EVCO S.p.A. | EV3294 | Instruction sheet ver. 1.

0 | Code 1043294E103 | Page 1 of 3 | PT 26/16

Controller for refrigerated cabinets, undercounters and islands, with energy-saving strategies and
EV3294 compatible with EVCO Android APP
4.1 Switching the device on/off 6.2 Set the date, time and day of the week (only if module EVIF23TSX or interface
EVIF25TBX is connected)
1. If POF = 1 (default), touch the ON/STAND-BY key for 2 s.

If the device is switched on, the display will show the P5 value ("cabinet temperature" default); N.B.
if the display shows an alarm code, see the section ALARMS. - Do not disconnect the device from the mains within two minutes since the setting
LED ON OFF FLASHING of the time and day of the week
compressor on compressor off - compressor protection active - If the device communicates with the APP EVconnect, the date, time and day of the
- setpoint setting active week will automatically be set by the smartphone or tablet.
defrost or pre-dripping - - defrost delay active
active - dripping active Check that the keypad is not locked.
I ENGLISH
evaporator fans on evaporator fans off evaporator fans stop active
- controller for low temperature units 1. Touch the DOWN key for 4 s.
- power supply 115... 230 VAC
reserved reserved reserved
- cabinet probe and evaporator probe (PTC/NTC) HACCP 2. Touch the UP or DOWN key within 15 s to select the label “rtc”.
- door switch input
energy saving active - - Touch the SET key: the display will show the label “yy” followed
- compressor relay 16 A res. @ 250 VAC 3.
by the last two figures of the year.
- TTL MODBUS slave port for EVCO Android APP or BMS
- cooling or heating operation. request for compres- - - settings active
4. Touch the UP or DOWN key within 15 s to set the year.
sor service - access to additional functions
active
1 MEASUREMENTS AND INSTALLATION 5. Repeat actions 3. and 4. to set the next labels.
Measurements in mm (inches). To be fitted to a panel, snap-in brackets provided. view temperature - overcooling or overheating active
°C/°F
LAB. DESCRIPTION OF THE NUMBERS FOLLOWING THE LABEL
auxiliary load on auxiliary load off - auxiliary load on by digital input n month (01… 12)
AUX
- auxiliary load delay active d day (01… 31)
device off device on device on/off active h time (00… 23)
n minute (00… 59)
Touch the SET key: the display will show the label for the day of
If Loc = 1 (default) and 30s have elapsed without the keys being pressed, the display will show 6.
the week.
the “Loc” label and the keypad will lock automatically. Touch the UP or DOWN key within 15s to set the day of the
7.
week.
4.2 Unlock keypad LAB. DESCRIPTION
Touch a key for 1 s: the display will show the label “UnL”.
Mon Monday
tuE Tuesday
4.3 Set the setpoint
UEd Wednesday
Check that the keypad is not locked.
thu Thursday
1. Touch the SET key. Fri Friday
Sat Saturday
Touch the UP or DOWN key within 15s to set the value within the
2. Sun Sunday
limits r1 and r2 (default “-50... 50”)
8. Touch the SET key: the device will exit the procedure.
3. Touch the SET key (or do not operate for 15s).

9. Touch the ON/STAND-BY key to exit the procedure beforehand.


INSTALLATION PRECAUTIONS 4.4 Activate manual defrost
- The thickness of the panel must be between 0.8 and 2.0 mm (1/32 and 1/16 in) Check that the keypad is not locked and that overcooling is not active.
- Ensure that the working conditions are within the limits stated in the TECHNICAL 6.3 Restore the factory settings (default) and store customized settings as default
1. Touch the UP key for 2 s.
SPECIFICATIONS section.
- Do not install the device close to heat sources, equipment with a strong magnetic field, If P3 = 1 (default), defrost is activated provided that the evaporator temperature is lower than N.B.
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations the d2 threshold. - Check that the factory settings are appropriate; see the section CONFIGURATION
or shocks. PARAMETERS.
- In compliance with safety regulations, the device must be installed properly to ensure 4.5 Cabinet light on/off (if u1 = 0, default) - the storing of customized settings overwrites the default.
adequate protection from contact with electrical parts. All protective parts must be
1. Touch the ON/STAND-BY key.
fixed in such a way as to need the aid of a tool to remove them.
1. Touch the SET key for 4 s: the display will show the label “PA”.
- if u1 = 1, the demisting heaters switch on for the u6 duration.
2 ELECTRICAL CONNECTION - if u1 = 2 and the keypad is not locked, auxiliary output switches on/off.
2. Touch the SET key.

N.B. 4.6 Silence buzzer (if present)


3. Touch the UP or DOWN key within 15 s to set the value.
- Use cables of an adequate section for the current running through them. Touch a key.
- To reduce any electromagnetic interference connect the power cables as far away If u1 = 3 and u4 = 1, the alarm output switches off. VAL. DESCRIPTION
as possible from the signal cables. 149 value to restore the factory settings (default)
5 ADDITIONAL FUNCTIONS 161 value to store customized settings as default
5.1 Activate/deactivate overcooling, overheating and manual energy saving Touch the SET key (or do not operate for 15 s): the display will
Check that the keypad is not locked. 4. show the label “dEF” (when value “149” is set) or the label

1. Touch the DOWN key. “MAP” (when value “161” is set).

5. Touch the SET key.


FUNCTION CONDITION CONSEQUENCE
overcooling r5 = 0, r8 = 1 and defrost the setpoint becomes “setpoint - 6. Touch the UP or DOWN key within 15 s to set “4”.
not active r6”, for the r7 duration Touch the SET key (or do not operate for 15 s): the display will
overheating r5 and r8 = 1 the setpoint becomes “setpoint + 7. show for 4 s “- - -“ flashing, then the device will exit the proce-
r6”, for the r7 duration dure.
energy saving r5 = 0 and r8 = 2 the setpoint becomes “setpoint + 8. Interrupt the power supply to the device.
r4”, at maximum for HE2 duration Touch the SET key 2 s before action 6. to exit the procedure be-
9.
forehand.
5.2 View/delete compressor functioning hours and view compressor start-up
number 7 CONFIGURATION PARAMETERS
Check that the keypad is not locked.
PRECAUTIONS FOR ELECTRICAL CONNECTION N. PAR. DEF. SETPOINT MIN... MAX.
1. Touch the DOWN key for 4 s.
- If using an electrical or pneumatic screwdriver, adjust the tightening torque.
1 SP 0,0 setpoint r1... r2; see r0
- If the device has been moved from a cold to a warm place, the humidity may have
2. Touch the UP or DOWN key within 15 s to select a label. N. PAR. DEF. ANALOGUE INPUTS MIN... MAX.
caused condensation to form inside. Wait about an hour before switching on the
2 CA1 0,0 if P4 = 0... 2, cabinet probe off- -25... 25 °C/°F
power. LAB. DESCRIPTION
set; if P4 = 3, inlet air probe off-
- Make sure that the supply voltage, electrical frequency and power are within the set CH view compressor functioning hours (hundreds) set
limits. See the section TECHNICAL SPECIFICATIONS. rCH delete compressor functioning hours 3 CA2 0,0 evaporator probe offset -25... 25 °C/°F
- Disconnect the power supply before doing any type of maintenance. nS1 compressor start-up number (thousands) 4 CA3 0,0 auxiliary probe offset -25... 25 °C/°F
- Do not use the device as safety device.
3. Touch the SET key. 5 P0 1 probe type 0 = PTC 1 = NTC
- For repairs and for further information, contact the EVCO sales network.
6 P1 1 enable °C decimal point 0 = NO 1 = YES
Touch the UP or DOWN key to set “149” (when label “rCH” is se-
3 FIRST-TIME 4. 7 P2 0 temperature unit of measure- 0 = °C 1 = °F
lected).
1. Install following the instructions given in the section MEASUREMENTS AND INSTALLA- ment
TION. 5. Touch the SET key. 8 P3 1 evaporator probe function 0 = absent
2. Power up the device as shown in the section ELECTRICAL CONNECTION and an internal 1 = defrost and fans
Touch the ON/STAND-BY key (or do not operate for 60 s) to exit 2 = fans
test will be run. 6.
the procedure.
The test normally takes a few seconds, when it is finished the display will switch off. 9 P4 0 configurable input function 0 = multipurpose input
3. Configure the device as shown in the section Setting configuration parameters. 0 = digital input (multipur- 1 = condenser probe
5.3 View the temperature detected by the probes
Recommended configuration parameters for first-time use. pose input) 2 = critical T probe
Check that the keypad is not locked.
PAR. DEF. PARAMETER MIN... MAX. 1... 3 = analogue input (aux- 3 = outlet air probe
SP 0.0 setpoint r1... r2 1. Touch the DOWN key for 4 s. iliary probe) if P4 = 3, regulation T = CPT;
P0 1 probe type 0 = PTC 1 = NTC see P7
P2 0 temperature unit of measurement 0 = °C 1 = °F 2. Touch the UP or DOWN key within 15 s to select a label. 10 P5 0 value displayed in normal opera- 0 = if P4 = 0... 2, cabinet T;
d1 0 defrost type 0 = electric 1 = hot gas tion if P4 = 3, CPT
LAB. DESCRIPTION 1 = SP
2 = compressor stopped
cabinet temperature (if P4 = 0, 1 or 2) 2 = evaporator T
Pb1
inlet air temperature (if P4 = 3) 3 = auxiliary T; see P4
Then check that the remaining settings are appropriate; see the section CONFIGURA-
Pb2 evaporator temperature (if P3 = 1 or 2) 4 = if P4 = 3, inlet air T
TION PARAMETERS.
Pb3 auxiliary temperature (if P4 = 1, 2 or 3) 11 P7 5 inlet air weight for calculated 0... 10 % x 10
4. Disconnect the device from the mains.
5. Make the electrical connection as shown in the section ELECTRICAL CONNECTION with- Pb4 calculated product temperature (CPT; if P4 = 3) product temperature (CPT) CPT = {[(P7 x (inlet air T)] +
out powering up the device. [(100 - P7) x (outlet air T)] :
3. Touch the SET key.
6. For the connection in an RS-485 network connect the interface EVIF22TSX or 100}
EVIF23TSX, to activate real time functions connect the module EVIF23TSX, to use the Touch the ON/STAND-BY key (or do not operate for 60 s) to exit 12 P8 5 display refresh time 0... 250 s : 10
4.
device with the APP EVconnect connect the interface EVIF25TBX (EVlink); see the rele- the procedure. N. PAR. DEF. MAIN REGULATOR MIN... MAX.
vant instruction sheets. 13 r0 2,0 setpoint differential 0,1 °C/1 °F... 15 °C/°F; see
7. Power up the device. 6 SETTINGS r12
6.1 Setting configuration parameters 14 r1 -50 minimum setpoint -99 °C/°F... r2
4 USER INTERFACE AND MAIN FUNCTIONS 15 r2 50,0 maximum setpoint r1... 199 °C/°F
1. Touch the SET key for 4 s: the display will show the label “PA”.
16 r4 0,0 if r5 = 0, setpoint offset in ener- 0... 99 °C/°F; see HE2
2. Touch the SET key. gy saving
17 r5 0 cooling or heating operation 0 = cooling
Touch the UP or DOWN key within 15 s to set the PAS value (de- 1 = heating
3.
fault “-19”). 18 r6 0,0 if r5 = 0, setpoint offset in over- 0... 99 °C/°F; see r7
Touch the SET key (or do not operate for 15 s): the display will cooling; if r5 = 1, setpoint offset
4.
show the label “SP”. in overheating

5. Touch the UP or DOWN key to select a parameter. 19 r7 30 if r5 = 0, overcooling duration; if 0... 240 min; see r6
r5 = 1 overheating duration

6. Touch the SET key. 20 r8 0 DOWN key additional function 0 = none


1 = if r5 = 0, overcooling; if

7. Touch the UP or DOWN key within 15s to set the value. r5 = 1, overheating
2 = energy saving

8. Touch the SET key (or do not operate for 15 s). 21 r12 0 type of setpoint differential r0 0 = symmetrical
1 = asymmetrical
Touch the SET key for 4 s (or do not operate for 60 s) to exit the
9.
procedure.
EVCO S.p.A. | EV3294 | Instruction sheet ver. 1.0 | Code 1043294E103 | Page 2 of 3 | PT 26/16
N. PAR. DEF. COMPRESSOR PROTECTIONS MIN... MAX. 74 i0 3 door switch input function 0 = none 8 ALARMS
22 C0 0 compressor ON delay after pow- 0... 240 min 1 = compressor and evapo-
er-on rator fans OFF COD. DESCRIPTION RESET REMEDIES
23 C2 3 compressor OFF minimum time 0... 240 min 2 = evaporator fans OFF Pr1 cabinet probe alarm automatic - check P0
24 C3 0 compressor ON minimum time 0... 240 s 3 = cabinet light ON Pr2 evaporator probe alarm automatic - check probe integrity
25 C4 10 compressor OFF time in cabinet 0... 240 min; see C5 4 = compressor and evapo- Pr3 auxiliary probe alarm automatic - check electrical connection
probe alarm rator fans OFF, cabinet rtc real time clock alarm manual set date, time and day of the week
26 C5 10 compressor ON time in cabinet 0... 240 min; see C4 light ON AL low temperature alarm automatic check A1
probe alarm 5 = evaporator fans OFF, AH high temperature alarm automatic check A4
cabinet light ON
27 C6 80,0 high condensing warning thre- 0... 199 °C/°F id door open alarm automatic check i0 e i1
shold differential = 2 °C/4 °F 75 i1 0 door switch input contact type 0 = normally open
PF power failure alarm manual - touch a key
1 = normally closed
28 C7 90,0 high condensing alarm threshold 0... 199 °C/°F - check electrical connection
76 i2 30 door open alarm delay -1... 120 min
29 C8 1 high condensing alarm delay 0... 15 min
-1 = absent COH high condensing warning automatic check C6
30 C10 1 compressor functioning hours for 0... 999 h x 100
77 i3 15 regulation by-pass maximum -1... 120 min
service 0 = absent CSd high condensing alarm manual - switch the device off and on
time with door open -1 = until the door closing
31 C11 0 compressor ON delay after other 0... 240 min - check C7
78 i5 2 multipurpose input function 0 = none
compressor ON iA multipurpose input alarm automatic check i5 and i6
1 = energy saving
32 C13 0 start-up number to rotate com- 0... 100 Cth compressor thermal protec- automatic check i5 and i6
2 = multipurpose input
pressors 0 = no rotation tion alarm
alarm
N. PAR. DEF. DEFROST (se r5 = 0) MIN... MAX. th global thermal protection manual - switch the device off and on
3 = auxiliary output ON
33 d0 8 if d8 = 0... 2, defrost interval; if 0... 99 h alarm - check i5 and i6
4 = device stand-by
d8 = 3 maximum defrost interval 0 = only manual dFd defrost time-out alarm manual - touch a key
5 = compressor thermal pro-
34 d1 0 defrost type 0 = electric - check d2, d3 and d11
tection alarm
1 = hot gas
6 = global thermal protec-
2 = compressor stopped 9 TECHNICAL SPECIFICATIONS
tion alarm
35 d2 8,0 threshold for defrost end -99... 99 °C/°F; see d3
79 i6 0 multipurpose input contact type 0 = normally open
36 d3 30 se P3 = 0 o 2, defrost duration; 0... 99 min; see d2 Purpose of the control device Function controller
1 = normally closed
se P3 = 1, maximum defrost du- Construction of the control device Built-in electronic device
80 i7 0 if i5 = 2, multipurpose input -1... 120 min
ration Container Black, self-extinguishing
alarm delay; if i5 = 5 or 6, com- -1 = absent
37 d4 0 se d8 = 0... 3, enable defrost af- 0 = NO 1 = YES Category of heat and fire resistance D
pressor ON delay after alarm end
ter power-on Measurements
81 i10 0 closed door consecutive time for 0... 999 min; see HE2
38 d5 0 se d4 = 1, defrost dealy after 0... 99 min 75.0 x 33.0 x 59.0 mm (2 15/16 x 1 5/16 x 75.0 x 33.0 x 81.5 mm (2 15/16 x 1 5/16 x
