You are on page 1of 7

RURAL AREAS ELETRICITY COMPANY S.A.O.

C
Condition Assessment of Power Plant Equipment
Insulation Resistance Measurment
Group :Group A
Contract No :RAEC:38/2014
Contract Title :Operation and Maintenance of Rural Power Stations
Location : Dibba Generating Station
Date 13/5/2015

IR Value in Mega Ohms


SL System Voltage
NO
Asset Tag
Level (kV)
Test Voltage Time Observation Recommendation
(U+V+W) - EARTH

0:15 27.2

0:30 27.8

0:45 28.4

1:00 30

2:00 38.4

3:00 44.6

4:00 52.4

1 GENERATOR - 2 0.415KV 500V 5:00 60.2

6:00 68.4

7:00 75.1

8:00 82.3

9:00 85.3

10:00 91.4

DAR 1.1

PI 3.04

Note:
Dielectric Absorption Ratio [DAR] = IR Value in 60 Sec / IR Value in 30 Sec
Polarization Index [PI] = IR Value in 600 Sec / IR Value in 60 Sec
As per the IEEE 43-2000 Recommendation on"Recommended Practice for Testing Insulation Resistance of Rotating Machinery" defines the minimum value of
the Polarization Index(PI) for AC and DC Rotating Machinery in temprature classes B, F and H as 2.0. And also the minimum value of the Dielectric Absorption
Ratio(DAR) as 1.25.

Inspected by Reviewed & Approved by


Name: Ramkumar.R Name: Jesudoss

Designation: Testing Engineer Designation: Manager-Testing

Signature: Signature:
RURAL AREAS ELETRICITY COMPANY S.A.O.C
Condition Assessment of Power Plant Equipment
Insulation Resistance Measurment
Group :Group A
Contract No :RAEC:38/2014
Contract Title :Operation and Maintenance of Rural Power Stations
Location : Dibba Generating Station
Date 31/5/2015

System IR Value in Mega Ohms


SL
Asset Tag Voltage Level Test Voltage Time Observation Recommendations
NO 1U-Earth 1V-Earth 1W-Earth
(kV)

0:15 1050 1130 1170

0:30 1400 1580 1550

0:45 1610 1880 1810

1:00 1780 2110 2020

2:00 2190 2690 2550

3:00 2420 3050 2870

4:00 2570 3320 3110

2 GENERATOR - 4 11KV 5000V 5:00 2720 3530 3270

6:00 2790 3710 3420

7:00 2890 3850 3550

8:00 2970 3990 3650

9:00 3030 4070 3730

10:00 3110 4240 3820

DAR 1.27 1.33 1.3

PI 1.76 2.02 1.91

Note:
Dielectric Absorption Ratio [DAR] = IR Value in 60 Sec / IR Value in 30 Sec
Polarization Index [PI] = IR Value in 600 Sec / IR Value in 60 Sec
As per the IEEE 43-2000 Recommendation on"Recommended Practice for Testing Insulation Resistance of Rotating Machinery" defines
the minimum value of the Polarization Index(PI) for AC and DC Rotating Machinery in temprature classes B, F and H as 2.0. And also the minimum
value of the Dielectric Absorption Ratio(DAR) as 1.25.
Inspected by Reviewed & Approved by
Name: Ramkumar.R Name: Jesudoss

Designation: Testing Engineer Designation: Manager-Testing

Signature: Signature:
RURAL AREAS ELETRICITY COMPANY S.A.O.
Condition Assessment of Power Plant Equipment
Insulation Resistance Measurment
Group :Group A
Contract No :RAEC:38/2014
Contract Title :Operation and Maintenance of Rural Power Stations
Location : Dibba Generating Station
Date 28/5/2015

IR Value in Mega Ohms


SL System Voltage
Asset Tag Test Voltage Time
NO Level (kV) 1U-Earth 1V-Earth 1W-Earth

0:15 486 473 471

0:30 590 603 583

0:45 658 673 643

1:00 701 722 679

2:00 798 816 762

3:00 839 861 800

4:00 868 888 824

3 GENERATOR - 5 11KV 5000V 5:00 890 908 834

6:00 905 920 846

7:00 914 926 858

8:00 924 936 863

9:00 934 941 873

10:00 937 947 872

DAR 1.18 1.2 1.16

PI 1.37 1.32 1.29

Note:
Dielectric Absorption Ratio [DAR] = IR Value in 60 Sec / IR Value in 30 Sec
Polarization Index [PI] = IR Value in 600 Sec / IR Value in 60 Sec
per the IEEE 43-2000 Recommendation on"Recommended Practice for Testing Insulation Resistance of Rotating Machinery" d
Polarization Index(PI) for AC and DC Rotating Machinery in temprature classes B, F and H as 2.0. And also the minimum value o
as 1.25.
Inspected by Reviewed &
Name: Ramkumar.R Name:

Designation: Testing Engineer Designation:

Signature: Signature:
ITY COMPANY S.A.O.C
Power Plant Equipment
nce Measurment

Observation Recommendations

Terminals slightly corbonised,dirt on


Need to be clean

windings

As
tion Resistance of Rotating Machinery" defines the minimum value of the
nd H as 2.0. And also the minimum value of the Dielectric Absorption Ratio(DAR)

Reviewed & Approved by


Name: Jesudoss

Designation: Manager-Testing

Signature:
RURAL AREAS ELETRICITY COMPANY S.A.O.C
Condition Assessment of Power Plant Equipment
Insulation Resistance Measurment
Group :Group A
Contract No :RAEC:38/2014
Contract Title :Operation and Maintenance of Rural Power Stations
Location : Dibba Generating Station
Date 3/6/2015

System IR Value in Mega Ohms


Test
SL NO Asset Tag Voltage Time
Voltage 1U-Earth 1V-Earth 1W-Earth
Level (kV)

0:15 1700 1720 1690

0:30 2920 2940 2720

0:45 3930 3980 3770

1:00 4820 4490 4820

2:00 7730 7400 8450

3:00 1150 1070 1310

4:00 1530 1420 1780

4 GENERATOR - 5 11KV 5000V 5:00 1780 1750 2190

6:00 2120 2000 2580

7:00 2290 2260 2960

8:00 2380 2510 3300

9:00 2500 2720 3590

10:00 2680 2840 3840

DAR 1.65 1.53 1.77

PI 5.6 6.38 8.14

Note:
Dielectric Absorption Ratio [DAR] = IR Value in 60 Sec / IR Value in 30 Sec
Polarization Index [PI] = IR Value in 600 Sec / IR Value in 60 Sec
As per the IEEE 43-2000 Recommendation on"Recommended Practice for Testing Insulation Resistance of R
Machinery" defines the minimum value of the Polarization Index(PI) for AC and DC Rotating Machinery in temprature classes B
And also the minimum value of the Dielectric Absorption Ratio(DAR) as 1.25.
Inspected by Reviewed & Approve
Name: Ramkumar.R Name:

Designation: Testing Engineer Designation:

Signature: Signature:
PANY S.A.O.C
Equipment
t

Observation Recommendations

r Testing Insulation Resistance of Rotating


Machinery in temprature classes B, F and H as 2.0.

Reviewed & Approved by


Name: Jesudoss

Designation: Manager-Testing

Signature: