Issue Date
Aug 30, 2019
Table of Contents Page
1. Safety Precautions......................................................................................... 1
1. In case of Accidents or Emergency
2. Pre-Installation and Installation
3. Operation and Maintenance
2. Specifications................................................................................................. 3
1. Model Reference
2. Electrical Wiring Diagrams
3. Product Features............................................................................................ 20
1. Operation Modes and Functions
5. Troubleshooting............................................................................................. 82
1. Safety Caution
2. General Troubleshooting
3. Error Diagnosis and Troubleshooting Without Error Code
4. Quick Maintenance by Error Code
5. Troubleshooting by Error Code
Appendix.............................................................................................................. 106
i) Temperature Sensor Resistance Value Table for T1,T2,T3 and T4 (°C – K)
ii) Pressure On Service Port
Safety Precautions
Contents
1. In Case of Accidents or Emergency.......................................................................2
2. Pre-Installation........................................................................................................2
service manual and its relevant sections. the unit as well as the edges of the fins on the con-
Safety
CAUTION CAUTION
•• Clean and ventilate the unit at regular intervals when •• Do not install or operate the unit for an extended
operating it near a stove or near similar devices. period of time in areas of high humidity or in an
•• Do not use the unit during severe weather conditions. environment directly exposing it to sea wind or salt
If possible, remove the product from the window spray.
before such occurrences. •• Do not install the unit on a defective or damaged
installation stand, or in an unsecure location.
•• Ensure the unit is installed at a level position
2. Pre-Installation and Installation •• Do not install the unit where noise or air discharge
created by the outdoor unit will negatively impact the
WARNING environment or nearby residences.
•• Use this unit only on a dedicated circuit. •• Do not expose skin directly to the air discharged by
•• Damage to the installation area could cause the unit the unit for prolonged periods of time.
to fall, potentially resulting in personal injury, prop- •• Ensure the unit operates in areas water or other
erty damage, or product failure. liquids.
•• Only qualified personnel should disassemble, install, •• Ensure the drain hose is installed correctly to ensure
remove, or repair the unit. proper water drainage.
•• Only a qualified electrician should perform electri- •• When lifting or transporting the unit, it is
cal work. For more information, contact your dealer, recommended that two or more people are used for
seller, or an authorized Midea service center. this task.
•• When the unit is not to be used for an extended time,
disconnect the power supply or turn off the breaker.
Page 2
Specifications
Contents
1. Model Reference.....................................................................................................4
Outdoor Unit Model indoor Unit Model Capacity (Btu) Power Supply
YFFE18BXTM-M-R1
1ɸ, 220-230V~,
YUFE18BYTM-MO-X YKFE18BXTM-M-R1 18k
60Hz
Specifications
YEFE18BXTM-M-W1
YFFE24BXTM-M-R1
1ɸ, 220-230V~,
YUFE24BYTM-MO-X YKFE24BXTM-M-R1 24k
60Hz
YEFE24BXTM-M-W1
YFFE36BXTM-M-R1
1ɸ, 220-230V~,
YUFE36BYTM-MO-X YKFE36BXTM-M-R1 36k
60Hz
YEFE36BXTM-M-W1
YFFE36BXTM-M-R1
YEFE36BXTM-M-W1
YFFE48BXTM-M-R1
1ɸ, 220-230V~,
YUFE48BYTM-MS-1 YKFE48BXTM-M-R1 48k
60Hz
YEFE48BXTM-M-W1
YFFE48BXTM-M-R1
YEFE48BXTM-M-W1
YFFE60BXTM-M-R1
1ɸ, 220-230V~,
YUFE60BYTM-MS-1 YKFE60BXTM-M-R1 60k
60Hz
YEFE60BXTM-M-W1
YFFE60BXTM-M-R1
YKFE60BXTM-M-R1
YEFE60BXTM-M-W1
Page 4
2. Electrical Wiring Diagrams
Abbreviation Paraphrase
Specifications
FAN1, FAN2 Indoor Fan
M Swing Motor
PUMP PUMP
L LIVE
N NEUTRAL
P2 High Speed
Page 5
YFFE18BXTM-M-R1, YFFE24BXTM-M-R1, YFFE36BXTM-M-R1, YFFE48BXTM-M-R1, YFFE60BXTM-M-R1
K3 16022700000005
Specifications
P2
4
ORANGE
PUMP
K3 W. P. SENSOR
FAN2
WHITE WHITE
NOTE: CAP2
The wi r i ng di agr am
i s f or expl anat i on
pur pose onl y. The
act ual shape of t he
component s may be
di f f er ent . 24V~
J
R6
To CCM
Comm.Bus
1
0
X YE
J
R6
N
EWF
AN
1
602
250
000
278
4
Page 6
YEFE18BXTM-M-W1, YEFE24BXTM-M-W1, YEFE48BXTM-M-W1, YEFE60BXTM-M-W1, YEFE18BXTM-M-W1,
YEFE24BXTM-M-W1, YEFE48BXTM-M-W1, YEFE60BXTM-M-W1
FAN FOR THE
FRESH AIR
OR ANION Alarm Remote
GENERATOR Output Control
ALARM ON/OFF
Specifications
M CN10 BOARD CONTROLLER
T2
INDOOR UNIT CN6
4
BLACK INDOOR COIL TEMP. SENSOR
MAINBOARD T1
WHITE ROOM TEMP. SENSOR
CN5
COOLING&HEATING COOLING ONLY
CN9
CN18
CN111
CN40 YELLOW
CN25
CN1
CN2
X Y E
RED
3
BLACK
RED
Y/G
MAGNETIC RING
BLUE
BLACK
BROWN
4
BLUE
GREEN
CONTROLLER
WIRE
To CCM
Comm.Bus
YEFE36BXTM-M-W1, YEFE36BXTM-M-W1
FAN FOR THE
FRESH AIR
OR ANION Alarm Remote
GENERATOR Output Control
ALARM ON/OFF
T2
INDOOR UNIT CN6
4
BLACK INDOOR COIL TEMP. SENSOR
MAINBOARD T1
WHITE ROOM TEMP. SENSOR
CN5
COOLING&HEATING COOLING ONLY
CN9
CN18
CN111
CN40 YELLOW
CN25
CN1
CN2
X Y E
RED
3
BLACK
RED
Y/G
MAGNETIC RING
BLUE
BLACK
BROWN
4
BLUE
GREEN
CONTROLLER
WIRE
To CCM
Comm.Bus
Page 7
YKFE60BXTM-M-R1, YKFE60BXTM-M-R1
16022500000850
Specifications
P1 SUPER HI GH SPEED
P2 HI GH SPEED
T3 TRANSFORMER
N OT E:F OR F AN O P ER A TE S I N S U PE R
H IG H S PE E D, P LE A S E S W IT C H HI G H
S PE E D TO S UP E R HI G H SP E ED , SE E
F AN - WI R I NG P AR T F OR D E TA I L
I NF O RM A T IO N !
Page 8
For all models:
INDOOR UNIT
For Cooling&Heating For Cooling only
4-core cable 2-core cable
4×1.0mm2 2×1.0mm 2 C1 N1 V1 F1 L N
C1
Specifications
For 1phase INDOOR POWER:
3-core cable 208-240V~
OUTDOOR POWER: 208-240V~ 3-core cable
2 3×1.5mm 2
2
2
2
Page 9
2.2 Outdoor Unit
Abbreviation Paraphrase
KM8 Contactor
Specifications
COMP Compressor
XT4 Terminal
R1 Resistance
XP1~XP5,XS1~XS5 Connectors
Page 10
YUFE18BYTM-MO-X, YUFE24BYTM-MO-X
Y/G
Specifications
L N C1 N1
24V~
Page 11
YUFE36BYTM-MO-X
BLACK
BLACK
KM8
XT3 T1 L1
FAN RED
RED WHITE
C
BROWN
( BLUE)
BLUE
A1 S
Specifications
COMP Y/G
RED R
BLACK
OUTDOOR WIRING DIAGRAM
BLACK
BLUE BLUE
CODE PART NAME
COMP COMPRESSOR
BLUE W
16022000026290
CN201
V COMP
SW1 CN200
K2
LN ABCN Y/ G
RED WHI TE U
CN9 RED
RED
CN206
P. C. B
CN38
BLACK XP2XP2 BLACK
WHI TE
CN39
CN203 CT2
XP1XS1
CN40
CN208
TRANS RED
T3 WHI TE
BLUE
XP3XS3
XP4XS4
RED
RED
1
21
5
3
A1
K1 K3
XT4 KM8
RED
22
A2
6
4
2
FAN
T4 BLACK/ BLUE BLACK
BROWN
( BLUE)
BLUE
BLUE
BLACK
BLACK
BLACK
WHI TE
RED
RED
24V~
Page 12
YUFE48BYTM-MS-1
Specifications
C1 N1
24V~ 16022500001328
YUFE48BYSM-MS-1
202075790237
24V~
16022700001387
Page 13
YUFE60BYTM-MS-1
Specifications
C
S
R
YUFE60BYSM-MS-1
Page 14
1. Operation Modes and Functions
1.1 Abbreviation
Unit element abbreviations
Abbreviation Element
T1 Indoor room temperature
T2 Coil temperature of evaporator
Specifications
T3 Coil temperature of condenser
T4 Outdoor ambient temperature
TS Set temperature
Page 15
Product Features
Contents
1. Operation Modes and Functions.........................................................................21
1.1 Abbreviation.................................................................................................21
1.6 Auto-mode...................................................................................................22
Product Features
1.5.2 Indoor Fan Control
In cooling mode, the indoor fan operates continuously. The
fan speed can be set to high, medium, low or auto.
Super-slim Cassette
1.5.3 Outdoor Fan Control
The On-off outdoor units have single fan speed. The
outdoor fan runs following the compressor except when
AC is in evaporator high temperature protection in heating
mode, condenser high temperature protection in cooling
mode, defrosting mode and the current protection.
Page 17
operation of compressor, except the following situations. preset time.
• High temperature protection of evaperator • Timer Off. The machine turns off automatically at the
preset time.
• Defrosting
• Timer On/Off. The machine turns on automatically at
• Current protection the preset On Time, and then turns off automatically
1.6.4 Defrosting mode at the preset Off Time.
• The unit enters defrosting mode according to changes • Timer Off/On. The machine turns on automatically at
in the temperature value of T3。 the preset Off Time and then turns off automatically at
the preset On Time.
• If any one of the following conditions is satisfied,
defrosting ends and the machine switches to normal • The timer does not change the unit operation mode.
heating mode: If the unit is off now, it does not start up immediately
after the “timer off” function is set. When the setting
• Unit runs for 10 minutes consecutively in defrosting
time is reached, the timer LED switches off and the
mode.
unit running mode remains unchanged.
• T3≥TE18 or other setting value.
• The timer uses relative time, not clock time
• AC is turned off, or other mode is set.
1.10 Sleep function
Product Features
1.7 Auto-mode
• The sleep function is available in cooling, heating, or
• This mode can be selected with the remote controller auto mode.
and the setting temperature can be changed between
• The operational process for sleep mode is as follows:
17°C~30°C.
• When cooling, the temperature rises 1°C (to not
• In auto mode, the machine selects cooling, heating, or
higher than 30°C) every hour. After 2 hours, the
fan-only mode on the basis of ∆T (∆T =T1-Ts).
temperature stops rising and the indoor fan is fixed
∆T Running mode at low speed.
∆T>2℃ Cooling • When heating, the temperature decreases 1°C(to
not lower than 17°C) every hour. After 2 hours, the
-3℃≤∆T≤2℃ Fan-only
temperature stops decreasing and the indoor fan is
∆T<-3℃ Heating* fixed at low speed. Anti-cold wind function takes
• The louver operates same as in relevant mode. priority.
• If the machine changes running mode to auto mode, • Entering shutdown, changing mode or speed setting
it will choose running mode again. cancels sleep mode..
• If the machine switches mode between heating and • In this mode, the fan speed is forced into AUTO mode.
cooling, the compressor will keep stopping for certain
time and then choose running mode according to 1.11 Auto-Restart function
T1-Ts.
• The indoor unit has an auto-restart module that
• If the setting temperature is modified, the machine will allows the unit to restart automatically. The module
choose running mode again. automatically stores the current settings (not including
the swing setting) and, in the case of a sudden power
1.8 Drying mode failure, will restore those setting automatically within 3
minutes after power returns.
• Indoor fan speed is fixed at breeze and can’t be
changed. The louver angle is the same as in cooling • If the unit was in forced cooling mode, it will run in
mode. this mode for 30 minutes and turn to auto mode with
temperature set to 24°C.
• All protections are active and the same as that in
cooling mode. • If there is a power failure while the unit is running, the
compressor starts 3 minutes after the unit restarts. If
the unit was already off before the power failure, the
1.9 Timer Function compressor starts 1 minute after the unit restarts.
• The timing range is 24 hours.
• Timer On. The machine turns on automatically at the
1.12 Refrigerant Leakage Detection
Page 18
With this new technology, the display area will show “EC” 1. Maintenance
when the outdoor unit detects refrigerant leakage.
1.1 First Time Installation Check
1.13 Follow me(Optional)
Air and moisture trapped in the refrigerant system affects
• If you press “Follow Me” on the remote, the indoor the performance of the air conditioner by:
unit will beep. This indicates the follow me function is
active. • Increasing pressure in the system.
• Once active, the remote control will send a signal • Increasing the operating current.
every 3 minutes, with no beeps. The unit automatically • Decreasing the cooling or heating efficiency.
sets the temperature according to the measurements • Congesting the capillary tubing due to ice build-up in
from the remote control. the refrigerant circuit.