energy saving after cabinet T /CPT < SP
power-on 2 5/16 in) with fixed screw terminal blocks 3 3/16 in) with removable screw terminal
0 = absent
39 d6 2 if P5 = 0, value displayed in de- 0 = cabinet T /CPT blocks
82 i13 180 number of door openings for de- 0... 240
frost 1 = at maximum “SP + r0” Mounting methods for the control device To be fitted to a panel, snap-in brackets pro-
frost 0 = absent
or cabinet T/CPT at de- vided
83 i14 32 open door consecutive time for 0... 240 min
frost activation Degree of protection provided by the cover- IP65 (front)
defrost 0 = absent
2 = code “dEF” ing
N. PAR. DEF. DIGITAL OUTPUTS MIN... MAX.
40 d7 2 dripping duration 0... 15 min Connection method
84 u1 0 auxiliary relay function 0 = cabinet light
41 d8 0 defrost interval d0 counting mo- 0 = device ON Fixed screw terminal blocks Removable screw terminal Micro-MaTch connector
1 = demisting heaters
de 1 = compressor ON for wires up to 2,5 mm² blocks for wires up to
2 = auxiliary output
2 = evaporator T < d9 2,5 mm²; by request
3 = alarm output
3 = adaptive Maximum permitted length for connection cables
4 = door heaters
4 = real time Power supply: 10 m (32.8 ft) Analogue inputs: 10 m (32.8 ft)
5 = neutral zone heaters
42 d9 0,0 if d8 = 2, evaporator tempera- -99... 99 °C/°F Digital inputs: 10 m (32.8 ft) Digital outputs: 10 m (32.8 ft)
6 = condenser fans
ture threshold for defrost interval Operating temperature From 0 to 55 °C (from 32 to 131 °F)
7 = on/stand-by output
d0 counting Storage temperature From -25 to 70 °C (from -13 to 158 °F)
8 = compressor 2
43 d11 0 enable defrost time-out alarm 0 = NO 1 = YES Operating humidity Relative humidity without condensate from
85 u2 0 enable cabinet light and auxiliary 0 = NO 1 = YES
44 d15 0 if d1 = 1, consecutive compres- 0... 99 min output ON/OFF in stand-by only manual 10 to 90%
sor ON minimum time for defrost Pollution status of the control device 2
86 u4 0 enable alarm output OFF with 0 = NO 1 = YES
consent
buzzer silencing Conformity
45 d16 0 if d1 = 1, pre-dripping duration 0... 99 min
87 u5 -1,0 threshold for door heaters ON -99... 99 °C/°F RoHS 2011/65/CE WEEE 2012/19/EU REACH (EC) Regulation
46 d18 40 if d8 = 3, defrost interval 0... 999 min; see d0 differential = 2 °C/4 °F 1907/2006
if compressor ON and evapo-
88 u6 5 duration demisting heaters ON 1... 120 min EMC 2014/30/UE LVD 2014/35/UE
rator T < d22
89 u7 -5,0 threshold relative to setpoint for -99... 99 °C/°F Power supply 115... 230 VAC (+10% -15%), 50/60 Hz (±3
0 = only manual
neutral zone heaters ON differential = 2 °C/4 °F Hz), max. 3.2 VA insulated
47 d19 3,0 if d8 = 3, threshold relative to 0... 40 °C/°F
“SP + u7” Earthing methods for the control device None
optimal evaporator temperature “optimal T - d19”
N. PAR. DEF. ENERGY SAVING MIN... MAX. Rated impulse-withstand voltage 2.5 KV
for defrost
90 HE2 0 maximum energy saving duration 0... 999 min; see i10 Over-voltage category II
48 d20 180 consecutive compressor ON time 0... 999 min
-1 = until the door opening Software class and structure A
for defrost 0 = absent
N. PAR. DEF. REAL TIME ENERGY SAVING MIN... MAX. Analogue inputs 2 for PTC or NTC probes (cabinet probe and
49 d21 200 consecutive compressor ON time 0... 500 min
91 H01 0 Monday energy saving time 0... 23 h; see H02 evaporator probe)
after power-on and after over- if “(cabinet T /CPT - SP) >
92 H02 0 Monday energy saving duration 0... 24 h; see H01 PTC probes Sensor type KTY 81-121 (990 Ω @ 25 °C, 77 °F)
cooling for defrost 10°C/20 °F”
93 H03 0 Tuesday energy saving time 0... 23 h; see H04 Measurement field from -50 to 150 °C (from -58 to 302 °F)
0 = absent
94 H04 0 Tuesday energy saving duration 0... 24 h; see H03 Resolution 0.1 °C (1 °F)
50 d22 -2,0 if d8 = 3, threshold relative to -10... 10 °C/°F
optimal evaporator temperature “optimal T + d22”
95 H05 0 Wednesday energy saving time 0... 23 h; see H06 NTC probes Sensor type ß3435 (10 KΩ @ 25 °C, 77 °F)

