L-Angle
1. Make sure of cabinet leveling during
installation by using water leveling.
Water leveling
Alarm
Alarm Name Boolean Number
ID
65033 AC1 1
65034 AC2 2
65045 Main Power Failure 13-14-15-16
65049 Water 17
65050 Temp 18
65051 Smoke 19
65052 Door 20
65056 Humidity 24
Terminals to be
installed in All DC
cables connection
with DC input (need
clear photos)
1. AC cables installed with
terminals
1. leave spacing of 4 cm between cabinet and
shelter wall.
2. At indoor sites install all cables : power , E1 ,
10 cm
earth and alarm cables as shown on the shelter
wall using plastic clips.
3. Spacing between the plastic clips is 10 cm
between each other.
4. Install power and earth cables at left side .
5. Install E1 , fiber and alarm cables at right side.
6. Make sure that all cables are in good
arrangement and avoid any crossing.
Jumper installed in u
shape over ladder 1. Jumper installed in u shape over ladder.
2. E1 & alarm cable installed on the last hole
near shelter wall.
3. Power cables installed on hole (7)& (8) over
ladder.
E1 & alarm cable
installed on the last hole
Macaroni Flexible
Water leveling