• The unit will only change modes if the information • Corroding the refrigerant system.
from the remote control makes it necessary, not from
the unit’s temperature setting. To prevent air and moisture from affecting the air
conditioner’s performance, the indoor unit, as well as the
• If the unit does not receive a signal for 7 minutes, the pipes between the indoor and outdoor unit, must be be
function turns off. The unit regulates temperature leak tested and evacuated.
Product Features
based on its own sensor and settings.
• Wired remote controller is prior to wireless remote Leak test (soap water method)
controller. Use a soft brush to apply soapy water or a neutral liquid
• Use the water-level switch to control drain pump. detergent onto the indoor unit connections and outdoor
• The system checks the water level every 5 seconds. unit connections. If there is gas leakage, bubbles will form
on the connection.
• When the A/C operates in cooling (including auto
cooling) or forced cooling mode, the pump begins Air purging with vacuum pump
running immediately and continuously until cooling
stops.
• If the water level increases up to the control point,
the LED displays an alarm code and the drain pump
opens and continually monitors the water level. If
the water level falls and LED alarm code is no longer
displayed (drain pump close delay is 1 minute), the
unit goes back into its last mode. Otherwise, the
entire system (including the pump) stops and the
LED displays an alarm again after 3 minutes.
Page 19
Page 20
Product Features
Maintenance and Disassembly
Contents
1. Maintenance.........................................................................................................26
2. Disassembly..........................................................................................................33
:]U]G_\GR\K
)RUYK
-GYYOJK
3GTOLURJ\GR\K :NXKK]G_\GR\K
)USVU[TJSKZKX 6XKYY[XK
)RUYK
MG[MK
36G
2U .O
.GTJRK2U .GTJRK.O
)NGXMKNUYK )NGXMKNUYK
<GI[[S
V[SV
Maintenance and
Disassembly
<GI[[S
V[SV
Procedure:
1. Tighten the flare nuts of the indoor and outdoor units, and confirm that both the 2- and 3-way valves are closed.
2. Connect the charge hose with the push pin of Handle Lo to the gas service port of the 3-way valve.
3. Connect another charge hose to the vacuum pump.
4. Fully open the Handle Lo manifold valve.
5. Using the vacuum pump, evacuate the system for
30 minutes.
a. Check whether the compound meter indicates -0.1 MPa (14.5 Psi).
• If the meter does not indicate -0.1 MPa
(14.5 Psi) after 30 minutes, continue
evacuating for an additional 20 minutes.
• If the pressure does not achieve -0.1 MPa
(14.5 Psi) after 50 minutes, check for leakage.
• If the pressure successfully reaches -0.1 MPa (14.5 Psi), fully close the Handle Lo valve, then cease vacuum
pump operations.
b. Wait for 5 minutes then check whether the gauge needle moves after turning off the vacuum pump. If the
gauge needle moves backwards, check whether there is gas leakage.
Page 22
6. Loosen the flare nut of the 3-way valve for 6 or
7 seconds and then tighten the flare nut again.
a. Confirm the pressure display in the pressure
indicator is slightly higher than the atmospheric
pressure.
b. Remove the charge hose from the 3-way valve.
7. Fully open the 2- and 3-way valves and tighten the
cap of the 2- and 3-way valve.
Maintenance and
Disassembly
Page 23
/TJUUX[TOZ 2OW[OJYOJK 5[ZJUUX[TOZ
:]U]G_\GR\K
5VKT
-GYYOJK
:NXKK]G_\GR\K
)NKIQ\GR\K
5VKT
)NGXMOTM
I_ROTJKX 2U .O
56+4 )259+
+RKIZXUTOIYIGRK
Prior to recharging the refrigerant, confirm the additional amount of refrigerant required using the following table:
Procedure:
Page 24
1.3.1 Indoor Unit
Collecting the refrigerant into the outdoor unit
:]U]G_\GR\K
)RUYK
-GYYOJK
:NXKK]G_\GR\K
5VKT
)RUYK
2U .O
)RUYK
Maintenance and
Disassembly
Procedure:
Page 25
/TJUUX[TOZ 2OW[OJYOJK 5[ZJUUX[TOZ
:]U]G_\GR\K
)RUYK
-GYYOJK
3GTOLURJ\GR\K :NXKK]G_\GR\K
)USVU[TJSKZKX 6XKYY[XK
)RUYK
MG[MK
36G
2U .O
.GTJRK2U .GTJRK.O
)NGXMKNUYK )NGXMKNUYK
<GI[[S
V[SV
Maintenance and
Disassembly
<GI[[S
V[SV
Procedure:
Page 26
Evacuation for the whole system
:]U]G_\GR\K
5VKT
-GYYOJK
:NXKK]G_\GR\K
5VKT
56+4
2U .O
<GI[[SV[SV
)259+
Procedure:
Maintenance and
Disassembly
1. Confirm that the 2- and 3-way valves are opened.
2. Connect the vacuum pump to the 3-way valve’s needle moves after turning off the vacuum pump. If
service port. the gauge needle moves backward, check whether
3. Evacuate the system for approximately one hour. there is gas leakage.
Confirm that the compound meter indicates 5. Disconnect the charge hose from the vacuum pump.
-0.1 MPa (14.5Psi). 6. Mount the caps of service port and 2- and 3-way
4. Close the valve (Low side) on the charge set and turn valves.
off the vacuum pump. 7. Use a torque wrench to tighten the caps to a torque
Wait for five minutes then check whether the gauge of 18N.m.
Page 27
Refrigerant charging
:]U]G_\GR\K
5VKT
-GYYOJK
:NXKK]G_\GR\K
)NKIQ\GR\K
5VKT
)NGXMOTM
I_ROTJKX 2U .O
56+4 )259+
+RKIZXUTOIYIGRK
Procedure:
Maintenance and
Disassembly
1. Tighten the flare nuts of the indoor and outdoor and record the starting weight.
units, and confirm that both the 2- and 3-way valves 7. Fully open the Handle Lo manifold valve, 2- and
are closed. 3-way valves.
2. Slightly connect the Handle Lo charge hose to the 8. Operate the air conditioner in cooling mode and
3-way service port. charge the system with liquid refrigerant.
3. Connect the charge hose to the valve at the bottom 9. When the electronic scale displays the correct weight
of the cylinder. (refer to the gauge and the pressure of the low
If the refrigerant is R410A, invert the cylinder to side to confirm), turn off the air conditioner, then
ensure a complete liquid charge. disconnect the charge hose from the 3-way service
4. Partially open the Handle Lo manifold valve. port immediately..
5. Open the valve at the bottom of the cylinder for 5 10. Mount the caps of service port and 2- and 3-way
seconds to purge the air in the charge hose, then fully valves.
tighten the charge hose with the push pin of Handle 11. Use a torque wrench to tighten the caps to a torque
Lo to the gas service port of the 3-way valve. of 18N.m.
6. Place the charging cylinder onto an electronic scale 12. Check for gas leakage.
Note: 1. Mechanical connectors used indoors shall comply with local regulations.
2. When mechanical connectors are reused indoors, sealing parts shall be renewed. When flared joints
are reused indoors, the flare part shall be re-fabricated.
Page 28
2. Disassembly
Procedure Illustration
Maintenance and
Disassembly
CJ_CF_001
CJ_CF_002
Note: This section is for reference only. Actual unit appearance may vary.
Page 29
2. Electrical parts (Antistatic gloves must be worn.)
Procedure Illustration
CJ_CF_003
Maintenance and
Disassembly
CJ_CF_004
Note: This section is for reference only. Actual unit appearance may vary.
Page 30
3. Fan motor and fan
Procedure Illustration
CJ_CF_005
Maintenance and
Disassembly
2) Remove the screws of fan motor
support and then remove the screw of
ground wire. (see CJ_CF_006)
CJ_CF_006
Note: This section is for reference only. Actual unit appearance may vary.
Page 31
Procedure Illustration
CJ_CF_007
Maintenance and
Disassembly
CJ_CF_008
Note: This section is for reference only. Actual unit appearance may vary.
Page 32
Procedure Illustration
CJ_CF_009
Maintenance and
Disassembly
Note: This section is for reference only. Actual unit appearance may vary.
Page 33
4. Evaporator
Procedure Illustration
CJ_CF_010
Maintenance and
Disassembly
CJ_CF_011
Note: This section is for reference only. Actual unit appearance may vary.
Page 34
Procedure Illustration
CJ_CF_012
Maintenance and
Disassembly
4) Remove the 4 screws of board and
then remove it. (see CJ_CF_013)
CJ_CF_013
Note: This section is for reference only. Actual unit appearance may vary.
Page 35
Procedure Illustration
CJ_CF_014
Maintenance and
Disassembly
CJ_CF_015
Note: This section is for reference only. Actual unit appearance may vary.
Page 36
Procedure Illustration
CJ_CF_016
Maintenance and
Disassembly
CJ_CF_017
CJ_CF_018
Note: This section is for reference only. Actual unit appearance may vary.
Page 37
5. Display Board
Procedure Illustration
CJ_CF_019
Maintenance and
Disassembly
Note: This section is for reference only. Actual unit appearance may vary.
Page 38
2.1.2 A6 Duct
1. Electrical parts (Antistatic gloves must be worn.)
Procedure Illustration
CJ_A6_001
Maintenance and
Disassembly
2) Remove the 2 screws of the electronic
control box. Then release the 2 hooks
of the main control board. (see CJ_
A6_002)
CJ_A6_002
Note: This section is for reference only. Actual unit appearance may vary.
Page 39
Procedure Illustration
(see CJ_A6_004)
CJ_A6_004
Note: This section is for reference only. Actual unit appearance may vary.
Page 40
Procedure Illustration
Maintenance and
CJ_A6_005
Disassembly
Note: This section is for reference only. Actual unit appearance may vary.
Page 41
2. Fan motor and fan
Procedure Illustration
CJ_A6_006
Maintenance and
Disassembly
CJ_A6_007
Note: This section is for reference only. Actual unit appearance may vary.
Page 42
Procedure Illustration
CJ_A6_008
Maintenance and
Disassembly
Note: This section is for reference only. Actual unit appearance may vary.
Page 43
3. Evaporator
Procedure Illustration
CJ_A6_009
Maintenance and
Disassembly
CJ_A6_010
Note: Remove the front panel (refer to 1. Front panel) before disassembling electrical parts.
Page 44
Procedure Illustration
CJ_A6_011
Maintenance and
Disassembly
4) Remove the fixing screw of the
evaporator and then remove it. (see
CJ_A6_012)
CJ_A6_012
Note: This section is for reference only. Actual unit appearance may vary.
Page 45
2.1.3 Cassette
1. Front Panel and Display Board
Procedure Illustration
CJ_CASSETTE_001
CJ_CASSETTE_002
Note: This section is for reference only. Actual unit appearance may vary.
Page 46
Procedure Illustration
CJ_CASSETTE_003
Maintenance and
Disassembly
Note: This section is for reference only. Actual unit appearance may vary.
Page 47
2. Electrical parts (Antistatic gloves must be worn.)
Procedure Illustration
CJ_CASSETTE_004
Maintenance and
Disassembly
CJ_CASSETTE_005
Note: This section is for reference only. Actual unit appearance may vary.
Page 48
Procedure Illustration
CJ_CASSETTE_006
Maintenance and
Disassembly
Note: This section is for reference only. Actual unit appearance may vary.
Page 49
3. Display Board
Procedure Illustration
CJ_CASSETTE_007
Maintenance and
Disassembly
CJ_CASSETTE_008
Note: This section is for reference only. Actual unit appearance may vary.
Page 50
4. Fan motor and fan
Procedure Illustration
CJ_CASSETTE_009
Maintenance and
Disassembly
2) Remove the 2 screws of fixing board
and the 4 fixing nuts of fan motor.
(see CJ_CASSETTE_010)
CJ_CASSETTE_010
Note: This section is for reference only. Actual unit appearance may vary.
Page 51
5. Evaporator
Procedure Illustration
CJ_CASSETTE_012
Note: This section is for reference only. Actual unit appearance may vary.
Page 52
Procedure Illustration
CJ_CASSETTE_013
Maintenance and
evaporator fixing bracket and then
Disassembly
remove it. (see CJ_CASSETTE_014)
CJ_CASSETTE_014
Note: This section is for reference only. Actual unit appearance may vary.
Page 53
6. Water Pump
Procedure Illustration
CJ_CASSETTE_015
Maintenance and
Disassembly
CJ_CASSETTE_016
Note: This section is for reference only. Actual unit appearance may vary.
Page 54
Procedure Illustration
Maintenance and
Disassembly
CJ_CASSETTE_017
Note: This section is for reference only. Actual unit appearance may vary.
Page 55
2.2 Outdoor unit
1. Panel Plate
YUFE18BYTM-MO-X, YUFE24BYTM-MO-X, MOCA30U-18HN1-NB8, MOCA30U-24HN1-NB8
Procedure Illustration
CJ_CA30_001
Top Cover
CJ_CA30_002
Note: This section is for reference only. Actual unit appearance may vary.
Page 56
Procedure Illustration
Front Panel
CJ_CA30_003
Maintenance and
Disassembly
5) Remove the screws of water collecting
cover and then remove the water
collecting cover (1 screw) (see CJ_ Water Collecting Cover
CA30_004).
CJ_CA30_004
Note: This section is for reference only. Actual unit appearance may vary.
Page 57
Procedure Illustration
Right Panel
CJ_CA30_005
Note: This section is for reference only. Actual unit appearance may vary.