for defrost interval d18 counting 96 H06 0 Wednesday energy saving dura- 0... 24 h; see H05 Measurement field from -40 to 105 °C (from -40 to 221 °F)
tion Resolution 0.1 °C (1 °F)
N. PAR. DEF. TEMPERATURE ALARMS MIN... MAX.
97 H07 0 Thursday energy saving time 0... 23 h; see H08 Digital inputs 1 dry contact (door switch)
51 AA 0 temperature selection for high 0 = cabinet T/CPT
and low temperature alarm 1 = evaporator T 98 H08 0 Thursday energy saving duration 0... 24 h; see H07 Dry contact Contact type 5 VDC, 1.5 mA
2 = auxiliary T; see P4 99 H09 0 Friday energy saving time 0... 23 h; see H010 Power supply None
see A1 and A4 100 H10 0 Friday energy saving duration 0... 24 h; see H09 Protection None
52 A1 -10,0 low temperature alarm threshold -99... 99 °C/°F; see AA, A2 101 H11 0 Saturday energy saving time 0... 23 h; see H012 Other inputs input configurable for analogue input (auxiliary probe) or
and A11 102 H12 0 Saturday energy saving duration 0... 24 h; see H11 digital input (multipurpose input)
53 A2 2 low temperature alarm type 0 = absent 103 H13 0 Sunday energy saving time 0... 23 h; see H014 Digital outputs 4 electro-mechanical relays (compressor, defrost, evaporator
1 = relat. to SP (“SP - A1”) 104 H14 0 Sunday energy saving duration 0... 24 h; see H13 fans and auxiliary relay)
2 = absolute (A1) N. PAR. DEF. REAL TIME DEFROST (if d8 = 4) MIN... MAX. Compressor relay (K1): SPST, 16 A res. @ 250 VAC
54 A4 10,0 high temperature alarm thre- -99... 99 °C/°F; see AA, A5 105 Hd1 h- first daily defrost time h- = absent Defrost relay (K2): SPST, 8 A res. @ 250 VAC
shold and A11 106 Hd2 h- second daily defrost time h- = absent Evaporator fans relay (K3): SPST, 5 A res. @ 250 VAC
55 A5 2 high temperature alarm type 0 = absent 107 Hd3 h- third daily defrost time h- = absent Auxiliary relay (K4): SPST, 5 A res. @ 250 VAC
1 = relat. to SP (“SP + A4”) 108 Hd4 h- fourth daily defrost time h- = absent The device guarantees double insulation between each digital output connector and the rest
2 = assoluto (A4) 109 Hd5 h- fifth daily defrost time h- = absent of the components of the device.
56 A6 99 high temperature alarm delay af- 0... 99 min x 10 110 Hd6 h- sixth daily defrost time h- = absent Type 1 or Type 2 Actions Type 1
ter power-on N. PAR. DEF. SAFETIES MIN... MAX. Additional features of Type 1 or Type 2 ac- C
57 A7 15 high and low temperature alarms 0... 240 min 111 POF 1 enable ON/STAND-BY key 0 = NO 1 = YES tions
delay 112 PAS -19 configuration parameters settings -99... 999 Displays 3 digits custom display, with function icons
58 A8 15 high temperature alarm delay af- 0... 240 min password Alarm buzzer By request
ter defrost end 113 PA1 426 User password Android APP EVCO -99... 999 Communication ports 1 TTL MODBUS slave port for EVCO Android
59 A9 15 high temperature alarm delay af- 0... 240 min APP or BMS
ter door closing 114 PA2 824 Maintenance password Android -99... 999
