functions in substations.

Integrated Engineering Tool 405


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
406
1MRK500114-UEN Rev. X Section 37
Glossary of Terms

Section 37 Glossary of Terms GUID-05606D78-08AE-4069-86B8-66F2C0E7BED9 v1

Term Description
CID-file Configured IED description.
According to IEC 61850, this file transports data from the
IED configuration tool to the IED. In the current
engineering context, it is also used do designate a file
containing a con- figured IED description to be imported
into IET NG. In IEC 61850, V2, there is another file
specified for this process, the IID-file.
DATA (spelt with capital letters), refers to the IEC 61850 DATA
model, i.e. Logical Nodes, DATA objects and DATA
attributes.
In this document, DATA is sometimes used in a sense
that also include Logical Devices and Servers.
Dataflow refers to the IEC-61850-specific items that define what
data are exchanged (i.e. Datasets) and how they are
exchanged; (i.e. all kinds of Control Blocks, like RCBs,
GCBs and SVCBs)
Data Type Template In many Logical Nodes, there are very similar data
repeated again and again. To save space, IEC 61850
specifies not to store such data for each LN individually,
but via a rather sophisticated system of references to
minimize the length of files. This whole system of
references and data is contained in the so-called Data
Type Templates.
GCB Goose Control Block (as defined in IEC 61850)
GUI Graphical User Interface
HMI Human-Machine interface
IED Intelligent Electronic Device, general term in IEC 61850
for everything programmable and electronic. In the sense
of IEC 61850, e.g. HMIs or NCC gateways are also IEDs
and appear as such in an SCL file.
In this document, the term ‘IED’ is mostly used in a
narrower sense, designating Protection and Control
IEDs; HMIs Gate- ways etc. are labeled as such.

IED Configuration Tool a manufacturer- or IED-specific tool that must be able to


provide IED-specific settings and generate IED-specific
configuration files (ICD-, IID-files). It must be able to
import SCD-files.

ICD file IED Capability Description file. According to IEC 61850,


this file must contain exactly one IED whose capabilities
are described:

• the IED name must be TEMPLATE.


• the file must contain the needed data type
templates inclusive logical node type definitions
• the file may contain an optional substationsection,
where the substation name shall be TEMPLATE.

The substation section of this file may contain Logical


Node references. Any substation, in which this IED shall
be used, must match an appropriate substation topology
part
Table continues on next page

Integrated Engineering Tool 407


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
Section 37 1MRK500114-UEN Rev. X
Glossary of Terms

IID-file Instantiated IED Description file (IEC 61850, V2).


Describes the project-specific configuration of an IED.

LN Logical Node, in IEC 61850 a container for all data


related to one specific function (e.g. PTOC for time-
delayed overcurrent protection, or CSWI for Switch
control). LNs are product-specific.

LNode Logical Node Reference in a Substation Tree element. It


can either be used as a standalone name to specify
some desired functionality in an SSD-file, or it can
connect an LN in an IED to an object of the Substation
Tree. The latter is helpful to:

• attach a functionality to a substation object (e.g. a


protection function PTOC to a Bay or a control
function CSWI to a specific circuit breaker or
switch).
• distinguish functionalities (e.g. Protection Trip from
a Main Protection Device or from a Backup
Protection device).
• support automated naming in the HMI according
tothe Substation Tree.

NCC Network Control Center, general term for a place that


controls substations remotely.

RCB Report Control Block (as defined in IEC 61850)

SCD file System Configuration Description file. According to IEC


61850, this file contains all IEDs, a communication
configuration section and a substation description
section.

SCL file A file written in System Configuration description


Language. SCL is a specific XML namespace defined in
IEC 61850.
This term is typically used to include all more specifically
defined files (SCD, SSD, IID etc.).

SED file System Exchange Description file (IEC 61850, Ed.2). A


file designed to exchange IEC 61850 data between two
different projects/substations/System Configuration tools.

Signal Corresponds to one line in an event or alarm list; or one


process information.
IEC 61850 does not really know data points, but object
structures. For the purpose of this document and when
talking with a customer, a data point is roughly equivalent
to a DAI, except that quality and timestamp are separate
DAIs in IEC 61850, but included in a data point.
Table continues on next page

408 Integrated Engineering Tool


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
1MRK500114-UEN Rev. X Section 37
Glossary of Terms

SSD file System Specification Description file. According toIEC


61850,

• the file must contain a substation


descriptionsection
• the file may contain Logical Node references and, if
so, then must contain the needed data type
templatesand logical node type definitions.

Substation Tree A tree with one Substation as its root, containing all the
primary equipment for this Substation (e.g. Circuit
Breakers, Disconnectors etc.) in a hierarchy defined by
IEC 61850 (Voltage Levels, Bays, Functions,
Subfunctions).

SV Sampled Value (as defined in IEC 61850)

SVCB Sampled Value Control Block (as defined in IEC 61850)

System Configuration Tool An IED independent system level tool that must be able
to import IED-specific configuration files (ICD-, IID-files).
It must be able to export SCD-files. It should also be able
to read an SSD file. According to IEC 61850, Ed.2, it
needs to be able to handle SED-files, also.

Integrated Engineering Tool 409


User manual
© 2013 - 2022 Hitachi Energy. All rights reserved
410
411
Hitachi Energy Sweden AB
Grid Automation Products
SE-721 59 Västerås
Phone +46 (0) 10 738 00 00
E-Mail:contact-us@hitachienergy.com
Scan this QR code to visit our website
https://hitachienergy.com/substation-automation
1MRK500114-UEN

© 2013 - 2022 Hitachi Energy.


All rights reserved