Page 58
YUFE36BYTM-MO-X , YUFE36BYSM-MO-1, MOD30U-36HN1-NB8
Procedure Illustration
Maintenance and
Disassembly
CJ_D30_001
3) Remove the screws of the top cover
and then remove the top cover (4 Top Cover
screws). Two of the screws is located
underneath the big handle (see CJ_
D30_002).
CJ_D30_002
Note: This section is for reference only. Actual unit appearance may vary.
Page 59
Procedure Illustration
CJ_D30_003
Maintenance and
Disassembly
Front Panel
CJ_D30_004
Note: This section is for reference only. Actual unit appearance may vary.
Page 60
Procedure Illustration
CJ_D30_005
Maintenance and
7) Remove the screws of the right panel
Disassembly
and then remove the right panel
(8 screws) (see CJ_D30_006).
Right Panel
CJ_D30_006
Note: This section is for reference only. Actual unit appearance may vary.
Page 61
YUFE48BYTM-MS-1, YUFE48BYSM-MS-1, MOE30U-48HN1-NB8, YUFE60BYTM-MS-1, YUFE60BYSM-MS-1,
MOE30U-60HN1-NB8
Procedure Illustration
CJ_E30_001
Maintenance and
CJ_E30_002
Note: This section is for reference only. Actual unit appearance may vary.
Page 62
Procedure Illustration
Maintenance and
Disassembly
CJ_E30_004
Note: This section is for reference only. Actual unit appearance may vary.
Page 63
Procedure Illustration
Front Panel
Maintenance and
CJ_E30_005
Disassembly
Right Panel
CJ_E30_006
Note: This section is for reference only. Actual unit appearance may vary.
Page 64
2. Fan disassembly
Note: Remove the panel plate and (refer to 1. Panel plate) before disassembling fan.
YUFE18BYTM-MO-X, YUFE24BYTM-MO-X, YUFE36BYTM-MO-X
Procedure Illustration
D-cut
CJ_ODU_001
Maintenance and
Disassembly
3) Disconnect the connectors for fan
motor. (Blue wire, yellow wire, red
wire, brown wire and black wire. The
blue wire and red wire are on the
capacitor. The black wire connects
with terminal 4.) (see CJ_ODU_002)
Note: This section is for reference only. Actual unit appearance may vary.
Page 65
Procedure Illustration
Fan Motor
Maintenance and
Disassembly
CJ_ODU_003
Note: This section is for reference only. Actual unit appearance may vary.
Page 66
MOCA30U-18HN1-NB8, MOCA30U-24HN1-NB8 , MOD30U-36HN1-NB8, YUFE36BYSM-MO-1
Procedure Illustration
D-cut
CJ_ODU_004
Maintenance and
Disassembly
3) Disconnect the connectors for fan
motor. (see CJ_ODU_005)
CJ_ODU_005
Note: This section is for reference only. Actual unit appearance may vary.
Page 67
Procedure Illustration
Fan Motor
Maintenance and
CJ_ODU_006
Disassembly
Note: This section is for reference only. Actual unit appearance may vary.
Page 68
YUFE48BYTM-MS-1, YUFE48BYSM-MS-1, MOE30U-48HN1-NB8, YUFE60BYTM-MS-1, YUFE60BYSM-MS-1,
MOE30U-60HN1-NB8
Procedure Illustration
D-cut
CJ_ODU_007
Fan Motor
Maintenance and
Disassembly
4) Remove the fixing screws of the fan
motor (4 screws) (see CJ_ODU_008).
5) Remove the fan motor.
CJ_ODU_008
Note: This section is for reference only. Actual unit appearance may vary.
Page 69
3. Electrical parts
Note: Remove the panel plate and fan assembly (refer to 1. Panel plate and 2. Fan assembly) before
disassembling electrical parts.
YUFE18BYTM-MO-X, YUFE24BYTM-MO-X, YUFE36BYTM-MO-X
Procedure Illustration
ODU_009)
Disassembly
CJ_ODU_009
Note: This section is for reference only. Actual unit appearance may vary.
Page 70
MOCA30U-18HN1-NB8, MOCA30U-24HN1-NB8 , MOD30U-36HN1-NB8, YUFE36BYSM-MO-1
Procedure Illustration
Maintenance and
Disassembly
CJ_ODU_010
Note: This section is for reference only. Actual unit appearance may vary.
Page 71
YUFE48BYTM-MS-1, YUFE48BYSM-MS-1, MOE30U-48HN1-NB8, YUFE60BYTM-MS-1, YUFE60BYSM-MS-1,
MOE30U-60HN1-NB8
Procedure Illustration
CJ_ODU_011
CJ_ODU_012
Note: This section is for reference only. Actual unit appearance may vary.
Page 72
Procedure Illustration
CJ_ODU_013
Maintenance and
and then remove it. (see CJ_
Disassembly
ODU_014)
CJ_ODU_014
Note: This section is for reference only. Actual unit appearance may vary.
Page 73
4. Sound blanket
WARNING: Recover refrigerant from the refrigerant circuit before remove the compressor.
Note: Remove the panel plate, electrical parts, and fan assembly (refer to 1. Panel plate, 2. Electrical parts,
and 3. Fan assembly) before disassembling sound blanket.
Procedure Illustration
Sound Blanket(top)
Sound Blanket(side)
CJ_ODU_015
Maintenance and
Disassembly
Note: This section is for reference only. Actual unit appearance may vary.
Page 74
5. Four-way valve (For heat pump models)
WARNING: Recover refrigerant from the refrigerant circuit before remove the four-way valve.
Note: Remove the panel plate, electrical parts, and fan assembly (refer to 1. Panel plate, 2. Electrical parts,
and 3. Fan assembly) before disassembling four-way valve.
Procedure Illustration
Maintenance and
Disassembly
CJ_ODU_016
Note: This section is for reference only. Actual unit appearance may vary.
Page 75
6. Compressor
WARNING: Recover refrigerant from the refrigerant circuit before remove the compressor.
Note: Remove the panel plate, electrical parts, and fan assembly (refer to 1. Panel plate, 2. Electrical parts,
and 3. Fan assembly) before disassembling compressor.
Procedure Illustration
Terminal Cover
Maintenance and
Disassembly
CJ_ODU_017
CJ_ODU_018
Note: This section is for reference only. Actual unit appearance may vary.
Page 76
Procedure Illustration
CJ_ODU_019
Maintenance and
Suction Pipe
Disassembly
4) Heat up the brazed parts and then remove
the the discharge pipe and the suction
pipe (see CJ_ODU_020).
Discharge Pipe
5) Lift the compressor from the base pan
assembly with pliers.
CJ_ODU_020
Note: This section is for reference only. Actual unit appearance may vary.