APP EVCO
60 A10 10 power failure duration for power 0... 240 min
failure alarm storing N. PAR. DEF. REAL TIME CLOCK MIN... MAX.
61 A11 2,0 A1 and A4 differential 0,1 °C/1 °F... 15 °C/°F 115 Hr0 1 enable real time clock 0 = NO 1 = YES
N. PAR. DEF. EVAPORATOR AND CONDENSER MIN... MAX. N. PAR. DEF. DATA-LOGGING ON EVLINK MIN... MAX.
FANS 116 bLE 1 enable EVlink 0 = NO 1 = SÌ
62 F0 1 evaporator fans mode in normal 0 = OFF 1 = ON 117 rE0 15 data-logging interval on EVlink 0... 240 min
operation 2 = with F15 and F16 if 118 rE1 1 temperature selection for data- 0 = none 1 = cabinet T
compressor OFF, ON if logging on EVlink 2 = evaporator T
compressor ON 3 = auxiliary T
3 = with F1 4 = cabinet and evaporat. T
4 = OFF if compressor OFF, 5 = all
with F1 if compressor N. PAR. DEF. MODBUS MIN... MAX.
ON 119 LA 247 MODBUS address 1... 247
63 F1 -4,0 if F0 = 3 or 4 | if r5 = 0, thre- -99... 99 °C/°F 120 Lb 2 MODBUS baud rate 0 = 2,400 baud
shold for evaporator fans OFF; if differential = 1 °C/2 °F (no parity) 1 = 4,800 baud
r5 = 1, threshold for evaporator 2 = 9,600 baud
fans ON 3 = 19,200 baud
64 F2 0 evaporator fans mode in defrost 0 = OFF 1 = ON
and dripping 2 = with F0
65 F3 2 maximum evaporator fans stop 0... 15 min; see F7
duration
66 F4 0 evaporator fans OFF time in 0... 240 s x 10; see F5
energy saving
67 F5 10 evaporator fans ON time in ener- 0... 240 s x 10; see F4
gy saving
N.B.
68 F7 5,0 threshold relative to setpoint for -99... 99 °C/°F; see F3
The device must be disposed of according to local regulations governing the collection
evaporator fans stop end “SP + F7”
of electrical and electronic waste.
69 F9 0 if F0 = 2, evaporator fans OFF 0... 240 s
delay after compressor OFF
This document and the solutions contained therein are the intellectual property of EVCO and thus pro-
70 F11 15,0 threshold condenser fans ON 0... 99 °C/°F
tected by the Italian Intellectual Property Rights Code (CPI). EVCO imposes an absolute ban on the full
differential = 2 °C/4 °F
or partial reproduction and disclosure of the content other than with the express approval of EVCO. The
71 F12 30 if P4 ≠ 1, condenser fans OFF 0... 240 s
customer (manufacturer, installer or end-user) assumes all responsibility for the configuration of the de-
delay after compressor OFF
vice. EVCO accepts no liability for any possible errors in this document and reserves the right to make
72 F15 0 if F0 = 2, evaporator fans OFF 0... 240 s; see F16
any changes, at any time without prejudice to the essential functional and safety features of the equip-
time with compressor OFF
ment.
73 F16 1 if F0 = 2, evaporator fans ON 0... 240 s; see F15
time with compressor OFF
EVCO S.p.A.
N. PAR. DEF. DIGITAL INPUTS MIN... MAX.
Via Feltre 81, 32036 Sedico (BL) ITALY
telefono 0437 8422 | fax 0437 83648
email info@evco.it | web www.evco.it
EVCO S.p.A. | EV3294 | Instruction sheet ver. 1.0 | Code 1043294E103 | Page 3 of 3 | PT 26/16