Page 77
Troubleshooting
Contents
1. Safety Caution......................................................................................................84
2. General Troubleshooting.....................................................................................85
solution..................................................................................................................96
Contents
5.8 Phase Sequence diagnosis and solution......................................................102
For other models, connect discharge resistance (approx.100Ω 40W) or a soldering iron plug between the positive and
negative terminals of the electrolytic capacitor. The terminals are located on the bottom surface of the outdoor PCB.
Troubleshooting
Note: This picture is for reference only. Actual appearances may vary.
Page 80
2. General Troubleshooting
Flash Flash OFF OFF E7 Indoor unit EEPROM parameter error Page 97
Troubleshooting
5 times OFF E4 Page 96
short circuited
Page 81
For Super-slim cassette type:
Flash Flash OFF OFF E7 Indoor unit EEPROM parameter error Page 97
Page 82
2.2 Error Display (Outdoor Unit) (excep for 18k/24k/36k single phase cooling-only models)
Troubleshooting
Page 83
3. Error Diagnosis and Troubleshooting Without Error Code
WARNING
Be sure to turn off unit before any maintenance to prevent damage or injury.
Problem Solution
2 The power switch is on but fans will not start Page 90-91
Page 84
3.2 Field maintenance
Problem Solution
3 Compressor and condenser (outdoor) fan will not start Page 92-93
Troubleshooting
15 Horizontal louver can not revolve Page 92-93
Page 85
Troubleshooting
Unit is noisy
Page 86
Unit will not start
☆
☆
Test voltage The voltage is too high or too low
Replace the battery of the remote control The remote control is powered off
Electrical Circuit
☆ ☆
☆
Clean or replace Dirty air filter
☆ ☆
Clean Dirty condenser fins
The setting temperature is higher/lower than the
☆
☆
☆
☆
Tighten bolts or screws Loosen hold down bolts and / or screws
Close all the windows and doors Bad airproof
☆ ☆
☆
Remove the obstacles The air inlet or outlet of either unit is blocked
Others
Reconnect the power or press ON/OFF Interference from cell phone towers and remote
☆
button on remote control to restart boosters
☆
Remove them Shipping plates remain attached
Page 87
Troubleshooting
Troubleshooting
Too cool
Unit will not start
Page 88
Compressor is noisy
Low suction pressure
High suction pressure
Low discharge pressure
High discharge pressure
Unit runs, but shortly stops
☆ ☆
☆
☆
☆
☆
Test circuits with tester Shorted or broken wires
☆ ☆ ☆ ☆ ☆
☆
☆
☆
☆
Test continuity of thermostat / sensor & wiring Faulty thermostat / room temperature sensor
Place the temperature sensor at the central of
☆
Wrong setting place of temperature sensor
the air inlet grille
☆
Test coninuity of coil & contacts Faulty magnetic contactor for compressor
Electrical Circuit
☆
☆
Test coninuity of coil & contacts Faulty magnetic contactor for fan
☆
☆
☆
Replace the stepping motor Faulty stepping motor
☆
☆
☆
Leak test Shortage of refrigerant
☆ ☆
Replace restricted part Restricted liquid line
Clean or replace Dirty air filter
Clean coil Dirty evaporator coil
☆ ☆ ☆ ☆ ☆
☆ ☆ ☆ ☆ ☆
Check fan Insufficient air through evaporator coil
☆
☆
Change charged refrigerant volume Overcharge of refrigerant
☆ ☆
☆ ☆
Clean condenser or remove obstacle Dirty or partially blocked condenser
Purge, evacuate and recharge Air or noncodensable gas in refrigerant cycle
☆ ☆ ☆
Remove obstruction to air folow Short cycling of condensing air
Remove obstruction in air or water flow High temperature condensing medium
☆ ☆ ☆ ☆ ☆ ☆
Remove obstruction in air or water flow Insufficient condensing medium
Refrigerant Circuit
☆
Replace compressor Broken compressor internal parts
☆
☆
☆
Test compressor efficiency Inefficient compressor
Replace valve Expansion valve obstructed
Replace valve Expansion valve or capillary tube closed completely
☆ ☆ ☆
☆ ☆
Replace valve Leaking power element on expansion valve
Fix feeler bulb Poor installation of feeler bulb
☆
☆ ☆
Check heat load Heavy load condition
Tighten bolts or screws Loosen hold down bolts and / or screws
☆ ☆
Remove them Shipping plates remain attached
Choose AC of lager capacity or add the number
☆
Poor choices of capacity
Others
of AC
Rectify piping so as not to contact each other or
☆
Contact of piping with other piping or external plate
with external plate
Page 89
Troubleshooting
4. Quick Maintenance by Error Code
If you do not have the time to test whether specific parts are faulty, you can directly change the required parts according
the error code.
You can find the parts to replace by error code in the following table.
For ceiling&floor type and super-slim cassette type:
Error Code
Part requiring replacement
E2 E3 E4 E7 E8 E0 EC F0 F1
Indoor PCB x x
T1 sensor x x x x x x x x
T2 Sensor x x x x x x x
T3 Sensor x x x x x x x x
Additional refrigerant x x x x x x x
Water-level switch x x x x x x x x
Water pump x x x x x x x x
Louver motor x x x x x x x x
Error Code
Part requiring replacement
E0 E4 E5 EE EC F2 FA
Troubleshooting
Indoor PCB x
T1 sensor x x x x x x
T2 Sensor x x x x x
T3 Sensor x x x x x x
Additional refrigerant x x x x x x
Water-level switch x x x x x x
Water pump x x x x x x
Page 90
5. Troubleshooting by Error Code
Troubleshooting
Page 91
5.2 E2/E3/E4 for ceiling&floor type and super slim cassette type&E4/E5/F2 for A6 duct
type (Open circuit or short circuit of temperature sensor diagnosis and solution)
Description: If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED will display the failure.
Recommended parts to prepare:
• Wiring mistake
• Faulty sensor
• Faulty PCB
Troubleshooting and repair:
Y ES
M easure the resistance value
of the sensor.
Is it w ithin acceptable
NO Replace the Sensor.
param eters?
Y ES
Replace the indoor PC B or the
outdoor electronic controlbox.
Troubleshooting
Page 92
5.3 E7 for ceiling&floor type and super slim cassette type&E0 for A6 duct type (EEPROM
parameter error)
Description: Indoor PCB main chip does not receive feedback from EEPROM chip.
Recommended parts to prepare:
• Indoor PCB
• Troubleshooting and repair:
Is it stilldisplaying
NO The unit is operating norm ally.
the error code?
Y ES
Remarks:
The location of the EEPROM chip on the indoor PCB is shown in the following image:
Troubleshooting
Page 93
5.4 E8 for ceiling&floor type and super slim cassette type&EE for A6 duct type (Water
level alarm malfunction diagnosis and solution)
Description: The water level switch is at the max. position to shut down the unit.
Recommended parts to prepare:
• Faulty drain pump (for units with drain pump)
• Installation mistake of water level switch (for units with drain pump)
• Short-circuit jumper is missing or broken (for units without drain pump)
• Faulty indoor PCB
Troubleshooting and repair:
Pow
Pow ereroff,
off,then
then restart
restartthe
the uni
unitt22 mm iinutes
nutes
llater.
ater. Is it stildisplaying the error
I
s it still di
spl aying the errorcode?
code?
IIffthe
the ww ater-l
ater-level
evelsw
sw iitch
tch iiss IInsert
nsertthe
the ww ater-l
ater-level
evelsw
sw iitch
tch
NO
iinserted w ell
?
nserted w ell? ww el
elll
Y ES
IIffthe
the ww ater-l
ater-level
evelsw
sw iitch
tch iiss NO Repl
Replace
ace the
the ww ater-l
ater-level
evelsw
sw iitch
tch
broken?
broken?
Y ES
Repl
Replace
ace the
the ww ater
aterpum
pum pp
Y ES
Troubleshooting
IIffmm al
alfuncti
function
on iisssti
stilllnot
not
solved?
solved?
Y ES
Repl
Replace
ace the
the iindoor
ndoormm ai
ainn PC
PCBB
Page 94
5.5 EC (Refrigerant Leakage Detection diagnosis and solution)
Description: Define the evaporator coil temp.T2 of the compressor just starts running as Tcool.
If the following occurs 3 times, the display shows “EC” and the unit switches off:
In the first 8 minutes after the compressor starts up, if T2 <Tcool-2°C is not maintained for 4 seconds and compressor
running frequency is not higher than 50Hz for 3 minutes.
Recommended parts to prepare:
• Faulty T2 sensor
• Faulty compressor
• Faulty capacitor of compressor
• Faulty indoor PCB
• System problems, such as leakage or blockages
• Faulty capacitor of fan motor
• Faulty outdoor fan
Troubleshooting and repair:
Pow
Pow er
eroff,
off,then
then restart
restartthe
the uni
unitt22 mm iinutes
nutesllater.
ater.
DDoes
oesaa probl
problem
em rem
rem ai
ain?
n?
Y ES
Put
Putyour
yourhands
handsiinn front
frontofofthe
the
iindoor
ndoorai
airroutl
outlet.
et.
IIssthere
there cool
coolai
airrbl
blow
ow iing
ng Y ES CCheck
heck the
the T2
T2 sensor.
sensor.
out
outfrom
from iindoor
ndoorai
airroutl
outlet?
et?
IIssiittsecurel
securelyy Rei
NO Reinsert
nsertthe
the T2
T2 sensor
Troubleshooting
sensor
attached?
attached?
NO NO NO
Y ES
The
The com
com pressor
pressor does
doesnot
not The
The com
com pressor
pressoroperates
operates The
The com
com pressor
pressor iissoperati
operating
ng MM easure
easure the
the resi
resistance
stance val
value
ue
operate
operate several
severalmm iinutes
nutesthen
then ceases
ceases constantl
constantlyy of
ofthe
the sensor.
sensor.
IIssiittww iithi
thinn acceptabl
acceptablee NO Repl
Replace
ace the
the sensor.
sensor.
param
param eters?
eters?
Repl
Replace
ace the
the capaci
capacitor
torof
of Repl
Replace
ace the
the capaci
capacitor
torof
offan
fan CCheck
heck system
system for
forlleakages.
eakages.
com
com pressor
pressor mm otor
otor Y ES
NO NO NO Repl
Replace
ace iindoor
ndoorPC
PCBB
Repai
Repairrthe
the lleakage
eakage and
and
DDoes
oesaa probl
problem
em rem
rem ai
ain?
n? DDoes
oesaa probl
problem
em rem
rem ai
ain?
n? AAre
re any
any lleakages
eakagespresent?
present? Y ES
recharge
recharge the
the refri
refrigerant.
gerant.
NO NO NO
CCheck
heck System
System for
forbl
blockages
ockagesand
and cl
clear
ear
Repl
Replace
ace the
the com
com pressor
pressor Repl
Replace
ace the
the outdoor
outdoorfan
fan bl
blockages
ockagesiiffpresent.
present.
Page 95
5.6 F0(Communication malfunction between indoor unit and auto-lifting panel diagnosis
and solution)
Description: Indoor PCB does not get the feedback from the PCB of auto-lifting panel.
Recommended parts to prepare:
• Wiring mistake between indoor PCB and auto-lifting panel
• Faulty PCB of auto-lifting panel
• Faulty indoor PCB
Troubleshooting and repair:
Communication
Communication failure
failure between
between indoor
indoor unit
unit and
and
auto-lifting
auto-lifting panel
panel
Check
Check the
the wire
wire connection
connection between
between auto-lifting
auto-lifting
panel
panel and
and indoor
indoor unit
unit
isis itit in
in working
working order?
order? NO Correct
Correct the
the connection
connection
Y ES
Replace
Replace the
the main
main control
control of
of auto-lifting
auto-lifting panel.
panel.
Troubleshooting
Has
Has the
the problem
problem been
been solved?
solved?
NO
Replace
Replace the
the indoor
indoor main
main PCB
PCB
Page 96
5.7 F1(Auto-lifting panel malfunction diagnosis and solution)
Description: Indoor PCB does not get the right close position from the PCB of auto lifting-panel when the panel motor
stops
Recommended parts to prepare:
• Wiring mistake between indoor PCB and auto-lifting panel
• Faulty PCB of auto-lifting panel
• Faulty louver motor
Troubleshooting and repair:
AAuto-l
uto-liifti
fting
ng panel
panelmm al
alfuncti
function
on
CControl
ontrolpanel
panelto
to lliift
ftor
ordrop
drop by
by control
controlller
er
CCan
an the
the auto-l
auto-liifti
fting
ng panel
panelmm ove
ove
Y es
norm
norm al allly?
y?
Y es
Pow
Pow er
eroff,
off,then
then restart
restartthe
the uni
unitt22
CCheck
heck the
the ww iiri
ring
ng of
ofthe
the llouver
ouvermm otors.
otors. mm iinutes
nutesllater.
ater.
HHas
asthe
the probl
problem
em been
been
No AAre
re they
they ww iired
red iincorrectl
ncorrectly?
y? sol
solved?
ved?
Y es No
Reconnect
Reconnect
Repl
Replace
ace the
the llouver
ouvermm otors.
otors. CCheck
heck the
the ww iiri
ring
ng of
oflleft
eftand
and ri
right
ght
sensors.
sensors.
Troubleshooting
HHas
asthe
the probl
problem
em been
been
sol
solved?
ved?
AAre
re they
they correctl
correctlyy ww iired?
red? No Reconnect
Reconnect
HHas
asthe
the probl
problem
em been
been
sol
solved?
ved?
Y es
NO The
The mm ai
ainn control
controlPC
PCBB of
ofauto-l
auto-liifti
fting
ng
panel NO
paneliissdefecti
defective.
ve.Repl
Replace
ace iitt
Page 97
5.8 Phase sequence error diagnosis and solution
Description: Outdoor PCB detects the wrong phase sequence of 3-phase power supply.
Recommended parts to prepare:
• Wiring mistake of 3-phase power supply
• Faulty outdoor PCB
Troubleshooting and repair:
Phase
Phase sequence
sequence error
error
CChange
hange thethe order
orderof
oftw
tw oo of
ofthe
the
ww iires
resto
to pow
pow er
ersuppl
supply.y.
Sw
Sw iitch
tch on
on the
the uni
unittagai
againn
IIffmm al
alfuncti
function
on iisssti
stilllnot
notsol
solved?
ved?
Y ES
Repl
Replace
ace the
the outdoor
outdoormm ai
ainn PC
PCBB
Troubleshooting
Page 98
5.9 Lack of Phase diagnosis and solution
Description: Outdoor PCB detects the voltage of one or two phase are very low.
Recommended parts to prepare:
• Problems of 3-phase power supply
• Wiring mistake of 3-phase power supply
• Faulty outdoor PCB
Troubleshooting and repair:
Lack
Lack of
ofphase
phase
CCheck
heck the
the pow
pow er
ersuppl
supplyy
Restart
Restartthe
the uni
unittww hen
hen the
the pow
pow er
er
iissiitt33 phase,
phase,220-230V
220-230V?? NO
suppl
supplyy returns
returnsto to norm
norm al
al
Y ES
CCheck
heck the
the connecti
connection
on betw
betw een
een pow
pow er
ersuppl
supplyy
and
and term
term iinal
nal
IIssthe
the vol
voltage
tage iinn outdoor
outdoorterm
term iinal
naliiss33 iissthe
the pow
pow er
erww iiri
ring
ng
NO NO Reconnect
Reconnectthe
the pow
pow er
erww iiri
ring
ng
phase,
phase,220-230V
220-230V?? ww iired
red correctl
correctly?y?
Y ES
Repl
Replace
ace the
the outdoor
outdoormm ai
ainn PC
PCBB Y ES
Troubleshooting
Page 99
5.10 Overload current protection diagnosis and solution
Description: An abnormal current rise is detected by checking the specified current detection circuit.
Recommended parts to prepare:
• Power supply problems.
• System blockage
• Faulty PCB
• Wiring mistake
• Compressor malfunction
Troubleshooting and repair:
Y ES
Y ES
Y ES
Y ES
Y ES
Page 100
5.11 High temperature or protection of pressure diagnosis and solution
Description: The High pressure switch detects a ultra high pressure or the Low pressure switch detects a ultra low
switch, which could damage the system.
Recommended parts to prepare:
• Bad wiring of the pressure switches
• Faulty pressure switches
• Refrigeration system is over load or blocked or lack of refrigerant
Troubleshooting and repair:
HHiigh
gh tem
tem perature
perature or
orprotecti
protection
on
of
ofpressure
pressure
IIssiittk1
k1 or
orKK22 open
open ??
IIssttem
em per
perat
atur uree
pr
prot
otectectiive
vesw
sw iittch
ch K1
K1 IIsspressure
pressure protecti
protective
ve
open
open sw
sw iittch
ch K2
K2 open
open
Y ES Y ES
Possi
Possibl blee reason
reason Possi
Possibl blee reason
reason
1.
1.The
The ww iires
resiisslloose
oose toto KK11 1.
1.The
The ww iires
resiisslloose
oose toto KK22
2.
2.AAiirror
orother
othergas gasiinn the
the refri
refrigerant.
gerant. 2.
2.AAiirror
orother
othergas gasiinn the
the refri
refrigerant.
gerant.
3.
3.HHeat
eatexchanger
exchangeriissdi dirty
rty 3.
3.HHeat
eatexchanger
exchangeriissdi dirty
rty
4.
4.OO utdoor
utdoorfan fan or orfan
fan blblade
ade iissdefecti
defective
ve 4.
4.OO utdoor
utdoormm otor otoror orfan
fan bl
blade
ade iissdefecti
defective
ve
5.
5.OO utdoor
utdooruni unittiissiinn bad
bad venti
ventillati
ation
on 5.
5.OO utdoor
utdooruni unittiissiinn bad
bad venti
ventillati
ation
on
6.
6.Refri
Refrigerant
gerantiisslleakage
eakage 6.
6.Refri
Refrigerant
gerantiisstootoo mm uch
uch
Troubleshooting
Page 101
Contents
i) Temperature Sensor Resistance Value Table for T1, T2, T3, and T4 (°C – K)...112
Page 103
ii) Pressure On Service Port(R410A)
Cooling chart:
ODT 15 45 75 85 105 115 120
°F(°C) 0(-17) 5(-15) 95 (35)
IDT (9.44) (7.22) (23.89) (29.44) (40.56) (46.11) (48.89)
BAR 70/59 6.4 6.5 7.3 8.0 8.2 7.8 8.1 8.6 10.1 10.6
BAR 75/63 6.7 6.8 7.9 8.6 8.6 8.3 8.7 9.1 10.7 11.2
BAR 80/67 7.1 7.2 8.5 9.5 9.3 8.9 9.1 9.6 11.2 11.9
BAR 90/73 7.7 7.8 9.6 10.5 10.3 9.5 10.0 10.6 12.4 13.0
PSI 70/59 93 94 106 116 119 113 117 125 147 154
PSI 75/63 97 99 115 125 124 120 126 132 155 162
PSI 80/67 103 104 123 138 135 129 132 140 162 173
PSI 90/73 112 113 139 152 149 138 145 154 180 189
MPA 70/59 0.64 0.65 0.73 0.8 0.82 0.78 0.81 0.86 1.01 1.06
MPA 75/63 0.67 0.68 0.79 0.86 0.86 0.83 0.87 0.91 1.07 1.12
MPA 80/67 0.71 0.72 0.85 0.95 0.93 0.89 0.91 0.96 1.12 1.19
MPA 90/73 0.77 0.78 0.96 1.05 1.03 0.95 1 1.06 1.24 1.3
1.4
1.2
0.8
70/59
0.6 75/63
Appendix
80/67
0.4
90/73
0.2
Page 104
Heating chart:
ODT 57/53 47/43 37/33 27/23 17/13 (-8.33/- 0/-2 -17/-18
°F(°C)
IDT (13.89/11.67) (8.33/6.11) (2.78/0.56) (-2.78/-5) 10.56) (-17/-19) (-27/-28)
4
3.5
3
2.5
2
1.5 55
1 65
0.5 75
0
Appendix
Page 105
2019 Johnson Controls, Inc. www.johnsoncontrols.com Form: MYFETM-MOW1-190830
Johnson Controls reserve the right to change product features without prior notice.